- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1580 lines
50 KiB
Text
1580 lines
50 KiB
Text
-- Jacarta interSeptor MIB
|
|
-- MIB for interSeptor Environmental Monitoring System
|
|
--
|
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) jacarta(19011)
|
|
-- product(1) webAppliance(3) inSept(1)
|
|
-- ==============================================================================================
|
|
---
|
|
--- Revision History
|
|
---
|
|
--- V1.00 - Initial Release - July 03
|
|
--- V1.01 - Minor SNMP bug fix - Aug 03
|
|
--- v1.10 - Add temperature unit object - Oct, 15 2004
|
|
--- Add date format object
|
|
--- Add inSeptConfigAccessControlTable
|
|
--- Add object
|
|
--- v1.11 Change interSeptor-MIB to InterSeptor-MIB - Dec, 20 2004
|
|
--- Updated InSeptsensorConfigSensorEntry and SensorMonitorSensorEntry
|
|
--- V1.12 - Modified syntax error - May, 10 2005
|
|
--- Fixed SYNTAX InSeptConfigTrapsReceiversEntry
|
|
--- Changed SYNTAX inSeptConfigTrapsReceiversEntry to SYNTAX InSeptConfigTrapsReceiversEntry
|
|
--- V1.13 - Modified syntax error - June, 27 2006
|
|
--- Check error form http://wwwsnmp.cs.utwente.nl/ietf/mibs/validate/
|
|
--- ===========================================================================================
|
|
InterSeptor-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
jacarta OBJECT IDENTIFIER ::= { enterprises 19011 }
|
|
product OBJECT IDENTIFIER ::= { jacarta 1 }
|
|
webAppliance OBJECT IDENTIFIER ::= { product 3 }
|
|
inSept OBJECT IDENTIFIER ::= { webAppliance 1}
|
|
inSeptObjects OBJECT IDENTIFIER ::= { inSept 1 }
|
|
inSeptTraps OBJECT IDENTIFIER ::= { inSept 2 }
|
|
|
|
inSeptIdent OBJECT IDENTIFIER ::= { inSeptObjects 1 }
|
|
inSeptConfig OBJECT IDENTIFIER ::= { inSeptObjects 2 }
|
|
inSeptsensorMonitor OBJECT IDENTIFIER ::= { inSeptObjects 3 }
|
|
inSeptsensorConfig OBJECT IDENTIFIER ::= { inSeptObjects 4 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- inSeptIdentification
|
|
--
|
|
-- All objects in this group except for inSeptIdentName and
|
|
-- inSeptIdentAttachedDevices are set at device initialization
|
|
-- and remain static.
|
|
--
|
|
-- ===========================================================================
|
|
|
|
inSeptIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the interSeptor manufacturer."
|
|
::= { inSeptIdent 1 }
|
|
|
|
inSeptIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The interSeptor Model designation."
|
|
::= { inSeptIdent 2 }
|
|
|
|
inSeptIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The interSeptor software/firmware version."
|
|
::= { inSeptIdent 3 }
|
|
|
|
inSeptIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the interSeptor. This object should be
|
|
set by the administrator."
|
|
::= { inSeptIdent 4 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- inSeptConfig
|
|
--
|
|
-- ===========================================================================
|
|
|
|
inSeptConfigMibVersion OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The version of MIB spec."
|
|
::= { inSeptConfig 1}
|
|
|
|
inSeptConfigNetwork OBJECT IDENTIFIER ::= { inSeptConfig 2 }
|
|
|
|
inSeptConfigIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The ip address that NMS can identify the managed
|
|
device"
|
|
::= { inSeptConfigNetwork 1 }
|
|
|
|
inSeptConfigGateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The default gateway that allows the device to be managed
|
|
through routers "
|
|
::= { inSeptConfigNetwork 2 }
|
|
|
|
inSeptConfigSubnetMask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Internet address subnet mask"
|
|
::= { inSeptConfigNetwork 3 }
|
|
|
|
inSeptConfigDateTime OBJECT IDENTIFIER ::= { inSeptConfig 3 }
|
|
|
|
inSeptConfigDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (10..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date in inSept, format is (dd/mm/yyyy)"
|
|
::= { inSeptConfigDateTime 1}
|
|
|
|
inSeptConfigTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (8..8))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in interSeptor, format is (hh:mm:ss)"
|
|
::= { inSeptConfigDateTime 2}
|
|
|
|
inSeptConfigTimeFromNtp OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable update date/time from NTP server."
|
|
::= { inSeptConfigDateTime 3}
|
|
|
|
inSeptConfigNtpIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"NTP IP address."
|
|
::= { inSeptConfigDateTime 4}
|
|
|
|
inSeptConfigNtpTimeZone OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
gMT-1200(1),
|
|
gMT-1100(2),
|
|
gMT-1000(3),
|
|
gMT-0900(4),
|
|
gMT-0800(5),
|
|
gMT-0700(6),
|
|
gMT-0600(7),
|
|
gMT-0500(8),
|
|
gMT-0400(9),
|
|
gMT-0330(10),
|
|
gMT-0300(11),
|
|
gMT-0200(12),
|
|
gMT-0100(13),
|
|
gMT-0000(14),
|
|
gMT0100(15),
|
|
gMT0200(16),
|
|
gMT0300(17),
|
|
gMT0330(18),
|
|
gMT0400(19),
|
|
gMT0500(20),
|
|
gMT0530(21),
|
|
gMT0600(22),
|
|
gMT0700(23),
|
|
gMT0800(24),
|
|
gMT0900(25),
|
|
gMT1000(26),
|
|
gMT1100(27),
|
|
gMT1200(28)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable update date/time from NTP server."
|
|
::= { inSeptConfigDateTime 5}
|
|
|
|
inSeptConfigDayLightSaving OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable daylight saving for NTP time, if enabled, the time get from NTP will be set
|
|
set one hour in advance to reflect daylight saving status."
|
|
::= { inSeptConfigDateTime 6}
|
|
|
|
inSeptConfigLog OBJECT IDENTIFIER ::= { inSeptConfig 4 }
|
|
|
|
inSeptConfigHistoryLogFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (5..3600) -- in seconds
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The frequency of the update of the history log. The value
|
|
is in seconds"
|
|
::= { inSeptConfigLog 1}
|
|
|
|
inSeptConfigExtHistoryLogFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (1..1440) -- in minutes
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The frequency of the update of the extended history log.
|
|
The value is in seconds"
|
|
::= { inSeptConfigLog 2}
|
|
|
|
inSeptConfigConfigurationLog OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Enable/disable inSept to log parameter change."
|
|
::= { inSeptConfigLog 3}
|
|
|
|
inSeptConfigDhcpStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable DHCP/BootP capability"
|
|
::= { inSeptConfig 5}
|
|
|
|
inSeptConfigPingStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable Ping Echo capability"
|
|
::= { inSeptConfig 6}
|
|
|
|
inSeptConfigTftpStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable TFTP network upgrade capability"
|
|
::= { inSeptConfig 7}
|
|
|
|
inSeptConfigTelnet OBJECT IDENTIFIER ::= { inSeptConfig 8 }
|
|
|
|
inSeptConfigTelnetStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable telnet access"
|
|
::= { inSeptConfigTelnet 1}
|
|
|
|
inSeptConfigTelnetPortNumber OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting the server port of telnet."
|
|
::= { inSeptConfigTelnet 2}
|
|
|
|
inSeptConfigHttp OBJECT IDENTIFIER ::= { inSeptConfig 9 }
|
|
|
|
inSeptConfigHttpStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable HTTP access"
|
|
::= { inSeptConfigHttp 1}
|
|
|
|
inSeptConfigHttpPortNumber OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting the server port of HTTP."
|
|
::= { inSeptConfigHttp 2}
|
|
|
|
inSeptConfigHttpSecurity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable HTTP access for read-only users"
|
|
::= { inSeptConfigHttp 3}
|
|
|
|
|
|
inSeptConfigSnmp OBJECT IDENTIFIER ::= { inSeptConfig 10 }
|
|
inSeptConfigSnmpStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable SNMP access"
|
|
::= { inSeptConfigSnmp 1}
|
|
|
|
inSeptConfigSnmpPortNumber OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting the server port of SNMP."
|
|
::= { inSeptConfigSnmp 2}
|
|
|
|
inSeptConfigControl OBJECT IDENTIFIER ::= { inSeptConfig 11 }
|
|
inSeptConfigResetToDefault OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
reset(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reset all parameters of interSeptor to default value"
|
|
::= { inSeptConfigControl 1}
|
|
|
|
inSeptConfigRestart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
restart(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Restart interSeptor"
|
|
::= { inSeptConfigControl 2}
|
|
|
|
inSeptConfigTrap OBJECT IDENTIFIER ::= { inSeptConfig 12 }
|
|
inSeptConfigTrapRetryCount OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The count of repeat traps to send to NMS before trap
|
|
acknowledgement is received."
|
|
::= { inSeptConfigTrap 1}
|
|
|
|
inSeptConfigTrapRetryTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time between retrying to send traps to NMS."
|
|
::= { inSeptConfigTrap 2}
|
|
|
|
inSeptConfigTrapAckSignature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The signature of trap acknowledgement."
|
|
::= { inSeptConfigTrap 3}
|
|
|
|
|
|
inSeptConfigPollRate OBJECT-TYPE
|
|
SYNTAX INTEGER (3..60)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The frequency that interSeptor updates readings from sensors
|
|
(unit : second)."
|
|
::= { inSeptConfig 13}
|
|
|
|
inSeptConfigTrapsReceiversTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InSeptConfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send traps to. The number of
|
|
entries is given by the value of inSeptConfigNumTrapReceivers"
|
|
::= { inSeptConfig 14}
|
|
|
|
inSeptConfigTrapsReceiversEntry OBJECT-TYPE
|
|
SYNTAX InSeptConfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers to send traps to."
|
|
INDEX { inSepttrapsIndex}
|
|
::= { inSeptConfigTrapsReceiversTable 1 }
|
|
|
|
InSeptConfigTrapsReceiversEntry ::=
|
|
SEQUENCE {
|
|
inSepttrapsIndex
|
|
INTEGER,
|
|
inSepttrapsReceiverAddr
|
|
IpAddress,
|
|
inSeptreceiverCommunityString
|
|
DisplayString,
|
|
inSeptreceiverSeverityLevel
|
|
INTEGER,
|
|
inSeptreceiverDescription
|
|
DisplayString
|
|
}
|
|
|
|
inSepttrapsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2147483647)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a trap receiver entry."
|
|
::= { inSeptConfigTrapsReceiversEntry 1 }
|
|
|
|
inSepttrapsReceiverAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to send a trap to."
|
|
::= { inSeptConfigTrapsReceiversEntry 2 }
|
|
|
|
inSeptreceiverCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..19))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use in the trap when
|
|
sent to the manager."
|
|
::= { inSeptConfigTrapsReceiversEntry 3 }
|
|
|
|
inSeptreceiverSeverityLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
informational(1),
|
|
warning(2),
|
|
severe(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The severity level of traps to be received by this manager."
|
|
::= { inSeptConfigTrapsReceiversEntry 4 }
|
|
|
|
inSeptreceiverDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of trap receivers"
|
|
::= { inSeptConfigTrapsReceiversEntry 5 }
|
|
|
|
inSeptConfigAccessControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InSeptConfigAccessControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers which can access interSeptor with private
|
|
community string."
|
|
::= { inSeptConfig 15}
|
|
|
|
inSeptConfigAccessControlEntry OBJECT-TYPE
|
|
SYNTAX InSeptConfigAccessControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers."
|
|
INDEX { accessIndex}
|
|
::= { inSeptConfigAccessControlTable 1 }
|
|
|
|
InSeptConfigAccessControlEntry ::=
|
|
SEQUENCE {
|
|
accessIndex
|
|
INTEGER,
|
|
accessControlAddr
|
|
IpAddress,
|
|
accessCommunityString
|
|
DisplayString,
|
|
accessControlMode
|
|
INTEGER
|
|
}
|
|
|
|
accessIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2147483647)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a access control entry."
|
|
::= { inSeptConfigAccessControlEntry 1 }
|
|
|
|
accessControlAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to access interSeptor"
|
|
::= { inSeptConfigAccessControlEntry 2 }
|
|
|
|
accessCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..19))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use in the manager when
|
|
access interSeptor"
|
|
::= { inSeptConfigAccessControlEntry 3 }
|
|
|
|
accessControlMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
readOnly (1),
|
|
read-write (2),
|
|
notAccess (3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Access type, only read/Write access type can change parameter
|
|
of interSeptor"
|
|
::= { inSeptConfigAccessControlEntry 4 }
|
|
|
|
|
|
inSeptConfigTemperatureUnit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
celsius(1),
|
|
fahrenheit(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature unit of the system, can be Celsius or Farenheit"
|
|
::= { inSeptConfig 16}
|
|
|
|
inSeptConfigDateFormat OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
dd-mm-yyyy(1),
|
|
mm-dd-yyyy(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy"
|
|
::= { inSeptConfig 17}
|
|
|
|
|
|
-- Sensor Monitoring
|
|
|
|
inSeptsensorMonitorSensorNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of sensors that can be monitored."
|
|
::= { inSeptsensorMonitor 1}
|
|
|
|
inSeptsensorMonitorSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SensorMonitorSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of sensor devices to be monitored."
|
|
::= { inSeptsensorMonitor 2}
|
|
|
|
inSeptsensorMonitorSensorEntry OBJECT-TYPE
|
|
SYNTAX SensorMonitorSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The sensor device."
|
|
INDEX { inSeptsensorMonitorDeviceIndex}
|
|
::= { inSeptsensorMonitorSensorTable 1 }
|
|
|
|
SensorMonitorSensorEntry ::=
|
|
SEQUENCE {
|
|
inSeptsensorMonitorDeviceIndex
|
|
INTEGER,
|
|
inSeptsensorMonitorDeviceStatus
|
|
INTEGER,
|
|
inSeptsensorMonitorDeviceTemperature
|
|
INTEGER,
|
|
inSeptsensorMonitorDeviceTemperatureAlarm
|
|
INTEGER,
|
|
inSeptsensorMonitorDeviceHumidity
|
|
INTEGER,
|
|
inSeptsensorMonitorDeviceHumidityAlarm
|
|
INTEGER,
|
|
inSeptsensorMonitorAlarm1
|
|
INTEGER,
|
|
inSeptsensorMonitorAlarm2
|
|
INTEGER
|
|
}
|
|
|
|
inSeptsensorMonitorDeviceIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2147483647)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a sensor device entry."
|
|
::= { inSeptsensorMonitorSensorEntry 1 }
|
|
|
|
inSeptsensorMonitorDeviceStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
disabled(2),
|
|
eMD-HT(3),
|
|
eMD-T(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The device type connected to interSeptor."
|
|
::= { inSeptsensorMonitorSensorEntry 2 }
|
|
|
|
inSeptsensorMonitorDeviceTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature of sensor on device interSeptor, the unit is 0.1 degree."
|
|
::= { inSeptsensorMonitorSensorEntry 3 }
|
|
|
|
inSeptsensorMonitorDeviceTemperatureAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
disabled(2),
|
|
normal(3),
|
|
lowWarning(4),
|
|
lowCritical(5),
|
|
highWarning(6),
|
|
highCritical(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm type of sensor on device interSeptor."
|
|
::= { inSeptsensorMonitorSensorEntry 4 }
|
|
|
|
inSeptsensorMonitorDeviceHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The humidity of sensor on device interSeptor, the unit is 0.1%."
|
|
::= { inSeptsensorMonitorSensorEntry 5 }
|
|
|
|
inSeptsensorMonitorDeviceHumidityAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
disabled(2),
|
|
normal(3),
|
|
lowWarning(4),
|
|
lowCritical(5),
|
|
highWarning(6),
|
|
highCritical(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm type of sensor on device interSeptor."
|
|
::= { inSeptsensorMonitorSensorEntry 6 }
|
|
|
|
inSeptsensorMonitorAlarm1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
disabled(2),
|
|
active(3),
|
|
inactive(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The device status of sensor 1 connected to interSeptor."
|
|
::= { inSeptsensorMonitorSensorEntry 7 }
|
|
|
|
inSeptsensorMonitorAlarm2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
disabled(2),
|
|
active(3),
|
|
inactive(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The device status of sensor 2 connected to interSeptor."
|
|
::= { inSeptsensorMonitorSensorEntry 8 }
|
|
|
|
-- Sensor Configuration
|
|
|
|
inSeptsensorConfigSensorNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of sensors that are connected to interSeptor."
|
|
::= { inSeptsensorConfig 1 }
|
|
|
|
inSeptsensorConfigSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF InSeptsensorConfigSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of sensor devices to be configured."
|
|
::= { inSeptsensorConfig 2 }
|
|
|
|
inSeptsensorConfigSensorEntry OBJECT-TYPE
|
|
SYNTAX InSeptsensorConfigSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The sensor device."
|
|
INDEX { inSeptsensorConfigDeviceIndex }
|
|
::= { inSeptsensorConfigSensorTable 1 }
|
|
|
|
InSeptsensorConfigSensorEntry ::=
|
|
SEQUENCE {
|
|
inSeptsensorConfigDeviceIndex
|
|
INTEGER,
|
|
inSeptsensorConfigDeviceName
|
|
DisplayString,
|
|
inSeptsensorConfigDeviceState
|
|
INTEGER
|
|
}
|
|
|
|
inSeptsensorConfigDeviceIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2147483647)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a sensor device entry."
|
|
::= { inSeptsensorConfigSensorEntry 1 }
|
|
|
|
inSeptsensorConfigDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the sensor device for identification."
|
|
::= { inSeptsensorConfigSensorEntry 2 }
|
|
|
|
inSeptsensorConfigDeviceState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
auto(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The setup of sensor device type."
|
|
::= { inSeptsensorConfigSensorEntry 3 }
|
|
|
|
inSeptsensorConfigSensor1 OBJECT IDENTIFIER ::= { inSeptsensorConfig 3 }
|
|
|
|
inSeptsensorConfigSensor1DeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of sensor device."
|
|
::= { inSeptsensorConfigSensor1 1}
|
|
|
|
inSeptsensorConfigSensor1DeviceState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
auto(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The setup of sensor device type."
|
|
::= { inSeptsensorConfigSensor1 2 }
|
|
|
|
inSeptsensorConfigSensor1Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 3 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature sensor name."
|
|
::= { inSeptsensorConfigSensor1Temperature 1 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureLowWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 2 }
|
|
|
|
|
|
inSeptsensorConfigSensor1TemperatureLowCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 3 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureHighWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 4 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureHighCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 5 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureHysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to prevent too many alarms when temperature is hovering around the
|
|
set threshold."
|
|
::= { inSeptsensorConfigSensor1Temperature 6 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
temperatureIncrease0Point0(1),
|
|
temperatureIncrease0Point5(2),
|
|
temperatureIncrease1Point0(3),
|
|
temperatureIncrease1Point5(4),
|
|
temperatureIncrease2Point0(5),
|
|
temperatureIncrease2Point5(6),
|
|
temperatureIncrease3Point0(7),
|
|
temperatureMinus0Point5(8),
|
|
temperatureMinus1Point0(9),
|
|
temperatureMinus1Point5(10),
|
|
temperatureMinus2Point0(11),
|
|
temperatureMinus2Point5(12),
|
|
temperatureMinusPoint0(13)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to get the correct temperature according to your reference temperature."
|
|
::= { inSeptsensorConfigSensor1Temperature 7 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureLowWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 8 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureLowCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 9 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureHighWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 10 }
|
|
|
|
inSeptsensorConfigSensor1TemperatureHighCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor1Temperature 11 }
|
|
|
|
inSeptsensorConfigSensor1Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 4 }
|
|
|
|
inSeptsensorConfigSensor1HumdityName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The humidity sensor name."
|
|
::= { inSeptsensorConfigSensor1Humidity 1 }
|
|
|
|
inSeptsensorConfigSensor1HumidityLowWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 2 }
|
|
|
|
|
|
inSeptsensorConfigSensor1HumidityLowCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshole to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 3 }
|
|
|
|
inSeptsensorConfigSensor1HumidityHighWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 4 }
|
|
|
|
inSeptsensorConfigSensor1HumidityHighCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 5 }
|
|
|
|
inSeptsensorConfigSensor1HumidityHysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to prevent too many alarms when Humidity is hovering around the
|
|
set threshold."
|
|
::= { inSeptsensorConfigSensor1Humidity 6 }
|
|
|
|
inSeptsensorConfigSensor1HumidityCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
humidityIncrease0Point0(1),
|
|
humidityIncrease1Point0(2),
|
|
humidityIncrease2Point0(3),
|
|
humidityIncrease3Point0(4),
|
|
humidityIncrease4Point0(5),
|
|
humidityIncrease5Point0(6),
|
|
humidityIncrease6Point0(7),
|
|
humidityMinus1Point0(8),
|
|
humidityMinus2Point0(9),
|
|
humidityMinus3Point0(10),
|
|
humidityMinus4Point0(11),
|
|
humidityMinus5Point0(12),
|
|
humidityMinus6Point0(13)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to get the correct temperature according to your reference temperature."
|
|
::= { inSeptsensorConfigSensor1Humidity 7 }
|
|
|
|
inSeptsensorConfigSensor1HumidityLowWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 8 }
|
|
|
|
inSeptsensorConfigSensor1HumidityLowCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 9 }
|
|
|
|
inSeptsensorConfigSensor1HumidityHighWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 10 }
|
|
|
|
inSeptsensorConfigSensor1HumidityHighCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor1Humidity 11 }
|
|
|
|
inSeptsensorConfigSensor1Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 5 }
|
|
|
|
inSeptsensorConfigSensor1Alarm1Name OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of alarm-1."
|
|
::= { inSeptsensorConfigSensor1Alarm1 1 }
|
|
|
|
inSeptsensorConfigSensor1Alarm1State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
normalOpen(2),
|
|
normalClose(3),
|
|
highActive(4),
|
|
lowActive(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup the signal type to trigger alarm."
|
|
::= { inSeptsensorConfigSensor1Alarm1 2 }
|
|
|
|
inSeptsensorConfigSensor1Alarm1Hysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to delay the alarm triggered when event occurs."
|
|
::= { inSeptsensorConfigSensor1Alarm1 3 }
|
|
|
|
inSeptsensorConfigSensor1Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 6 }
|
|
|
|
inSeptsensorConfigSensor1Alarm2Name OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of alarm-1."
|
|
::= { inSeptsensorConfigSensor1Alarm2 1 }
|
|
|
|
inSeptsensorConfigSensor1Alarm2State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
normalOpen(2),
|
|
normalClose(3),
|
|
highActive(4),
|
|
lowActive(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup the signal type to trigger alarm."
|
|
::= { inSeptsensorConfigSensor1Alarm2 2 }
|
|
|
|
inSeptsensorConfigSensor1Alarm2Hysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to delay the alarm triggered when event occurs."
|
|
::= { inSeptsensorConfigSensor1Alarm2 3 }
|
|
|
|
inSeptsensorConfigSensor2 OBJECT IDENTIFIER ::= { inSeptsensorConfig 4 }
|
|
|
|
inSeptsensorConfigSensor2DeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of sensor device."
|
|
::= { inSeptsensorConfigSensor2 1}
|
|
|
|
inSeptsensorConfigSensor2DeviceState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
auto(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The setup of sensor device type."
|
|
::= { inSeptsensorConfigSensor2 2 }
|
|
|
|
inSeptsensorConfigSensor2Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 3 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The temperature sensor name."
|
|
::= { inSeptsensorConfigSensor2Temperature 1 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureLowWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 2 }
|
|
|
|
|
|
inSeptsensorConfigSensor2TemperatureLowCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 3 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureHighWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 4 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureHighCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 5 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureHysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to prevent too many alarms when temperature is hovering around the
|
|
set threshold."
|
|
::= { inSeptsensorConfigSensor2Temperature 6 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
temperatureIncrease0Point0(1),
|
|
temperatureIncrease0Point5(2),
|
|
temperatureIncrease1Point0(3),
|
|
temperatureIncrease1Point5(4),
|
|
temperatureIncrease2Point0(5),
|
|
temperatureIncrease2Point5(6),
|
|
temperatureIncrease3Point0(7),
|
|
temperatureMinus0Point5(8),
|
|
temperatureMinus1Point0(9),
|
|
temperatureMinus1Point5(10),
|
|
temperatureMinus2Point0(11),
|
|
temperatureMinus2Point5(12),
|
|
temperatureMinusPoint0(13)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to get the correct temperature according to your reference temperature."
|
|
::= { inSeptsensorConfigSensor2Temperature 7 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureLowWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 8 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureLowCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 9 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureHighWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 10 }
|
|
|
|
inSeptsensorConfigSensor2TemperatureHighCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor2Temperature 11 }
|
|
|
|
inSeptsensorConfigSensor2Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 4 }
|
|
|
|
inSeptsensorConfigSensor2HumdityName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The humidity sensor name."
|
|
::= { inSeptsensorConfigSensor2Humidity 1 }
|
|
|
|
inSeptsensorConfigSensor2HumidityLowWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 2 }
|
|
|
|
|
|
inSeptsensorConfigSensor2HumidityLowCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 3 }
|
|
|
|
inSeptsensorConfigSensor2HumidityHighWarning OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 4 }
|
|
|
|
inSeptsensorConfigSensor2HumidityHighCritical OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The threshold to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 5 }
|
|
|
|
inSeptsensorConfigSensor2HumidityHysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to prevent too many alarms when Humidity is hovering around the
|
|
set threshold."
|
|
::= { inSeptsensorConfigSensor2Humidity 6 }
|
|
|
|
inSeptsensorConfigSensor2HumidityCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
humidityIncrease0Point0(1),
|
|
humidityIncrease1Point0(2),
|
|
humidityIncrease2Point0(3),
|
|
humidityIncrease3Point0(4),
|
|
humidityIncrease4Point0(5),
|
|
humidityIncrease5Point0(6),
|
|
humidityIncrease6Point0(7),
|
|
humidityMinus1Point0(8),
|
|
humidityMinus2Point0(9),
|
|
humidityMinus3Point0(10),
|
|
humidityMinus4Point0(11),
|
|
humidityMinus5Point0(12),
|
|
humidityMinus6Point0(13)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to get the correct temperature according to your reference temperature."
|
|
::= { inSeptsensorConfigSensor2Humidity 7 }
|
|
|
|
inSeptsensorConfigSensor2HumidityLowWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low warning alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 8 }
|
|
|
|
inSeptsensorConfigSensor2HumidityLowCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger low critical alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 9 }
|
|
|
|
inSeptsensorConfigSensor2HumidityHighWarningStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high warning alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 10 }
|
|
|
|
inSeptsensorConfigSensor2HumidityHighCriticalStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable/disable the set point to trigger high critical alarm."
|
|
::= { inSeptsensorConfigSensor2Humidity 11 }
|
|
|
|
inSeptsensorConfigSensor2Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 5 }
|
|
|
|
inSeptsensorConfigSensor2Alarm1Name OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of alarm-1."
|
|
::= { inSeptsensorConfigSensor2Alarm1 1 }
|
|
|
|
inSeptsensorConfigSensor2Alarm1State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
normalOpen(2),
|
|
normalClose(3),
|
|
highActive(4),
|
|
lowActive(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup the signal type to trigger alarm."
|
|
::= { inSeptsensorConfigSensor2Alarm1 2 }
|
|
|
|
inSeptsensorConfigSensor2Alarm1Hysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to delay the alarm triggered when event occurs."
|
|
::= { inSeptsensorConfigSensor2Alarm1 3 }
|
|
|
|
inSeptsensorConfigSensor2Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 6 }
|
|
|
|
inSeptsensorConfigSensor2Alarm2Name OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of alarm-1."
|
|
::= { inSeptsensorConfigSensor2Alarm2 1 }
|
|
|
|
inSeptsensorConfigSensor2Alarm2State OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
normalOpen(2),
|
|
normalClose(3),
|
|
highActive(4),
|
|
lowActive(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setup the signal type to trigger alarm."
|
|
::= { inSeptsensorConfigSensor2Alarm2 2 }
|
|
|
|
inSeptsensorConfigSensor2Alarm2Hysteresis OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set value to delay the alarm triggered when event occurs."
|
|
::= { inSeptsensorConfigSensor2Alarm2 3 }
|
|
|
|
|
|
-- ===========================================================================
|
|
-- inSeptTraps
|
|
--
|
|
-- Traps group
|
|
-- ===========================================================================
|
|
-- This section defines the well-known notifications sent by
|
|
-- inSept agents.
|
|
-- Care must be taken to ensure that no particular notification
|
|
-- is sent to a single receiving entity more often than once
|
|
-- every five seconds.
|
|
|
|
inSeptCommunicationRestored TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Communication between interSeptor and sensor has been
|
|
established."
|
|
::= 1
|
|
|
|
inSeptCommunicationLost TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"WARNING: Communication between interSeptor and sensor has been
|
|
lost."
|
|
::= 2
|
|
|
|
inSeptAlarm1Inactive TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Alarm1 of sensor has returned from active state."
|
|
::= 3
|
|
|
|
inSeptAlarm1Active TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"WARNING: Alarm1 has become active."
|
|
::= 4
|
|
|
|
inSeptAlarm2Inactive TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Alarm2 of sensor has returned from active state."
|
|
::= 5
|
|
|
|
inSeptAlarm2Active TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"WARNING: Alarm2 has become active."
|
|
::= 6
|
|
|
|
inSeptTemperatureNotHighWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The temperature of sensor has returned from High warning to normal."
|
|
::= 7
|
|
|
|
inSeptTemperatureHighWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"WARNING: The temperature of sensor is higher than High warning set point."
|
|
::= 8
|
|
|
|
inSeptTemperatureNotLowWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The temperature of sensor has returned from low warning to normal."
|
|
::= 9
|
|
|
|
inSeptTemperatureLowWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"WARNING: The temperature of sensor is lower than low warning set point."
|
|
::= 10
|
|
|
|
inSeptTemperatureNotHighCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The temperature of sensor is lower than high critical set point."
|
|
::= 11
|
|
|
|
inSeptTemperatureHighCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"CRITICAL: The temperature of sensor is higher than high critical set point."
|
|
::= 12
|
|
|
|
inSeptTemperatureNotLowCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The temperature of sensor is higher than low critical set point."
|
|
::= 13
|
|
|
|
inSeptTemperatureLowCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"CRITICAL: The temperature of sensor is lower than low critical set point."
|
|
::= 14
|
|
|
|
inSeptHumidityNotHighWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The humidity of sensor has returned from High warning to normal."
|
|
::= 15
|
|
|
|
inSeptHumidityHighWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"WARNING: The humidity of sensor is higher than High warning set point."
|
|
::= 16
|
|
|
|
inSeptHumidityNotLowWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The humidity of sensor has returned from low warning to normal."
|
|
::= 17
|
|
|
|
inSeptHumidityLowWarning TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"WARNING: The humidity of sensor is lower than low warning set point."
|
|
::= 18
|
|
|
|
inSeptHumidityNotHighCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The humidity of sensor is lower than high critical set point."
|
|
::= 19
|
|
|
|
inSeptHumidityHighCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"CRITICAL: The humidity of sensor is higher than high critical set point."
|
|
::= 20
|
|
|
|
inSeptHumidityNotLowCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The humidity of sensor is higher than low critical set point."
|
|
::= 21
|
|
|
|
inSeptHumidityLowCritical TRAP-TYPE
|
|
ENTERPRISE inSeptTraps
|
|
DESCRIPTION
|
|
"CRITICAL: The humidity of sensor is lower than low critical set point."
|
|
::= 22
|
|
|
|
END
|
|
|