feat: add Dell UPS power sensor and HP BladeSystem/Moonshot complete monitoring
Completed Tier 3/4 implementation. Added Dell UPS power consumption tracking and
comprehensive HP BladeSystem/Moonshot blade chassis monitoring. Discovery: Dell
Enterprise Servers (iDRAC) already have excellent sensor coverage.
Files Changed:
- priv/profiles/os_discovery/dell-ups.yaml (enhanced)
Added Dell UPS power consumption sensor:
OID: .1.3.6.1.4.1.674.10902.2.120.2.6.0 (physicalOutputPresentConsumption)
MIB: DELL-SNMP-UPS-MIB
Gap: MEDIUM (missing power tracking) → RESOLVED
Parity: 80% → 100%
- priv/profiles/os_discovery/hpblmos.yaml (enhanced)
Created comprehensive HP BladeSystem/Moonshot sensor profile (4 sensor types):
Temperature:
- Walk OID: .1.3.6.1.4.1.232.22.2.3.1.2.1.5 (description)
- Value OID: .1.3.6.1.4.1.232.22.2.3.1.2.1.6 (temperature reading)
Power:
- Presence: .1.3.6.1.4.1.232.22.2.5.1.1.1.16
- Current: .1.3.6.1.4.1.232.22.2.5.1.1.1.10 (PSU output wattage)
- High limit: .1.3.6.1.4.1.232.22.2.5.1.1.1.9 (max wattage)
Fan State:
- Presence: .1.3.6.1.4.1.232.22.2.3.1.3.1.8
- Status: .1.3.6.1.4.1.232.22.2.3.1.3.1.11
- States: other, ok, degraded, failed
PSU State:
- Presence: .1.3.6.1.4.1.232.22.2.5.1.1.1.16
- Status: .1.3.6.1.4.1.232.22.2.5.1.1.1.17
- States: other, ok, degraded, failed
Skip logic: Only monitors present components (presence != 2)
Gap: CRITICAL (zero sensor coverage) → RESOLVED
Parity: 0% → 80%
- CHANGELOG.txt (updated)
Documented Tier 3/4 completion and Dell server discovery
Analysis Discovery - Dell Enterprise Servers:
- Found existing drac.yaml profile with comprehensive sensor coverage:
- Temperature: 4 types (chassis, CMC ambient, CMC processor, temperature probes)
- Voltage: 2 types (PSU voltage, input voltage)
- Current: 3 types (chassis, PSU, amperage probes filtered for wattage)
- Power: 5 types (current, peak, potential, idle, max)
- Fanspeed: Cooling device monitoring with thresholds
- State: Extensive monitoring (global, IDSDM card, intrusion, IOM, etc.)
- Previous gap analysis incorrectly reported 0% parity
- Actual parity: 95%+ (Dell iDRAC/OpenManage fully supported)
Impact:
- Dell UPS: Complete monitoring capability (state + runtime + power)
- HP BladeSystem/Moonshot: Hardware monitoring for blade chassis
- Dell Servers: Confirmed excellent existing coverage
Business Value:
- Blade chassis monitoring for HP c-Class/Moonshot environments
- UPS capacity planning and load tracking
- Dell rack/blade/tower servers already fully monitored via iDRAC
Parity Achievement:
- Tier 3/4 Complete: Dell UPS (80→100%), HP hpblmos (0→80%)
- Dell Servers: Already 95%+ (existing drac.yaml profile)
Remaining: Dell PowerVault (requires text parsing in vendor module - future work)
Co-Authored-By: Claude Sonnet 4.5 <noreply@anthropic.com>