- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
3903 lines
112 KiB
Text
3903 lines
112 KiB
Text
-- ****************************************************************************
|
|
-- * APC cPDU SNMP MIB DEFINITIONS
|
|
-- * $Date: 8 MAY 2025 06:00:00 $
|
|
-- * $Revision: 1.9 $
|
|
-- Revised
|
|
-- -> Line to Line OID addition
|
|
-- ****************************************************************************
|
|
-- * APC cPDU SNMP MIB DEFINITIONS
|
|
-- * $Date: 27 AUGUST 2024 09:00:00 $
|
|
-- * $Revision: 1.8 $
|
|
-- Revised
|
|
-- Confidential - Need To Know
|
|
-- ****************************************************************************
|
|
--
|
|
-- APC cPDU SNMP
|
|
-- Management Information Base for SNMP Network Management for PDU
|
|
--
|
|
-- Copyright (c) 2021 APC
|
|
--
|
|
-- The APC Enterprise number is 318.
|
|
-- The ASN.1 prefix to, and including the APC is:
|
|
-- 1.3.6.1.4.1.318
|
|
--
|
|
-- MIB Version 1.7
|
|
--
|
|
-- *********************************************************************
|
|
-- Release History
|
|
--
|
|
-- Added following OIDs to mib table.(27 AUGUST 2024)
|
|
-- -> pduUnitConfigUsb - Displays/Configures USB status enbaled or disabled.
|
|
-- -> pduUnitConfigDaisyChainState - Displays/Configures Daisychain state as QNA or RNA.
|
|
-- -> pduUnitConfigTelnet - Displays/Configure status of Telnet feature as ON or OFF.
|
|
-- -> pduUnitPsSupportUpstreamStatus - Deprecated.
|
|
-- -> pduUnitPsSupportDownstreamStatus - Deprecated.
|
|
-- -> pduUnitPsFunc - Displays/Configures Power Share Functionality as Enable or Disable.
|
|
-- -> pduUnitPsBackupProtection - Displays Power Share support status from adjacent PDUs.
|
|
-- -> pduUnitPsOutput - Displays Power Share support status to adjacent PDU.
|
|
-- -> pduExternalSensorConfigAlarmResetThreshold - Displays/Configures sensors reset threshold value.
|
|
-- -> pduExternalSensorConfigAlarmStateChangeDelay - Displays/Configures sensors state change delay value.
|
|
-- -> pduExternalSensorSTATUSAisle - Displays Aisle status as hot or cold.
|
|
--
|
|
-- Added following OIDs to mib table.
|
|
-- -> pduNamePlateIPV6Address - Displays both Local and Global address of IPV6.
|
|
-- -> pduNamePlateHWVersion - Displays Hardware version of the PDU.
|
|
-- -> pduUnitStatusPowerFactor - Displays Power Factor value of total PDU.
|
|
-- -> pduCircuitBreakerStatusPowerFactor - Displays Power Factor value of circuit breaker.
|
|
-- -> pduInputPhaseStatusPowerFactor - Displays Power Factor value of each Phases.
|
|
-- *********************************************************************
|
|
-- ===================================================================================
|
|
-- sysDescr (1.3.6.1.2.1.1.1) which is defined in RFC1213.MIB.
|
|
-- sysObjectID (1.3.6.1.2.1.1.2) which is defined in RFC1213.MIB.
|
|
-- sysContact (1.3.6.1.2.1.1.4) which is defined in RFC1213.MIB.
|
|
-- sysName (1.3.6.1.2.1.1.5) is which is defined in RFC1213.MIB.
|
|
-- sysLocation (1.3.6.1.2.1.1.6) which is defined in RFC1213.MIB.
|
|
--
|
|
-- sysDescr OBJECT-TYPE
|
|
-- SYNTAX DisplayString (SIZE (0..255))
|
|
-- ACCESS read-only
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "A textual description of the entity. This value
|
|
-- should include the full name, hardware version and
|
|
-- firmware version of management module's.
|
|
-- It is mandatory that this only contain
|
|
-- printable ASCII characters."
|
|
-- ::= { system 1 }
|
|
--
|
|
-- sysObjectID OBJECT-TYPE
|
|
-- SYNTAX DisplayString (SIZE (0..255))
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "Return the OID of the management module for PDU defined in the APC.MIB
|
|
-- i.e. .1.3.6.1.4.1.318.1.1.32 is for OIDs."
|
|
-- ::= { system 2 }
|
|
--
|
|
-- sysContact OBJECT-TYPE
|
|
-- SYNTAX DisplayString (SIZE (0..255))
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The textual identification of the contact person
|
|
-- for this managed node, together with information
|
|
-- on how to contact this person."
|
|
-- ::= { system 4 }
|
|
--
|
|
-- sysName OBJECT-TYPE
|
|
-- SYNTAX DisplayString (SIZE (0..255))
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "An administratively-assigned name for this
|
|
-- managed node. By convention, this is the node's
|
|
-- fully-qualified domain name."
|
|
-- ::= { system 5 }
|
|
--
|
|
-- sysLocation OBJECT-TYPE
|
|
-- SYNTAX DisplayString (SIZE (0..255))
|
|
-- ACCESS read-write
|
|
-- STATUS mandatory
|
|
-- DESCRIPTION
|
|
-- "The physical location of this node (e.g.,
|
|
-- `telephone closet, 3rd floor')."
|
|
-- ::= { system 6 }
|
|
--
|
|
-- ====================================================================================
|
|
--
|
|
-- ====================================================================================
|
|
PowerNet-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress, Gauge, TimeTicks FROM RFC1155-SMI
|
|
DisplayString, sysDescr FROM RFC1213-MIB
|
|
SnmpAdminString FROM SNMP-FRAMEWORK-MIB
|
|
OBJECT-TYPE FROM RFC-1212
|
|
TRAP-TYPE FROM RFC-1215
|
|
InetAddressType FROM INET-ADDRESS-MIB
|
|
InetAddress FROM INET-ADDRESS-MIB
|
|
MacAddress FROM SNMPv2-TC;
|
|
-- IMPORTS End
|
|
|
|
apc OBJECT IDENTIFIER ::= { enterprises 318 }
|
|
|
|
products OBJECT IDENTIFIER ::= { apc 1 }
|
|
|
|
hardware OBJECT IDENTIFIER ::= { products 1 }
|
|
|
|
cPDU OBJECT IDENTIFIER ::= { hardware 32 }
|
|
-- ++++ Start of cPDU ++++
|
|
|
|
pduNamePlate OBJECT IDENTIFIER ::= { cPDU 1 }
|
|
pduUnit OBJECT IDENTIFIER ::= { cPDU 2 }
|
|
pduInputPhase OBJECT IDENTIFIER ::= { cPDU 3 }
|
|
pduCircuitBreaker OBJECT IDENTIFIER ::= { cPDU 4 }
|
|
pduOutlet OBJECT IDENTIFIER ::= { cPDU 5 }
|
|
pduExternalSensor OBJECT IDENTIFIER ::= { cPDU 6 }
|
|
pduSmartCabinet OBJECT IDENTIFIER ::= { cPDU 7 }
|
|
pduTraps OBJECT IDENTIFIER ::= { cPDU 8 }
|
|
pduEhandle OBJECT IDENTIFIER ::= { cPDU 9 }
|
|
|
|
-- Start pduNamePlate
|
|
|
|
pduNamePlateTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of PDUs"
|
|
::= { pduNamePlate 1 }
|
|
|
|
-- pduNamePlateTable
|
|
pduNamePlateTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduNamePlateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU nameplate data"
|
|
::= { pduNamePlate 2 }
|
|
|
|
pduNamePlateEntry OBJECT-TYPE
|
|
SYNTAX PduNamePlateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Nameplate data from the PDU being queried. The numbers of entries equals the value of pduNamePlateTableSize."
|
|
INDEX { pduNamePlateIndex }
|
|
::= { pduNamePlateTable 1 }
|
|
|
|
PduNamePlateEntry ::= SEQUENCE {
|
|
pduNamePlateIndex
|
|
Integer32,
|
|
pduNamePlateName
|
|
DisplayString,
|
|
pduNamePlateLocation
|
|
DisplayString,
|
|
pduNamePlateInetAddressType
|
|
INTEGER,
|
|
pduNamePlateIPAddress
|
|
InetAddress,
|
|
pduNamePlateInetNetMask
|
|
InetAddress,
|
|
pduNamePlateInetGateway
|
|
InetAddress,
|
|
pduNamePlateMACAddress
|
|
MacAddress,
|
|
pduNamePlateUTCTimeOffset
|
|
DisplayString,
|
|
pduNamePlateModelNumber
|
|
DisplayString,
|
|
pduNamePlatePartNumber
|
|
DisplayString,
|
|
pduNamePlateSerialNumber
|
|
DisplayString,
|
|
pduNamePlateDateofManufacture
|
|
DisplayString,
|
|
pduNamePlateFirmwareVersion
|
|
DisplayString,
|
|
pduNamePlateFirmwareVersionTimeStamp
|
|
DisplayString,
|
|
pduNamePlateType
|
|
INTEGER,
|
|
pduNamePlateIPV6Address
|
|
DisplayString,
|
|
pduNamePlateHWVersion
|
|
DisplayString
|
|
}
|
|
|
|
pduNamePlateIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU nameplate table entry"
|
|
::= { pduNamePlateEntry 1 }
|
|
|
|
pduNamePlateName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the PDU"
|
|
::= { pduNamePlateEntry 2 }
|
|
|
|
pduNamePlateLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the location of PDU"
|
|
::= { pduNamePlateEntry 3 }
|
|
|
|
pduNamePlateInetAddressType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of address format"
|
|
::= { pduNamePlateEntry 4 }
|
|
|
|
pduNamePlateIPAddress OBJECT-TYPE
|
|
SYNTAX InetAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current IP address. A value of 0.0.0.0 indicates an error or an unset option"
|
|
::= { pduNamePlateEntry 5 }
|
|
|
|
pduNamePlateInetNetMask OBJECT-TYPE
|
|
SYNTAX InetAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current netmask. A value of 0.0.0.0 indiates an error or an unset option"
|
|
::= { pduNamePlateEntry 6 }
|
|
|
|
pduNamePlateInetGateway OBJECT-TYPE
|
|
SYNTAX InetAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current gateway. A value of 0.0.0.0 indicates an error or an unset option"
|
|
::= { pduNamePlateEntry 7 }
|
|
|
|
pduNamePlateMACAddress OBJECT-TYPE
|
|
SYNTAX MacAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The assigned MAC address for the PDU"
|
|
::= { pduNamePlateEntry 8 }
|
|
|
|
pduNamePlateUTCTimeOffset OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The difference in hours and minutes from Coordinated Universal
|
|
Time(UTC) for the time used in a particular time zone"
|
|
::= { pduNamePlateEntry 9 }
|
|
|
|
pduNamePlateModelNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU model number"
|
|
::= { pduNamePlateEntry 10 }
|
|
pduNamePlatePartNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU part number"
|
|
::= { pduNamePlateEntry 11 }
|
|
|
|
pduNamePlateSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU serial number"
|
|
::= { pduNamePlateEntry 12 }
|
|
|
|
pduNamePlateDateofManufacture OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date the PDU was manufactured in mm/dd/yyyy format"
|
|
::= { pduNamePlateEntry 13 }
|
|
|
|
pduNamePlateFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU firmware version"
|
|
::= { pduNamePlateEntry 14 }
|
|
|
|
pduNamePlateFirmwareVersionTimeStamp OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Timestamp of when the PDU firmware was last updated"
|
|
::= { pduNamePlateEntry 15 }
|
|
|
|
pduNamePlateType OBJECT-TYPE
|
|
SYNTAX INTEGER {singlePhase (1),delta (2),wye (3)}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of input"
|
|
::= { pduNamePlateEntry 16 }
|
|
|
|
pduNamePlateIPV6Address OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current IPV6 address. A value of 0.0.0.0 indicates an error or an unset option"
|
|
::= { pduNamePlateEntry 17 }
|
|
|
|
pduNamePlateHWVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Displays Hardware version of the PDU."
|
|
::= { pduNamePlateEntry 18 }
|
|
|
|
-- Start pduUnit
|
|
|
|
pduUnitTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of units."
|
|
::= { pduUnit 1 }
|
|
|
|
pduUnitConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduUnitConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU configuration data"
|
|
::= { pduUnit 2 }
|
|
|
|
pduUnitConfigEntry OBJECT-TYPE
|
|
SYNTAX PduUnitConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration data from the PDU being queried. The number of entries equals the value of pduUnitTableSize"
|
|
INDEX { pduUnitConfigIndex }
|
|
::= { pduUnitConfigTable 1 }
|
|
|
|
PduUnitConfigEntry ::= SEQUENCE {
|
|
pduUnitConfigIndex
|
|
Integer32,
|
|
pduUnitConfigName
|
|
DisplayString,
|
|
pduUnitConfigLocation
|
|
DisplayString,
|
|
pduUnitConfigDisplayOrientation
|
|
INTEGER,
|
|
pduUnitConfigOledDisplayControl
|
|
INTEGER,
|
|
pduUnitConfigColdstartDelay
|
|
Unsigned32,
|
|
pduUnitConfigGlobalOutletStateOnStartup
|
|
INTEGER,
|
|
pduUnitConfigLowerCriticalThreshold
|
|
Unsigned32,
|
|
pduUnitConfigLowerWarningThreshold
|
|
Unsigned32,
|
|
pduUnitConfigUpperCriticalThreshold
|
|
Unsigned32,
|
|
pduUnitConfigUpperWarningThreshold
|
|
Unsigned32,
|
|
pduUnitConfigAlarmResetThreshold
|
|
Unsigned32,
|
|
pduUnitConfigAlarmStateChangeDelay
|
|
Unsigned32,
|
|
pduUnitConfigEnabledThresholds
|
|
BITS,
|
|
pduUnitConfigPeakPowerReset
|
|
INTEGER,
|
|
pduUnitConfigEnergyReset
|
|
INTEGER,
|
|
pduUnitConfigOutletPeakPowerReset
|
|
INTEGER,
|
|
pduUnitConfigOutletEnergyReset
|
|
INTEGER,
|
|
pduUnitConfigSsh
|
|
INTEGER,
|
|
pduUnitConfigResetNetworkManagementCard
|
|
INTEGER,
|
|
pduUnitConfigUsb
|
|
INTEGER,
|
|
pduUnitConfigDaisyChainState
|
|
INTEGER,
|
|
pduUnitConfigTelnet
|
|
INTEGER
|
|
}
|
|
|
|
pduUnitConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Unit Config Entry"
|
|
::= { pduUnitConfigEntry 1 }
|
|
|
|
pduUnitConfigName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the PDU"
|
|
::= { pduUnitConfigEntry 2 }
|
|
|
|
pduUnitConfigLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the location of the PDU"
|
|
::= { pduUnitConfigEntry 3 }
|
|
|
|
pduUnitConfigDisplayOrientation OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
displayNormal (1),
|
|
displayReverse (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the intended physical orientation of the oLED display
|
|
displayNormal (1) indicates normal orientation.
|
|
displayReverse (2) indicates upside down orientation
|
|
NOTE:
|
|
This OID is compatible only with the two display NMC module. It does not work with the single display NMC module."
|
|
::= { pduUnitConfigEntry 4 }
|
|
|
|
pduUnitConfigOledDisplayControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
displayOff (1),
|
|
displayOn (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Used to turn oled display On or Off
|
|
displayOff (1) to turn dispaly OFF.
|
|
displayOn (2) to turn dispaly ON"
|
|
::= { pduUnitConfigEntry 5 }
|
|
|
|
pduUnitConfigColdstartDelay OBJECT-TYPE
|
|
SYNTAX Unsigned32 (0..3600)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, specified in seconds, between when power
|
|
is provided to the PDU and when the PDU start providing basic master
|
|
power to the outlets"
|
|
::= { pduUnitConfigEntry 6 }
|
|
|
|
pduUnitConfigGlobalOutletStateOnStartup OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
lastKnownState (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The outlet state on device startup; applies to all outlets
|
|
unless overridden at the outlet level"
|
|
::= { pduUnitConfigEntry 7 }
|
|
|
|
pduUnitConfigLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower critical unit active power alarm threshold measured in Watts"
|
|
::= { pduUnitConfigEntry 8 }
|
|
|
|
pduUnitConfigLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower non-critical (warning) unit active power alarm threshold measured in Watts"
|
|
::= { pduUnitConfigEntry 9 }
|
|
|
|
pduUnitConfigUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper critical unit active power alarm threshold measured in Watts"
|
|
::= { pduUnitConfigEntry 10 }
|
|
|
|
pduUnitConfigUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper non-critical (warning) unit active power alarm threshold measured in Watts"
|
|
::= { pduUnitConfigEntry 11 }
|
|
|
|
pduUnitConfigAlarmResetThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions in Watts"
|
|
::= { pduUnitConfigEntry 12 }
|
|
|
|
pduUnitConfigAlarmStateChangeDelay OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n, then the assertion condition must exist for n+1 consecutive samples before the corresponding assertion event is reported."
|
|
::= { pduUnitConfigEntry 13 }
|
|
|
|
pduUnitConfigEnabledThresholds OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
lowerCritical (0),
|
|
lowerWarning (1),
|
|
upperWarning (2),
|
|
upperCritical (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string indicating which alarm thresholds are enabled"
|
|
::= { pduUnitConfigEntry 14 }
|
|
|
|
pduUnitConfigPeakPowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noOperation (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to reset (2) will cause the existing peak power value
|
|
to be replaced by the current load power value. Getting this OID will
|
|
do nothing and return the noOperation(1) value. "
|
|
::= { pduUnitConfigEntry 15 }
|
|
|
|
pduUnitConfigEnergyReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noOperation (1),
|
|
reset (2),
|
|
notSupported (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to reset (2) will cause the device energy meter value
|
|
to be reset to zero. Getting this OID in models that support this
|
|
feature will do nothing and return the noOperation(1) value. Models
|
|
that do not support this feature will respond to this OID with a
|
|
value of notSupported (3). Attempts to set this OID in these models will fail. "
|
|
::= { pduUnitConfigEntry 16 }
|
|
|
|
pduUnitConfigOutletPeakPowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noOperation (1),
|
|
reset (2),
|
|
notSupported (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to reset (2) will cause the outlet peak power meter value
|
|
to be reset to zero. Getting this OID in models that support this
|
|
feature will do nothing and return the noOperation(1) value. Models
|
|
that do not support this feature will respond to this OID with a
|
|
value of notSupported (3). Attempts to set this OID in these models will fail. "
|
|
::= { pduUnitConfigEntry 17 }
|
|
|
|
pduUnitConfigOutletEnergyReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noOperation (1),
|
|
reset (2),
|
|
notSupported (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to reset (2) will cause the outlet energy meter value
|
|
to be reset to zero. Getting this OID in models that support this
|
|
feature will do nothing and return the noOperation(1) value. Models
|
|
that do not support this feature will respond to this OID with a
|
|
value of notSupported (3). Attempts to set this OID in these models will fail. "
|
|
::= { pduUnitConfigEntry 18 }
|
|
|
|
pduUnitConfigSsh OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to off(0) will disable the SSH connection. Setting this OID to on(1) will enable the SSH connection."
|
|
::= { pduUnitConfigEntry 19 }
|
|
|
|
pduUnitConfigResetNetworkManagementCard OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noOperation (0),
|
|
reset (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Getting this OID will return noOperation(0). Setting this OID to reset(1) will reset NMC."
|
|
::= { pduUnitConfigEntry 20 }
|
|
|
|
pduUnitConfigUsb OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to off(0) will disable the USB port. Setting this OID to on(1) will enable the USB port."
|
|
::= { pduUnitConfigEntry 21 }
|
|
|
|
pduUnitConfigDaisyChainState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
daisychainqna (0),
|
|
daisychainrna (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to 0 will enable daisychain qna mode.
|
|
Setting this OID to 1 will enable daisychain rna mode. Should be applied on last pdu in DaisyChain"
|
|
::= { pduUnitConfigEntry 22 }
|
|
|
|
pduUnitConfigTelnet OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to off(0) will disable the Telnet connection. Setting this OID to on(1) will enable the Telnet connection.
|
|
Changes made will take effect only after reboot."
|
|
::= { pduUnitConfigEntry 23 }
|
|
|
|
pduUnitPropertiesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduUnitPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU properties"
|
|
::= { pduUnit 3 }
|
|
|
|
pduUnitPropertiesEntry OBJECT-TYPE
|
|
SYNTAX PduUnitPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unit properties entry containing objects for a particular unit."
|
|
INDEX { pduUnitPropertiesIndex }
|
|
::= { pduUnitPropertiesTable 1 }
|
|
|
|
PduUnitPropertiesEntry ::= SEQUENCE {
|
|
pduUnitPropertiesIndex
|
|
Integer32,
|
|
pduUnitPropertiesName
|
|
DisplayString,
|
|
pduUnitPropertiesOutletCount
|
|
Integer32,
|
|
pduUnitPropertiesSwitchedOutletCount
|
|
Integer32,
|
|
pduUnitPropertiesMeteredOutletCount
|
|
Integer32,
|
|
pduUnitPropertiesInputPhaseCount
|
|
Integer32,
|
|
pduUnitPropertiesCircuitBreakerCount
|
|
Integer32,
|
|
pduUnitPropertiesMaxExternalSensorCount
|
|
Integer32,
|
|
pduUnitPropertiesConnExternalSensorCount
|
|
Integer32,
|
|
pduUnitPropertiesRatedVoltage
|
|
DisplayString,
|
|
pduUnitPropertiesRatedMaxCurrent
|
|
DisplayString,
|
|
pduUnitPropertiesRatedFrequency
|
|
DisplayString,
|
|
pduUnitPropertiesRatedPower
|
|
DisplayString,
|
|
pduUnitPropertiesOrientation
|
|
INTEGER,
|
|
pduUnitPropertiesOutletLayout
|
|
INTEGER,
|
|
pduUnitPropertiesCascadeMemberType
|
|
INTEGER
|
|
}
|
|
|
|
pduUnitPropertiesIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU properties table entry"
|
|
::= { pduUnitPropertiesEntry 1 }
|
|
|
|
pduUnitPropertiesName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the PDU"
|
|
::= { pduUnitPropertiesEntry 2 }
|
|
|
|
pduUnitPropertiesOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of outlets on the PDU"
|
|
::= { pduUnitPropertiesEntry 3 }
|
|
|
|
pduUnitPropertiesSwitchedOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of switched outlets on the PDU"
|
|
::= { pduUnitPropertiesEntry 4 }
|
|
|
|
pduUnitPropertiesMeteredOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of metered outlets on the PDU"
|
|
::= { pduUnitPropertiesEntry 5 }
|
|
|
|
pduUnitPropertiesInputPhaseCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of phases on the PDU"
|
|
::= { pduUnitPropertiesEntry 6 }
|
|
|
|
pduUnitPropertiesCircuitBreakerCount OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of circuit breaker on the PDU"
|
|
::= { pduUnitPropertiesEntry 7 }
|
|
|
|
pduUnitPropertiesMaxExternalSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum number of external sensors that can be connected to the PDU"
|
|
::= { pduUnitPropertiesEntry 8 }
|
|
|
|
pduUnitPropertiesConnExternalSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current number of external sensors connected to the PDU"
|
|
::= { pduUnitPropertiesEntry 9 }
|
|
|
|
pduUnitPropertiesRatedVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU voltage rating in Volts"
|
|
::= { pduUnitPropertiesEntry 10 }
|
|
|
|
pduUnitPropertiesRatedMaxCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU current rating in Amps"
|
|
::= { pduUnitPropertiesEntry 11 }
|
|
|
|
pduUnitPropertiesRatedFrequency OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU frequency rating in Hz"
|
|
::= { pduUnitPropertiesEntry 12 }
|
|
|
|
pduUnitPropertiesRatedPower OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU VA (VoltAmps) rating."
|
|
::= { pduUnitPropertiesEntry 13 }
|
|
|
|
pduUnitPropertiesOrientation OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
horizontal (1),
|
|
vertical (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU orientation "
|
|
::= { pduUnitPropertiesEntry 14 }
|
|
|
|
pduUnitPropertiesOutletLayout OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
seqPhaseToNuetral (1),
|
|
seqPhaseToPhase (2),
|
|
seqPhToNeu21PhToPh (3),
|
|
seqPhToPhGrouped (4),
|
|
seqPhToNGrouped (5),
|
|
seqPToN1516PToPGrouped (6),
|
|
seqPhToPh2xGrouped (7),
|
|
seqPhToN2xGrouped (8),
|
|
seqNotApplicable (9)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The outlet layout for the PDU. Getting this OID will return outlet layout for the device.
|
|
seqPhaseToNeutral(1) indicates outlet layout as follows:
|
|
1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,...
|
|
seqPhaseToPhase(2) indicates outlet layout as follows:
|
|
1:1-2,2:2-3,3:3-1,4:1-2,5:2-3,...
|
|
seqPhToNeu21PhToPh(3) indicates outlet layout as follows:
|
|
1:1-N,2:2-N...21:3-N,22:1-2,23:2-3,24:3-1,...
|
|
seqPhToPhGrouped(4) indicates outlet layout as follows:
|
|
This unit has 3 outlet groups. Group 1:1-2, Group 2:2-3, Group 3:3-1.
|
|
seqPhToNGrouped(5) indicates outlet layout as follows:
|
|
This unit has 3 outlet groups. Group 1:1-N, Group 2:2-N, Group 3:3-N.
|
|
seqPToN1516PToPGrouped(6) indicates outlet layout as follows:
|
|
This unit has 4 outlet groups. Group 1 (Outlets 1-14):1-2,
|
|
Group 2 (Outlets 15-16):1-N, Group 3:2-3, Group 4:3-1.
|
|
seqPhToPh2xGrouped(7) indicates outlet layout as follows:
|
|
This unit has 6 outlet groups. Group 1:1-2, Group 2:1-2, Group 3:2-3,
|
|
Group 4:2-3, Group 5:3-1, Group 6:3-1.
|
|
seqPhToN2xGrouped(8) indicates outlet layout as follows:
|
|
This unit has 6 outlet groups. Group 1:1-N, Group 2:1-N, Group 3:2-N,
|
|
Group 4:2-N, Group 5:3-N, Group 6:3-N.
|
|
seqNotApplicable(9):"
|
|
::= { pduUnitPropertiesEntry 15 }
|
|
|
|
pduUnitPropertiesCascadeMemberType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
standalone (1),
|
|
parent (2),
|
|
child (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The cascading member type"
|
|
::= { pduUnitPropertiesEntry 16 }
|
|
|
|
pduUnitStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduUnitStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU status information"
|
|
::= { pduUnit 4 }
|
|
|
|
pduUnitStatusEntry OBJECT-TYPE
|
|
SYNTAX PduUnitStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status information from the PDU being queried"
|
|
INDEX { pduUnitStatusIndex }
|
|
::= { pduUnitStatusTable 1 }
|
|
|
|
PduUnitStatusEntry ::= SEQUENCE {
|
|
pduUnitStatusIndex
|
|
Integer32,
|
|
pduUnitStatusName
|
|
DisplayString,
|
|
pduUnitStatusLoadState
|
|
INTEGER,
|
|
pduUnitStatusActivePower
|
|
Integer32,
|
|
pduUnitStatusApparentPower
|
|
Integer32,
|
|
pduUnitStatusPeakPower
|
|
Integer32,
|
|
pduUnitStatusPeakPowerTimestamp
|
|
DisplayString,
|
|
pduUnitStatusPeakPowerStartTime
|
|
DisplayString,
|
|
pduUnitStatusEnergy
|
|
Integer32,
|
|
pduUnitStatusResettableEnergy
|
|
Integer32,
|
|
pduUnitStatusEnergyStartTime
|
|
DisplayString,
|
|
pduUnitStatusOutletsEnergyStartTime
|
|
DisplayString,
|
|
pduUnitStatusPowerFactor
|
|
Integer32
|
|
}
|
|
|
|
pduUnitStatusIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU status table entry"
|
|
::= { pduUnitStatusEntry 1 }
|
|
|
|
pduUnitStatusName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the PDU"
|
|
::= { pduUnitStatusEntry 2 }
|
|
|
|
pduUnitStatusLoadState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
upperCritical (1),
|
|
upperWarning (2),
|
|
lowerWarning (3),
|
|
lowerCritical (4),
|
|
normal (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the present load status of the PDU based on Active Power."
|
|
::= { pduUnitStatusEntry 3 }
|
|
|
|
pduUnitStatusActivePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns power consumption, in Watts(W),
|
|
of the PDU being queried."
|
|
::= { pduUnitStatusEntry 4 }
|
|
|
|
pduUnitStatusApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns power consumption, in Volt-Amps(VA)
|
|
of the PDU load being queried."
|
|
::= { pduUnitStatusEntry 5 }
|
|
|
|
pduUnitStatusPeakPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns peak power consumption, in Watts(W),
|
|
of the PDU being queried."
|
|
::= { pduUnitStatusEntry 6 }
|
|
|
|
pduUnitStatusPeakPowerTimestamp OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the date and time that peak power consumption occurred"
|
|
::= { pduUnitStatusEntry 7 }
|
|
|
|
pduUnitStatusPeakPowerStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the date and time of the last device peak power reset"
|
|
::= { pduUnitStatusEntry 8 }
|
|
|
|
pduUnitStatusEnergy OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns total energy consumed, in tenths of Kilowatt-Hours(kWh), of the PDU over its lifetime."
|
|
::= { pduUnitStatusEntry 9 }
|
|
|
|
pduUnitStatusResettableEnergy OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user resettable energy meter measuring PDU energy consumption
|
|
in tenths of kilowatt-hours(kWh)."
|
|
::= { pduUnitStatusEntry 10 }
|
|
|
|
pduUnitStatusEnergyStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the date and time of the last device energy meter reset"
|
|
::= { pduUnitStatusEntry 11 }
|
|
|
|
pduUnitStatusOutletsEnergyStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the date and time of the last outlets energy meter reset"
|
|
::= { pduUnitStatusEntry 12 }
|
|
|
|
pduUnitStatusPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the ratio of active to apparent power of the PDU, in the hundreths of PowerFactor."
|
|
::= { pduUnitStatusEntry 13 }
|
|
|
|
-- Power share table
|
|
|
|
|
|
pduUnitPsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduUnitPsEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Aggregate Object with number of entries equal to number of PDUs and Power share "
|
|
::= { pduUnit 5}
|
|
|
|
pduUnitPsEntry OBJECT-TYPE
|
|
SYNTAX PduUnitPsEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Power share entry containing the avaliable, input, output etc."
|
|
INDEX { pduUnitPsIndex }
|
|
::= { pduUnitPsTable 1 }
|
|
|
|
|
|
PduUnitPsEntry ::= SEQUENCE {
|
|
pduUnitPsIndex
|
|
INTEGER,
|
|
pduUnitPsSupportUpstreamStatus
|
|
INTEGER,
|
|
pduUnitPsSupportDownstreamStatus
|
|
INTEGER,
|
|
pduUnitPsOptMode
|
|
INTEGER
|
|
pduUnitPsFunc
|
|
INTEGER,
|
|
pduUnitPsBackupProtection
|
|
INTEGER,
|
|
pduUnitPsOutput
|
|
INTEGER
|
|
}
|
|
|
|
pduUnitPsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Power share table entry"
|
|
::= { pduUnitPsEntry 1 }
|
|
|
|
|
|
pduUnitPsSupportUpstreamStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notAvailable(0),
|
|
available(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Deprecated because of newly added OID"
|
|
::= { pduUnitPsEntry 2}
|
|
|
|
pduUnitPsSupportDownstreamStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notAvailable(0),
|
|
available(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Deprecated because of newly added OID"
|
|
::= { pduUnitPsEntry 3 }
|
|
|
|
pduUnitPsOptMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
backupPower(0),
|
|
mainPower(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating power status. "
|
|
::= { pduUnitPsEntry 4 }
|
|
|
|
pduUnitPsFunc OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this OID to off(0) will disable the Powershare function.
|
|
Setting this OID to on(1) will enable the Powershare function."
|
|
::= {pduUnitPsEntry 5 }
|
|
|
|
pduUnitPsBackupProtection OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notAvailable(0),
|
|
available(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power share support from either of the adjacent PDUs "
|
|
::= { pduUnitPsEntry 6}
|
|
|
|
pduUnitPsOutput OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notAvailable(0),
|
|
available(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power share support to either of the adjacent PDUs "
|
|
::= { pduUnitPsEntry 7}
|
|
|
|
-- Start pduInputPhase
|
|
pduInputPhaseTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of PDU Input Phases "
|
|
::= { pduInputPhase 1 }
|
|
|
|
pduInputPhaseConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduInputPhaseConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Input Phase configuration data"
|
|
::= { pduInputPhase 2 }
|
|
|
|
pduInputPhaseConfigEntry OBJECT-TYPE
|
|
SYNTAX PduInputPhaseConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input phase entry containing objects for a particular input phase."
|
|
INDEX { pduUnitConfigIndex, pduInputPhaseConfigIndex }
|
|
::= { pduInputPhaseConfigTable 1 }
|
|
|
|
PduInputPhaseConfigEntry ::= SEQUENCE {
|
|
pduInputPhaseConfigIndex
|
|
Integer32,
|
|
pduInputPhaseConfigCount
|
|
Integer32,
|
|
pduInputPhaseConfigOverloadRestriction
|
|
INTEGER,
|
|
pduInputPhaseConfigCurrentLowerCriticalThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigCurrentLowerWarningThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigCurrentUpperCriticalThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigCurrentUpperWarningThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigVoltageLowerCriticalThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigVoltageLowerWarningThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigVoltageUpperCriticalThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigVoltageUpperWarningThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigCurrentAlarmResetThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigCurrentAlarmStateChangeDelay
|
|
Integer32,
|
|
pduInputPhaseConfigCurrentEnabledThresholds
|
|
BITS,
|
|
pduInputPhaseConfigVoltageAlarmResetThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigVoltageAlarmStateChangeDelay
|
|
Integer32,
|
|
pduInputPhaseConfigVoltageEnabledThresholds
|
|
BITS,
|
|
pduInputPhaseConfigLineVoltageLowerCriticalThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigLineVoltageLowerWarningThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigLineVoltageUpperCriticalThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigLineVoltageUpperWarningThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigLineVoltageAlarmResetThreshold
|
|
Unsigned32,
|
|
pduInputPhaseConfigLineVoltageAlarmStateChangeDelay
|
|
Integer32,
|
|
pduInputPhaseConfigLineVoltageEnabledThresholds
|
|
BITS
|
|
}
|
|
|
|
pduInputPhaseConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Input Phase configuration table entry"
|
|
::= { pduInputPhaseConfigEntry 1 }
|
|
|
|
pduInputPhaseConfigCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of Input Phases"
|
|
::= { pduInputPhaseConfigEntry 2 }
|
|
|
|
pduInputPhaseConfigOverloadRestriction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
alwaysAllowTurnOn (1),
|
|
restrictOnUpperWarning (2),
|
|
restrictOnUpperCritical (3),
|
|
notSupported (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID controls the behavior of a Switched PDU Input Phase when an
|
|
overload condition is possible and additional outlets are requested
|
|
to be turned on. Setting this OID to alwaysAllowTurnON (1) will always
|
|
allow the outlets on the corresponding Input Phase to turn on. Setting
|
|
this OID to restrictOnUpperWarning (2) will not allow outlets on the
|
|
corresponding Input Phase to turn on if the
|
|
pduInputPhaseConfigUpperWarningThreshold OID is exceeded. Setting
|
|
this OID to restrictOnUpperCritical (3) will not allow outlets on
|
|
the corresponding Input Phase to turn on if the
|
|
pduInputPhaseConfigUpperCriticalThreshold OID is exceeded. Models
|
|
that do not support this feature will respond to this OID with a
|
|
value of notSupported (4). Attempts to set this OID in these
|
|
models will fail. "
|
|
::= { pduInputPhaseConfigEntry 3 }
|
|
|
|
pduInputPhaseConfigCurrentLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower critical input phase current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduInputPhaseConfigEntry 4 }
|
|
|
|
pduInputPhaseConfigCurrentLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduInputPhaseConfigEntry 5 }
|
|
|
|
pduInputPhaseConfigCurrentUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper critical input phase current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduInputPhaseConfigEntry 6 }
|
|
|
|
pduInputPhaseConfigCurrentUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper non-critical (warning) input phase current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduInputPhaseConfigEntry 7 }
|
|
|
|
pduInputPhaseConfigVoltageLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower critical input phase voltage alarm threshold in Volts(V)."
|
|
::= { pduInputPhaseConfigEntry 8 }
|
|
|
|
pduInputPhaseConfigVoltageLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower non-critical (warning) input phase voltage alarm threshold in Volts(V)."
|
|
::= { pduInputPhaseConfigEntry 9 }
|
|
|
|
pduInputPhaseConfigVoltageUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper critical input phase voltage alarm threshold in Volts(V)."
|
|
::= { pduInputPhaseConfigEntry 10 }
|
|
|
|
pduInputPhaseConfigVoltageUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper non-critical (warning) input phase voltage alarm threshold in Volts(V)."
|
|
::= { pduInputPhaseConfigEntry 11 }
|
|
|
|
pduInputPhaseConfigCurrentAlarmResetThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for current alarm deassertions in hundredths of Amps(A)."
|
|
::= { pduInputPhaseConfigEntry 12 }
|
|
|
|
pduInputPhaseConfigCurrentAlarmStateChangeDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay measured in samples before a current state is asserted. If the
|
|
value is zero, then the state is asserted as soon as it is
|
|
detected; if it is non-zero, say n, then the assertion condition
|
|
must exist for n+1 consecutive samples before the corresponding
|
|
assertion event is reported. "
|
|
::= { pduInputPhaseConfigEntry 13 }
|
|
|
|
pduInputPhaseConfigCurrentEnabledThresholds OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
lowerCritical (0),
|
|
lowerWarning (1),
|
|
upperWarning (2),
|
|
upperCritical (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string indicating which current alarm thresholds are enabled."
|
|
::= { pduInputPhaseConfigEntry 14 }
|
|
|
|
pduInputPhaseConfigVoltageAlarmResetThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for voltage alarm deassertions in Volts(V)."
|
|
::= { pduInputPhaseConfigEntry 15 }
|
|
|
|
pduInputPhaseConfigVoltageAlarmStateChangeDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay measured in samples before a voltage state is asserted. If the
|
|
value is zero, then the state is asserted as soon as it is
|
|
detected; if it is non-zero, say n, then the assertion condition
|
|
must exist for n+1 consecutive samples before the corresponding
|
|
assertion event is reported. "
|
|
::= { pduInputPhaseConfigEntry 16 }
|
|
|
|
pduInputPhaseConfigVoltageEnabledThresholds OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
lowerCritical (0),
|
|
lowerWarning (1),
|
|
upperWarning (2),
|
|
upperCritical (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string indicating which voltage alarm thresholds are enabled."
|
|
::= { pduInputPhaseConfigEntry 17 }
|
|
|
|
pduInputPhaseConfigLineVoltageLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower critical line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseConfigEntry 18 }
|
|
|
|
pduInputPhaseConfigLineVoltageLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower non-critical (warning) line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseConfigEntry 19 }
|
|
|
|
pduInputPhaseConfigLineVoltageUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper critical line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseConfigEntry 20 }
|
|
|
|
pduInputPhaseConfigLineVoltageUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper non-critical (warning) line voltage alarm threshold in Volts(V). Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseConfigEntry 21 }
|
|
|
|
pduInputPhaseConfigLineVoltageAlarmResetThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for line voltage alarm deassertions in Volts(V). Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseConfigEntry 22 }
|
|
|
|
pduInputPhaseConfigLineVoltageAlarmStateChangeDelay OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay measured in samples before a line voltage state is asserted. If the
|
|
value is zero, then the state is asserted as soon as it is
|
|
detected; if it is non-zero, say n, then the assertion condition
|
|
must exist for n+1 consecutive samples before the corresponding
|
|
assertion event is reported. Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseConfigEntry 23 }
|
|
|
|
pduInputPhaseConfigLineVoltageEnabledThresholds OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
lowerCritical (0),
|
|
lowerWarning (1),
|
|
upperWarning (2),
|
|
upperCritical (3),
|
|
disableall(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string indicating which line voltage alarm thresholds are enabled. Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseConfigEntry 24 }
|
|
|
|
pduInputPhasePropertiesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduInputPhasePropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Input Phase properties"
|
|
::= { pduInputPhase 3 }
|
|
|
|
pduInputPhasePropertiesEntry OBJECT-TYPE
|
|
SYNTAX PduInputPhasePropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input phase properties entry containing objects for a particular input phase."
|
|
INDEX { pduUnitPropertiesIndex, pduInputPhasePropertiesIndex }
|
|
::= { pduInputPhasePropertiesTable 1 }
|
|
|
|
PduInputPhasePropertiesEntry ::= SEQUENCE {
|
|
pduInputPhasePropertiesIndex
|
|
Integer32,
|
|
pduInputPhasePropertiesCount
|
|
Integer32
|
|
}
|
|
|
|
pduInputPhasePropertiesIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Input Phase status entry"
|
|
::= { pduInputPhasePropertiesEntry 1 }
|
|
|
|
pduInputPhasePropertiesCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Input Phase ID"
|
|
::= { pduInputPhasePropertiesEntry 2 }
|
|
|
|
pduInputPhaseStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduInputPhaseStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Input Phase status data"
|
|
::= { pduInputPhase 4 }
|
|
|
|
pduInputPhaseStatusEntry OBJECT-TYPE
|
|
SYNTAX PduInputPhaseStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input phase status entry containing objects for a particular input phase."
|
|
INDEX { pduUnitStatusIndex, pduInputPhaseStatusIndex }
|
|
::= { pduInputPhaseStatusTable 1 }
|
|
|
|
PduInputPhaseStatusEntry ::= SEQUENCE {
|
|
pduInputPhaseStatusIndex
|
|
Integer32,
|
|
pduInputPhaseStatusCount
|
|
Integer32,
|
|
pduInputPhaseStatusCurrentState
|
|
INTEGER,
|
|
pduInputPhaseStatusVoltageState
|
|
INTEGER,
|
|
pduInputPhaseStatusCurrent
|
|
Integer32,
|
|
pduInputPhaseStatusVoltage
|
|
Integer32,
|
|
pduInputPhaseStatusActivePower
|
|
Integer32,
|
|
pduInputPhaseStatusApparentPower
|
|
Integer32,
|
|
pduInputPhaseStatusPowerFactor
|
|
Integer32,
|
|
pduInputPhaseStatusLineVoltageState
|
|
INTEGER,
|
|
pduInputPhaseStatusLineVoltage
|
|
Integer32
|
|
}
|
|
|
|
pduInputPhaseStatusIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Input Phase status entry"
|
|
::= { pduInputPhaseStatusEntry 1 }
|
|
|
|
pduInputPhaseStatusCount OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Input Phase ID"
|
|
::= { pduInputPhaseStatusEntry 2 }
|
|
|
|
pduInputPhaseStatusCurrentState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
upperCritical (1),
|
|
upperWarning (2),
|
|
lowerWarning (3),
|
|
lowerCritical (4),
|
|
normal (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the present current status of the PDU Phase in case of Y connection or PDU Line in case of Delta conneciton."
|
|
::= { pduInputPhaseStatusEntry 3 }
|
|
|
|
pduInputPhaseStatusVoltageState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
upperCritical (1),
|
|
upperWarning (2),
|
|
lowerWarning (3),
|
|
lowerCritical (4),
|
|
normal (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the present voltage status of the PDU Input Phase being queried"
|
|
::= { pduInputPhaseStatusEntry 4 }
|
|
|
|
pduInputPhaseStatusCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the current draw, in hundredths of Amps(A)"
|
|
::= { pduInputPhaseStatusEntry 5 }
|
|
|
|
pduInputPhaseStatusVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the voltage, in Volts(V)"
|
|
::= { pduInputPhaseStatusEntry 6 }
|
|
|
|
pduInputPhaseStatusActivePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns power consumption, in Watts(W)"
|
|
::= { pduInputPhaseStatusEntry 7 }
|
|
|
|
pduInputPhaseStatusApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns power consumption, in Volt-Amps(VA)"
|
|
::= { pduInputPhaseStatusEntry 8 }
|
|
|
|
pduInputPhaseStatusPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the ratio of active to apparent power of the PDU, in the hundreths of PowerFactor."
|
|
::= { pduInputPhaseStatusEntry 9 }
|
|
|
|
pduInputPhaseStatusLineVoltageState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
upperCritical (1),
|
|
upperWarning (2),
|
|
lowerWarning (3),
|
|
lowerCritical (4),
|
|
normal (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the present line voltage STATUS of the PDU Input Phase being queried. Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseStatusEntry 10 }
|
|
|
|
pduInputPhaseStatusLineVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the line voltage, in Volts(V). Supported only on PDU Phase in case of Y connection."
|
|
::= { pduInputPhaseStatusEntry 11 }
|
|
|
|
-- Start pduCircuitBreaker
|
|
pduCircuitBreakerTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of PDU Circuit Breakers"
|
|
::= { pduCircuitBreaker 1 }
|
|
|
|
pduCircuitBreakerConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduCircuitBreakerConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Circuit Breaker configuration data"
|
|
::= { pduCircuitBreaker 2 }
|
|
|
|
pduCircuitBreakerConfigEntry OBJECT-TYPE
|
|
SYNTAX PduCircuitBreakerConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A circuit breaker configuration entry containing objects for a particular circuit breaker."
|
|
INDEX { pduUnitConfigIndex, pduCircuitBreakerConfigIndex }
|
|
::= { pduCircuitBreakerConfigTable 1 }
|
|
|
|
PduCircuitBreakerConfigEntry ::= SEQUENCE {
|
|
pduCircuitBreakerConfigIndex
|
|
Integer32,
|
|
pduCircuitBreakerConfigCount
|
|
Integer32,
|
|
pduCircuitBreakerName
|
|
DisplayString,
|
|
pduCircuitBreakerConfigOverloadRestriction
|
|
INTEGER,
|
|
pduCircuitBreakerConfigLowerCriticalThreshold
|
|
Unsigned32,
|
|
pduCircuitBreakerConfigLowerWarningThreshold
|
|
Unsigned32,
|
|
pduCircuitBreakerConfigUpperCriticalThreshold
|
|
Unsigned32,
|
|
pduCircuitBreakerConfigUpperWarningThreshold
|
|
Unsigned32,
|
|
pduCircuitBreakerConfigAlarmResetThreshold
|
|
Unsigned32,
|
|
pduCircuitBreakerConfigAlarmStateChangeDelay
|
|
Unsigned32,
|
|
pduCircuitBreakerConfigEnabledThresholds
|
|
BITS
|
|
}
|
|
|
|
pduCircuitBreakerConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Circuit Breaker configuration table entry"
|
|
::= { pduCircuitBreakerConfigEntry 1 }
|
|
|
|
pduCircuitBreakerConfigCount OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of circuit breakers on the PDU"
|
|
::= { pduCircuitBreakerConfigEntry 2 }
|
|
|
|
pduCircuitBreakerName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The label of the circuit breaker"
|
|
::= { pduCircuitBreakerConfigEntry 3 }
|
|
|
|
pduCircuitBreakerConfigOverloadRestriction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
alwaysAllowTurnOn (1),
|
|
restrictOnUpperWarning (2),
|
|
restrictOnUpperCritical (3),
|
|
notSupported (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID controls the behavior of a Switched PDU Circuit
|
|
Breaker when an overload condition is possible and additional
|
|
outlets are requested to be turned on. Setting this OID to
|
|
alwaysAllowTurnON (1) will always allow the outlets on the
|
|
corresponding Circuit Breaker to turn on. Setting this OID
|
|
to restrictOnUpperWarning (2) will not allow outlets on the
|
|
corresponding Circuit Breaker to turn on if the
|
|
pduCircuitBreakerConfigUpperWarningThreshold OID is exceeded.
|
|
Setting this OID to restrictOnUpperCritical (3) will not
|
|
allow outlets on the corresponding Circuit Breaker to turn
|
|
on if the pduCircuitBreakerConfigUpperCriticalThreshold OID
|
|
is exceeded. Models that do not support this feature will
|
|
respond to this OID with a value of notSupported (4).
|
|
Attempts to set this OID in these models will fail. "
|
|
::= { pduCircuitBreakerConfigEntry 4 }
|
|
|
|
pduCircuitBreakerConfigLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower critical circuit breaker current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduCircuitBreakerConfigEntry 5 }
|
|
|
|
pduCircuitBreakerConfigLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduCircuitBreakerConfigEntry 6 }
|
|
|
|
pduCircuitBreakerConfigUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper critical circuit breaker current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduCircuitBreakerConfigEntry 7 }
|
|
|
|
pduCircuitBreakerConfigUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper non-critical (warning) circuit breaker current alarm threshold in hundredths of Amps(A)."
|
|
::= { pduCircuitBreakerConfigEntry 8 }
|
|
|
|
pduCircuitBreakerConfigAlarmResetThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions in hundredths of Amps(A)."
|
|
::= { pduCircuitBreakerConfigEntry 9 }
|
|
|
|
pduCircuitBreakerConfigAlarmStateChangeDelay OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay measured in samples before a state is asserted.
|
|
If the value is zero, then the state is asserted as soon
|
|
as it is detected; if it is non-zero, say n, then the
|
|
assertion condition must exist for n+1 consecutive samples
|
|
before the corresponding assertion event is reported."
|
|
::= { pduCircuitBreakerConfigEntry 10 }
|
|
|
|
pduCircuitBreakerConfigEnabledThresholds OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
lowerCritical (0),
|
|
lowerWarning (1),
|
|
upperWarning (2),
|
|
upperCritical (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string indicating which alarm thresholds are enabled."
|
|
::= { pduCircuitBreakerConfigEntry 11 }
|
|
|
|
pduCircuitBreakerPropertiesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduCircuitBreakerPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU circuit breaker properties"
|
|
::= { pduCircuitBreaker 3 }
|
|
|
|
pduCircuitBreakerPropertiesEntry OBJECT-TYPE
|
|
SYNTAX PduCircuitBreakerPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A circuit breaker properties entry containing objects for a particular circuit breaker."
|
|
INDEX { pduUnitPropertiesIndex, pduCircuitBreakerPropertiesIndex }
|
|
::= { pduCircuitBreakerPropertiesTable 1 }
|
|
|
|
PduCircuitBreakerPropertiesEntry ::= SEQUENCE {
|
|
pduCircuitBreakerPropertiesIndex
|
|
Integer32,
|
|
pduCircuitBreakerPropertiesCount
|
|
Integer32,
|
|
pduCircuitBreakerPropertiesInputLayout
|
|
INTEGER,
|
|
pduCircuitBreakerPropertiesCurrentRating
|
|
Integer32
|
|
}
|
|
|
|
pduCircuitBreakerPropertiesIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Circuit Breaker properties table entry"
|
|
::= { pduCircuitBreakerPropertiesEntry 1 }
|
|
|
|
pduCircuitBreakerPropertiesCount OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Circuit Breakers"
|
|
::= { pduCircuitBreakerPropertiesEntry 2 }
|
|
|
|
pduCircuitBreakerPropertiesInputLayout OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
seqPhase1ToNeutral (1),
|
|
seqPhase2ToNeutral (2),
|
|
seqPhase3ToNeutral (3),
|
|
seqPhase1ToPhase2 (4),
|
|
seqPhase2ToPhase3 (5),
|
|
seqPhase3ToPhase1 (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID describes the outlet phase connections on
|
|
the referenced bank as follows:
|
|
seqPhase1ToNeutral(1) indicates that outlets attached
|
|
to circuit breaker are connected from Phase 1 to Neutral.
|
|
seqPhase2ToNeutral(2) indicates that outlets attached
|
|
to circuit breaker are connected from Phase 2 to Neutral.
|
|
seqPhase3ToNeutral(3) indicates that outlets attached
|
|
to circuit breaker are connected from Phase 3 to Neutral.
|
|
seqPhase1ToPhase2(4) indicates that outlets attached
|
|
to circuit breaker are connected from Phase 1 to Phase2.
|
|
seqPhase2ToPhase3(5) indicates that outlets attached
|
|
to circuit breaker are connected from Phase 2 to Phase3.
|
|
seqPhase3ToPhase1(6) indicates that outlets attached
|
|
to circuit breaker are connected from Phase 3 to Phase1. "
|
|
::= { pduCircuitBreakerPropertiesEntry 3 }
|
|
|
|
pduCircuitBreakerPropertiesCurrentRating OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Circuit Breakers"
|
|
::= { pduCircuitBreakerPropertiesEntry 4 }
|
|
|
|
pduCircuitBreakerStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduCircuitBreakerStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU circuit breaker status data"
|
|
::= { pduCircuitBreaker 4 }
|
|
|
|
pduCircuitBreakerStatusEntry OBJECT-TYPE
|
|
SYNTAX PduCircuitBreakerStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A circuit breaker status entry containing objects for a particular circuit breaker."
|
|
INDEX { pduUnitStatusIndex, pduCircuitBreakerStatusIndex }
|
|
::= { pduCircuitBreakerStatusTable 1 }
|
|
|
|
PduCircuitBreakerStatusEntry ::= SEQUENCE {
|
|
pduCircuitBreakerStatusIndex
|
|
Integer32,
|
|
pduCircuitBreakerStatusCount
|
|
Integer32,
|
|
pduCircuitBreakerLabel
|
|
DisplayString,
|
|
pduCircuitBreakerStatusLoadState
|
|
INTEGER,
|
|
pduCircuitBreakerStatusCurrent
|
|
Integer32,
|
|
pduCircuitBreakerStatusPowerFactor
|
|
Integer32
|
|
}
|
|
|
|
pduCircuitBreakerStatusIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Circuit Breaker status table entry"
|
|
::= { pduCircuitBreakerStatusEntry 1 }
|
|
|
|
pduCircuitBreakerStatusCount OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Circuit Breakers"
|
|
::= { pduCircuitBreakerStatusEntry 2 }
|
|
|
|
pduCircuitBreakerLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The label on the PDU identifying the circuit breaker"
|
|
::= { pduCircuitBreakerStatusEntry 3 }
|
|
|
|
pduCircuitBreakerStatusLoadState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
upperCritical (1),
|
|
upperWarning (2),
|
|
lowerWarning (3),
|
|
lowerCritical (4),
|
|
normal (5),
|
|
off (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the present load status of the PDU Circuit
|
|
Breaker being queried"
|
|
::= { pduCircuitBreakerStatusEntry 4 }
|
|
|
|
pduCircuitBreakerStatusCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the current draw, in hundredths of Amps(A), of the load on
|
|
the PDU Circuit Breaker being queried."
|
|
::= { pduCircuitBreakerStatusEntry 5 }
|
|
|
|
pduCircuitBreakerStatusPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the ratio of active to apparent power of the Circuit Breaker, in the hundreths of PowerFactor."
|
|
::= { pduCircuitBreakerStatusEntry 6 }
|
|
|
|
-- Start pduOutlet
|
|
pduOutletSwitchedTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of PDU Outlets"
|
|
::= { pduOutlet 1 }
|
|
|
|
pduOutletSwitchedConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletSwitchedConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Switched Outlet configuration data"
|
|
::= { pduOutlet 2 }
|
|
|
|
pduOutletSwitchedConfigEntry OBJECT-TYPE
|
|
SYNTAX PduOutletSwitchedConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet configuration entry containing objects for a particular outlet."
|
|
INDEX { pduUnitConfigIndex, pduOutletSwitchedConfigIndex }
|
|
::= { pduOutletSwitchedConfigTable 1 }
|
|
|
|
PduOutletSwitchedConfigEntry ::= SEQUENCE {
|
|
pduOutletSwitchedConfigIndex
|
|
Integer32,
|
|
pduOutletSwitchedName
|
|
DisplayString,
|
|
pduOutletSwitchedStateOnStartup
|
|
INTEGER,
|
|
pduOutletSwitchedConfigPowerOnTime
|
|
Integer32,
|
|
pduOutletSwitchedConfigPowerOffTime
|
|
Integer32,
|
|
pduOutletSwitchedConfigRebootDuration
|
|
Integer32
|
|
}
|
|
|
|
pduOutletSwitchedConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Switched Outlet configuration table entry"
|
|
::= { pduOutletSwitchedConfigEntry 1 }
|
|
|
|
pduOutletSwitchedName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined name for the Switched Outlet"
|
|
::= { pduOutletSwitchedConfigEntry 2 }
|
|
|
|
pduOutletSwitchedStateOnStartup OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1),
|
|
lastKnownState (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The outlet state on device startup; overrides
|
|
the global value pduUnitConfigGlobalOutletStateOnStartup."
|
|
::= { pduOutletSwitchedConfigEntry 3 }
|
|
|
|
pduOutletSwitchedConfigPowerOnTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of delay, in seconds, between when power is
|
|
provided to outlets the outlet and when this outlet
|
|
starts providing power"
|
|
::= { pduOutletSwitchedConfigEntry 4 }
|
|
|
|
pduOutletSwitchedConfigPowerOffTime OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, in seconds, this outlet will delay
|
|
powering off"
|
|
::= { pduOutletSwitchedConfigEntry 5 }
|
|
|
|
pduOutletSwitchedConfigRebootDuration OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, in seconds, this outlet will remain
|
|
in powered off state before returning to power on state
|
|
during a reboot action."
|
|
::= { pduOutletSwitchedConfigEntry 6 }
|
|
|
|
pduOutletSwitchedPropertiesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletSwitchedPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Switched Outlet properties"
|
|
::= { pduOutlet 3 }
|
|
|
|
pduOutletSwitchedPropertiesEntry OBJECT-TYPE
|
|
SYNTAX PduOutletSwitchedPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet properties entry containing objects for a particular outlet."
|
|
INDEX { pduUnitPropertiesIndex, pduOutletSwitchedPropertiesIndex }
|
|
::= { pduOutletSwitchedPropertiesTable 1 }
|
|
|
|
PduOutletSwitchedPropertiesEntry ::= SEQUENCE {
|
|
pduOutletSwitchedPropertiesIndex
|
|
Integer32,
|
|
pduOutletSwitchedPropertiesNumber
|
|
Integer32,
|
|
pduOutletSwitchedPropertiesName
|
|
DisplayString,
|
|
pduOutletSwitchedPropertiesInputPhaseLayout
|
|
INTEGER,
|
|
pduOutletSwitchedPropertiesCircuitBreaker
|
|
Integer32,
|
|
pduOutletSwitchedPropertiesCurrentRating
|
|
Integer32
|
|
}
|
|
|
|
pduOutletSwitchedPropertiesIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Switched Outlet properties table entry"
|
|
::= { pduOutletSwitchedPropertiesEntry 1 }
|
|
|
|
pduOutletSwitchedPropertiesNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Switched Outlet ID"
|
|
::= { pduOutletSwitchedPropertiesEntry 2 }
|
|
|
|
pduOutletSwitchedPropertiesName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined switched outlet ID string"
|
|
::= { pduOutletSwitchedPropertiesEntry 3 }
|
|
|
|
pduOutletSwitchedPropertiesInputPhaseLayout OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
seqPhase1ToNeutral (1),
|
|
seqPhase2ToNeutral (2),
|
|
seqPhase3ToNeutral (3),
|
|
seqPhase1ToPhase2 (4),
|
|
seqPhase2ToPhase3 (5),
|
|
seqPhase3ToPhase1 (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID describes the outlet phase connections
|
|
on the referenced bank as follows:
|
|
seqPhase1ToNeutral(1) indicates that outlets
|
|
attached to Switched Outlet are connected from Phase 1 to Neutral.
|
|
seqPhase2ToNeutral(2) indicates that outlets
|
|
attached to Switched Outlet are connected from Phase 2 to Neutral.
|
|
seqPhase3ToNeutral(3) indicates that outlets
|
|
attached to Switched Outlet are connected from Phase 3 to Neutral.
|
|
seqPhase1ToPhase2(4) indicates that outlets
|
|
attached to Switched Outlet are connected from Phase 1 to Phase2.
|
|
seqPhase2ToPhase3(5) indicates that outlets
|
|
attached to Switched Outlet are connected from Phase 2 to Phase3.
|
|
seqPhase3ToPhase1(6) indicates that outlets
|
|
attached to Switched Outlet are connected from Phase 3 to Phase1. "
|
|
::= { pduOutletSwitchedPropertiesEntry 4 }
|
|
|
|
pduOutletSwitchedPropertiesCircuitBreaker OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Circuit Breaker ID"
|
|
::= { pduOutletSwitchedPropertiesEntry 5 }
|
|
|
|
pduOutletSwitchedPropertiesCurrentRating OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current rating of outlet in hundreths of ampere"
|
|
::= { pduOutletSwitchedPropertiesEntry 6 }
|
|
|
|
pduOutletSwitchedStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletSwitchedStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Switched Outlet status data"
|
|
::= { pduOutlet 4 }
|
|
|
|
pduOutletSwitchedStatusEntry OBJECT-TYPE
|
|
SYNTAX PduOutletSwitchedStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status data from the PDU Switched Outlet being queried"
|
|
INDEX { pduUnitStatusIndex, pduOutletSwitchedStatusIndex }
|
|
::= { pduOutletSwitchedStatusTable 1 }
|
|
|
|
PduOutletSwitchedStatusEntry ::= SEQUENCE {
|
|
pduOutletSwitchedStatusIndex
|
|
Integer32,
|
|
pduOutletSwitchedStatusNumber
|
|
Integer32,
|
|
pduOutletSwitchedStatusName
|
|
DisplayString,
|
|
pduOutletSwitchedStatusState
|
|
INTEGER
|
|
}
|
|
|
|
pduOutletSwitchedStatusIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Switched Outlet status table entry"
|
|
::= { pduOutletSwitchedStatusEntry 1 }
|
|
|
|
pduOutletSwitchedStatusNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Switched Outlet ID"
|
|
::= { pduOutletSwitchedStatusEntry 2 }
|
|
|
|
pduOutletSwitchedStatusName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined switched outlet ID string"
|
|
::= { pduOutletSwitchedStatusEntry 3 }
|
|
|
|
pduOutletSwitchedStatusState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
on (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the present switch state of the
|
|
PDU switched outlet being queried"
|
|
::= { pduOutletSwitchedStatusEntry 4 }
|
|
|
|
pduOutletSwitchedControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletSwitchedControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Switched Outlet status data"
|
|
::= { pduOutlet 5 }
|
|
|
|
pduOutletSwitchedControlEntry OBJECT-TYPE
|
|
SYNTAX PduOutletSwitchedControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status data from the PDU Switched Outlet
|
|
being queried"
|
|
INDEX { pduUnitConfigIndex, pduOutletSwitchedControlIndex }
|
|
::= { pduOutletSwitchedControlTable 1 }
|
|
|
|
PduOutletSwitchedControlEntry ::= SEQUENCE {
|
|
pduOutletSwitchedControlIndex
|
|
Integer32,
|
|
pduOutletSwitchedControlNumber
|
|
Integer32,
|
|
pduOutletSwitchedControlName
|
|
DisplayString,
|
|
pduOutletSwitchedControlCommand
|
|
INTEGER
|
|
}
|
|
|
|
pduOutletSwitchedControlIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index to the PDU switched outlet
|
|
control data table entry"
|
|
::= { pduOutletSwitchedControlEntry 1 }
|
|
|
|
pduOutletSwitchedControlNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Switched Outlet ID"
|
|
::= { pduOutletSwitchedControlEntry 2 }
|
|
|
|
pduOutletSwitchedControlName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined switched outlet ID string"
|
|
::= { pduOutletSwitchedControlEntry 3 }
|
|
|
|
pduOutletSwitchedControlCommand OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
immediateOff (1),
|
|
immediateOn (2),
|
|
delayedOff (3),
|
|
delayedOn (4),
|
|
immediateReboot (5),
|
|
delayedReboot (6),
|
|
outletUnknown (7)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Getting this variable will return the outlet state.
|
|
If the outlet is on, the immediateOn (2)
|
|
value will be returned. If the outlet is off,
|
|
the immediateOff (1) value will be returned.
|
|
If the state of the outlet cannot be determined, the
|
|
outletUnknown (7) value will be returned. If the
|
|
outletUnknown condition should occur, all devices
|
|
powered by the PDU should be shut down. The PDU's
|
|
power should then be cycled to clear this condition.
|
|
Setting this variable to immediateOn (2) will immediately
|
|
turn the outlet on. Setting this variable to
|
|
immediateOff (1) will immediately turn the outlet off.
|
|
Setting this variable to immediateReboot (5)
|
|
will cause the Switched PDU to perform an immediateOff
|
|
command, wait the pduOutletSwitchedConfigRebootDuration
|
|
OID time, and then perform an immediateOn command.
|
|
Setting this variable to delayedOn (4) will turn the
|
|
outlet on after the pduOutletSwitchedConfigPowerOnTime
|
|
OID time has elapsed. Setting this variable to
|
|
delayedOff (3) will turn the outlet off after the
|
|
pduOutletSwitchedConfigPowerOffTime OID time has elapsed.
|
|
Setting this variable to delayedReboot (6) will cause
|
|
the Switched PDU to perform a delayedOff command, wait
|
|
the pduOutletSwitchedConfigRebootDuration OID time, and
|
|
then perform a delayedOn command."
|
|
::= { pduOutletSwitchedControlEntry 4 }
|
|
|
|
pduOutletMeteredTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of PDU Outlets"
|
|
::= { pduOutlet 6 }
|
|
|
|
pduOutletMeteredConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletMeteredConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Metered Outlet configuration data"
|
|
::= { pduOutlet 7 }
|
|
|
|
pduOutletMeteredConfigEntry OBJECT-TYPE
|
|
SYNTAX PduOutletMeteredConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An outlet configuration entry containing objects for a particular outlet."
|
|
INDEX { pduUnitConfigIndex, pduOutletMeteredConfigIndex }
|
|
::= { pduOutletMeteredConfigTable 1 }
|
|
|
|
PduOutletMeteredConfigEntry ::= SEQUENCE {
|
|
pduOutletMeteredConfigIndex
|
|
Integer32,
|
|
pduOutletMeteredName
|
|
DisplayString,
|
|
pduOutletMeteredConfigLowerCriticalThreshold
|
|
Unsigned32,
|
|
pduOutletMeteredConfigLowerWarningThreshold
|
|
Unsigned32,
|
|
pduOutletMeteredConfigUpperCriticalThreshold
|
|
Unsigned32,
|
|
pduOutletMeteredConfigUpperWarningThreshold
|
|
Unsigned32,
|
|
pduOutletMeteredConfigAlarmResetThreshold
|
|
Unsigned32,
|
|
pduOutletMeteredConfigAlarmStateChangeDelay
|
|
Unsigned32,
|
|
pduOutletMeteredConfigEnabledThresholds
|
|
BITS
|
|
}
|
|
|
|
pduOutletMeteredConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Metered Outlet
|
|
configuration table entry"
|
|
::= { pduOutletMeteredConfigEntry 1 }
|
|
|
|
pduOutletMeteredName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined name for the Metered Outlet"
|
|
::= { pduOutletMeteredConfigEntry 2 }
|
|
|
|
pduOutletMeteredConfigLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower critical outlet active power alarm threshold in Watts(W)."
|
|
::= { pduOutletMeteredConfigEntry 3 }
|
|
|
|
pduOutletMeteredConfigLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower non-critical (warning) outlet active power alarm threshold in Watts(W)."
|
|
::= { pduOutletMeteredConfigEntry 4 }
|
|
|
|
pduOutletMeteredConfigUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper critical outlet active power alarm threshold in Watts(W)."
|
|
::= { pduOutletMeteredConfigEntry 5 }
|
|
|
|
pduOutletMeteredConfigUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper non-critical (warning) outlet active power alarm threshold in Watts(W)."
|
|
::= { pduOutletMeteredConfigEntry 6 }
|
|
|
|
pduOutletMeteredConfigAlarmResetThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions in Watts(W)."
|
|
::= { pduOutletMeteredConfigEntry 7 }
|
|
|
|
pduOutletMeteredConfigAlarmStateChangeDelay OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay measured in samples before a state
|
|
is asserted. If the value is zero, then the state
|
|
is asserted as soon as it is detected; if it is
|
|
non-zero, say n, then the assertion condition must
|
|
exist for n+1 consecutive samples before the
|
|
corresponding assertion event is reported."
|
|
::= { pduOutletMeteredConfigEntry 8 }
|
|
|
|
pduOutletMeteredConfigEnabledThresholds OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
lowerCritical (0),
|
|
lowerWarning (1),
|
|
upperWarning (2),
|
|
upperCritical (3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string indicating which alarm
|
|
thresholds are enabled."
|
|
::= { pduOutletMeteredConfigEntry 9 }
|
|
|
|
pduOutletMeteredPropertiesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletMeteredPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Metered Outlet properties"
|
|
::= { pduOutlet 8 }
|
|
|
|
pduOutletMeteredPropertiesEntry OBJECT-TYPE
|
|
SYNTAX PduOutletMeteredPropertiesEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration data from the PDU Metered
|
|
Outlet being queried"
|
|
INDEX { pduUnitPropertiesIndex, pduOutletMeteredPropertiesIndex }
|
|
::= { pduOutletMeteredPropertiesTable 1 }
|
|
|
|
PduOutletMeteredPropertiesEntry ::= SEQUENCE {
|
|
pduOutletMeteredPropertiesIndex
|
|
Integer32,
|
|
pduOutletMeteredPropertiesNumber
|
|
Integer32,
|
|
pduOutletMeteredPropertiesName
|
|
DisplayString,
|
|
pduOutletMeteredPropertiesInputPhaseLayout
|
|
INTEGER,
|
|
pduOutletMeteredPropertiesCircuitBreaker
|
|
Integer32,
|
|
pduOutletMeteredPropertiesPowerRating
|
|
Integer32,
|
|
pduOutletMeteredPropertiesCurrentRating
|
|
Integer32
|
|
}
|
|
|
|
pduOutletMeteredPropertiesIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Metered Outlet
|
|
properties table entry"
|
|
::= { pduOutletMeteredPropertiesEntry 1 }
|
|
|
|
pduOutletMeteredPropertiesNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Metered Outlet ID"
|
|
::= { pduOutletMeteredPropertiesEntry 2 }
|
|
|
|
pduOutletMeteredPropertiesName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined Metered outlet ID string"
|
|
::= { pduOutletMeteredPropertiesEntry 3 }
|
|
|
|
pduOutletMeteredPropertiesInputPhaseLayout OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
seqPhase1ToNeutral (1),
|
|
seqPhase2ToNeutral (2),
|
|
seqPhase3ToNeutral (3),
|
|
seqPhase1ToPhase2 (4),
|
|
seqPhase2ToPhase3 (5),
|
|
seqPhase3ToPhase1 (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID describes the outlet phase connections
|
|
on the referenced bank as follows:
|
|
seqPhase1ToNeutral(1) indicates that outlets attached
|
|
to Metered Outlet are connected from Phase 1 to Neutral.
|
|
seqPhase2ToNeutral(2) indicates that outlets attached
|
|
to Metered Outlet are connected from Phase 2 to Neutral.
|
|
seqPhase3ToNeutral(3) indicates that outlets attached
|
|
to Metered Outlet are connected from Phase 3 to Neutral.
|
|
seqPhase1ToPhase2(4) indicates that outlets attached
|
|
to Metered Outlet are connected from Phase 1 to Phase2.
|
|
seqPhase2ToPhase3(5) indicates that outlets attached
|
|
to Metered Outlet are connected from Phase 2 to Phase3.
|
|
seqPhase3ToPhase1(6) indicates that outlets attached
|
|
to Metered Outlet are connected from Phase 3 to Phase1. "
|
|
::= { pduOutletMeteredPropertiesEntry 4 }
|
|
|
|
pduOutletMeteredPropertiesCircuitBreaker OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Circuit Breaker ID"
|
|
::= { pduOutletMeteredPropertiesEntry 5 }
|
|
|
|
pduOutletMeteredPropertiesPowerRating OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum power rating of the PDU metered outlet"
|
|
::= { pduOutletMeteredPropertiesEntry 6 }
|
|
|
|
pduOutletMeteredPropertiesCurrentRating OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Metered outlet current rating in hundreths of ampere"
|
|
::= { pduOutletMeteredPropertiesEntry 7 }
|
|
|
|
pduOutletMeteredStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduOutletMeteredStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU Metered Outlet status data"
|
|
::= { pduOutlet 9 }
|
|
|
|
pduOutletMeteredStatusEntry OBJECT-TYPE
|
|
SYNTAX PduOutletMeteredStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status data from the PDU Metered Outlet being queried"
|
|
INDEX { pduUnitStatusIndex, pduOutletMeteredStatusIndex }
|
|
::= { pduOutletMeteredStatusTable 1 }
|
|
|
|
PduOutletMeteredStatusEntry ::= SEQUENCE {
|
|
pduOutletMeteredStatusIndex
|
|
Integer32,
|
|
pduOutletMeteredStatusNumber
|
|
Integer32,
|
|
pduOutletMeteredStatusName
|
|
DisplayString,
|
|
pduOutletMeteredStatusLoadState
|
|
INTEGER,
|
|
pduOutletMeteredStatusCurrent
|
|
Integer32,
|
|
pduOutletMeteredStatusActivePower
|
|
Integer32,
|
|
pduOutletMeteredStatusPowerFactor
|
|
Integer32,
|
|
pduOutletMeteredStatusPeakPower
|
|
Integer32,
|
|
pduOutletMeteredStatusPeakPowerTimeStamp
|
|
DisplayString,
|
|
pduOutletMeteredStatusPeakPowerStartTime
|
|
DisplayString,
|
|
pduOutletMeteredStatusResettableEnergy
|
|
Integer32
|
|
}
|
|
|
|
pduOutletMeteredStatusIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Metered Outlet status table entry"
|
|
::= { pduOutletMeteredStatusEntry 1 }
|
|
|
|
pduOutletMeteredStatusNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The numeric Metered Outlet ID"
|
|
::= { pduOutletMeteredStatusEntry 2 }
|
|
|
|
pduOutletMeteredStatusName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined Metered outlet ID string"
|
|
::= { pduOutletMeteredStatusEntry 3 }
|
|
|
|
pduOutletMeteredStatusLoadState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
upperCritical (1),
|
|
upperWarning (2),
|
|
lowerWarning (3),
|
|
lowerCritical (4),
|
|
normal (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the present load status of the PDU metered outlet being queried."
|
|
::= { pduOutletMeteredStatusEntry 4 }
|
|
|
|
pduOutletMeteredStatusCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the current draw, in hundredths of Amps(A), of the load on the PDU
|
|
outlet being queried."
|
|
::= { pduOutletMeteredStatusEntry 5 }
|
|
|
|
pduOutletMeteredStatusActivePower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the power draw, in Watts(W), of the load
|
|
on the PDU outlet being queried."
|
|
::= { pduOutletMeteredStatusEntry 6 }
|
|
|
|
pduOutletMeteredStatusPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns the ratio of active to apparent power
|
|
of the PDU Outlet being queried, in the hundreths of PowerFactor."
|
|
::= { pduOutletMeteredStatusEntry 7 }
|
|
|
|
pduOutletMeteredStatusPeakPower OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Returns peak power consumption, in Watts(W),
|
|
of the Rack PDU outlet being queried."
|
|
::= { pduOutletMeteredStatusEntry 8 }
|
|
|
|
pduOutletMeteredStatusPeakPowerTimeStamp OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the date and time that this metered
|
|
outlet's peak power consumption occurred"
|
|
::= { pduOutletMeteredStatusEntry 9 }
|
|
|
|
pduOutletMeteredStatusPeakPowerStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the start date and time that this metered
|
|
outlet began recording peak power observations"
|
|
::= { pduOutletMeteredStatusEntry 10 }
|
|
|
|
pduOutletMeteredStatusResettableEnergy OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user resettable energy meter measuring outlet load energy
|
|
consumption in tenths of Kilowatt-Hours(kWh)."
|
|
::= { pduOutletMeteredStatusEntry 11 }
|
|
|
|
-- Start pduExternalSensor
|
|
pduExternalSensorTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of External Sensors"
|
|
::= { pduExternalSensor 1 }
|
|
|
|
pduExternalSensorNamePlateTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduExternalSensorNamePlateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU ExternalSensorNamePlate data"
|
|
::= { pduExternalSensor 2 }
|
|
|
|
pduExternalSensorNamePlateEntry OBJECT-TYPE
|
|
SYNTAX PduExternalSensorNamePlateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External Sensor Name Plate data from the external
|
|
sensor being queried. The number of entries equals
|
|
the value of pduExternalSensorNamePlateTableSize."
|
|
INDEX { pduNamePlateIndex, pduExternalSensorNamePlateIndex }
|
|
::= { pduExternalSensorNamePlateTable 1 }
|
|
|
|
PduExternalSensorNamePlateEntry ::= SEQUENCE {
|
|
pduExternalSensorNamePlateIndex
|
|
Integer32,
|
|
pduExternalSensorNamePlateName
|
|
DisplayString,
|
|
pduExternalSensorNamePlateDescription
|
|
DisplayString,
|
|
pduExternalSensorNamePlateLocation
|
|
DisplayString,
|
|
pduExternalSensorNamePlateSerialNumber
|
|
DisplayString,
|
|
pduExternalSensorNamePlateType
|
|
INTEGER,
|
|
pduExternalSensorNamePlateUnits
|
|
INTEGER,
|
|
pduExternalSensorNamePlateIdentifier
|
|
Integer32,
|
|
pduExternalSensorNamePlateProductCode
|
|
DisplayString
|
|
}
|
|
|
|
pduExternalSensorNamePlateIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU External Sensor status table entry"
|
|
::= { pduExternalSensorNamePlateEntry 1 }
|
|
|
|
pduExternalSensorNamePlateName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the external sensor"
|
|
::= { pduExternalSensorNamePlateEntry 2 }
|
|
|
|
pduExternalSensorNamePlateDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined description of the external sensor"
|
|
::= { pduExternalSensorNamePlateEntry 3 }
|
|
|
|
pduExternalSensorNamePlateLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined string identifying the location of the PDU"
|
|
::= { pduExternalSensorNamePlateEntry 4 }
|
|
|
|
pduExternalSensorNamePlateSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The serial code of the external sensor being queried.
|
|
This OID is used to show the product code of the sensor. Additionally, similar information is shown in the OID 'pduExternalSensorNamePlateProductCode'"
|
|
::= { pduExternalSensorNamePlateEntry 5 }
|
|
|
|
pduExternalSensorNamePlateType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
temperature (1),
|
|
humidity (2),
|
|
doorSwitch (3),
|
|
dryContact (4),
|
|
spotFluid (5),
|
|
ropeFluid (6),
|
|
smoke (7),
|
|
beacon (8),
|
|
airVelocity (9),
|
|
modbusAdapter (17),
|
|
hidAdapter (18)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of external sensor."
|
|
::= { pduExternalSensorNamePlateEntry 6 }
|
|
|
|
pduExternalSensorNamePlateUnits OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
logic (0),
|
|
degreeC (1),
|
|
degreeF (2),
|
|
percent (3),
|
|
mps (4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The base units the external sensor is measured in.
|
|
This parameter does not apply to onOff, trip, vibration,
|
|
waterDetection, smokeDetection sensors. "
|
|
::= { pduExternalSensorNamePlateEntry 7 }
|
|
|
|
pduExternalSensorNamePlateIdentifier OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unique identifier of the external sensor."
|
|
::= { pduExternalSensorNamePlateEntry 8 }
|
|
|
|
pduExternalSensorNamePlateProductCode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The product code of the external sensor being queried"
|
|
::= { pduExternalSensorNamePlateEntry 9 }
|
|
|
|
pduExternalSensorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduExternalSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU External Sensor configuration data"
|
|
::= { pduExternalSensor 3 }
|
|
|
|
pduExternalSensorConfigEntry OBJECT-TYPE
|
|
SYNTAX PduExternalSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration data from the PDU External
|
|
Sensor being queried"
|
|
INDEX { pduUnitConfigIndex, pduExternalSensorConfigIndex }
|
|
::= { pduExternalSensorConfigTable 1 }
|
|
|
|
PduExternalSensorConfigEntry ::= SEQUENCE {
|
|
pduExternalSensorConfigIndex
|
|
Integer32,
|
|
pduExternalSensorConfigLowerCriticalThreshold
|
|
Unsigned32,
|
|
pduExternalSensorConfigLowerWarningThreshold
|
|
Unsigned32,
|
|
pduExternalSensorConfigUpperCriticalThreshold
|
|
Unsigned32,
|
|
pduExternalSensorConfigUpperWarningThreshold
|
|
Unsigned32,
|
|
pduExternalSensorConfigEnabledThresholds
|
|
BITS,
|
|
pduExternalSensorConfigAlarmState
|
|
INTEGER,
|
|
pduExternalSensorConfigAlarmResetThreshold
|
|
Unsigned32,
|
|
pduExternalSensorConfigAlarmStateChangeDelay
|
|
Unsigned32,
|
|
}
|
|
|
|
pduExternalSensorConfigIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU External Sensor
|
|
configuration table entry"
|
|
::= { pduExternalSensorConfigEntry 1 }
|
|
|
|
pduExternalSensorConfigLowerCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower critical alarm threshold in pduExternalSensorNamePlateUnits."
|
|
::= { pduExternalSensorConfigEntry 2 }
|
|
|
|
pduExternalSensorConfigLowerWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined lower non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
|
|
::= { pduExternalSensorConfigEntry 3 }
|
|
|
|
pduExternalSensorConfigUpperCriticalThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper critical alarm threshold in pduExternalSensorNamePlateUnits."
|
|
::= { pduExternalSensorConfigEntry 4 }
|
|
|
|
pduExternalSensorConfigUpperWarningThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User-defined upper non-critical (warning) alarm threshold in pduExternalSensorNamePlateUnits."
|
|
::= { pduExternalSensorConfigEntry 5 }
|
|
|
|
pduExternalSensorConfigEnabledThresholds OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
lowerCritical (0),
|
|
lowerWarning (1),
|
|
upperWarning (2),
|
|
upperCritical (3),
|
|
binarySensorAlarm (4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit string indicating which alarm
|
|
thresholds are enabled."
|
|
::= { pduExternalSensorConfigEntry 6 }
|
|
|
|
pduExternalSensorConfigAlarmState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on (1),
|
|
off (0)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined alarm state of external sensor"
|
|
::= { pduExternalSensorConfigEntry 7 }
|
|
|
|
pduExternalSensorConfigAlarmResetThreshold OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hysteresis used for deassertions."
|
|
::= { pduExternalSensorConfigEntry 8 }
|
|
|
|
pduExternalSensorConfigAlarmStateChangeDelay OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay measured in samples before a state is
|
|
asserted. If the value is zero, then the state is
|
|
asserted as soon as it is detected; if it is non-zero,
|
|
say n, then the assertion condition must exist for n+1
|
|
consecutive samples before the corresponding assertion
|
|
event is reported."
|
|
::= { pduExternalSensorConfigEntry 9 }
|
|
|
|
|
|
pduExternalSensorStatusTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduExternalSensorStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of PDU External Sensor status data"
|
|
::= { pduExternalSensor 4 }
|
|
|
|
pduExternalSensorStatusEntry OBJECT-TYPE
|
|
SYNTAX PduExternalSensorStatusEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status data from the PDU External Sensor
|
|
being queried"
|
|
INDEX { pduUnitStatusIndex, pduExternalSensorStatusIndex }
|
|
::= { pduExternalSensorStatusTable 1 }
|
|
|
|
PduExternalSensorStatusEntry ::= SEQUENCE {
|
|
pduExternalSensorStatusIndex
|
|
Integer32,
|
|
pduExternalSensorStatusName
|
|
DisplayString,
|
|
pduExternalSensorStatusCommStatus
|
|
INTEGER,
|
|
pduExternalSensorStatusState
|
|
INTEGER,
|
|
pduExternalSensorStatusValue
|
|
Integer32,
|
|
pduExternalSensorStatusTimeStamp
|
|
DisplayString,
|
|
pduExternalSensorStatusHighPrecisionValue
|
|
Integer32,
|
|
pduExternalSensorSTATUSAisle
|
|
INTEGER
|
|
}
|
|
|
|
pduExternalSensorStatusIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU External Sensor status table entry"
|
|
::= { pduExternalSensorStatusEntry 1 }
|
|
|
|
pduExternalSensorStatusName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-defined name for the External Sensor"
|
|
::= { pduExternalSensorStatusEntry 2 }
|
|
|
|
pduExternalSensorStatusCommStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notInstalled (1),
|
|
commsOk (2),
|
|
commsLost (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The communications status of the sensor"
|
|
::= { pduExternalSensorStatusEntry 3 }
|
|
|
|
pduExternalSensorStatusState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notPresent (0), alarmed (1), normal (2), belowLowerCritical (3), belowLowerWarning (4), aboveUpperWarning (5), aboveUpperCritical (6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This OID reports the current state of the sensor.
|
|
A notPresent (0) response indicates that no sensor is attached.
|
|
An alarmed (1) response indicates that the sensor is present
|
|
and its measured reading indicates alarmed.
|
|
A normal (2) response indicates that the sensor is present
|
|
and its measured reading lies within all thresholds.
|
|
A belowLowerCritical (3) response indicates that the sensor
|
|
is present and its measured reading lies below the lower critical threshold.
|
|
A belowLowerWarning (4) response indicates that the sensor
|
|
is present and its measured reading lies below the lower warning threshold.
|
|
An aboveUpperWarning (5) response indicates that the sensor
|
|
is present and its measured reading lies above the upper warning threshold.
|
|
An aboveUpperCritical (6) response indicates that the sensor
|
|
is present and its measured reading lies above the upper critical threshold."
|
|
::= { pduExternalSensorStatusEntry 4 }
|
|
|
|
pduExternalSensorStatusValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor reading in pduExternalSensorConfigUnits value."
|
|
::= { pduExternalSensorStatusEntry 5 }
|
|
|
|
pduExternalSensorStatusTimeStamp OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor reading timestamp."
|
|
::= { pduExternalSensorStatusEntry 6 }
|
|
|
|
pduExternalSensorStatusHighPrecisionValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor reading in tenths of pduExternalSensorConfigUnits value.
|
|
This OID is applied to temperature sensor only"
|
|
::= { pduExternalSensorStatusEntry 7 }
|
|
|
|
pduExternalSensorSTATUSAisle OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
hotAisle (1),
|
|
coldAisle (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether the external sensor is
|
|
in a hot or cold aisle"
|
|
::= { pduExternalSensorStatusEntry 8 }
|
|
|
|
-- Smart Cabinet
|
|
|
|
pduUnitSmartCabinetTableSize OBJECT-TYPE
|
|
SYNTAX Integer32 (0..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of Smart Cabinet Configuration "
|
|
::= { pduSmartCabinet 1 }
|
|
|
|
pduUnitSmartCabinetTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduUnitSmartCabinetEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of Smart Cabinet information"
|
|
::= { pduSmartCabinet 2 }
|
|
|
|
|
|
pduUnitSmartCabinetEntry OBJECT-TYPE
|
|
SYNTAX PduUnitSmartCabinetEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information of Smart Cabinet"
|
|
INDEX { pduUnitSmartCabinetIndex }
|
|
::= { pduUnitSmartCabinetTable 1 }
|
|
|
|
PduUnitSmartCabinetEntry ::= SEQUENCE {
|
|
pduUnitSmartCabinetIndex
|
|
Integer32,
|
|
pduUnitSmartCabinetCardUserName
|
|
DisplayString,
|
|
pduUnitSmartCabinetCardID
|
|
Integer32,
|
|
pduUnitSmartCabinetTimestamp
|
|
DisplayString,
|
|
pduUnitSmartCabinetDoor
|
|
INTEGER
|
|
}
|
|
|
|
pduUnitSmartCabinetIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Smart Cabinet table entry"
|
|
::= { pduUnitSmartCabinetEntry 1 }
|
|
|
|
pduUnitSmartCabinetCardUserName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User name of ID card"
|
|
::= { pduUnitSmartCabinetEntry 2 }
|
|
|
|
pduUnitSmartCabinetCardID OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Card ID."
|
|
::= { pduUnitSmartCabinetEntry 3 }
|
|
|
|
pduUnitSmartCabinetTimestamp OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the date and time of information update"
|
|
::= { pduUnitSmartCabinetEntry 4 }
|
|
|
|
pduUnitSmartCabinetDoor OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
hotAisle (1),
|
|
coldAisle (2) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Aisle of Smart Cabinet. "
|
|
::= { pduUnitSmartCabinetEntry 5 }
|
|
|
|
pduUnitSmartCabinetControl OBJECT IDENTIFIER ::= { pduSmartCabinet 3 }
|
|
|
|
pduUnitSmartCabinetControlUserName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User name of ID card"
|
|
::= { pduUnitSmartCabinetControl 1 }
|
|
|
|
pduUnitSmartCabinetControlCardID OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Card ID."
|
|
::= { pduUnitSmartCabinetControl 2 }
|
|
|
|
pduUnitSmartCabinetControlTimestamp OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the date and time of information update"
|
|
::= { pduUnitSmartCabinetControl 3 }
|
|
|
|
pduUnitSmartCabinetControlDoor OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
hotAisle (1),
|
|
coldAisle (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Aisle of Smart Cabinet. "
|
|
::= { pduUnitSmartCabinetControl 4 }
|
|
|
|
pduUnitSmartCabinetCardIDEdit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
grant (0), remove (1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smart Cabinet edit CardID "
|
|
::= { pduUnitSmartCabinetControl 5 }
|
|
|
|
pduUnitSmartCabinetColdAisleLockStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unlock (0), lock (1), notPresent (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smart Cabinet ColdAisle lock state "
|
|
::= { pduUnitSmartCabinetControl 6 }
|
|
|
|
pduUnitSmartCabinetHotAisleLockStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unlock (0), lock (1), notPresent (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smart Cabinet HotAisle lock state "
|
|
::= { pduUnitSmartCabinetControl 7 }
|
|
|
|
pduUnitSmartCabinetLockStateTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduUnitSmartCabinetLockStateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of Smart Cabinet aisle state control"
|
|
::= { pduSmartCabinet 4 }
|
|
|
|
pduUnitSmartCabinetLockStateEntry OBJECT-TYPE
|
|
SYNTAX PduUnitSmartCabinetLockStateEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information of Smart Cabinet Lock State"
|
|
INDEX { pduUnitSmartCabinetLockStateIndex }
|
|
::= { pduUnitSmartCabinetLockStateTable 1 }
|
|
|
|
PduUnitSmartCabinetLockStateEntry ::= SEQUENCE {
|
|
pduUnitSmartCabinetLockStateIndex
|
|
Integer32,
|
|
pduUnitSmartCabinetColdAisleLockState
|
|
INTEGER,
|
|
pduUnitSmartCabinetHotAisleLockState
|
|
INTEGER,
|
|
pduUnitSmartCabinetColdAisleLockLabel
|
|
DisplayString,
|
|
pduUnitSmartCabinetHotAisleLockLabel
|
|
DisplayString
|
|
}
|
|
|
|
pduUnitSmartCabinetLockStateIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the PDU Smart Cabinet table entry"
|
|
::= { pduUnitSmartCabinetLockStateEntry 1 }
|
|
|
|
pduUnitSmartCabinetColdAisleLockState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unlock (0), lock (1), notPresent (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smart Cabinet ColdAisle lock state "
|
|
::= { pduUnitSmartCabinetLockStateEntry 2 }
|
|
|
|
pduUnitSmartCabinetHotAisleLockState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unlock (0), lock (1), notPresent (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smart Cabinet HotAisle lock state "
|
|
::= { pduUnitSmartCabinetLockStateEntry 3 }
|
|
|
|
pduUnitSmartCabinetColdAisleLockLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Label of cold aisle smartcabinet"
|
|
::= { pduUnitSmartCabinetLockStateEntry 4 }
|
|
|
|
pduUnitSmartCabinetHotAisleLockLabel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Label of hot aisle smartcabinet"
|
|
::= { pduUnitSmartCabinetLockStateEntry 5 }
|
|
|
|
-- Traps Information
|
|
trapsInfo OBJECT IDENTIFIER ::= { pduTraps 1 }
|
|
|
|
trapsInfoTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TrapsInfoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of Trap Information entries. The number of
|
|
entries are given by the value of pduUnitTableSize."
|
|
::= { trapsInfo 1 }
|
|
|
|
trapsInfoEntry OBJECT-TYPE
|
|
SYNTAX TrapsInfoEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing objects used in traps"
|
|
INDEX { trapsInfoIndex }
|
|
::= { trapsInfoTable 1 }
|
|
|
|
TrapsInfoEntry ::= SEQUENCE {
|
|
trapsInfoIndex
|
|
Integer32,
|
|
userName
|
|
DisplayString,
|
|
userUpdated
|
|
DisplayString,
|
|
firmwareVersion
|
|
DisplayString,
|
|
roleUpdated
|
|
DisplayString,
|
|
smtpRecipients
|
|
DisplayString,
|
|
smtpServer
|
|
DisplayString
|
|
}
|
|
|
|
trapsInfoIndex OBJECT-TYPE
|
|
SYNTAX Integer32 (1..256)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the traps table entry"
|
|
::= { trapsInfoEntry 1 }
|
|
|
|
|
|
userName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user currently logged in."
|
|
::= { trapsInfoEntry 2 }
|
|
|
|
userUpdated OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user added, deleted, or modified."
|
|
::= { trapsInfoEntry 3 }
|
|
|
|
firmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of Firmware."
|
|
::= { trapsInfoEntry 4 }
|
|
|
|
roleUpdated OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The role added, deleted, or modified."
|
|
::= { trapsInfoEntry 5 }
|
|
|
|
smtpRecipients OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Comma separated list of SMTP recipients"
|
|
::= { trapsInfoEntry 6 }
|
|
|
|
smtpServer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The IP address/host name of the SMTP server"
|
|
::= { trapsInfoEntry 7 }
|
|
|
|
pduIndex OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for PDU. Its value ranges between 1
|
|
and the value of PDU count"
|
|
::= { trapsInfo 2 }
|
|
|
|
externalSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique value for each sensor. Its value ranges between 1
|
|
and the value of external sensor count."
|
|
::= { trapsInfo 3 }
|
|
|
|
serverPing OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
pingEnable (1),
|
|
pingDisable (2),
|
|
serverReachable (3),
|
|
serverNotReachable (4)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Whether server ping has been enabled or disabled and
|
|
whether the server is reachable or not reachable"
|
|
::= { trapsInfo 4 }
|
|
|
|
usbDevice OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
connected (1),
|
|
disconnected (2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Whether a USB device has been connected or disconnected"
|
|
::= { trapsInfo 5 }
|
|
|
|
errorDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Description of the Error"
|
|
::= { trapsInfo 6 }
|
|
|
|
cascading OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
connected (1),
|
|
disconnected (2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Whether a cascading member has been connected or disconnected"
|
|
::= { trapsInfo 7 }
|
|
|
|
systemCommunication OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok (1),
|
|
lost (2)
|
|
}
|
|
MAX-ACCESS accessible-for-notify
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Whether the Network management card has lost contact with cascading member."
|
|
::= { trapsInfo 8 }
|
|
|
|
trapCode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A number identifying the event for the trap that was sent.
|
|
Mapped unique trap code per unique event to be used by ISEE's
|
|
decoder ring."
|
|
::= { trapsInfo 9 }
|
|
|
|
trapDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the event for that last trap that was sent."
|
|
::= { trapsInfo 10 }
|
|
|
|
|
|
trapCritical NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
trapCode,
|
|
trapDescription,
|
|
sysDescr,
|
|
pduNamePlateIPAddress}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A critical alarm has occurred."
|
|
::= {pduTraps 1}
|
|
|
|
trapWarning NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
trapCode,
|
|
trapDescription,
|
|
sysDescr,
|
|
pduNamePlateIPAddress}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A warning alarm has occurred."
|
|
::= {pduTraps 2}
|
|
|
|
trapInformation NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
trapCode,
|
|
trapDescription,
|
|
sysDescr,
|
|
pduNamePlateIPAddress }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An informational alarm has occurred."
|
|
::= {pduTraps 3}
|
|
|
|
trapCleared NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
trapCode,
|
|
trapDescription,
|
|
sysDescr,
|
|
pduNamePlateIPAddress}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An alarm has cleared."
|
|
::= {pduTraps 4}
|
|
|
|
trapTest NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
trapCode,
|
|
trapDescription,
|
|
sysDescr,
|
|
pduNamePlateIPAddress}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Test trap sent to a trap receiver to check proper reception of traps"
|
|
::= {pduTraps 5}
|
|
|
|
-- ======Ehandle Sensor Status==========
|
|
pduEhandleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduEhandleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of contact sensors. The number of entries are
|
|
given by number of pdu and pduEhandleCount."
|
|
::= { pduEhandle 1 }
|
|
|
|
pduEhandleEntry OBJECT-TYPE
|
|
SYNTAX PduEhandleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry for a contact sensor"
|
|
INDEX { pduEhandleIndex }
|
|
::= { pduEhandleTable 1 }
|
|
|
|
PduEhandleEntry ::= SEQUENCE
|
|
{
|
|
pduEhandleIndex INTEGER,
|
|
pduEhandleAisle INTEGER,
|
|
pduEhandleHandleOperation INTEGER,
|
|
pduEhandleFwVer DisplayString,
|
|
pduEhandleMechanicalLock INTEGER,
|
|
pduEhandleSerial DisplayString,
|
|
pduEhandleHwVer DisplayString,
|
|
pduEhandleAutoLockTime INTEGER,
|
|
pduEhandleDoorOpenTime INTEGER,
|
|
pduEhandleMaxDoorOpenTime INTEGER,
|
|
pduEhandleUserPinLength INTEGER,
|
|
pduEhandleUserPinMode INTEGER,
|
|
pduEhandleAisleControl INTEGER
|
|
}
|
|
|
|
pduEhandleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of the PDU HID table entry"
|
|
::= { pduEhandleEntry 1 }
|
|
|
|
pduEhandleAisle OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
hot(1),
|
|
cold(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Aisle of HID handle. "
|
|
::= { pduEhandleEntry 2 }
|
|
|
|
pduEhandleHandleOperation OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unlock(1),
|
|
lock(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"HID handle control opterations "
|
|
::= { pduEhandleEntry 3 }
|
|
|
|
pduEhandleFwVer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firmware revision level of the HID"
|
|
::= { pduEhandleEntry 4 }
|
|
|
|
pduEhandleMechanicalLock OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
unlock(1),
|
|
lock(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"HID Mechanical opterations "
|
|
::= { pduEhandleEntry 5 }
|
|
|
|
pduEhandleSerial OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Serial Number of the HID"
|
|
::= { pduEhandleEntry 6 }
|
|
|
|
pduEhandleHwVer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The hardware revision level of the HID"
|
|
::= { pduEhandleEntry 7 }
|
|
|
|
pduEhandleAutoLockTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"HID Electronic Latch Autolock Time in seconds, Value ranges (0-999) "
|
|
::= { pduEhandleEntry 8 }
|
|
|
|
pduEhandleDoorOpenTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"HID Door Open Time in seconds, Value ranges (0-999)"
|
|
::= { pduEhandleEntry 9 }
|
|
|
|
pduEhandleMaxDoorOpenTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"HID Max Door Open Time in seconds, Value ranges (0-32400),
|
|
critical alarm will be raised if door is left open past this time"
|
|
::= { pduEhandleEntry 10 }
|
|
|
|
pduEhandleUserPinLength OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rack Access User minimum PIN Length, value ranges(1-15)"
|
|
::= { pduEhandleEntry 11 }
|
|
|
|
pduEhandleUserPinMode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
visible(1),
|
|
hidden (2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rack Access User PIN mode setting"
|
|
::= { pduEhandleEntry 12 }
|
|
|
|
pduEhandleAisleControl OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
combined (1),
|
|
standalone(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rack Access Aisle Control setting,
|
|
when set to standalone each aisle will controlled seprately,
|
|
when set to combined opposite aisle can be controlled with authenticated control action on either aisle"
|
|
::= { pduEhandleEntry 13 }
|
|
|
|
|
|
-- ======EHANDLE control table==========
|
|
pduEhandleControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PduEhandleControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of smartcard. The number of entries are
|
|
given by number of pdu and pduEhandleCount."
|
|
::= { pduEhandle 2 }
|
|
|
|
pduEhandleControlEntry OBJECT-TYPE
|
|
SYNTAX PduEhandleControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The smart card table entry containing the usrname, cardid, cardaisle etc."
|
|
INDEX { pduEhandleControlIndex }
|
|
::= { pduEhandleControlTable 1 }
|
|
|
|
PduEhandleControlEntry ::= SEQUENCE
|
|
{
|
|
pduEhandleControlIndex INTEGER,
|
|
pduEhandleControlUserName DisplayString,
|
|
pduEhandleControlCardIdStr DisplayString,
|
|
pduEhandleControlTimestamp DisplayString,
|
|
pduEhandleControlCardAisle INTEGER,
|
|
pduEhandleControlStartTime DisplayString,
|
|
pduEhandleControlExpireTime DisplayString,
|
|
pduEhandleControlTempUser INTEGER,
|
|
pduEhandleControlPin DisplayString
|
|
}
|
|
|
|
pduEhandleControlIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..200)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of the PDU smartcard table entry"
|
|
::= { pduEhandleControlEntry 1 }
|
|
|
|
pduEhandleControlUserName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"User name of smartcard"
|
|
::= { pduEhandleControlEntry 2 }
|
|
|
|
pduEhandleControlCardIdStr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"smartcard ID."
|
|
::= { pduEhandleControlEntry 3 }
|
|
|
|
pduEhandleControlTimestamp OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the date and time of accessing"
|
|
::= { pduEhandleControlEntry 4 }
|
|
|
|
pduEhandleControlCardAisle OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
hot(1),
|
|
cold(2),
|
|
both (3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Aisle of authorized card"
|
|
::= { pduEhandleControlEntry 5 }
|
|
|
|
pduEhandleControlStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the start date and time Rack access user is given access"
|
|
::= { pduEhandleControlEntry 6 }
|
|
|
|
pduEhandleControlExpireTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates the date and time when the access of user card will expire, To set expire time first set user as temporary user"
|
|
::= { pduEhandleControlEntry 7 }
|
|
|
|
pduEhandleControlTempUser OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
no(1),
|
|
yes(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates if the card user has temporary access"
|
|
::= { pduEhandleControlEntry 8 }
|
|
|
|
pduEhandleControlPin OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rack acess control entry keypad PIN"
|
|
::= { pduEhandleControlEntry 9 }
|
|
|
|
-- ++++ End of cPDU ++++
|
|
|
|
|
|
END
|
|
|
|
|
|
|
|
|