- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1078 lines
26 KiB
Text
1078 lines
26 KiB
Text
NETTRACK-E3METER-SNMP-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Integer32,
|
|
enterprises
|
|
FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION,
|
|
TruthValue
|
|
FROM SNMPv2-TC
|
|
;
|
|
|
|
nettrack OBJECT IDENTIFIER
|
|
::= { enterprises 21695 }
|
|
|
|
public OBJECT IDENTIFIER
|
|
::= { nettrack 1 }
|
|
|
|
e3Mib
|
|
MODULE-IDENTITY
|
|
LAST-UPDATED "201810090000Z"
|
|
ORGANIZATION "net-track GmbH"
|
|
CONTACT-INFO "net-track GmbH
|
|
Duensstrasse 1
|
|
3186 Duedingen
|
|
Switzerland
|
|
www.net-track.ch"
|
|
DESCRIPTION "Management Information for E3METER IPM products
|
|
www.e3meter.com"
|
|
REVISION "201810090000Z"
|
|
DESCRIPTION "Added RCM traps."
|
|
REVISION "201810080000Z"
|
|
DESCRIPTION "Added RCM-related stuff."
|
|
REVISION "201604180000Z"
|
|
DESCRIPTION "Added e3IpmAlarmTable."
|
|
REVISION "201602030000Z"
|
|
DESCRIPTION "Added traps."
|
|
REVISION "201204120000Z"
|
|
DESCRIPTION "Added import of TEXTUAL-CONVENTION."
|
|
REVISION "201111020000Z"
|
|
DESCRIPTION "Added channel type and channel groups."
|
|
REVISION "201108190000Z"
|
|
DESCRIPTION "Added e3IpmChannelName."
|
|
REVISION "201101260000Z"
|
|
DESCRIPTION "Corrected some syntax errors for very picky parsers."
|
|
REVISION "201012060000Z"
|
|
DESCRIPTION "Added sensor data."
|
|
REVISION "201010200000Z"
|
|
DESCRIPTION "Initial version of this MIB module."
|
|
::= { public 10 }
|
|
|
|
e3Ipm OBJECT IDENTIFIER
|
|
::= { e3Mib 7 }
|
|
|
|
-- ===========================================================================
|
|
-- Textual conventions
|
|
--
|
|
|
|
Watts ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Watts"
|
|
SYNTAX INTEGER
|
|
|
|
VoltAmpereReactives ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-ampere reactives"
|
|
SYNTAX Integer32
|
|
|
|
VoltAmperes ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-amperes"
|
|
SYNTAX Integer32
|
|
|
|
WattHours ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Watt hours"
|
|
SYNTAX Integer32
|
|
|
|
VoltAmpereReactiveHours ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-ampere reactive hours"
|
|
SYNTAX Integer32
|
|
|
|
VoltAmpereHours ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Volt-ampere hours"
|
|
SYNTAX Integer32
|
|
|
|
MilliAmperes ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Milli-amperes"
|
|
SYNTAX Integer32
|
|
|
|
MilliVolts ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Milli-volts"
|
|
SYNTAX Integer32
|
|
|
|
MilliHertz ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Milli-hertz"
|
|
SYNTAX Integer32
|
|
|
|
DeciDegreesCelsius ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Deci-degrees celsius"
|
|
SYNTAX Integer32
|
|
|
|
Permil ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Per mil"
|
|
SYNTAX INTEGER
|
|
|
|
-- ===========================================================================
|
|
-- Agent information
|
|
--
|
|
|
|
e3IpmInfo OBJECT IDENTIFIER
|
|
::= { e3Ipm 1 }
|
|
|
|
e3IpmInfoSerial OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number."
|
|
::= { e3IpmInfo 1 }
|
|
|
|
e3IpmInfoModel OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model number."
|
|
::= { e3IpmInfo 2 }
|
|
|
|
e3IpmInfoHWVersion OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
rev-a (0),
|
|
rev-b (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Hardware revision."
|
|
::= { e3IpmInfo 3 }
|
|
|
|
e3IpmInfoFWVersion OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Integer representation of the firmware revision
|
|
(major.minor) represented as a 16 bit integer."
|
|
::= { e3IpmInfo 4 }
|
|
|
|
e3IpmInfoMeters OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of power meters in this IPS."
|
|
::= { e3IpmInfo 5 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM meters
|
|
--
|
|
|
|
e3IpmMeterTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmMeterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmMeterTable holds information related to the
|
|
powermeters of all IPS nodes."
|
|
::= { e3Ipm 2 }
|
|
|
|
e3IpmMeterEntry OBJECT-TYPE
|
|
SYNTAX E3IpmMeterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific powermeter."
|
|
INDEX { e3IpmMeter }
|
|
::= { e3IpmMeterTable 1 }
|
|
|
|
E3IpmMeterEntry ::= SEQUENCE {
|
|
e3IpmMeter Integer32,
|
|
e3IpmEnergyP WattHours,
|
|
e3IpmEnergyQ VoltAmpereReactiveHours,
|
|
e3IpmEnergyS VoltAmpereHours,
|
|
e3IpmPowerP Watts,
|
|
e3IpmPowerQ VoltAmpereReactives,
|
|
e3IpmPowerS VoltAmperes,
|
|
e3IpmUrms MilliVolts,
|
|
e3IpmIrms MilliAmperes,
|
|
e3IpmFrequency MilliHertz,
|
|
e3IpmChannelName OCTET STRING,
|
|
e3IpmChannelType INTEGER
|
|
}
|
|
|
|
e3IpmMeter OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the powermeter of this IPS."
|
|
::= { e3IpmMeterEntry 1 }
|
|
|
|
e3IpmEnergyP OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Active energy in watt hours."
|
|
::= { e3IpmMeterEntry 2 }
|
|
|
|
e3IpmEnergyQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactiveHours
|
|
UNITS "varh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reactive energy in volt-ampere reactives hours."
|
|
::= { e3IpmMeterEntry 3 }
|
|
|
|
e3IpmEnergyS OBJECT-TYPE
|
|
SYNTAX VoltAmpereHours
|
|
UNITS "VAh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent energy in volt-ampere hours."
|
|
::= { e3IpmMeterEntry 4 }
|
|
|
|
e3IpmPowerP OBJECT-TYPE
|
|
SYNTAX Watts
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Active power at a given instant."
|
|
::= { e3IpmMeterEntry 5 }
|
|
|
|
e3IpmPowerQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactives
|
|
UNITS "var"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reactive power at a given instant."
|
|
::= { e3IpmMeterEntry 6 }
|
|
|
|
e3IpmPowerS OBJECT-TYPE
|
|
SYNTAX VoltAmperes
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Apparent power at a given instant."
|
|
::= { e3IpmMeterEntry 7 }
|
|
|
|
e3IpmUrms OBJECT-TYPE
|
|
SYNTAX MilliVolts
|
|
UNITS "mV"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RMS voltage at a given instant."
|
|
::= { e3IpmMeterEntry 8 }
|
|
|
|
e3IpmIrms OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RMS current at a given instant."
|
|
::= { e3IpmMeterEntry 9 }
|
|
|
|
e3IpmFrequency OBJECT-TYPE
|
|
SYNTAX MilliHertz
|
|
UNITS "mHz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Frequency measured a given instant."
|
|
::= { e3IpmMeterEntry 10 }
|
|
|
|
e3IpmChannelName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel name."
|
|
::= { e3IpmMeterEntry 11 }
|
|
|
|
e3IpmChannelType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
live-wire (0),
|
|
neutral-wire (1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel type: For neutral wire channels, only I_rms will
|
|
contain meaningful values."
|
|
::= { e3IpmMeterEntry 12 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM sensors
|
|
--
|
|
|
|
e3IpmSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmSensorTable holds information related to the
|
|
sensor of this IPM."
|
|
::= { e3Ipm 3 }
|
|
|
|
e3IpmSensorEntry OBJECT-TYPE
|
|
SYNTAX E3IpmSensorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific sensor."
|
|
INDEX { e3IpmSensor }
|
|
::= { e3IpmSensorTable 1 }
|
|
|
|
E3IpmSensorEntry ::= SEQUENCE {
|
|
e3IpmSensor Integer32,
|
|
e3IpmSensorType INTEGER,
|
|
e3IpmSensorVersion OCTET STRING,
|
|
e3IpmSensorTemperatureCelsius DeciDegreesCelsius,
|
|
e3IpmSensorHumidity Permil
|
|
}
|
|
|
|
e3IpmSensor OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor port number."
|
|
::= { e3IpmSensorEntry 1 }
|
|
|
|
e3IpmSensorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none (0),
|
|
temp (1),
|
|
temp-humidity (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor type."
|
|
::= { e3IpmSensorEntry 2 }
|
|
|
|
e3IpmSensorVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor version."
|
|
::= { e3IpmSensorEntry 3 }
|
|
|
|
e3IpmSensorTemperatureCelsius OBJECT-TYPE
|
|
SYNTAX DeciDegreesCelsius
|
|
UNITS "deg-C/10"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature in tenth degrees."
|
|
::= { e3IpmSensorEntry 4 }
|
|
|
|
e3IpmSensorHumidity OBJECT-TYPE
|
|
SYNTAX Permil
|
|
UNITS "/1000"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Relative humidity in per mil."
|
|
::= { e3IpmSensorEntry 5 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM predefined channel groups
|
|
--
|
|
|
|
e3IpmPGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmPGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmPGroupTable holds information related to predefined
|
|
channel groups."
|
|
::= { e3Ipm 4 }
|
|
|
|
e3IpmPGroupEntry OBJECT-TYPE
|
|
SYNTAX E3IpmPGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific group."
|
|
INDEX { e3IpmPGroup }
|
|
::= { e3IpmPGroupTable 1 }
|
|
|
|
E3IpmPGroupEntry ::= SEQUENCE {
|
|
e3IpmPGroup Integer32,
|
|
e3IpmPGName OCTET STRING,
|
|
e3IpmPGMembers Integer32,
|
|
e3IpmPGEnergyP WattHours,
|
|
e3IpmPGEnergyQ VoltAmpereReactiveHours,
|
|
e3IpmPGEnergyS VoltAmpereHours,
|
|
e3IpmPGPowerP Watts,
|
|
e3IpmPGPowerQ VoltAmpereReactives,
|
|
e3IpmPGPowerS VoltAmperes,
|
|
e3IpmPGIrms MilliAmperes
|
|
}
|
|
|
|
e3IpmPGroup OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Predefined channel group number."
|
|
::= { e3IpmPGroupEntry 1 }
|
|
|
|
e3IpmPGName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group name."
|
|
::= { e3IpmPGroupEntry 2 }
|
|
|
|
e3IpmPGMembers OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit set specifying the channels which are
|
|
members of this channel group. If bit 0 is set,
|
|
this means that channel CH1 is member of this
|
|
group. Bit 1 stands for CH2 and so on."
|
|
::= { e3IpmPGroupEntry 3 }
|
|
|
|
e3IpmPGEnergyP OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active energy in watt hours."
|
|
::= { e3IpmPGroupEntry 4 }
|
|
|
|
e3IpmPGEnergyQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactiveHours
|
|
UNITS "varh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive energy in volt-ampere reactives hours."
|
|
::= { e3IpmPGroupEntry 5 }
|
|
|
|
e3IpmPGEnergyS OBJECT-TYPE
|
|
SYNTAX VoltAmpereHours
|
|
UNITS "VAh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent energy in volt-ampere hours."
|
|
::= { e3IpmPGroupEntry 6 }
|
|
|
|
e3IpmPGPowerP OBJECT-TYPE
|
|
SYNTAX Watts
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active power at a given instant."
|
|
::= { e3IpmPGroupEntry 7 }
|
|
|
|
e3IpmPGPowerQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactives
|
|
UNITS "var"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive power at a given instant."
|
|
::= { e3IpmPGroupEntry 8 }
|
|
|
|
e3IpmPGPowerS OBJECT-TYPE
|
|
SYNTAX VoltAmperes
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent power at a given instant."
|
|
::= { e3IpmPGroupEntry 9 }
|
|
|
|
e3IpmPGIrms OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group RMS current at a given instant."
|
|
::= { e3IpmPGroupEntry 10 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM user defined channel groups
|
|
--
|
|
|
|
e3IpmUGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmUGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmUGroupTable holds information related to user
|
|
defined channel groups."
|
|
::= { e3Ipm 5 }
|
|
|
|
e3IpmUGroupEntry OBJECT-TYPE
|
|
SYNTAX E3IpmUGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds the information related to one specific group."
|
|
INDEX { e3IpmUGroup }
|
|
::= { e3IpmUGroupTable 1 }
|
|
|
|
E3IpmUGroupEntry ::= SEQUENCE {
|
|
e3IpmUGroup Integer32,
|
|
e3IpmUGName OCTET STRING,
|
|
e3IpmUGMembers Integer32,
|
|
e3IpmUGEnergyP WattHours,
|
|
e3IpmUGEnergyQ VoltAmpereReactiveHours,
|
|
e3IpmUGEnergyS VoltAmpereHours,
|
|
e3IpmUGPowerP Watts,
|
|
e3IpmUGPowerQ VoltAmpereReactives,
|
|
e3IpmUGPowerS VoltAmperes,
|
|
e3IpmUGIrms MilliAmperes
|
|
}
|
|
|
|
e3IpmUGroup OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User defined channel group number."
|
|
::= { e3IpmUGroupEntry 1 }
|
|
|
|
e3IpmUGName OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(0..15))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group name."
|
|
::= { e3IpmUGroupEntry 2 }
|
|
|
|
e3IpmUGMembers OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A bit set specifying the channels which are
|
|
members of this channel group. If bit 0 is set,
|
|
this means that channel CH1 is member of this
|
|
group. Bit 1 stands for CH2 and so on. If no
|
|
members are configured, the group is inactive."
|
|
::= { e3IpmUGroupEntry 3 }
|
|
|
|
e3IpmUGEnergyP OBJECT-TYPE
|
|
SYNTAX WattHours
|
|
UNITS "Wh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active energy in watt hours."
|
|
::= { e3IpmUGroupEntry 4 }
|
|
|
|
e3IpmUGEnergyQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactiveHours
|
|
UNITS "varh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive energy in volt-ampere reactives hours."
|
|
::= { e3IpmUGroupEntry 5 }
|
|
|
|
e3IpmUGEnergyS OBJECT-TYPE
|
|
SYNTAX VoltAmpereHours
|
|
UNITS "VAh"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent energy in volt-ampere hours."
|
|
::= { e3IpmUGroupEntry 6 }
|
|
|
|
e3IpmUGPowerP OBJECT-TYPE
|
|
SYNTAX Watts
|
|
UNITS "W"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group active power at a given instant."
|
|
::= { e3IpmUGroupEntry 7 }
|
|
|
|
e3IpmUGPowerQ OBJECT-TYPE
|
|
SYNTAX VoltAmpereReactives
|
|
UNITS "var"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group reactive power at a given instant."
|
|
::= { e3IpmUGroupEntry 8 }
|
|
|
|
e3IpmUGPowerS OBJECT-TYPE
|
|
SYNTAX VoltAmperes
|
|
UNITS "VA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group apparent power at a given instant."
|
|
::= { e3IpmUGroupEntry 9 }
|
|
|
|
e3IpmUGIrms OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Channel group RMS current at a given instant."
|
|
::= { e3IpmUGroupEntry 10 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM Alarm Settings
|
|
--
|
|
|
|
e3IpmAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF E3IpmAlarmTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds alarm settings."
|
|
::= { e3Ipm 6 }
|
|
|
|
e3IpmAlarmTableEntry OBJECT-TYPE
|
|
SYNTAX E3IpmAlarmTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Holds alarm settings for one specific measured value."
|
|
INDEX { e3IpmAlarmIndex }
|
|
::= { e3IpmAlarmTable 1 }
|
|
|
|
E3IpmAlarmTableEntry ::= SEQUENCE {
|
|
e3IpmAlarmIndex INTEGER,
|
|
e3IpmAlarmState INTEGER,
|
|
e3IpmAlarmCritLowSet TruthValue,
|
|
e3IpmAlarmCritLow Integer32,
|
|
e3IpmAlarmWarnLowSet TruthValue,
|
|
e3IpmAlarmWarnLow Integer32,
|
|
e3IpmAlarmWarnHighSet TruthValue,
|
|
e3IpmAlarmWarnHigh Integer32,
|
|
e3IpmAlarmCritHighSet TruthValue,
|
|
e3IpmAlarmCritHigh Integer32
|
|
}
|
|
|
|
e3IpmAlarmIndex OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
current-l1 (0),
|
|
current-l2 (1),
|
|
current-l3 (2),
|
|
current-n (3),
|
|
temp-int (4),
|
|
temp-ext1 (5),
|
|
temp-ext2 (6),
|
|
rh-ext1 (7),
|
|
rh-ext2 (8)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Defines the alarm described by the current entry. There
|
|
are alarms for the current of all phases, for the
|
|
temperature and the relative humidity."
|
|
::= { e3IpmAlarmTableEntry 1 }
|
|
|
|
e3IpmAlarmState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
critical-low (0),
|
|
warn-low (1),
|
|
normal (2),
|
|
warn-high (3),
|
|
critical-high (4),
|
|
unknown (5)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shows this alarm entries' state. If no alarm settings
|
|
are defined, the state is unknown."
|
|
::= { e3IpmAlarmTableEntry 2 }
|
|
|
|
e3IpmAlarmCritLowSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'critical low' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 3 }
|
|
|
|
e3IpmAlarmCritLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'critical low' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 4 }
|
|
|
|
e3IpmAlarmWarnLowSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'warn low' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 5 }
|
|
|
|
e3IpmAlarmWarnLow OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'warn low' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 6 }
|
|
|
|
e3IpmAlarmWarnHighSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'warn high' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 7 }
|
|
|
|
e3IpmAlarmWarnHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'warn high' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 8 }
|
|
|
|
e3IpmAlarmCritHighSet OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"True if a 'critical high' alarm level for the current
|
|
entry is defined, false otherwise."
|
|
::= { e3IpmAlarmTableEntry 9 }
|
|
|
|
e3IpmAlarmCritHigh OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'critical high' alarm level for the current entry
|
|
in hundredths of the relevant unit (i.e. amperes, degrees
|
|
celsius and %RH). If no alarm level is configured, this
|
|
reads 0."
|
|
::= { e3IpmAlarmTableEntry 10 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM RCM Data
|
|
--
|
|
|
|
e3IpmRcmTable OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Table holding all residual current monitoring (RCM)
|
|
data of this IPS."
|
|
::= { e3Ipm 7 }
|
|
|
|
e3IpmRcmTableEntry OBJECT-TYPE
|
|
SYNTAX E3IpmRcmTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One entry in the RCM table."
|
|
INDEX { e3IpmRcmChannel }
|
|
::= { e3IpmRcmTable 1 }
|
|
|
|
E3IpmRcmTableEntry ::= SEQUENCE {
|
|
e3IpmRcmChannel Integer32,
|
|
e3IpmRcmAcLimit MilliAmperes,
|
|
e3IpmRcmDcLimit MilliAmperes,
|
|
e3IpmRcmStatus Integer32,
|
|
e3IpmRcmAc MilliAmperes,
|
|
e3IpmRcmDc MilliAmperes
|
|
}
|
|
|
|
e3IpmRcmChannel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
total(0)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RCM channel: 0 (total) is the total of all phases in this IPS."
|
|
::= { e3IpmRcmTableEntry 1 }
|
|
|
|
e3IpmRcmAcLimit OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory configured AC RCM limit. Any measurement
|
|
higher than this limit is considered a critical problem."
|
|
::= { e3IpmRcmTableEntry 2 }
|
|
|
|
e3IpmRcmDcLimit OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory configured DC RCM limit. Any measurement
|
|
higher than this limit is considered a critical problem."
|
|
::= { e3IpmRcmTableEntry 3 }
|
|
|
|
e3IpmRcmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
valid(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the RcmAc/RcmDc data. If the residual
|
|
current cannot be measured, 0 (unknown) is signalled
|
|
here, otherwise 1 (valid)."
|
|
::= { e3IpmRcmTableEntry 4 }
|
|
|
|
e3IpmRcmAc OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The latest AC RCM measurement."
|
|
::= { e3IpmRcmTableEntry 5 }
|
|
|
|
e3IpmRcmDc OBJECT-TYPE
|
|
SYNTAX MilliAmperes
|
|
UNITS "mA"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The latest DC RCM measurement."
|
|
::= { e3IpmRcmTableEntry 6 }
|
|
|
|
-- ===========================================================================
|
|
-- IPM Traps
|
|
--
|
|
|
|
e3IpmTraps OBJECT IDENTIFIER
|
|
::= { e3Mib 8 }
|
|
|
|
-- Current
|
|
|
|
e3IpmCurrentCritLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentCritLow is triggered when the current
|
|
on the given channel is less than or equal to the configured
|
|
critical low threshold."
|
|
::= { e3IpmTraps 1 }
|
|
|
|
e3IpmCurrentWarnLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentWarnLow is triggered when the current
|
|
on the given channel is less than or equal to the configured
|
|
warn low threshold."
|
|
::= { e3IpmTraps 2 }
|
|
|
|
e3IpmCurrentNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentNormal is triggered when the current
|
|
on the given channel is not outside any configured
|
|
limits."
|
|
::= { e3IpmTraps 3 }
|
|
|
|
e3IpmCurrentWarnHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentWarnHigh is triggered when the current
|
|
on the given channel is greater than or equal to the
|
|
configured warn high threshold."
|
|
::= { e3IpmTraps 4 }
|
|
|
|
e3IpmCurrentCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmMeter, e3IpmIrms }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmCurrentCritHigh is triggered when the current
|
|
on the given channel is greater than or equal to the
|
|
configured critical high threshold."
|
|
::= { e3IpmTraps 5 }
|
|
|
|
-- Temperature
|
|
|
|
e3IpmTempCritLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempCritLow is triggered when the temperature
|
|
on the given sensor is less than or equal to the configured
|
|
critical low threshold."
|
|
::= { e3IpmTraps 6 }
|
|
|
|
e3IpmTempWarnLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempWarnLow is triggered when the temperature
|
|
on the given sensor is less than or equal to the configured
|
|
warn low threshold."
|
|
::= { e3IpmTraps 7 }
|
|
|
|
e3IpmTempNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempNormal is triggered when the temperature
|
|
on the given sensor is not outside any configured
|
|
limits."
|
|
::= { e3IpmTraps 8 }
|
|
|
|
e3IpmTempWarnHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempWarnHigh is triggered when the temperature
|
|
on the given sensor is greater than or equal to the
|
|
configured warn high threshold."
|
|
::= { e3IpmTraps 9 }
|
|
|
|
e3IpmTempCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorTemperatureCelsius }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmTempCritHigh is triggered when the temperature
|
|
on the given sensor is greater than or equal to the
|
|
configured critical high threshold."
|
|
::= { e3IpmTraps 10 }
|
|
|
|
-- Relative Humidity
|
|
|
|
e3IpmRHCritLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHCritLow is triggered when the relative humidity
|
|
on the given sensor is less than or equal to the configured
|
|
critical low threshold."
|
|
::= { e3IpmTraps 11 }
|
|
|
|
e3IpmRHWarnLow NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHWarnLow is triggered when the relative humidity
|
|
on the given sensor is less than or equal to the configured
|
|
warn low threshold."
|
|
::= { e3IpmTraps 12 }
|
|
|
|
e3IpmRHNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHNormal is triggered when the relative humidity
|
|
on the given sensor is not outside any configured
|
|
limits."
|
|
::= { e3IpmTraps 13 }
|
|
|
|
e3IpmRHWarnHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHWarnHigh is triggered when the relative humidity
|
|
on the given sensor is greater than or equal to the
|
|
configured warn high threshold."
|
|
::= { e3IpmTraps 14 }
|
|
|
|
e3IpmRHCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmSensor, e3IpmSensorHumidity }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRHCritHigh is triggered when the relative humidity
|
|
on the given sensor is greater than or equal to the
|
|
configured critical high threshold."
|
|
::= { e3IpmTraps 15 }
|
|
|
|
-- RCM Alarms
|
|
|
|
e3IpmRcmAcNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmAcNormal is triggered when the AC part of
|
|
the residual current falls below the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 16 }
|
|
|
|
e3IpmRcmAcCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmAc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmAcCritHigh is triggered when the AC part
|
|
of the residual current is greater than the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 17 }
|
|
|
|
e3IpmRcmDcNormal NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmDcNormal is triggered when the DC part of
|
|
the residual current falls below the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 18 }
|
|
|
|
e3IpmRcmDcCritHigh NOTIFICATION-TYPE
|
|
OBJECTS { e3IpmInfoSerial, e3IpmRcmChannel, e3IpmRcmDc }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The e3IpmRcmDcCritHigh is triggered when the DC part
|
|
of the residual current is greater than the
|
|
factory-configured limit."
|
|
::= { e3IpmTraps 19 }
|
|
|
|
END
|