-- Jacarta interSeptor MIB
-- MIB for interSeptor Environmental Monitoring System
--
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) jacarta(19011)
-- product(1) webAppliance(3) inSept(1)
-- ==============================================================================================
---
--- Revision History
---
--- V1.00 - Initial Release - July 03
--- V1.01 - Minor SNMP bug fix - Aug 03
--- v1.10 - Add temperature unit object - Oct, 15 2004
--- Add date format object
--- Add inSeptConfigAccessControlTable
--- Add object
--- v1.11 Change interSeptor-MIB to InterSeptor-MIB - Dec, 20 2004
--- Updated InSeptsensorConfigSensorEntry and SensorMonitorSensorEntry
--- V1.12 - Modified syntax error - May, 10 2005
--- Fixed SYNTAX InSeptConfigTrapsReceiversEntry
--- Changed SYNTAX inSeptConfigTrapsReceiversEntry to SYNTAX InSeptConfigTrapsReceiversEntry
--- V1.13 - Modified syntax error - June, 27 2006
--- Check error form http://wwwsnmp.cs.utwente.nl/ietf/mibs/validate/
--- ===========================================================================================
InterSeptor-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
DisplayString
FROM RFC1213-MIB
TRAP-TYPE
FROM RFC-1215;
jacarta OBJECT IDENTIFIER ::= { enterprises 19011 }
product OBJECT IDENTIFIER ::= { jacarta 1 }
webAppliance OBJECT IDENTIFIER ::= { product 3 }
inSept OBJECT IDENTIFIER ::= { webAppliance 1}
inSeptObjects OBJECT IDENTIFIER ::= { inSept 1 }
inSeptTraps OBJECT IDENTIFIER ::= { inSept 2 }
inSeptIdent OBJECT IDENTIFIER ::= { inSeptObjects 1 }
inSeptConfig OBJECT IDENTIFIER ::= { inSeptObjects 2 }
inSeptsensorMonitor OBJECT IDENTIFIER ::= { inSeptObjects 3 }
inSeptsensorConfig OBJECT IDENTIFIER ::= { inSeptObjects 4 }
-- ===========================================================================
--
-- inSeptIdentification
--
-- All objects in this group except for inSeptIdentName and
-- inSeptIdentAttachedDevices are set at device initialization
-- and remain static.
--
-- ===========================================================================
inSeptIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The name of the interSeptor manufacturer."
::= { inSeptIdent 1 }
inSeptIdentModel OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..63))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The interSeptor Model designation."
::= { inSeptIdent 2 }
inSeptIdentAgentSoftwareVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The interSeptor software/firmware version."
::= { inSeptIdent 3 }
inSeptIdentName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"A string identifying the interSeptor. This object should be
set by the administrator."
::= { inSeptIdent 4 }
-- ===========================================================================
--
-- inSeptConfig
--
-- ===========================================================================
inSeptConfigMibVersion OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The version of MIB spec."
::= { inSeptConfig 1}
inSeptConfigNetwork OBJECT IDENTIFIER ::= { inSeptConfig 2 }
inSeptConfigIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The ip address that NMS can identify the managed
device"
::= { inSeptConfigNetwork 1 }
inSeptConfigGateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The default gateway that allows the device to be managed
through routers "
::= { inSeptConfigNetwork 2 }
inSeptConfigSubnetMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Internet address subnet mask"
::= { inSeptConfigNetwork 3 }
inSeptConfigDateTime OBJECT IDENTIFIER ::= { inSeptConfig 3 }
inSeptConfigDate OBJECT-TYPE
SYNTAX DisplayString (SIZE (10..10))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date in inSept, format is (dd/mm/yyyy)"
::= { inSeptConfigDateTime 1}
inSeptConfigTime OBJECT-TYPE
SYNTAX DisplayString (SIZE (8..8))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time in interSeptor, format is (hh:mm:ss)"
::= { inSeptConfigDateTime 2}
inSeptConfigTimeFromNtp OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable update date/time from NTP server."
::= { inSeptConfigDateTime 3}
inSeptConfigNtpIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"NTP IP address."
::= { inSeptConfigDateTime 4}
inSeptConfigNtpTimeZone OBJECT-TYPE
SYNTAX INTEGER {
gMT-1200(1),
gMT-1100(2),
gMT-1000(3),
gMT-0900(4),
gMT-0800(5),
gMT-0700(6),
gMT-0600(7),
gMT-0500(8),
gMT-0400(9),
gMT-0330(10),
gMT-0300(11),
gMT-0200(12),
gMT-0100(13),
gMT-0000(14),
gMT0100(15),
gMT0200(16),
gMT0300(17),
gMT0330(18),
gMT0400(19),
gMT0500(20),
gMT0530(21),
gMT0600(22),
gMT0700(23),
gMT0800(24),
gMT0900(25),
gMT1000(26),
gMT1100(27),
gMT1200(28)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable update date/time from NTP server."
::= { inSeptConfigDateTime 5}
inSeptConfigDayLightSaving OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable daylight saving for NTP time, if enabled, the time get from NTP will be set
set one hour in advance to reflect daylight saving status."
::= { inSeptConfigDateTime 6}
inSeptConfigLog OBJECT IDENTIFIER ::= { inSeptConfig 4 }
inSeptConfigHistoryLogFrequency OBJECT-TYPE
SYNTAX INTEGER (5..3600) -- in seconds
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The frequency of the update of the history log. The value
is in seconds"
::= { inSeptConfigLog 1}
inSeptConfigExtHistoryLogFrequency OBJECT-TYPE
SYNTAX INTEGER (1..1440) -- in minutes
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The frequency of the update of the extended history log.
The value is in seconds"
::= { inSeptConfigLog 2}
inSeptConfigConfigurationLog OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
" Enable/disable inSept to log parameter change."
::= { inSeptConfigLog 3}
inSeptConfigDhcpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable DHCP/BootP capability"
::= { inSeptConfig 5}
inSeptConfigPingStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable Ping Echo capability"
::= { inSeptConfig 6}
inSeptConfigTftpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable TFTP network upgrade capability"
::= { inSeptConfig 7}
inSeptConfigTelnet OBJECT IDENTIFIER ::= { inSeptConfig 8 }
inSeptConfigTelnetStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable telnet access"
::= { inSeptConfigTelnet 1}
inSeptConfigTelnetPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port of telnet."
::= { inSeptConfigTelnet 2}
inSeptConfigHttp OBJECT IDENTIFIER ::= { inSeptConfig 9 }
inSeptConfigHttpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable HTTP access"
::= { inSeptConfigHttp 1}
inSeptConfigHttpPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port of HTTP."
::= { inSeptConfigHttp 2}
inSeptConfigHttpSecurity OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable HTTP access for read-only users"
::= { inSeptConfigHttp 3}
inSeptConfigSnmp OBJECT IDENTIFIER ::= { inSeptConfig 10 }
inSeptConfigSnmpStatue OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable or disable SNMP access"
::= { inSeptConfigSnmp 1}
inSeptConfigSnmpPortNumber OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setting the server port of SNMP."
::= { inSeptConfigSnmp 2}
inSeptConfigControl OBJECT IDENTIFIER ::= { inSeptConfig 11 }
inSeptConfigResetToDefault OBJECT-TYPE
SYNTAX INTEGER {
reset(1),
nothing(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reset all parameters of interSeptor to default value"
::= { inSeptConfigControl 1}
inSeptConfigRestart OBJECT-TYPE
SYNTAX INTEGER {
restart(1),
nothing(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Restart interSeptor"
::= { inSeptConfigControl 2}
inSeptConfigTrap OBJECT IDENTIFIER ::= { inSeptConfig 12 }
inSeptConfigTrapRetryCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The count of repeat traps to send to NMS before trap
acknowledgement is received."
::= { inSeptConfigTrap 1}
inSeptConfigTrapRetryTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The time between retrying to send traps to NMS."
::= { inSeptConfigTrap 2}
inSeptConfigTrapAckSignature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The signature of trap acknowledgement."
::= { inSeptConfigTrap 3}
inSeptConfigPollRate OBJECT-TYPE
SYNTAX INTEGER (3..60)
ACCESS read-write
STATUS mandatory
DESCRIPTION
" The frequency that interSeptor updates readings from sensors
(unit : second)."
::= { inSeptConfig 13}
inSeptConfigTrapsReceiversTable OBJECT-TYPE
SYNTAX SEQUENCE OF InSeptConfigTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers to send traps to. The number of
entries is given by the value of inSeptConfigNumTrapReceivers"
::= { inSeptConfig 14}
inSeptConfigTrapsReceiversEntry OBJECT-TYPE
SYNTAX InSeptConfigTrapsReceiversEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers to send traps to."
INDEX { inSepttrapsIndex}
::= { inSeptConfigTrapsReceiversTable 1 }
InSeptConfigTrapsReceiversEntry ::=
SEQUENCE {
inSepttrapsIndex
INTEGER,
inSepttrapsReceiverAddr
IpAddress,
inSeptreceiverCommunityString
DisplayString,
inSeptreceiverSeverityLevel
INTEGER,
inSeptreceiverDescription
DisplayString
}
inSepttrapsIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a trap receiver entry."
::= { inSeptConfigTrapsReceiversEntry 1 }
inSepttrapsReceiverAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to send a trap to."
::= { inSeptConfigTrapsReceiversEntry 2 }
inSeptreceiverCommunityString OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..19))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the trap when
sent to the manager."
::= { inSeptConfigTrapsReceiversEntry 3 }
inSeptreceiverSeverityLevel OBJECT-TYPE
SYNTAX INTEGER {
informational(1),
warning(2),
severe(3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The severity level of traps to be received by this manager."
::= { inSeptConfigTrapsReceiversEntry 4 }
inSeptreceiverDescription OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..31))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Description of trap receivers"
::= { inSeptConfigTrapsReceiversEntry 5 }
inSeptConfigAccessControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF InSeptConfigAccessControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of managers which can access interSeptor with private
community string."
::= { inSeptConfig 15}
inSeptConfigAccessControlEntry OBJECT-TYPE
SYNTAX InSeptConfigAccessControlEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The managers."
INDEX { accessIndex}
::= { inSeptConfigAccessControlTable 1 }
InSeptConfigAccessControlEntry ::=
SEQUENCE {
accessIndex
INTEGER,
accessControlAddr
IpAddress,
accessCommunityString
DisplayString,
accessControlMode
INTEGER
}
accessIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a access control entry."
::= { inSeptConfigAccessControlEntry 1 }
accessControlAddr OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The IP address of the manager to access interSeptor"
::= { inSeptConfigAccessControlEntry 2 }
accessCommunityString OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..19))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The community name to use in the manager when
access interSeptor"
::= { inSeptConfigAccessControlEntry 3 }
accessControlMode OBJECT-TYPE
SYNTAX INTEGER {
readOnly (1),
read-write (2),
notAccess (3)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Access type, only read/Write access type can change parameter
of interSeptor"
::= { inSeptConfigAccessControlEntry 4 }
inSeptConfigTemperatureUnit OBJECT-TYPE
SYNTAX INTEGER {
celsius(1),
fahrenheit(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature unit of the system, can be Celsius or Farenheit"
::= { inSeptConfig 16}
inSeptConfigDateFormat OBJECT-TYPE
SYNTAX INTEGER {
dd-mm-yyyy(1),
mm-dd-yyyy(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy"
::= { inSeptConfig 17}
-- Sensor Monitoring
inSeptsensorMonitorSensorNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of sensors that can be monitored."
::= { inSeptsensorMonitor 1}
inSeptsensorMonitorSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF SensorMonitorSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of sensor devices to be monitored."
::= { inSeptsensorMonitor 2}
inSeptsensorMonitorSensorEntry OBJECT-TYPE
SYNTAX SensorMonitorSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The sensor device."
INDEX { inSeptsensorMonitorDeviceIndex}
::= { inSeptsensorMonitorSensorTable 1 }
SensorMonitorSensorEntry ::=
SEQUENCE {
inSeptsensorMonitorDeviceIndex
INTEGER,
inSeptsensorMonitorDeviceStatus
INTEGER,
inSeptsensorMonitorDeviceTemperature
INTEGER,
inSeptsensorMonitorDeviceTemperatureAlarm
INTEGER,
inSeptsensorMonitorDeviceHumidity
INTEGER,
inSeptsensorMonitorDeviceHumidityAlarm
INTEGER,
inSeptsensorMonitorAlarm1
INTEGER,
inSeptsensorMonitorAlarm2
INTEGER
}
inSeptsensorMonitorDeviceIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a sensor device entry."
::= { inSeptsensorMonitorSensorEntry 1 }
inSeptsensorMonitorDeviceStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
eMD-HT(3),
eMD-T(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device type connected to interSeptor."
::= { inSeptsensorMonitorSensorEntry 2 }
inSeptsensorMonitorDeviceTemperature OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The temperature of sensor on device interSeptor, the unit is 0.1 degree."
::= { inSeptsensorMonitorSensorEntry 3 }
inSeptsensorMonitorDeviceTemperatureAlarm OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
normal(3),
lowWarning(4),
lowCritical(5),
highWarning(6),
highCritical(7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The alarm type of sensor on device interSeptor."
::= { inSeptsensorMonitorSensorEntry 4 }
inSeptsensorMonitorDeviceHumidity OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The humidity of sensor on device interSeptor, the unit is 0.1%."
::= { inSeptsensorMonitorSensorEntry 5 }
inSeptsensorMonitorDeviceHumidityAlarm OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
normal(3),
lowWarning(4),
lowCritical(5),
highWarning(6),
highCritical(7)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The alarm type of sensor on device interSeptor."
::= { inSeptsensorMonitorSensorEntry 6 }
inSeptsensorMonitorAlarm1 OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
active(3),
inactive(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device status of sensor 1 connected to interSeptor."
::= { inSeptsensorMonitorSensorEntry 7 }
inSeptsensorMonitorAlarm2 OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
disabled(2),
active(3),
inactive(4)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The device status of sensor 2 connected to interSeptor."
::= { inSeptsensorMonitorSensorEntry 8 }
-- Sensor Configuration
inSeptsensorConfigSensorNumber OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The number of sensors that are connected to interSeptor."
::= { inSeptsensorConfig 1 }
inSeptsensorConfigSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF InSeptsensorConfigSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"A list of sensor devices to be configured."
::= { inSeptsensorConfig 2 }
inSeptsensorConfigSensorEntry OBJECT-TYPE
SYNTAX InSeptsensorConfigSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"The sensor device."
INDEX { inSeptsensorConfigDeviceIndex }
::= { inSeptsensorConfigSensorTable 1 }
InSeptsensorConfigSensorEntry ::=
SEQUENCE {
inSeptsensorConfigDeviceIndex
INTEGER,
inSeptsensorConfigDeviceName
DisplayString,
inSeptsensorConfigDeviceState
INTEGER
}
inSeptsensorConfigDeviceIndex OBJECT-TYPE
SYNTAX INTEGER (1..2147483647)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The index to a sensor device entry."
::= { inSeptsensorConfigSensorEntry 1 }
inSeptsensorConfigDeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE(0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of the sensor device for identification."
::= { inSeptsensorConfigSensorEntry 2 }
inSeptsensorConfigDeviceState OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
auto(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The setup of sensor device type."
::= { inSeptsensorConfigSensorEntry 3 }
inSeptsensorConfigSensor1 OBJECT IDENTIFIER ::= { inSeptsensorConfig 3 }
inSeptsensorConfigSensor1DeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of sensor device."
::= { inSeptsensorConfigSensor1 1}
inSeptsensorConfigSensor1DeviceState OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
auto(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The setup of sensor device type."
::= { inSeptsensorConfigSensor1 2 }
inSeptsensorConfigSensor1Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 3 }
inSeptsensorConfigSensor1TemperatureName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature sensor name."
::= { inSeptsensorConfigSensor1Temperature 1 }
inSeptsensorConfigSensor1TemperatureLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor1Temperature 2 }
inSeptsensorConfigSensor1TemperatureLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm."
::= { inSeptsensorConfigSensor1Temperature 3 }
inSeptsensorConfigSensor1TemperatureHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { inSeptsensorConfigSensor1Temperature 4 }
inSeptsensorConfigSensor1TemperatureHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { inSeptsensorConfigSensor1Temperature 5 }
inSeptsensorConfigSensor1TemperatureHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when temperature is hovering around the
set threshold."
::= { inSeptsensorConfigSensor1Temperature 6 }
inSeptsensorConfigSensor1TemperatureCalibration OBJECT-TYPE
SYNTAX INTEGER {
temperatureIncrease0Point0(1),
temperatureIncrease0Point5(2),
temperatureIncrease1Point0(3),
temperatureIncrease1Point5(4),
temperatureIncrease2Point0(5),
temperatureIncrease2Point5(6),
temperatureIncrease3Point0(7),
temperatureMinus0Point5(8),
temperatureMinus1Point0(9),
temperatureMinus1Point5(10),
temperatureMinus2Point0(11),
temperatureMinus2Point5(12),
temperatureMinusPoint0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to your reference temperature."
::= { inSeptsensorConfigSensor1Temperature 7 }
inSeptsensorConfigSensor1TemperatureLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor1Temperature 8 }
inSeptsensorConfigSensor1TemperatureLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low critical alarm."
::= { inSeptsensorConfigSensor1Temperature 9 }
inSeptsensorConfigSensor1TemperatureHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high warning alarm."
::= { inSeptsensorConfigSensor1Temperature 10 }
inSeptsensorConfigSensor1TemperatureHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high critical alarm."
::= { inSeptsensorConfigSensor1Temperature 11 }
inSeptsensorConfigSensor1Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 4 }
inSeptsensorConfigSensor1HumdityName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity sensor name."
::= { inSeptsensorConfigSensor1Humidity 1 }
inSeptsensorConfigSensor1HumidityLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor1Humidity 2 }
inSeptsensorConfigSensor1HumidityLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshole to trigger low critical alarm."
::= { inSeptsensorConfigSensor1Humidity 3 }
inSeptsensorConfigSensor1HumidityHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { inSeptsensorConfigSensor1Humidity 4 }
inSeptsensorConfigSensor1HumidityHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { inSeptsensorConfigSensor1Humidity 5 }
inSeptsensorConfigSensor1HumidityHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when Humidity is hovering around the
set threshold."
::= { inSeptsensorConfigSensor1Humidity 6 }
inSeptsensorConfigSensor1HumidityCalibration OBJECT-TYPE
SYNTAX INTEGER {
humidityIncrease0Point0(1),
humidityIncrease1Point0(2),
humidityIncrease2Point0(3),
humidityIncrease3Point0(4),
humidityIncrease4Point0(5),
humidityIncrease5Point0(6),
humidityIncrease6Point0(7),
humidityMinus1Point0(8),
humidityMinus2Point0(9),
humidityMinus3Point0(10),
humidityMinus4Point0(11),
humidityMinus5Point0(12),
humidityMinus6Point0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to your reference temperature."
::= { inSeptsensorConfigSensor1Humidity 7 }
inSeptsensorConfigSensor1HumidityLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor1Humidity 8 }
inSeptsensorConfigSensor1HumidityLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low critical alarm."
::= { inSeptsensorConfigSensor1Humidity 9 }
inSeptsensorConfigSensor1HumidityHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high warning alarm."
::= { inSeptsensorConfigSensor1Humidity 10 }
inSeptsensorConfigSensor1HumidityHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high critical alarm."
::= { inSeptsensorConfigSensor1Humidity 11 }
inSeptsensorConfigSensor1Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 5 }
inSeptsensorConfigSensor1Alarm1Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { inSeptsensorConfigSensor1Alarm1 1 }
inSeptsensorConfigSensor1Alarm1State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { inSeptsensorConfigSensor1Alarm1 2 }
inSeptsensorConfigSensor1Alarm1Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { inSeptsensorConfigSensor1Alarm1 3 }
inSeptsensorConfigSensor1Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor1 6 }
inSeptsensorConfigSensor1Alarm2Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { inSeptsensorConfigSensor1Alarm2 1 }
inSeptsensorConfigSensor1Alarm2State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { inSeptsensorConfigSensor1Alarm2 2 }
inSeptsensorConfigSensor1Alarm2Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { inSeptsensorConfigSensor1Alarm2 3 }
inSeptsensorConfigSensor2 OBJECT IDENTIFIER ::= { inSeptsensorConfig 4 }
inSeptsensorConfigSensor2DeviceName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of sensor device."
::= { inSeptsensorConfigSensor2 1}
inSeptsensorConfigSensor2DeviceState OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
auto(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The setup of sensor device type."
::= { inSeptsensorConfigSensor2 2 }
inSeptsensorConfigSensor2Temperature OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 3 }
inSeptsensorConfigSensor2TemperatureName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The temperature sensor name."
::= { inSeptsensorConfigSensor2Temperature 1 }
inSeptsensorConfigSensor2TemperatureLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor2Temperature 2 }
inSeptsensorConfigSensor2TemperatureLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm."
::= { inSeptsensorConfigSensor2Temperature 3 }
inSeptsensorConfigSensor2TemperatureHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { inSeptsensorConfigSensor2Temperature 4 }
inSeptsensorConfigSensor2TemperatureHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { inSeptsensorConfigSensor2Temperature 5 }
inSeptsensorConfigSensor2TemperatureHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when temperature is hovering around the
set threshold."
::= { inSeptsensorConfigSensor2Temperature 6 }
inSeptsensorConfigSensor2TemperatureCalibration OBJECT-TYPE
SYNTAX INTEGER {
temperatureIncrease0Point0(1),
temperatureIncrease0Point5(2),
temperatureIncrease1Point0(3),
temperatureIncrease1Point5(4),
temperatureIncrease2Point0(5),
temperatureIncrease2Point5(6),
temperatureIncrease3Point0(7),
temperatureMinus0Point5(8),
temperatureMinus1Point0(9),
temperatureMinus1Point5(10),
temperatureMinus2Point0(11),
temperatureMinus2Point5(12),
temperatureMinusPoint0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to your reference temperature."
::= { inSeptsensorConfigSensor2Temperature 7 }
inSeptsensorConfigSensor2TemperatureLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor2Temperature 8 }
inSeptsensorConfigSensor2TemperatureLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low critical alarm."
::= { inSeptsensorConfigSensor2Temperature 9 }
inSeptsensorConfigSensor2TemperatureHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high warning alarm."
::= { inSeptsensorConfigSensor2Temperature 10 }
inSeptsensorConfigSensor2TemperatureHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high critical alarm."
::= { inSeptsensorConfigSensor2Temperature 11 }
inSeptsensorConfigSensor2Humidity OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 4 }
inSeptsensorConfigSensor2HumdityName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The humidity sensor name."
::= { inSeptsensorConfigSensor2Humidity 1 }
inSeptsensorConfigSensor2HumidityLowWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor2Humidity 2 }
inSeptsensorConfigSensor2HumidityLowCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger low critical alarm."
::= { inSeptsensorConfigSensor2Humidity 3 }
inSeptsensorConfigSensor2HumidityHighWarning OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high warning alarm."
::= { inSeptsensorConfigSensor2Humidity 4 }
inSeptsensorConfigSensor2HumidityHighCritical OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The threshold to trigger high critical alarm."
::= { inSeptsensorConfigSensor2Humidity 5 }
inSeptsensorConfigSensor2HumidityHysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to prevent too many alarms when Humidity is hovering around the
set threshold."
::= { inSeptsensorConfigSensor2Humidity 6 }
inSeptsensorConfigSensor2HumidityCalibration OBJECT-TYPE
SYNTAX INTEGER {
humidityIncrease0Point0(1),
humidityIncrease1Point0(2),
humidityIncrease2Point0(3),
humidityIncrease3Point0(4),
humidityIncrease4Point0(5),
humidityIncrease5Point0(6),
humidityIncrease6Point0(7),
humidityMinus1Point0(8),
humidityMinus2Point0(9),
humidityMinus3Point0(10),
humidityMinus4Point0(11),
humidityMinus5Point0(12),
humidityMinus6Point0(13)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to get the correct temperature according to your reference temperature."
::= { inSeptsensorConfigSensor2Humidity 7 }
inSeptsensorConfigSensor2HumidityLowWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low warning alarm."
::= { inSeptsensorConfigSensor2Humidity 8 }
inSeptsensorConfigSensor2HumidityLowCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger low critical alarm."
::= { inSeptsensorConfigSensor2Humidity 9 }
inSeptsensorConfigSensor2HumidityHighWarningStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high warning alarm."
::= { inSeptsensorConfigSensor2Humidity 10 }
inSeptsensorConfigSensor2HumidityHighCriticalStatus OBJECT-TYPE
SYNTAX INTEGER {
enabled(1),
disabled(2)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Enable/disable the set point to trigger high critical alarm."
::= { inSeptsensorConfigSensor2Humidity 11 }
inSeptsensorConfigSensor2Alarm1 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 5 }
inSeptsensorConfigSensor2Alarm1Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { inSeptsensorConfigSensor2Alarm1 1 }
inSeptsensorConfigSensor2Alarm1State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { inSeptsensorConfigSensor2Alarm1 2 }
inSeptsensorConfigSensor2Alarm1Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { inSeptsensorConfigSensor2Alarm1 3 }
inSeptsensorConfigSensor2Alarm2 OBJECT IDENTIFIER ::= { inSeptsensorConfigSensor2 6 }
inSeptsensorConfigSensor2Alarm2Name OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..15))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The name of alarm-1."
::= { inSeptsensorConfigSensor2Alarm2 1 }
inSeptsensorConfigSensor2Alarm2State OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
normalOpen(2),
normalClose(3),
highActive(4),
lowActive(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Setup the signal type to trigger alarm."
::= { inSeptsensorConfigSensor2Alarm2 2 }
inSeptsensorConfigSensor2Alarm2Hysteresis OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"The set value to delay the alarm triggered when event occurs."
::= { inSeptsensorConfigSensor2Alarm2 3 }
-- ===========================================================================
-- inSeptTraps
--
-- Traps group
-- ===========================================================================
-- This section defines the well-known notifications sent by
-- inSept agents.
-- Care must be taken to ensure that no particular notification
-- is sent to a single receiving entity more often than once
-- every five seconds.
inSeptCommunicationRestored TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: Communication between interSeptor and sensor has been
established."
::= 1
inSeptCommunicationLost TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"WARNING: Communication between interSeptor and sensor has been
lost."
::= 2
inSeptAlarm1Inactive TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: Alarm1 of sensor has returned from active state."
::= 3
inSeptAlarm1Active TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"WARNING: Alarm1 has become active."
::= 4
inSeptAlarm2Inactive TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: Alarm2 of sensor has returned from active state."
::= 5
inSeptAlarm2Active TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"WARNING: Alarm2 has become active."
::= 6
inSeptTemperatureNotHighWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The temperature of sensor has returned from High warning to normal."
::= 7
inSeptTemperatureHighWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"WARNING: The temperature of sensor is higher than High warning set point."
::= 8
inSeptTemperatureNotLowWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The temperature of sensor has returned from low warning to normal."
::= 9
inSeptTemperatureLowWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"WARNING: The temperature of sensor is lower than low warning set point."
::= 10
inSeptTemperatureNotHighCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The temperature of sensor is lower than high critical set point."
::= 11
inSeptTemperatureHighCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"CRITICAL: The temperature of sensor is higher than high critical set point."
::= 12
inSeptTemperatureNotLowCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The temperature of sensor is higher than low critical set point."
::= 13
inSeptTemperatureLowCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"CRITICAL: The temperature of sensor is lower than low critical set point."
::= 14
inSeptHumidityNotHighWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The humidity of sensor has returned from High warning to normal."
::= 15
inSeptHumidityHighWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"WARNING: The humidity of sensor is higher than High warning set point."
::= 16
inSeptHumidityNotLowWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The humidity of sensor has returned from low warning to normal."
::= 17
inSeptHumidityLowWarning TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"WARNING: The humidity of sensor is lower than low warning set point."
::= 18
inSeptHumidityNotHighCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The humidity of sensor is lower than high critical set point."
::= 19
inSeptHumidityHighCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"CRITICAL: The humidity of sensor is higher than high critical set point."
::= 20
inSeptHumidityNotLowCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"INFORMATION: The humidity of sensor is higher than low critical set point."
::= 21
inSeptHumidityLowCritical TRAP-TYPE
ENTERPRISE inSeptTraps
DESCRIPTION
"CRITICAL: The humidity of sensor is lower than low critical set point."
::= 22
END