- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1643 lines
48 KiB
Text
1643 lines
48 KiB
Text
-- RPS S.p.A enterprise MIB definition
|
|
|
|
-- Copyright (c) RPS S.p.A.
|
|
-- Version: 1.0.3 by Michele Marcon
|
|
-- Date: 29.05.2017
|
|
|
|
-- Title: RIELLOUPS-MIB
|
|
|
|
-- RielloUPS-MIB { iso org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) riello(5491) }
|
|
|
|
-- ************************************************************************
|
|
-- ************************************************************************
|
|
|
|
RIELLOUPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, NOTIFICATION-TYPE,
|
|
OBJECT-IDENTITY, Counter32, Gauge32, Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString, TimeStamp, TimeInterval, TestAndIncr,
|
|
AutonomousType, TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC
|
|
MODULE-COMPLIANCE, OBJECT-GROUP
|
|
FROM SNMPv2-CONF
|
|
Gauge, Counter
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
rielloMIB
|
|
FROM RIELLO-MIB;
|
|
|
|
rupsMIB OBJECT IDENTIFIER ::= { rielloMIB 10 }
|
|
|
|
PositiveInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-zero and non-negative value."
|
|
SYNTAX INTEGER (1..2147483647)
|
|
|
|
NonNegativeInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-negative value."
|
|
SYNTAX INTEGER (0..2147483647)
|
|
|
|
|
|
rupsObjects OBJECT IDENTIFIER ::= { rupsMIB 1 }
|
|
|
|
rupsIdent OBJECT IDENTIFIER ::= { rupsObjects 1 }
|
|
|
|
rupsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { rupsIdent 1 }
|
|
|
|
rupsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { rupsIdent 2 }
|
|
|
|
rupsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not have the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { rupsIdent 3 }
|
|
|
|
rupsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not have the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations."
|
|
::= { rupsIdent 4 }
|
|
|
|
rupsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { rupsIdent 5 }
|
|
|
|
rupsIdentAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { rupsIdent 6 }
|
|
|
|
rupsIdentIOConfiguration OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS IO configuration."
|
|
::= { rupsIdent 7 }
|
|
|
|
rupsIdentUpsType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS type."
|
|
::= { rupsIdent 8 }
|
|
|
|
rupsIdentNominalPowerVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS nominal power VA."
|
|
::= { rupsIdent 9 }
|
|
|
|
rupsIdentNominalPowerW OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS nominal power W."
|
|
::= { rupsIdent 10 }
|
|
|
|
rupsIdentBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS nominal battery voltage."
|
|
::= { rupsIdent 11 }
|
|
|
|
rupsIdentBatteryCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS nominal battery capacity."
|
|
::= { rupsIdent 12 }
|
|
|
|
rupsIdentOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS nominal output voltage."
|
|
::= { rupsIdent 13 }
|
|
|
|
rupsIdentOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS nominal output frequency."
|
|
::= { rupsIdent 14 }
|
|
|
|
|
|
rupsBattery OBJECT IDENTIFIER ::= { rupsObjects 2 }
|
|
|
|
rupsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries. A value of batteryNormal
|
|
indicates that the remaining run-time is greater than
|
|
rupsConfigLowBattTime. A value of batteryLow indicates
|
|
that the remaining battery run-time is less than or
|
|
equal to rupsConfigLowBattTime. A value of
|
|
batteryDepleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility
|
|
power is lost (including the possibility that the
|
|
utility power is currently absent and the UPS is
|
|
unable to sustain the output)."
|
|
::= { rupsBattery 1 }
|
|
|
|
rupsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS seconds
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power."
|
|
::= { rupsBattery 2 }
|
|
|
|
rupsEstimatedMinutesRemaining OBJECT-TYPE
|
|
SYNTAX PositiveInteger -- UNITS minutes
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion
|
|
under the present load conditions if the utility power
|
|
is off and remains off, or if it were to be lost and
|
|
remain off."
|
|
::= { rupsBattery 3 }
|
|
|
|
rupsEstimatedChargeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS percent
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { rupsBattery 4 }
|
|
|
|
rupsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Volt DC
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage."
|
|
::= { rupsBattery 5 }
|
|
|
|
rupsBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 Amp DC
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present battery current."
|
|
::= { rupsBattery 6 }
|
|
|
|
rupsBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS degrees Centigrade
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing."
|
|
::= { rupsBattery 7 }
|
|
|
|
rupsBatteryPositiveVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS V
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Battery positive voltage."
|
|
::= { rupsBattery 8 }
|
|
|
|
rupsBatteryNegativeVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS V
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Battery negative voltage."
|
|
::= { rupsBattery 9 }
|
|
|
|
rupsBatteryPositiveCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 A
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Battery positive current."
|
|
::= { rupsBattery 10 }
|
|
|
|
rupsBatteryNegativeCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER (-2147483648..2147483647) -- UNITS 0.1 A
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Battery positive current."
|
|
::= { rupsBattery 11 }
|
|
|
|
rupsIsCharging OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
discharging(0),
|
|
charging(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The charging/discharging status of the battery"
|
|
::= { rupsBattery 12 }
|
|
|
|
rupsInput OBJECT IDENTIFIER ::= { rupsObjects 3 }
|
|
|
|
rupsInputLineBads OBJECT-TYPE
|
|
SYNTAX Counter
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the
|
|
manufacturer. This count is incremented by one each
|
|
time the input transitions from zero out-of-tolerance
|
|
lines to one or more input lines out-of-tolerance."
|
|
::= { rupsInput 1 }
|
|
|
|
rupsInputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
input table."
|
|
::= { rupsInput 2 }
|
|
|
|
rupsInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF RUpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputNumLines."
|
|
::= { rupsInput 3 }
|
|
|
|
rupsInputEntry OBJECT-TYPE
|
|
SYNTAX RUpsInputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line."
|
|
INDEX { rupsInputLineIndex }
|
|
::= { rupsInputTable 1 }
|
|
|
|
RUpsInputEntry ::=
|
|
SEQUENCE {
|
|
rupsInputLineIndex
|
|
PositiveInteger,
|
|
|
|
rupsInputFrequency
|
|
NonNegativeInteger,
|
|
|
|
rupsInputVoltage
|
|
NonNegativeInteger,
|
|
|
|
rupsInputCurrent
|
|
NonNegativeInteger,
|
|
|
|
rupsInputTruePower
|
|
NonNegativeInteger
|
|
}
|
|
|
|
rupsInputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input line identifier."
|
|
::= { rupsInputEntry 1 }
|
|
|
|
rupsInputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present input frequency."
|
|
::= { rupsInputEntry 2 }
|
|
|
|
rupsInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage."
|
|
::= { rupsInputEntry 3 }
|
|
|
|
rupsInputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input current."
|
|
::= { rupsInputEntry 4 }
|
|
|
|
rupsInputTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input true power."
|
|
::= { rupsInputEntry 5 }
|
|
|
|
rupsOutput OBJECT IDENTIFIER ::= { rupsObjects 4 }
|
|
|
|
rupsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker."
|
|
::= { rupsOutput 1 }
|
|
|
|
rupsOutputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output frequency."
|
|
::= { rupsOutput 2 }
|
|
|
|
rupsOutputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
output table."
|
|
::= { rupsOutput 3 }
|
|
|
|
rupsOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF RUpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of rupsOutputNumLines."
|
|
::= { rupsOutput 4 }
|
|
|
|
rupsOutputEntry OBJECT-TYPE
|
|
SYNTAX RUpsOutputEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line."
|
|
INDEX { rupsOutputLineIndex }
|
|
::= { rupsOutputTable 1 }
|
|
|
|
RUpsOutputEntry ::=
|
|
SEQUENCE {
|
|
rupsOutputLineIndex
|
|
PositiveInteger,
|
|
|
|
rupsOutputVoltage
|
|
NonNegativeInteger,
|
|
|
|
rupsOutputCurrent
|
|
NonNegativeInteger,
|
|
|
|
rupsOutputPower
|
|
NonNegativeInteger,
|
|
|
|
rupsOutputPercentLoad
|
|
INTEGER,
|
|
|
|
rupsOutputPeakCurrent
|
|
NonNegativeInteger
|
|
}
|
|
|
|
rupsOutputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output line identifier."
|
|
::= { rupsOutputEntry 1 }
|
|
|
|
rupsOutputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output voltage."
|
|
::= { rupsOutputEntry 2 }
|
|
|
|
rupsOutputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output current."
|
|
::= { rupsOutputEntry 3 }
|
|
|
|
rupsOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output true power."
|
|
::= { rupsOutputEntry 4 }
|
|
|
|
rupsOutputPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS percent
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line, i.e., the greater of
|
|
the percent load of true power capacity and the
|
|
percent load of VA."
|
|
::= { rupsOutputEntry 5 }
|
|
|
|
rupsOutputPeakCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output peak current."
|
|
::= { rupsOutputEntry 6 }
|
|
|
|
|
|
rupsBypass OBJECT IDENTIFIER ::= { rupsObjects 5 }
|
|
|
|
rupsBypassFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 Hertz
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass frequency."
|
|
::= { rupsBypass 1 }
|
|
|
|
rupsBypassNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device.
|
|
This entry indicates the number of rows in the bypass
|
|
table."
|
|
::= { rupsBypass 2 }
|
|
|
|
rupsBypassTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF RUpsBypassEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of
|
|
entries is given by the value of rupsBypassNumLines."
|
|
::= { rupsBypass 3 }
|
|
|
|
rupsBypassEntry OBJECT-TYPE
|
|
SYNTAX RUpsBypassEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bypass input."
|
|
INDEX { rupsBypassLineIndex }
|
|
::= { rupsBypassTable 1 }
|
|
|
|
RUpsBypassEntry ::=
|
|
SEQUENCE {
|
|
rupsBypassLineIndex
|
|
PositiveInteger,
|
|
|
|
rupsBypassVoltage
|
|
NonNegativeInteger,
|
|
|
|
rupsBypassCurrent
|
|
NonNegativeInteger,
|
|
|
|
rupsBypassPower
|
|
NonNegativeInteger
|
|
}
|
|
|
|
rupsBypassLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line identifier."
|
|
::= { rupsBypassEntry 1 }
|
|
|
|
rupsBypassVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS RMS Volts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass voltage."
|
|
::= { rupsBypassEntry 2 }
|
|
|
|
rupsBypassCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS 0.1 RMS Amp
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass current."
|
|
::= { rupsBypassEntry 3 }
|
|
|
|
rupsBypassPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger -- UNITS Watts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present true power conveyed by the bypass."
|
|
::= { rupsBypassEntry 4 }
|
|
|
|
rupsAlarm OBJECT IDENTIFIER ::= { rupsObjects 6 }
|
|
|
|
rupsAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { rupsAlarm 1 }
|
|
|
|
rupsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF RUpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or many rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains. The agent creates the first row with
|
|
rupsAlarmId equal to 1, and increments the value of
|
|
rupsAlarmId each time a new row is created, wrapping to
|
|
the first free value greater than or equal to 1 when
|
|
the maximum value of rupsAlarmId would otherwise be
|
|
exceeded. Consequently, after multiple operations,
|
|
the table may become sparse, e.g., containing entries
|
|
for rows 95, 100, 101, and 203 and the entries should
|
|
not be assumed to be in chronological order because
|
|
rupsAlarmId might have wrapped.
|
|
|
|
Alarms are named by an AutonomousType (OBJECT
|
|
IDENTIFIER), rupsAlarmDescr, to allow a single table to
|
|
reflect well known alarms plus alarms defined by a
|
|
particular implementation, i.e., as documented in the
|
|
private enterprise MIB definition for the device. No
|
|
two rows will have the same value of rupsAlarmDescr,
|
|
since alarms define conditions. In order to meet this
|
|
requirement, care should be taken in the definition of
|
|
alarm conditions to insure that a system cannot enter
|
|
the same condition multiple times simultaneously.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of rupsAlarmsPresent."
|
|
::= { rupsAlarm 2 }
|
|
|
|
rupsAlarmEntry OBJECT-TYPE
|
|
SYNTAX RUpsAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
|
|
|
|
|
|
|
|
|
|
particular alarm."
|
|
INDEX { rupsAlarmId }
|
|
::= { rupsAlarmTable 1 }
|
|
|
|
RUpsAlarmEntry ::=
|
|
SEQUENCE {
|
|
rupsAlarmId
|
|
PositiveInteger,
|
|
|
|
rupsAlarmDescr
|
|
OBJECT IDENTIFIER,
|
|
|
|
rupsAlarmTime
|
|
PositiveInteger
|
|
}
|
|
|
|
rupsAlarmId OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { rupsAlarmEntry 1 }
|
|
|
|
rupsAlarmDescr OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object referenced should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition."
|
|
::= { rupsAlarmEntry 2 }
|
|
|
|
rupsAlarmTime OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected. If the alarm condition was detected at the
|
|
time of agent startup and presumably existed before
|
|
agent startup, the value of rupsAlarmTime shall equal
|
|
0."
|
|
::= { rupsAlarmEntry 3 }
|
|
|
|
rupsWellKnownAlarms OBJECT IDENTIFIER ::= { rupsAlarm 3 }
|
|
|
|
rupsAlarmBatteryBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 1 }
|
|
|
|
rupsAlarmOnBattery OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 2 }
|
|
|
|
rupsAlarmLowBattery OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 3 }
|
|
|
|
rupsAlarmShutdownImminent OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 4 }
|
|
|
|
rupsAlarmTempBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 5 }
|
|
|
|
rupsAlarmFault OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 6 }
|
|
|
|
rupsAlarmInternal OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 7 }
|
|
|
|
rupsAlarmOutputOverload OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 8 }
|
|
|
|
rupsAlarmOnBypass OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 9 }
|
|
|
|
rupsAlarmBypassBad OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 10 }
|
|
|
|
rupsAlarmShutdownImminent OBJECT IDENTIFIER ::= { rupsWellKnownAlarms 11 }
|
|
|
|
--
|
|
-- The Test Group
|
|
--
|
|
|
|
rupsTest OBJECT IDENTIFIER ::= { rupsObjects 7 }
|
|
|
|
rupsTestId OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
ACCESS read-write
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"The test is named by an OBJECT IDENTIFIER which
|
|
allows a standard mechanism for the initiation of
|
|
tests, including the well known tests identified in
|
|
this document as well as those introduced by a
|
|
particular implementation, i.e., as documented in the
|
|
private enterprise MIB definition for the device.
|
|
|
|
Setting this variable initiates the named test. Sets
|
|
to this variable require the presence of
|
|
upsTestSpinLock in the same SNMP message.
|
|
|
|
The set request will be rejected with an appropriate
|
|
error message if the requested test cannot be
|
|
performed, including attempts to start a test when
|
|
another test is already in progress. The status of
|
|
the current or last test is maintained in
|
|
upsTestResultsSummary. Tests in progress may be
|
|
aborted by setting the rupsTestId variable to
|
|
rupsTestAbortTestInProgress.
|
|
|
|
Read operations return the value of the name of the
|
|
test in progress if a test is in progress or the name
|
|
of the last test performed if no test is in progress,
|
|
unless no test has been run, in which case the well
|
|
known value upsTestNoTestsInitiated is returned."
|
|
::= { rupsTest 1 }
|
|
|
|
-- see [6] for more information on the semantics of objects with
|
|
-- syntax of TestAndIncr
|
|
|
|
rupsTestSpinLock OBJECT-TYPE
|
|
SYNTAX TestAndIncr
|
|
ACCESS read-write
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"A spin lock on the test subsystem. The spinlock is
|
|
used as follows.
|
|
|
|
Before starting a test, a manager-station should make
|
|
sure that a test is not in progress as follows:
|
|
|
|
try_again:
|
|
get (upsTestSpinLock)
|
|
while (upsTestResultsSummary == inProgress) {
|
|
/* loop while a test is running for another
|
|
manager */
|
|
short delay
|
|
get (upsTestSpinLock)
|
|
}
|
|
lock_value = upsTestSpinLock
|
|
/* no test in progress, start the test */
|
|
set (upsTestSpinLock = lock_value, upsTestId =
|
|
requested_test)
|
|
if (error_index == 1) { /* (upsTestSpinLock
|
|
failed) */
|
|
/* if problem is not access control, then
|
|
some other manager slipped in ahead of us
|
|
*/
|
|
goto try_again
|
|
}
|
|
if (error_index == 2) { /* (upsTestId) */
|
|
/* cannot perform the test */
|
|
give up
|
|
}
|
|
/* test started ok */
|
|
/* wait for test completion by polling
|
|
upsTestResultsSummary */
|
|
get (upsTestSpinLock, upsTestResultsSummary,
|
|
upsTestResultsDetail)
|
|
while (upsTestResultsSummary == inProgress) {
|
|
short delay
|
|
get (upsTestSpinLock, upsTestResultsSummary,
|
|
upsTestResultsDetail)
|
|
}
|
|
/* when test completes, retrieve any additional
|
|
test results */
|
|
/* if upsTestSpinLock == lock_value + 1, then
|
|
these are our test */
|
|
/* results (as opposed to another manager's */
|
|
The initial value of upsTestSpinLock at agent
|
|
initialization shall
|
|
be 1."
|
|
::= { rupsTest 2 }
|
|
|
|
rupsTestResultsSummary OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
donePass(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestsInitiated(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
doneWarning(2), and doneError(3) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively. The value aborted(4) is
|
|
returned for tests which are aborted by setting the
|
|
value of upsTestId to upsTestAbortTestInProgress.
|
|
Tests which have not yet concluded are indicated by
|
|
inProgress(5). The value noTestsInitiated(6)
|
|
indicates that no previous test results are available,
|
|
such as is the case when no tests have been run since
|
|
the last reinitialization of the network management
|
|
subsystem and the system has no provision for non-
|
|
volatile storage of test results."
|
|
::= { rupsTest 3 }
|
|
|
|
rupsTestResultsDetail OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"Additional information about upsTestResultsSummary.
|
|
If no additional information available, a zero length
|
|
string is returned."
|
|
::= { rupsTest 4 }
|
|
|
|
rupsTestStartTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"The value of sysUpTime at the time the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the time the previous test was initiated. If the
|
|
value of upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestStartTime has the value 0."
|
|
::= { rupsTest 5 }
|
|
|
|
rupsTestElapsedTime OBJECT-TYPE
|
|
SYNTAX TimeInterval
|
|
ACCESS read-only
|
|
STATUS optional
|
|
DESCRIPTION
|
|
"The amount of time, in TimeTicks, since the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the previous test took to complete. If the value of
|
|
upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestElapsedTime has the value 0."
|
|
::= { rupsTest 6 }
|
|
|
|
--
|
|
-- Well known tests.
|
|
--
|
|
|
|
rupsWellKnownTests OBJECT IDENTIFIER ::= { rupsTest 7 }
|
|
|
|
|
|
rupsTestNoTestsInitiated OBJECT IDENTIFIER
|
|
-- "No tests have been initiated and no test is in
|
|
-- progress."
|
|
::= { rupsWellKnownTests 1 }
|
|
|
|
rupsTestAbortTestInProgress OBJECT IDENTIFIER
|
|
-- "The test in progress is to be aborted / the test in
|
|
-- progress was aborted."
|
|
::= { rupsWellKnownTests 2 }
|
|
|
|
rupsTestGeneralSystemsTest OBJECT IDENTIFIER
|
|
-- "The manufacturer's standard test of UPS device
|
|
-- systems."
|
|
::= { rupsWellKnownTests 3 }
|
|
|
|
rupsTestQuickBatteryTest OBJECT IDENTIFIER
|
|
-- "A test that is sufficient to determine if the battery
|
|
-- needs replacement."
|
|
::= { rupsWellKnownTests 4 }
|
|
|
|
rupsTestDeepBatteryCalibration OBJECT IDENTIFIER
|
|
-- "The system is placed on battery to a discharge level,
|
|
-- set by the manufacturer, sufficient to determine
|
|
-- battery replacement and battery run-time with a high
|
|
-- degree of confidence. WARNING: this test will leave
|
|
-- the battery in a low charge state and will require
|
|
-- time for recharging to a level sufficient to provide
|
|
-- normal battery duration for the protected load."
|
|
::= { rupsWellKnownTests 5 }
|
|
|
|
rupsControl OBJECT IDENTIFIER ::= { rupsObjects 8 }
|
|
|
|
rupsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
|
|
|
|
|
|
|
|
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off."
|
|
::= { rupsControl 1 }
|
|
|
|
rupsShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will shutdown (i.e., turn off)
|
|
either the UPS output or the UPS system (as determined
|
|
by the value of upsShutdownType at the time of
|
|
shutdown) after the indicated number of seconds, or
|
|
less if the UPS batteries become depleted. Setting
|
|
this object to 0 will cause the shutdown to occur
|
|
immediately. Setting this object to -1 will abort the
|
|
countdown. If the system is already in the desired
|
|
state at the time the countdown reaches 0, then
|
|
nothing will happen. That is, there is no additional
|
|
action at that time if upsShutdownType = system and
|
|
the system is already off. Similarly, there is no
|
|
additional action at that time if upsShutdownType =
|
|
output and the output is already off. When read,
|
|
upsShutdownAfterDelay will return the number of
|
|
seconds remaining until shutdown, or -1 if no shutdown
|
|
countdown is in effect. On some systems, if the agent
|
|
is restarted while a shutdown countdown is in effect,
|
|
the countdown may be aborted. Sets to this object
|
|
override any upsShutdownAfterDelay already in effect."
|
|
::= { rupsControl 2 }
|
|
|
|
rupsStartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds, including starting the
|
|
UPS, if necessary. Setting this object to 0 will
|
|
cause the startup to occur immediately. Setting this
|
|
|
|
|
|
|
|
|
|
|
|
object to -1 will abort the countdown. If the output
|
|
is already on at the time the countdown reaches 0,
|
|
then nothing will happen. Sets to this object
|
|
override the effect of any upsStartupAfterDelay
|
|
countdown or upsRebootWithDuration countdown in
|
|
progress. When read, upsStartupAfterDelay will return
|
|
the number of seconds until startup, or -1 if no
|
|
startup countdown is in effect. If the countdown
|
|
expires during a utility failure, the startup shall
|
|
not occur until the utility power is restored. On
|
|
some systems, if the agent is restarted while a
|
|
startup countdown is in effect, the countdown is
|
|
aborted."
|
|
::= { rupsControl 3 }
|
|
|
|
rupsRebootWithDuration OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS seconds
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object will immediately shutdown (i.e.,
|
|
turn off) either the UPS output or the UPS system (as
|
|
determined by the value of upsShutdownType at the time
|
|
of shutdown) for a period equal to the indicated
|
|
number of seconds, after which time the output will be
|
|
started, including starting the UPS, if necessary. If
|
|
the number of seconds required to perform the request
|
|
is greater than the requested duration, then the
|
|
requested shutdown and startup cycle shall be
|
|
performed in the minimum time possible, but in no case
|
|
shall this require more than the requested duration
|
|
plus 60 seconds. When read, upsRebootWithDuration
|
|
shall return the number of seconds remaining in the
|
|
countdown, or -1 if no countdown is in progress. If
|
|
the startup should occur during a utility failure, the
|
|
startup shall not occur until the utility power is
|
|
restored."
|
|
::= { rupsControl 4 }
|
|
|
|
rupsAutoRestart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this object to 'on' will cause the UPS system
|
|
to restart after a shutdown if the shutdown occurred
|
|
during a power loss as a result of either a
|
|
upsShutdownAfterDelay or an internal battery depleted
|
|
condition. Setting this object to 'off' will prevent
|
|
the UPS system from restarting after a shutdown until
|
|
an operator manually or remotely explicitly restarts
|
|
it. If the UPS is in a startup or reboot countdown,
|
|
then the UPS will not restart until that delay has
|
|
been satisfied."
|
|
::= { rupsControl 5 }
|
|
|
|
rupsTemperature OBJECT IDENTIFIER ::= { rupsObjects 10 }
|
|
|
|
rupsSystemTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 1 }
|
|
|
|
rupsPowerTemperature1 OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 2 }
|
|
|
|
rupsPowerTemperature2 OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 3 }
|
|
|
|
rupsPowerTemperature3 OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 4 }
|
|
|
|
rupsChargerTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 5 }
|
|
|
|
rupsBatteryPositiveTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 6 }
|
|
|
|
rupsBatteryNegativeTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 7 }
|
|
|
|
rupsBatteryExternalTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS degree Celsius
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present temperature."
|
|
::= { rupsTemperature 8 }
|
|
|
|
rupsMPS OBJECT IDENTIFIER ::= { rupsObjects 20 }
|
|
|
|
mpsAlarmGroupS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group s."
|
|
::= { rupsMPS 1 }
|
|
|
|
mpsAlarmGroupC OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group c."
|
|
::= { rupsMPS 2 }
|
|
|
|
mpsAlarmGroupB OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group b."
|
|
::= { rupsMPS 3 }
|
|
|
|
mpsAlarmGroupR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group r."
|
|
::= { rupsMPS 4 }
|
|
|
|
mpsAlarmGroupRI OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group RI."
|
|
::= { rupsMPS 5 }
|
|
|
|
mpsAlarmGroupI OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group I."
|
|
::= { rupsMPS 6 }
|
|
|
|
mpsAlarmGroupA0 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group A0."
|
|
::= { rupsMPS 7 }
|
|
|
|
mpsAlarmGroupA1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group A1."
|
|
::= { rupsMPS 8 }
|
|
|
|
mpsAlarmGroupA2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group A2."
|
|
::= { rupsMPS 9 }
|
|
|
|
mpsAlarmGroupA3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group A3."
|
|
::= { rupsMPS 10 }
|
|
|
|
mpsAlarmGroupA4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group A4."
|
|
::= { rupsMPS 11 }
|
|
|
|
mpsAlarmGroupA5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm group A5."
|
|
::= { rupsMPS 12 }
|
|
|
|
rupsMST OBJECT IDENTIFIER ::= { rupsObjects 21 }
|
|
|
|
mstWarningGroupW0W1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The anomaly group W0W1."
|
|
::= { rupsMST 1 }
|
|
|
|
mstAnomalyGroupA0A1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The anomaly group A0A1."
|
|
::= { rupsMST 2 }
|
|
|
|
mstAnomalyGroupA2A3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The anomaly group A2A3."
|
|
::= { rupsMST 3 }
|
|
|
|
mstAnomalyGroupA4A5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The anomaly group A4A5."
|
|
::= { rupsMST 4 }
|
|
|
|
mstFaultGroupF0F1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The fault group F0F1."
|
|
::= { rupsMST 5 }
|
|
|
|
mstFaultGroupF2F3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The fault group F2F3."
|
|
::= { rupsMST 6 }
|
|
|
|
mstFaultGroupF4F5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The fault group F4F5."
|
|
::= { rupsMST 7 }
|
|
|
|
mstLockGroupL0L1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The lock group L0L1."
|
|
::= { rupsMST 8 }
|
|
|
|
mstLockGroupL2L3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The lock group L2L3."
|
|
::= { rupsMST 9 }
|
|
|
|
mstLockGroupL4L5 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The lock group L4L5."
|
|
::= { rupsMST 10 }
|
|
|
|
mstEventGroupE0E1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The event group E0E1."
|
|
::= { rupsMST 11 }
|
|
|
|
rupsMPW OBJECT IDENTIFIER ::= { rupsObjects 22 }
|
|
|
|
mpwSystemStatusGroup1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The system status group 1."
|
|
::= { rupsMPW 1 }
|
|
|
|
mpwSystemStatusGroup2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The system status group 2."
|
|
::= { rupsMPW 2 }
|
|
|
|
mpwSystemStatusGroup3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The system status group 3."
|
|
::= { rupsMPW 3 }
|
|
|
|
mpwBypassModuleAlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass module alarm group."
|
|
::= { rupsMPW 4 }
|
|
|
|
mpwPowerModule1AlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module 1 alarm group."
|
|
::= { rupsMPW 5 }
|
|
|
|
mpwPowerModule2AlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module 2 alarm group."
|
|
::= { rupsMPW 6 }
|
|
|
|
mpwPowerModule3AlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module 3 alarm group."
|
|
::= { rupsMPW 7 }
|
|
|
|
mpwPowerModule4AlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module 4 alarm group."
|
|
::= { rupsMPW 8 }
|
|
|
|
mpwPowerModule5AlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module 5 alarm group."
|
|
::= { rupsMPW 9 }
|
|
|
|
mpwPowerModule6AlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module 6 alarm group."
|
|
::= { rupsMPW 10 }
|
|
|
|
mpwPowerModule7AlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The power module 7 alarm group."
|
|
::= { rupsMPW 11 }
|
|
|
|
mpwBypassModuleStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass module status."
|
|
::= { rupsMPW 12 }
|
|
|
|
mpwPowerModule1Status OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of power module 1."
|
|
::= { rupsMPW 13 }
|
|
|
|
mpwPowerModule2Status OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of power module 2."
|
|
::= { rupsMPW 14 }
|
|
|
|
mpwPowerModule3Status OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of power module 3."
|
|
::= { rupsMPW 15 }
|
|
|
|
mpwPowerModule4Status OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of power module 4."
|
|
::= { rupsMPW 16 }
|
|
|
|
mpwPowerModule5Status OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of power module 5."
|
|
::= { rupsMPW 17 }
|
|
|
|
mpwPowerModule6Status OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of power module 6."
|
|
::= { rupsMPW 18 }
|
|
|
|
mpwPowerModule7Status OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of power module 7."
|
|
::= { rupsMPW 19 }
|
|
|
|
mpwControl OBJECT IDENTIFIER ::= { rupsMPW 20 }
|
|
|
|
mpwCommandCode OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Command code."
|
|
::= { mpwControl 1 }
|
|
|
|
mpwShutdownDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Shutdown delay."
|
|
::= { mpwControl 2 }
|
|
|
|
mpwRestoreDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Restore delay."
|
|
::= { mpwControl 3 }
|
|
|
|
mpwModuleApplyCommand OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Module apply command"
|
|
::= { mpwControl 4 }
|
|
|
|
mpwCommandResult OBJECT-TYPE
|
|
SYNTAX INTEGER -- UNITS RMS Volts
|
|
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Result of command."
|
|
::= { mpwControl 5 }
|
|
|
|
|
|
rupsTraps OBJECT IDENTIFIER ::= { rupsMIB 2 }
|
|
|
|
rupsTrapOnBattery TRAP-TYPE
|
|
ENTERPRISE rupsTraps
|
|
VARIABLES { rupsEstimatedMinutesRemaining, rupsSecondsOnBattery,
|
|
rupsConfigLowBattTime }
|
|
DESCRIPTION
|
|
"The UPS is operating on battery power. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or is no longer running on
|
|
battery."
|
|
::= 1
|
|
|
|
rupsTrapTestCompleted TRAP-TYPE
|
|
ENTERPRISE rupsTraps
|
|
DESCRIPTION
|
|
"This trap is sent upon completion of a UPS diagnostic
|
|
test."
|
|
::= 2
|
|
|
|
rupsTrapAlarmEntryAdded TRAP-TYPE
|
|
ENTERPRISE rupsTraps
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is inserted into
|
|
to the alarm table. It is sent on the insertion of
|
|
|
|
all alarms except for rupsAlarmOnBattery and
|
|
rupsAlarmTestInProgress."
|
|
::= 3
|
|
|
|
rupsTrapAlarmEntryRemoved TRAP-TYPE
|
|
ENTERPRISE rupsTraps
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is removed from
|
|
the alarm table. It is sent on the removal of all
|
|
alarms except for rupsAlarmTestInProgress."
|
|
::= 4
|
|
|
|
|
|
END
|
|
|