- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
3056 lines
101 KiB
Text
3056 lines
101 KiB
Text
-- file: ORION-BASE-MIB.mib
|
||
|
||
ORION-BASE-MIB DEFINITIONS ::= BEGIN
|
||
|
||
IMPORTS
|
||
DisplayString
|
||
FROM SNMPv2-TC
|
||
OBJECT-GROUP,
|
||
NOTIFICATION-GROUP,
|
||
MODULE-COMPLIANCE
|
||
FROM SNMPv2-CONF
|
||
modules,
|
||
orion
|
||
FROM GLOBAL-REG
|
||
enterprises,
|
||
MODULE-IDENTITY,
|
||
OBJECT-TYPE,
|
||
NOTIFICATION-TYPE,
|
||
Gauge32,
|
||
Integer32,
|
||
IpAddress
|
||
FROM SNMPv2-SMI;
|
||
|
||
orionBaseMibModule MODULE-IDENTITY
|
||
LAST-UPDATED "200802211439Z"
|
||
ORGANIZATION "Delta Energy Systems (Switzerland) AG"
|
||
CONTACT-INFO
|
||
"postal: Delta Energy Systems (Switzerland) AG
|
||
Freiburgstrasse 251,
|
||
CH-3018 Bern-Buempliz
|
||
web: www.deltapowersolutions.com
|
||
email: patrick.camina@delta-es.com"
|
||
DESCRIPTION
|
||
"MIB for managing a DC power system with PSC 3."
|
||
|
||
REVISION "201204271200Z"
|
||
DESCRIPTION
|
||
"Rev V5.0 - ORION V5.10
|
||
- Add Multi-Stage temperature compensation
|
||
- Add dcBoD and dcEnableUsTempComp"
|
||
|
||
REVISION "201201261415Z"
|
||
DESCRIPTION
|
||
"Rev V2.1 - ORION V5.0
|
||
- changed product name from PSC3 to Orion"
|
||
|
||
REVISION "201106200734Z"
|
||
DESCRIPTION
|
||
"Rev V2.0 - PSC 3 V3.20
|
||
- hour meter functionality added"
|
||
|
||
REVISION "201102100901Z"
|
||
DESCRIPTION
|
||
"Rev V1.9 - PSC 3 V3.10
|
||
- dcPowerSystem can be negativ now
|
||
- added limits for DefaultLog and EventProcessing table
|
||
- added dcResendActiveAlarmTraps in deschMiscGroup"
|
||
|
||
REVISION "201006161027Z"
|
||
DESCRIPTION
|
||
"Rev V1.8 - PSC 3 V2.70
|
||
- new rectifier types added
|
||
- resend active alarm traps feature added
|
||
- measurement table added
|
||
- battery test result enum extended"
|
||
|
||
REVISION "201002241046Z"
|
||
DESCRIPTION
|
||
"Rev V1.7 - PSC 3 V2.60
|
||
- Critical alarm trap added
|
||
- Float Charge, Battery Test, Equalize, Boost Charge,
|
||
,System Voltage Supervision and Event Control Charge
|
||
parameter added
|
||
- Rectifier Group table added
|
||
- Rectifier power limitation and efficiency cycling
|
||
parameter added
|
||
- LVD table added
|
||
- Default Log event configuration table added
|
||
- Event Processing event configuration table added
|
||
- Loss of Backup time parameter added"
|
||
|
||
REVISION "200909040952Z"
|
||
DESCRIPTION
|
||
"Rev V1.6 - PSC 3 V2.50
|
||
- Generic Alarm table added
|
||
- Trap Destination table added"
|
||
|
||
REVISION "200802211439Z"
|
||
DESCRIPTION
|
||
"Rev V1.5 - PSC V2.20
|
||
- support of write access
|
||
- added battery parameters"
|
||
|
||
REVISION "200801180835Z"
|
||
DESCRIPTION
|
||
"Rev V1.4 - PSC 3 V2.10
|
||
- added event controlled charge state"
|
||
|
||
REVISION "200607271026Z"
|
||
DESCRIPTION
|
||
"Rev V1.3 - PSC 3 V1.70
|
||
- corrected Oid comment for dcStartTemp, dcStopTemp
|
||
and dcTotalBatteryCapacity"
|
||
|
||
REVISION "200603020855Z"
|
||
DESCRIPTION
|
||
"Rev V1.2
|
||
- added various parameters.
|
||
- added additional TRAP parameter."
|
||
|
||
REVISION "200602230932Z"
|
||
DESCRIPTION
|
||
"Rev V1.1 - PSC 3 V1.60
|
||
- extended dcChargeState with new sepCharge state."
|
||
|
||
REVISION "200506031107Z"
|
||
DESCRIPTION
|
||
"Rev V1.0 - PSC 3 V1.5 and older
|
||
- added dcCurrentLimit parameter.
|
||
- renamed module.
|
||
- increased dcSoftwareVersion string size.
|
||
- added recharge state to dcChargeState parameter.
|
||
- added max. number of entries in comment for event history."
|
||
|
||
-- 1.3.6.1.4.1.20246.2.1.1.2 --
|
||
::= { modules 2 }
|
||
|
||
|
||
-- root for items in the controller MIB module
|
||
|
||
orionBaseMib OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1 --
|
||
::= { orion 1 }
|
||
|
||
-- conformance area, containing groups and compliance specifications
|
||
|
||
controllerConfs OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1 --
|
||
::= { orionBaseMib 1 }
|
||
|
||
controllerGroups OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1 --
|
||
::= { controllerConfs 1 }
|
||
|
||
controllerCompl OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.2 --
|
||
::= { controllerConfs 2 }
|
||
|
||
-- sub-tree for objects, and for each functional area
|
||
|
||
controllerObjects OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2 --
|
||
::= { orionBaseMib 2 }
|
||
|
||
dcSystemInfo OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1 --
|
||
::= { controllerObjects 1 }
|
||
|
||
dcSystemAlarms OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2 --
|
||
::= { controllerObjects 2 }
|
||
|
||
dcSystemMonitor OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3 --
|
||
::= { controllerObjects 3 }
|
||
|
||
dcRectifier OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4 --
|
||
::= { controllerObjects 4 }
|
||
|
||
dcRectifierFunctions OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6 --
|
||
::= { dcRectifier 6 }
|
||
|
||
dcEfficiencyCycling OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1 --
|
||
::= { dcRectifierFunctions 1 }
|
||
|
||
dcPowerLimitation OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 --
|
||
::= { dcRectifierFunctions 2 }
|
||
|
||
dcBattery OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5 --
|
||
::= { controllerObjects 5 }
|
||
|
||
dcFloatCharge OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1 --
|
||
::= { dcBattery 1 }
|
||
|
||
dcBatteryTest OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2 --
|
||
::= { dcBattery 2 }
|
||
|
||
dcBatteryTestParameter OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1 --
|
||
::= { dcBatteryTest 1 }
|
||
|
||
dcBatteryTestResults OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2 --
|
||
::= { dcBatteryTest 2 }
|
||
|
||
dcBatteryParameter OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3 --
|
||
::= { dcBattery 3 }
|
||
|
||
dcLossOfBackupTime OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3 --
|
||
::= { dcBatteryParameter 3 }
|
||
|
||
dcEqualize OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4 --
|
||
::= { dcBattery 4 }
|
||
|
||
dcEqualizeParameter OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4 --
|
||
::= { dcEqualize 4 }
|
||
|
||
dcBoostCharge OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5 --
|
||
::= { dcBattery 5 }
|
||
|
||
dcBoostChargeParameter OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4 --
|
||
::= { dcBoostCharge 4 }
|
||
|
||
dcSystemVoltageSupervision OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6 --
|
||
::= { dcBattery 6 }
|
||
|
||
dcEvtCtrlCharge OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7 --
|
||
::= { dcBattery 7 }
|
||
|
||
dcEvtCtrlChargeParameter OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3 --
|
||
::= { dcEvtCtrlCharge 3 }
|
||
|
||
dcTempComp OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8 --
|
||
::= { dcBattery 8 }
|
||
|
||
dcTempSupervision OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9 --
|
||
::= { dcBattery 9 }
|
||
|
||
dcInputOutput OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6 --
|
||
::= { controllerObjects 6 }
|
||
|
||
dcMisc OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7 --
|
||
::= { controllerObjects 7 }
|
||
|
||
dcConfig OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8 --
|
||
::= { controllerObjects 8 }
|
||
|
||
dcMeasurement OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9 --
|
||
::= { controllerObjects 9 }
|
||
|
||
dcMeterPanel OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10 --
|
||
::= { controllerObjects 10 }
|
||
|
||
-- sub-tree for notifications
|
||
controllerEvents OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.3 --
|
||
::= { orionBaseMib 3 }
|
||
|
||
controllerEventObjects OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1 --
|
||
::= { controllerEvents 1 }
|
||
|
||
-- The following OBJECT IDENTIFIER is used to define SNMPv2 notifications
|
||
-- that are backward compatible with SNMPv1 traps
|
||
controllerEventsV2 OBJECT IDENTIFIER
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0 --
|
||
::= { controllerEventObjects 0 }
|
||
|
||
-- ================================
|
||
-- Scalar objects
|
||
-- ================================
|
||
dcSiteName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"An administratively-assigned site name for this
|
||
DC-power system."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1 --
|
||
::= { dcSystemInfo 1 }
|
||
|
||
dcSystemName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..16))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"An administratively-assigned system name for this
|
||
DC-power system."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2 --
|
||
::= { dcSystemInfo 2 }
|
||
|
||
dcSystemDateTime OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (19))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ISO 8601 representation of controller<65>s local date/time.
|
||
The value is in the format YYYY-MM-DDThh:mm:ss.
|
||
An example of a valid string is: '2004-10-04T13:45:00'."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3 --
|
||
::= { dcSystemInfo 3 }
|
||
|
||
dcSoftwareVersion OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (10..12))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The controller<65>s software version e.g V2.50Build1."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4 --
|
||
::= { dcSystemInfo 4 }
|
||
|
||
dcNumberUrgentAlarms OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of currently active urgent alarm sources. A zero
|
||
value indicates that urgent alarm is not active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3 --
|
||
::= { dcSystemAlarms 3 }
|
||
|
||
dcNumberNonUrgentAlarms OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of currently active non urgent alarm sources. A zero
|
||
value indicates that non urgent alarm is not active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4 --
|
||
::= { dcSystemAlarms 4 }
|
||
|
||
dcMainsFailureAlarm OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Mains failure alarm."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5 --
|
||
::= { dcSystemAlarms 5 }
|
||
|
||
dcUrgentAlarmIdentifier OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current unique urgent alarm event identifier. A zero value
|
||
indicates that urgent alarm is not active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6 --
|
||
::= { dcSystemAlarms 6 }
|
||
|
||
dcUrgentAlarmValue OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
false(1),
|
||
indeterminate(2), -- deprecated, not used anymore
|
||
true(3) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current urgent alarm event status that corresponds to the
|
||
urgent alarm identifier. If the urgent alarm identifier is zero
|
||
then the alarm value is false."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7 --
|
||
::= { dcSystemAlarms 7 }
|
||
|
||
dcNonUrgentAlarmIdentifier OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current unique non urgent alarm event identifier. A zero value
|
||
indicates that non urgent alarm is not active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8 --
|
||
::= { dcSystemAlarms 8 }
|
||
|
||
dcNonUrgentAlarmValue OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
false(1),
|
||
indeterminate(2), -- deprecated, not used anymore
|
||
true(3) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current non urgent alarm event status that corresponds to non urgent
|
||
alarm identifier. If the non urgent alarm identifier is zero then
|
||
the alarm value is false."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9 --
|
||
::= { dcSystemAlarms 9 }
|
||
|
||
dcUrgentAlarmName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current alarm name for urgent alarm that corresponds to urgent
|
||
alarm identifier."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10 --
|
||
::= { dcSystemAlarms 10 }
|
||
|
||
dcNonUrgentAlarmName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current alarm name for active non urgent alarm that corresponds
|
||
to non urgent alarm identifier."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11 --
|
||
::= { dcSystemAlarms 11 }
|
||
|
||
dcNumberCriticalAlarms OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of currently active critical alarm sources. A zero
|
||
value indicates that critical alarm is not active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.13 --
|
||
::= { dcSystemAlarms 13 }
|
||
|
||
dcCriticalAlarmIdentifier OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current unique critical alarm event identifier. A zero value
|
||
indicates that critical alarm is not active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.14 --
|
||
::= { dcSystemAlarms 14 }
|
||
|
||
dcCriticalAlarmValue OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
false(1),
|
||
indeterminate(2), -- deprecated, not used anymore
|
||
true(3) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current critical alarm event status that corresponds to the
|
||
critical alarm identifier. If the critical alarm identifier is zero
|
||
then the alarm value is false."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.15 --
|
||
::= { dcSystemAlarms 15 }
|
||
|
||
dcCriticalAlarmName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current alarm name for active critical alarm that corresponds
|
||
to critical alarm identifier."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.16 --
|
||
::= { dcSystemAlarms 16 }
|
||
|
||
dcSystemVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The measured system voltage. The max. value 2147483647
|
||
is used to indicate an invalid value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 --
|
||
::= { dcSystemMonitor 1 }
|
||
|
||
dcLoadCurrent OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The measured load current. The max. value 2147483647
|
||
is used to indicate an invalid value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2 --
|
||
::= { dcSystemMonitor 2 }
|
||
|
||
dcBatteryCurrent OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The measured battery current. The max. value 2147483647
|
||
is used to indicate an invalid value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 --
|
||
::= { dcSystemMonitor 3 }
|
||
|
||
dcBatteryTemperature OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The measured battery temperature. The max. value 2147483647
|
||
is used to indicate an invalid value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 --
|
||
::= { dcSystemMonitor 4 }
|
||
|
||
dcChargeState OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
float(1),
|
||
discharge(2),
|
||
equalize(3),
|
||
boost(4),
|
||
battTest(5),
|
||
recharge(6),
|
||
sepCharge(7),
|
||
evCtrlCharge(8) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery charge state."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 --
|
||
::= { dcSystemMonitor 5 }
|
||
|
||
dcCurrentLimit OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery current limit."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 --
|
||
::= { dcSystemMonitor 6 }
|
||
|
||
dcRectifierCurrent OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total current of all working rectifier modules.
|
||
The maximum value 2147483647 is used to indicate
|
||
an invalid value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 --
|
||
::= { dcSystemMonitor 7 }
|
||
|
||
dcSystemPower OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "1 W"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Calculated system power. The maximum value
|
||
2147483647 is used to indicate an invalid value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 --
|
||
::= { dcSystemMonitor 8 }
|
||
|
||
-- Rectifier
|
||
dcNumberRectifiers OBJECT-TYPE
|
||
SYNTAX Gauge32 (0..128)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The configured number of rectifiers plugged into
|
||
the system. The maximum number of rectifiersi is 128."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1 --
|
||
::= { dcRectifier 1 }
|
||
|
||
dcNumberRectifiersFailure OBJECT-TYPE
|
||
SYNTAX Gauge32 (0..128)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of rectifiers that are not properly working."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2 --
|
||
::= { dcRectifier 2 }
|
||
|
||
dcNumberRectifiersOkay OBJECT-TYPE
|
||
SYNTAX Gauge32 (0..128)
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Number of rectifiers that are properly working."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3 --
|
||
::= { dcRectifier 3 }
|
||
|
||
-- Rectifier - RectifierFunctions - EfficiencyCycling
|
||
dcEfficiencyCyclingEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable efficiency cycling."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.1 --
|
||
::= { dcEfficiencyCycling 1 }
|
||
|
||
dcLimitSwitchingTimes OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable limit switching times."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.2 --
|
||
::= { dcEfficiencyCycling 2 }
|
||
|
||
dcForceSwitchingOncePerMonth OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable force switching once per month."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.3 --
|
||
::= { dcEfficiencyCycling 3 }
|
||
|
||
dcMaximumLoadStep OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "1 W"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Maximum load setup."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.4 --
|
||
::= { dcEfficiencyCycling 4 }
|
||
|
||
dcMinimumLoadStep OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "1 W"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Minimum load setup."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.5 --
|
||
::= { dcEfficiencyCycling 5 }
|
||
|
||
-- Battery - FloatCharge
|
||
dcUsys20 OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage to regulate to at 20<32>C. If temperature compensation
|
||
is used, this voltage will vary."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1 --
|
||
::= { dcFloatCharge 1 }
|
||
|
||
|
||
-- Battery - BatteryTest - BatteryTestParameter
|
||
dcBatteryTestUsupport OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Support charge voltage for the battery."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1 --
|
||
::= { dcBatteryTestParameter 1 }
|
||
|
||
dcBatteryTestDuration OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "minute"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test duration."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2 --
|
||
::= { dcBatteryTestParameter 2 }
|
||
|
||
dcBatteryTestInterval OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "days"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Minimal time between programmed battery tests as start
|
||
condition."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3 --
|
||
::= { dcBatteryTestParameter 3 }
|
||
|
||
dcBatteryTestDischargeCurrent OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery discharge current. The maximum value 2147483647
|
||
is used to indicate an invalid value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4 --
|
||
::= { dcBatteryTestParameter 4 }
|
||
|
||
dcBatteryTestMinDuration OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "minutes"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Minimum battery test duration during which time a battery test
|
||
is not stopped in case of a voltage below the support voltage or
|
||
a current difference higher than the specified value defined in
|
||
Idiff measurement is detected."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 --
|
||
::= { dcBatteryTestParameter 5 }
|
||
|
||
dcBatteryTestVoltageWithinUfloat OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery voltage must be within Ufloat +/- set voltage for a
|
||
given time (see also dcBatteryTestVoltageWithinUfloatPeriod)
|
||
in order to start a battery test."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.6 --
|
||
::= { dcBatteryTestParameter 6 }
|
||
|
||
dcBatteryTestVoltageWithinUfloatPeriod OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "days"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcBatteryTestVoltageWithinUfloat parameter."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.7 --
|
||
::= { dcBatteryTestParameter 7 }
|
||
|
||
dcBatteryTestTempFrom OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery temperature must be within temperature range given by
|
||
dcBatteryTestTempFrom and dcBatteryTestTempTo, so that a battery
|
||
test can be started."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.8 --
|
||
::= { dcBatteryTestParameter 8 }
|
||
|
||
dcBatteryTestTempTo OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcBatteryTestTempFrom parameter."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.9 --
|
||
::= { dcBatteryTestParameter 9 }
|
||
|
||
dcBatteryTestIntervalEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable interval. For more details see dcBatteryTestInterval."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.10 --
|
||
::= { dcBatteryTestParameter 10 }
|
||
|
||
dcBatteryTestStartTimeFrom OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (8))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Defines start time window for battery test. The possible time window
|
||
is defined as the range between dcBatteryTestStartTimeFrom and
|
||
dcBatteryTestStartTimeTo. The value is in the format 'hh:mm:ss'."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.11 --
|
||
::= { dcBatteryTestParameter 11 }
|
||
|
||
dcBatteryTestStartTimeTo OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (8))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcBatteryTestStartTimeFrom."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.12 --
|
||
::= { dcBatteryTestParameter 12 }
|
||
|
||
-- Battery - BatteryTest - BatteryTestResults
|
||
dcBatteryTestDateTime OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (19))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ISO 8601 representation of the last performed battery test.
|
||
The value is in the format YYYY-MM-DDThh:mm:ss. This parameter
|
||
is valid only if there is a test result available."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1 --
|
||
::= { dcBatteryTestResults 1 }
|
||
|
||
dcBatteryTestResult OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
none(1),
|
||
failed(2),
|
||
aborted(3),
|
||
loadFailure(4),
|
||
okay(5),
|
||
abortedManual(6),
|
||
abortedEvCtrlCharge(7),
|
||
abortedInhibitEv(8) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Result of last performed battery test."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2 --
|
||
::= { dcBatteryTestResults 2 }
|
||
|
||
dcBatteryTestEndVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"System voltage at the end of the last performed battery test.
|
||
The maximum value 2147483647 is used to indicate an invalid
|
||
value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3 --
|
||
::= { dcBatteryTestResults 3 }
|
||
|
||
dcBatteryTestControl OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
start(1),
|
||
stop(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Start/stop of battery test. This special charge mode is used
|
||
to check the capacity of a battery. Please note that a battery
|
||
test can be started even if the battery is not fully charged.
|
||
In this case the test result is ambiguous and the set failure
|
||
event will become active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3 --
|
||
::= { dcBatteryTest 3 }
|
||
|
||
dcBatteryTestStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
starting(2),
|
||
stopping(3),
|
||
constantCurrent(4),
|
||
timeBased(5),
|
||
energyBased(6),
|
||
recovery(7),
|
||
realLoad(8),
|
||
stop(9) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Status of battery test."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4 --
|
||
::= { dcBatteryTest 4 }
|
||
|
||
dcBatteryTestFailureEvent OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
reset(1) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Reset battery test failure event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5 --
|
||
::= { dcBatteryTest 5 }
|
||
|
||
dcBatteryTestType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
none(1),
|
||
constantCurrent(2),
|
||
--timeBased(3), deprecated --
|
||
--energyBased(4), deprecated --
|
||
realLoad(5) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Battery test type used."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.6 --
|
||
::= { dcBatteryTest 6 }
|
||
|
||
-- Battery - BatteryParameter
|
||
dcTotalBatteryCapacity OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "100 mAh"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Total battery capacity for all available batteries."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1 --
|
||
::= { dcBatteryParameter 1 }
|
||
|
||
-- Battery - BatteryParameter - LossOfBackupTime
|
||
dcLossOfBackupTimeEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable loss of backup time functionality."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.1 --
|
||
::= { dcLossOfBackupTime 1 }
|
||
|
||
dcLossOfBackupTimeStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
ok(2),
|
||
occured(3),
|
||
fail(4) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Status of loss of backup time functionality."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.2 --
|
||
::= { dcLossOfBackupTime 2 }
|
||
|
||
dcExpectedBackupTime OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "minutes"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Expected backup time value. Based on the given value for
|
||
the parameter expected backup time, the corresponding
|
||
maximum discharge current is calculated."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.3 --
|
||
::= { dcLossOfBackupTime 3 }
|
||
|
||
-- Battery - Equalize
|
||
dcEqualizeControl OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
start(1),
|
||
stop(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Start/stop of battery equalize which is a special charge
|
||
mode that applies a higher voltage to the batteries than
|
||
the float charge. This ensures that the cells are all
|
||
equally charged."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1 --
|
||
::= { dcEqualize 1 }
|
||
|
||
dcEqualizeStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
starting(2),
|
||
stopping(3),
|
||
preparing(4),
|
||
cooking(5),
|
||
recovering(6) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current status of battery equalize."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2 --
|
||
::= { dcEqualize 2 }
|
||
|
||
dcEqualizeEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable equalize."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.3 --
|
||
::= { dcEqualize 3 }
|
||
|
||
-- Equalize - EqualizeParameter
|
||
dcEqualizeVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage used for equalize."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.1 --
|
||
::= { dcEqualizeParameter 1 }
|
||
|
||
dcEqualizeDuration OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "minutes"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Duration of equalize."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.2 --
|
||
::= { dcEqualizeParameter 2 }
|
||
|
||
dcEqualizeUseBattRoomFanEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable battery room fan during equalize."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.3 --
|
||
::= { dcEqualizeParameter 3 }
|
||
|
||
dcEqualizeLeadTime OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "minutes"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lead time for equalize."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.4 --
|
||
::= { dcEqualizeParameter 4 }
|
||
|
||
dcEqualizeTimeLag OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "minutes"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Time lag for equalize."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.5 --
|
||
::= { dcEqualizeParameter 5 }
|
||
|
||
dcEqualizeInterval OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "days"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Interval for equalize as start condition."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.6 --
|
||
::= { dcEqualizeParameter 6 }
|
||
|
||
dcEqualizeStartTimeIntervalFrom OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (8))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Defines start time window for equqlize. The possible time window
|
||
is defined as the range between dcEqualizeStartTimeIntervalFrom and
|
||
dcEqualizeStartTimeIntervalTo. The value is in the format 'hh:mm:ss'."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.7 --
|
||
::= { dcEqualizeParameter 7 }
|
||
|
||
dcEqualizeStartTimeIntervalTo OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (8))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For detail see dcEqualizeStartTimeIntervalFrom."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.8 --
|
||
::= { dcEqualizeParameter 8 }
|
||
|
||
dcEqualizeInhibitAfterBoost OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "hours"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Inhibit after boost as start condition."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.9 --
|
||
::= { dcEqualizeParameter 9 }
|
||
|
||
-- Battery - BoostCharge
|
||
dcBoostChargeControl OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
start(1),
|
||
stop(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Start/stop of boost charge which is a special charge mode
|
||
that applies a higher voltage to the batteries than the float
|
||
charge. This mode is started after a discharge phase to
|
||
recharge the batteries faster."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1 --
|
||
::= { dcBoostCharge 1 }
|
||
|
||
dcBoostChargeStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
starting(2),
|
||
stopping(3),
|
||
cooking(4),
|
||
recovering(5) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current status of boost charge."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2 --
|
||
::= { dcBoostCharge 2 }
|
||
|
||
dcBoostChargeType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
none(1),
|
||
currentBased(2),
|
||
timeBased(3),
|
||
energyBased(4) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Boost charge type."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.3 --
|
||
::= { dcBoostCharge 3 }
|
||
|
||
-- Battery - BoostCharge - BoostChargeParameter
|
||
dcBoostChargeVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage used for boost charge."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.1 --
|
||
::= { dcBoostChargeParameter 1 }
|
||
|
||
dcBoostChargeMaxDuration OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "hours"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Defines the maximum allowed time for boost charge to
|
||
prevent that the battery is charged forever."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.2 --
|
||
::= { dcBoostChargeParameter 2 }
|
||
|
||
dcBoostChargeUseBattRoomFanEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable battery room fan during boost charge."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.3 --
|
||
::= { dcBoostChargeParameter 3 }
|
||
|
||
dcBoostChargeTimeLag OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "minutes"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Time lag used for boost charge."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.4 --
|
||
::= { dcBoostChargeParameter 4 }
|
||
|
||
dcBoostChargeIstart OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For current based boost charge, the parameters Istart
|
||
and Istop are the battery current values at which boost charge
|
||
starts or stops."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.5 --
|
||
::= { dcBoostChargeParameter 5 }
|
||
|
||
dcBoostChargeIstop OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcBoostChargeIstart."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.6 --
|
||
::= { dcBoostChargeParameter 6 }
|
||
|
||
dcBoostChargeInhibitTime OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "hours"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A start condition for all types of boost charge. It defines
|
||
the time from last boost charge stop to the next acceptable boost
|
||
charge start."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.7 --
|
||
::= { dcBoostChargeParameter 7 }
|
||
|
||
-- Battery - SystemVoltageSupervision
|
||
dcUaMax OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"If the system voltage is outside the range specified by the values
|
||
UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the
|
||
system event 'S Ua low'/'S Ua high' is activated. The values for the
|
||
parameters UaMin and UaMax are not temperature compensated."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1 --
|
||
::= { dcSystemVoltageSupervision 1 }
|
||
|
||
dcUaMin OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcUaMax."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2 --
|
||
::= { dcSystemVoltageSupervision 2 }
|
||
|
||
dcUsMax OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"If the voltage is outside the range defined by the parameters UsMin (lower
|
||
safety voltage)/UsMax (upper safety voltage), the system event
|
||
'S Us low'/'S Us high' is activated. If temperature compensation is enabled,
|
||
the levels for Us min and / Us max are automatically temperature compensated
|
||
to correspond to the required system voltage. The parameters are defined
|
||
at 20<32>C."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3 --
|
||
::= { dcSystemVoltageSupervision 3 }
|
||
|
||
dcUsMin OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcUsMax."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4 --
|
||
::= { dcSystemVoltageSupervision 4 }
|
||
|
||
dcBoD OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage threshold for Battery on Discharge alarm."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5 --
|
||
::= { dcSystemVoltageSupervision 5 }
|
||
|
||
dcHysteresis OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Hysteresis used for Ua and Us."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6 --
|
||
::= { dcSystemVoltageSupervision 6 }
|
||
|
||
dcSuppressUaLowEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Suppress Ua Low alarm during mains failure."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7 --
|
||
::= { dcSystemVoltageSupervision 7 }
|
||
|
||
dcSuppressUsLowEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Suppress Us Low alarm during mains failure."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8 --
|
||
::= { dcSystemVoltageSupervision 8 }
|
||
|
||
dcEnableUsTempComp OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max)."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9 --
|
||
::= { dcSystemVoltageSupervision 9 }
|
||
|
||
-- Battery - EvtCtrlCharge
|
||
dcEvtCtrlChargeStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
voltageControlled(2),
|
||
noBatteryCharge(3),
|
||
currentLimitation(4) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Event control charge status."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1 --
|
||
::= { dcEvtCtrlCharge 1 }
|
||
|
||
dcEvtCtrlChargeType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
none(1),
|
||
voltageControlled(2),
|
||
noBatteryCharge(3),
|
||
currentLimitation(4) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Selected event control charge type."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.2 --
|
||
::= { dcEvtCtrlCharge 2 }
|
||
|
||
dcEvtCtrlChargeVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Voltage used for event control charge."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.1 --
|
||
::= { dcEvtCtrlChargeParameter 1}
|
||
|
||
dcEvtCtrlChargeTempCompEnabled OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable temperature compensation during event
|
||
control charge."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.2 --
|
||
::= { dcEvtCtrlChargeParameter 2 }
|
||
|
||
dcEvtCtrlChargeMaxIBatt OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Max. IBatt used for event control charge."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.3 --
|
||
::= { dcEvtCtrlChargeParameter 3}
|
||
|
||
dcTempCompType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
linear(2),
|
||
multi-stage(3) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable battery temperature compensation."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.1 --
|
||
::= { dcTempComp 1 }
|
||
|
||
dcSlope OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "-1 mV/<2F>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature compensation coefficient for system voltage."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.2 --
|
||
::= { dcTempComp 2 }
|
||
|
||
dcStartTemp OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Lower limit for the area in which the temperature compensation
|
||
is active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.3 --
|
||
::= { dcTempComp 3 }
|
||
|
||
dcStopTemp OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper limit for the area in which the temperature compensation
|
||
is active."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.4 --
|
||
::= { dcTempComp 4 }
|
||
|
||
dcMaxVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Upper limit for the area in which the temperature compensation
|
||
is not controlling the system voltage."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.5 --
|
||
::= { dcTempComp 5 }
|
||
|
||
dcLowStopVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The temperature compensation will not control the charging voltage above this parameter at low temperatures."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.6 --
|
||
::= { dcTempComp 6 }
|
||
|
||
dcLowStartTemp OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"High temperature limit of the lower range."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.7 --
|
||
::= { dcTempComp 7 }
|
||
|
||
dcLowTempSlope OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "-1 mV/<2F>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Compensation factor applied inside the low range."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.8 --
|
||
::= { dcTempComp 8 }
|
||
|
||
dcHighStartTemp OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The low temperature limit of the higher range."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.9 --
|
||
::= { dcTempComp 9 }
|
||
|
||
dcHighTempSlope OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "-1 mV/<2F>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Compensation factor applied inside the high range."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.10 --
|
||
::= { dcTempComp 10 }
|
||
|
||
dcHighStopVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The temperature compensation will not control the charging voltage below this parameter at high temperatures."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.11 --
|
||
::= { dcTempComp 11 }
|
||
|
||
dcRunawayTemp OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A threshold for detecting thermal runaway of the battery."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.12 --
|
||
::= { dcTempComp 12 }
|
||
|
||
dcRunawayVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Charging voltage while Runaway Temp has been exceeded."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13 --
|
||
::= { dcTempComp 13 }
|
||
|
||
dcHighTemp OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Temperature threshold for high battery temperature alarm 10<31>C ... 70<37>C"
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.1 --
|
||
::= { dcTempSupervision 1 }
|
||
|
||
dcHighTempHyst OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "0.1 <20>C"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Hysteresis for the High Temp 1<>C ... 70<37>C"
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.2 --
|
||
::= { dcTempSupervision 2 }
|
||
|
||
-- Misc
|
||
dcFileProcessingStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
idle(1),
|
||
inProgress(2),
|
||
successful(3),
|
||
error(4),
|
||
unknown(5) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"File processing status for software and setup up/downloads."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2 --
|
||
::= { dcMisc 2 }
|
||
|
||
dcResendActiveAlarmTraps OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
resend(1) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Resend all active Urgent, Non Urgent, and Critical Alarm Traps."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.4 --
|
||
::= { dcMisc 4 }
|
||
|
||
-- Event Processing Table
|
||
dcEventProcessingEventSelected OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Reference to dcEventProcessingEventIndex in order to select
|
||
a specific event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.3 --
|
||
::= { dcConfig 3 }
|
||
|
||
-- ====================================================================
|
||
-- Event History table
|
||
-- ====================================================================
|
||
dcEventHistoryTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcEventHistoryEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Controller<65>s event history table that shows the content of the
|
||
default log file."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 --
|
||
::= { dcSystemAlarms 1 }
|
||
|
||
dcEventHistoryEntry OBJECT-TYPE
|
||
SYNTAX DcEventHistoryEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular Event History entry."
|
||
INDEX { dcEventHistoryIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1 --
|
||
::= { dcEventHistoryTable 1 }
|
||
|
||
DcEventHistoryEntry ::= SEQUENCE {
|
||
|
||
dcEventHistoryIndex Integer32,
|
||
dcEventHistoryTimestamp DisplayString,
|
||
dcEventHistoryMessage DisplayString }
|
||
|
||
dcEventHistoryIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..10000)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1 --
|
||
::= { dcEventHistoryEntry 1 }
|
||
|
||
dcEventHistoryTimestamp OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (19))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"ISO8601 timestamp representation of a particular entry
|
||
in the form YYYY-MM-DDThh:mm:ss."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2 --
|
||
::= { dcEventHistoryEntry 2 }
|
||
|
||
dcEventHistoryMessage OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..255))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Event message of a particular entry."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3 --
|
||
::= { dcEventHistoryEntry 3 }
|
||
|
||
|
||
-- ====================================================================
|
||
-- Active Alarm table
|
||
-- ====================================================================
|
||
dcAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table that shows all currently active alarm sources
|
||
causing urgent or non-urgent alarm(s)."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 --
|
||
::= { dcSystemAlarms 2 }
|
||
|
||
dcAlarmEntry OBJECT-TYPE
|
||
SYNTAX DcAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular active alarm source entry."
|
||
INDEX { dcAlarmIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1 --
|
||
::= { dcAlarmTable 1 }
|
||
|
||
DcAlarmEntry ::= SEQUENCE {
|
||
dcAlarmIndex Integer32,
|
||
dcAlarmEventCategory INTEGER,
|
||
dcAlarmEventName DisplayString,
|
||
dcAlarmEventIdentifier Gauge32,
|
||
dcAlarmEventValue INTEGER }
|
||
|
||
dcAlarmIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..16)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1 --
|
||
::= { dcAlarmEntry 1 }
|
||
|
||
dcAlarmEventCategory OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
unknown(1),
|
||
urgent(2),
|
||
nonUrgent(3),
|
||
critical(4) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Specifies the type of alarm source."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2 --
|
||
::= { dcAlarmEntry 2 }
|
||
|
||
dcAlarmEventName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of a particular alarm source entry."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3 --
|
||
::= { dcAlarmEntry 3 }
|
||
|
||
dcAlarmEventIdentifier OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unique alarm event identifier."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4 --
|
||
::= { dcAlarmEntry 4 }
|
||
|
||
dcAlarmEventValue OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
false(1),
|
||
-- indeterminate(2), deprecated --
|
||
true(3) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Event status that corresponds to alarm event identifier."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5 --
|
||
::= { dcAlarmEntry 5 }
|
||
|
||
-- ====================================================================
|
||
-- Generic Alarm table
|
||
-- ====================================================================
|
||
dcGenericAlarmTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcGenericAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table that shows ten alarm event assignments that can be
|
||
configured via WEB interface."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 --
|
||
::= { dcSystemAlarms 12 }
|
||
|
||
dcGenericAlarmEntry OBJECT-TYPE
|
||
SYNTAX DcGenericAlarmEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular generic alarm entry."
|
||
INDEX { dcGenericAlarmIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1 --
|
||
::= { dcGenericAlarmTable 1 }
|
||
|
||
DcGenericAlarmEntry ::= SEQUENCE {
|
||
dcGenericAlarmIndex Integer32,
|
||
dcGenericAlarmEventName DisplayString,
|
||
dcGenericAlarmEventIdentifier Gauge32,
|
||
dcGenericAlarmEventValue INTEGER }
|
||
|
||
dcGenericAlarmIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..16)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1 --
|
||
::= { dcGenericAlarmEntry 1 }
|
||
|
||
dcGenericAlarmEventName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Plain text name of the assigned alarm event. Empty if not
|
||
configured."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2 --
|
||
::= { dcGenericAlarmEntry 2 }
|
||
|
||
dcGenericAlarmEventIdentifier OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unique numeric identifier of the assigned alarm event. Zero
|
||
if not configured."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3 --
|
||
::= { dcGenericAlarmEntry 3 }
|
||
|
||
dcGenericAlarmEventValue OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
false(1),
|
||
true(2) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current value of the assigned alarm event. Value is false if
|
||
not configured."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4 --
|
||
::= { dcGenericAlarmEntry 4 }
|
||
|
||
-- ====================================================================
|
||
-- Rectifier table
|
||
-- ====================================================================
|
||
dcRectifierTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcRectifierEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table that shows all currently active rectifier modules."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 --
|
||
::= { dcRectifier 4 }
|
||
|
||
dcRectifierEntry OBJECT-TYPE
|
||
SYNTAX DcRectifierEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular rectifier entry."
|
||
INDEX { dcRectifierIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1 --
|
||
::= { dcRectifierTable 1 }
|
||
|
||
DcRectifierEntry ::= SEQUENCE {
|
||
dcRectifierIndex Integer32,
|
||
dcRectifierIdentifier DisplayString,
|
||
dcRectifierStatus INTEGER }
|
||
|
||
dcRectifierIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..128)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1 --
|
||
::= { dcRectifierEntry 1 }
|
||
|
||
dcRectifierIdentifier OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unique rectifier identifier. If positioning active the
|
||
position number scheme is used otherwise the rectifier
|
||
instance is used to identify a rectifier."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2 --
|
||
::= { dcRectifierEntry 2 }
|
||
|
||
dcRectifierStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
unknown(1),
|
||
off(2),
|
||
on(3) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Specifies status of rectifiers."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3 --
|
||
::= { dcRectifierEntry 3 }
|
||
|
||
-- ====================================================================
|
||
-- Rectifier Group table
|
||
-- ====================================================================
|
||
dcRectifierGroupTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcRectifierGroupEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table that shows all available rectifier groups."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5 --
|
||
::= { dcRectifier 5 }
|
||
|
||
dcRectifierGroupEntry OBJECT-TYPE
|
||
SYNTAX DcRectifierGroupEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular rectifier group entry."
|
||
INDEX { dcRectifierGroupIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1 --
|
||
::= { dcRectifierGroupTable 1 }
|
||
|
||
DcRectifierGroupEntry ::= SEQUENCE {
|
||
dcRectifierGroupIndex Integer32,
|
||
dcRectifierGroupName DisplayString,
|
||
dcRectifierGroupRectifierType INTEGER,
|
||
dcRectifierGroupDefaultVoltage Integer32,
|
||
dcRectifierGroupDefaultCurrentLimit Integer32,
|
||
dcRectifierGroupDefaultPowerLimit Integer32,
|
||
dcRectifierGroupInputLowOff Integer32,
|
||
dcRectifierGroupInputLowOn Integer32,
|
||
dcRectifierGroupStartupVoltage Integer32,
|
||
dcRectifierGroupStartupCurrentLimit Integer32,
|
||
dcRectifierGroupStartupPowerLimit Integer32,
|
||
dcRectifierGroupStartupTimeLimit Gauge32,
|
||
dcRectifierGroupPowerupDelay Gauge32,
|
||
dcRectifierGroupPowerupTime Gauge32,
|
||
dcRectifierGroupUmaxOff Integer32 }
|
||
|
||
dcRectifierGroupIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..1)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1 --
|
||
::= { dcRectifierGroupEntry 1 }
|
||
|
||
dcRectifierGroupName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier group name to identify an individual device
|
||
parameter set."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2 --
|
||
::= { dcRectifierGroupEntry 2 }
|
||
|
||
dcRectifierGroupRectifierType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
unknown48V(1),
|
||
fR48V2000W(2),
|
||
dPR1200B48(3),
|
||
dPR1500B48(4),
|
||
dPR600B48(5),
|
||
dPR7200B48(6),
|
||
fR48to60V2000W(7),
|
||
unknown24V(8),
|
||
unknown60V(9),
|
||
dPR600B60(10),
|
||
dPR3500B48(11),
|
||
dPR3500B24(12),
|
||
dPR300B48(13),
|
||
dPR1600B48(14),
|
||
dPR2700B48(15),
|
||
dPR2400B48(16),
|
||
dPR4000B48(17),
|
||
dPR2900B48(18),
|
||
dPR4000B48to60(19),
|
||
dPR850B48(20),
|
||
dPR2000B48(21) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Rectifier type defined for this group."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3 --
|
||
::= { dcRectifierGroupEntry 3 }
|
||
|
||
dcRectifierGroupDefaultVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This default voltage is used by rectifiers when there
|
||
is no connection to PSC 3."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4 --
|
||
::= { dcRectifierGroupEntry 4 }
|
||
|
||
dcRectifierGroupDefaultCurrentLimit OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This default current limit is used by rectifiers when there
|
||
is no connection to PSC 3."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5 --
|
||
::= { dcRectifierGroupEntry 5 }
|
||
|
||
dcRectifierGroupDefaultPowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "1 W"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This default power limit is used by rectifiers when there
|
||
is no connection to PSC 3."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6 --
|
||
::= { dcRectifierGroupEntry 6 }
|
||
|
||
dcRectifierGroupInputLowOff OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Threshold for low AC input voltage. It can is used to
|
||
adjust the behaviour of the power system to the available
|
||
AC network limitation."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7 --
|
||
::= { dcRectifierGroupEntry 7 }
|
||
|
||
dcRectifierGroupInputLowOn OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcRectifierGroupInputLowOff."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8 --
|
||
::= { dcRectifierGroupEntry 8 }
|
||
|
||
dcRectifierGroupStartupVoltage OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Startup parameters are the values that rectifiers use
|
||
during the start-up phase. These parameters allow starting
|
||
the system smoothly after a mains failure even on a
|
||
discharged battery and even without PSC 3."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9 --
|
||
::= { dcRectifierGroupEntry 9 }
|
||
|
||
dcRectifierGroupStartupCurrentLimit OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcRectifierGroupStartupVoltage."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10 --
|
||
::= { dcRectifierGroupEntry 10 }
|
||
|
||
dcRectifierGroupStartupPowerLimit OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "1 W"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcRectifierGroupStartupVoltage."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11 --
|
||
::= { dcRectifierGroupEntry 11 }
|
||
|
||
dcRectifierGroupStartupTimeLimit OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "10 ms"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"For details see dcRectifierGroupStartupVoltage."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12 --
|
||
::= { dcRectifierGroupEntry 12 }
|
||
|
||
dcRectifierGroupPowerupDelay OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "10 ms"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This parameter is used after a mains failure to
|
||
delay the start-up of all rectifiers."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13 --
|
||
::= { dcRectifierGroupEntry 13 }
|
||
|
||
dcRectifierGroupPowerupTime OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "10 ms"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"This parameter used after a mains failure and allows
|
||
defining a time within all rectifiers needs to start-up
|
||
one after another."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14 --
|
||
::= { dcRectifierGroupEntry 14 }
|
||
|
||
dcRectifierGroupUmaxOff OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "10 mV"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Overvoltage protection value."
|
||
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15 --
|
||
::= { dcRectifierGroupEntry 15 }
|
||
|
||
-- ====================================================================
|
||
-- Rectifier Power Limitation table
|
||
-- ====================================================================
|
||
dcPowerLimitationTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcPowerLimitationEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table that shows parameters of the available power limitation
|
||
functions."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 --
|
||
::= { dcPowerLimitation 1 }
|
||
|
||
dcPowerLimitationEntry OBJECT-TYPE
|
||
SYNTAX DcPowerLimitationEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular power limitation entry."
|
||
INDEX { dcPowerLimitationIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1 --
|
||
::= { dcPowerLimitationTable 1 }
|
||
|
||
DcPowerLimitationEntry ::= SEQUENCE {
|
||
dcPowerLimitationIndex Integer32,
|
||
dcPowerLimitationEventName DisplayString,
|
||
dcPowerLimitationStatus INTEGER,
|
||
dcPowerLimitationType INTEGER,
|
||
dcPowerLimitationLimit Integer32,
|
||
dcPowerLimitationNoBatteryDischarge INTEGER }
|
||
|
||
dcPowerLimitationIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..16)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1 --
|
||
::= { dcPowerLimitationEntry 1 }
|
||
|
||
dcPowerLimitationEventName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the power limitation event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.2 --
|
||
::= { dcPowerLimitationEntry 2 }
|
||
|
||
dcPowerLimitationStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
disabled(1),
|
||
inactive(2),
|
||
powerLimit(3) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Status of power limitation."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.3 --
|
||
::= { dcPowerLimitationEntry 3 }
|
||
|
||
dcPowerLimitationType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
dynamic(1),
|
||
fixedLimit(2) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Power limitation type."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.4 --
|
||
::= { dcPowerLimitationEntry 4 }
|
||
|
||
dcPowerLimitationLimit OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "1 W"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Limit used for power limitation."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.5 --
|
||
::= { dcPowerLimitationEntry 5 }
|
||
|
||
dcPowerLimitationNoBatteryDischarge OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Enable/disable no battery discharge during power limitation."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.6 --
|
||
::= { dcPowerLimitationEntry 6 }
|
||
|
||
-- ====================================================================
|
||
-- BatteryString table
|
||
-- ====================================================================
|
||
dcBatteryStringTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcBatteryStringEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table that shows parameters of the available battery strings."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2 --
|
||
::= { dcBatteryParameter 2 }
|
||
|
||
dcBatteryStringEntry OBJECT-TYPE
|
||
SYNTAX DcBatteryStringEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular battery string entry."
|
||
INDEX { dcBatteryStringIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1 --
|
||
::= { dcBatteryStringTable 1 }
|
||
|
||
DcBatteryStringEntry ::= SEQUENCE {
|
||
dcBatteryStringIndex Integer32,
|
||
dcBatteryStringName DisplayString,
|
||
dcBatteryStringMaxIBatt Integer32,
|
||
dcBatteryStringCapacity Gauge32 }
|
||
|
||
dcBatteryStringIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..16)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1 --
|
||
::= { dcBatteryStringEntry 1 }
|
||
|
||
dcBatteryStringName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the battery string."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2 --
|
||
::= { dcBatteryStringEntry 2 }
|
||
|
||
dcBatteryStringMaxIBatt OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
UNITS "100 mA"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Maximum battery charging current for this string. This
|
||
parameter can be set individually for each battery.
|
||
PSC 3 then regulates the system voltage such that the maximum
|
||
battery charging current of each battery is respected."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3 --
|
||
::= { dcBatteryStringEntry 3 }
|
||
|
||
dcBatteryStringCapacity OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "100 mAh"
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Capacity of battery can be defined individually. It is used
|
||
to calculate the expected backup time of the system."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4 --
|
||
::= { dcBatteryStringEntry 4 }
|
||
|
||
-- ====================================================================
|
||
-- Control Event table
|
||
-- ====================================================================
|
||
dcControlEventTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcControlEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table that shows ten output event assignments that can be
|
||
configured via WEB interface."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 --
|
||
::= { dcInputOutput 1 }
|
||
|
||
dcControlEventEntry OBJECT-TYPE
|
||
SYNTAX DcControlEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular generic output entry."
|
||
INDEX { dcControlEventIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1 --
|
||
::= { dcControlEventTable 1 }
|
||
|
||
DcControlEventEntry ::= SEQUENCE {
|
||
dcControlEventIndex Integer32,
|
||
dcControlEventName DisplayString,
|
||
dcControlEventIdentifier Gauge32,
|
||
dcControlEventValue INTEGER }
|
||
|
||
dcControlEventIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..16)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1 --
|
||
::= { dcControlEventEntry 1 }
|
||
|
||
dcControlEventName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (0..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Plain text name of the assigned control event. Empty if not
|
||
configure."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2 --
|
||
::= { dcControlEventEntry 2 }
|
||
|
||
dcControlEventIdentifier OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unique numeric identifier of the assigned control event. Zero
|
||
if not configured."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3 --
|
||
::= { dcControlEventEntry 3 }
|
||
|
||
dcControlEventValue OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
false(1),
|
||
true(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Current value of the assigned control event. Value is false if
|
||
not configured."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4 --
|
||
::= { dcControlEventEntry 4 }
|
||
|
||
-- ====================================================================
|
||
-- Trap Destinations table
|
||
-- ====================================================================
|
||
dcTrapDestinationTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcTrapDestinationEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Trap table that shows all configured trap destinations."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 --
|
||
::= { dcMisc 1 }
|
||
|
||
dcTrapDestinationEntry OBJECT-TYPE
|
||
SYNTAX DcTrapDestinationEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular trap destination entry."
|
||
INDEX { dcTrapDestinationIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1 --
|
||
::= { dcTrapDestinationTable 1 }
|
||
|
||
DcTrapDestinationEntry ::= SEQUENCE {
|
||
dcTrapDestinationIndex Integer32,
|
||
dcTrapDestinationIp IpAddress,
|
||
dcTrapDestinationPort Gauge32 }
|
||
|
||
dcTrapDestinationIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..10)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1 --
|
||
::= { dcTrapDestinationEntry 1 }
|
||
|
||
dcTrapDestinationIp OBJECT-TYPE
|
||
SYNTAX IpAddress
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"IP address of the trap destination. Value is 0.0.0.0 if IP
|
||
address is not configured."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2 --
|
||
::= { dcTrapDestinationEntry 2 }
|
||
|
||
dcTrapDestinationPort OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Port number of the trap destination. By default port 162
|
||
is used."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3 --
|
||
::= { dcTrapDestinationEntry 3 }
|
||
|
||
-- ====================================================================
|
||
-- Default Log Config table
|
||
-- ====================================================================
|
||
dcDefaultLogEventTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcDefaultLogEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Event config table for default log."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1 --
|
||
::= { dcConfig 1 }
|
||
|
||
dcDefaultLogEventEntry OBJECT-TYPE
|
||
SYNTAX DcDefaultLogEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular event entry."
|
||
INDEX { dcDefaultLogEventIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1 --
|
||
::= { dcDefaultLogEventTable 1 }
|
||
|
||
DcDefaultLogEventEntry ::= SEQUENCE {
|
||
dcDefaultLogEventIndex Integer32,
|
||
dcDefaultLogEventName DisplayString,
|
||
dcDefaultLogEventLogged INTEGER }
|
||
|
||
dcDefaultLogEventIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..1000)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1 --
|
||
::= { dcDefaultLogEventEntry 1 }
|
||
|
||
dcDefaultLogEventName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Plain text name of the event that can be logged."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2 --
|
||
::= { dcDefaultLogEventEntry 2 }
|
||
|
||
dcDefaultLogEventLogged OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"If yes then this event is logged otherwise not."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3 --
|
||
::= { dcDefaultLogEventEntry 3 }
|
||
|
||
-- ====================================================================
|
||
-- Event Processing Config table
|
||
-- ====================================================================
|
||
dcEventProcessingEventTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcEventProcessingEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Event config table for event ORs."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2 --
|
||
::= { dcConfig 2 }
|
||
|
||
dcEventProcessingEventEntry OBJECT-TYPE
|
||
SYNTAX DcEventProcessingEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular event entry."
|
||
INDEX { dcEventProcessingEventIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1 --
|
||
::= { dcEventProcessingEventTable 1 }
|
||
|
||
DcEventProcessingEventEntry ::= SEQUENCE {
|
||
dcEventProcessingEventIndex Integer32,
|
||
dcEventProcessingEventName DisplayString,
|
||
dcEventProcessingEventAssigned INTEGER,
|
||
dcEventProcessingEventType INTEGER }
|
||
|
||
dcEventProcessingEventIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (0..1000)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1 --
|
||
::= { dcEventProcessingEventEntry 1 }
|
||
|
||
dcEventProcessingEventName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..35))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Plain text name of the input event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2 --
|
||
::= { dcEventProcessingEventEntry 2 }
|
||
|
||
dcEventProcessingEventAssigned OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
no(1),
|
||
yes(2) }
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"If yes then the input event is assigned to the selected
|
||
event. Please note, that it is only possible to change
|
||
assignment of event ORs."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3 --
|
||
::= { dcEventProcessingEventEntry 3 }
|
||
|
||
dcEventProcessingEventType OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
unknown(1),
|
||
eventOR(2) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Type of the input event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4 --
|
||
::= { dcEventProcessingEventEntry 4 }
|
||
|
||
-- ====================================================================
|
||
-- LVD Config table
|
||
-- ====================================================================
|
||
dcLvdTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcLvdEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table lists all available LVDs."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4 --
|
||
::= { dcConfig 4 }
|
||
|
||
dcLvdEntry OBJECT-TYPE
|
||
SYNTAX DcLvdEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular LVD entry."
|
||
INDEX { dcLvdIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1 --
|
||
::= { dcLvdTable 1 }
|
||
|
||
DcLvdEntry ::= SEQUENCE {
|
||
dcLvdIndex Integer32,
|
||
dcLvdName DisplayString,
|
||
dcLvdDisconnectDelay DisplayString }
|
||
|
||
dcLvdIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..96)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1 --
|
||
::= { dcLvdEntry 1 }
|
||
|
||
dcLvdName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the LVD."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2 --
|
||
::= { dcLvdEntry 2 }
|
||
|
||
dcLvdDisconnectDelay OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (8))
|
||
MAX-ACCESS read-write
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Time delay from the activation of the source event, after
|
||
which the LVD event is switched. The value is in the format
|
||
'hh:mm:ss'."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3 --
|
||
::= { dcLvdEntry 3 }
|
||
|
||
-- ====================================================================
|
||
-- Measurement table
|
||
-- ====================================================================
|
||
dcMeasurementTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcMeasurementEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table lists all available measurements."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1 --
|
||
::= { dcMeasurement 1 }
|
||
|
||
dcMeasurementEntry OBJECT-TYPE
|
||
SYNTAX DcMeasurementEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular measurement entry."
|
||
INDEX { dcMeasurementIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1 --
|
||
::= { dcMeasurementTable 1 }
|
||
|
||
DcMeasurementEntry ::= SEQUENCE {
|
||
dcMeasurementIndex Integer32,
|
||
dcMeasurementName DisplayString,
|
||
dcMeasurementValue Integer32,
|
||
dcMeasurementScaleFactor Integer32,
|
||
dcMeasurementUnit INTEGER }
|
||
|
||
dcMeasurementIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..500)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1 --
|
||
::= { dcMeasurementEntry 1 }
|
||
|
||
dcMeasurementName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the measurement."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2 --
|
||
::= { dcMeasurementEntry 2 }
|
||
|
||
dcMeasurementValue OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unscaled calibrated value of the measurement."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3 --
|
||
::= { dcMeasurementEntry 3 }
|
||
|
||
dcMeasurementScaleFactor OBJECT-TYPE
|
||
SYNTAX Integer32
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Scale factor as power of 10 to be multiplied with measurement value."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4 --
|
||
::= { dcMeasurementEntry 4 }
|
||
|
||
dcMeasurementUnit OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
unknown(1),
|
||
none(2),
|
||
voltDC(3),
|
||
voltAC(4),
|
||
ampere(5),
|
||
ampereHour(6),
|
||
degreeCelsius(7),
|
||
temperatureCoefficient(8),
|
||
watt(9),
|
||
wattHour(10),
|
||
seconds(11),
|
||
percent(12),
|
||
hertz(13),
|
||
voltAmpere(14),
|
||
voltAmpereReactive(15),
|
||
voltAmpereReactiveHour(16) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Unit of the measurement."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5 --
|
||
::= { dcMeasurementEntry 5 }
|
||
|
||
-- ====================================================================
|
||
-- Meter Panel Event table
|
||
-- ====================================================================
|
||
dcMeterPanelEventTable OBJECT-TYPE
|
||
SYNTAX SEQUENCE OF DcMeterPanelEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table lists all available meter panel events."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1 --
|
||
::= { dcMeterPanel 1 }
|
||
|
||
dcMeterPanelEventEntry OBJECT-TYPE
|
||
SYNTAX DcMeterPanelEventEntry
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"A particular meter panel event entry."
|
||
INDEX { dcMeterPanelEventIndex }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1 --
|
||
::= { dcMeterPanelEventTable 1 }
|
||
|
||
DcMeterPanelEventEntry ::= SEQUENCE {
|
||
dcMeterPanelEventIndex Integer32,
|
||
dcMeterPanelEventName DisplayString,
|
||
dcMeterPanelEventValue INTEGER,
|
||
dcMeterPanelEventHourMeterValue Gauge32 }
|
||
|
||
dcMeterPanelEventIndex OBJECT-TYPE
|
||
SYNTAX Integer32 (1..128)
|
||
MAX-ACCESS not-accessible
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Table index."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1 --
|
||
::= { dcMeterPanelEventEntry 1 }
|
||
|
||
dcMeterPanelEventName OBJECT-TYPE
|
||
SYNTAX DisplayString (SIZE (1..16))
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Name of the event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2 --
|
||
::= { dcMeterPanelEventEntry 2 }
|
||
|
||
dcMeterPanelEventValue OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
false(1),
|
||
indeterminate(2),
|
||
true(3) }
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Value of the event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3 --
|
||
::= { dcMeterPanelEventEntry 3 }
|
||
|
||
dcMeterPanelEventHourMeterValue OBJECT-TYPE
|
||
SYNTAX Gauge32
|
||
UNITS "hours"
|
||
MAX-ACCESS read-only
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Value of the hour meter event."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4 --
|
||
::= { dcMeterPanelEventEntry 4 }
|
||
|
||
-- ====================================================================
|
||
-- Notifications
|
||
-- ====================================================================
|
||
systemNonUrgentAlarm NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
dcSystemDateTime,
|
||
dcNumberNonUrgentAlarms,
|
||
dcNonUrgentAlarmIdentifier,
|
||
dcNonUrgentAlarmValue,
|
||
dcNonUrgentAlarmName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The controller reports that one or more elements have changed
|
||
into none urgent alarm state."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1 --
|
||
::= { controllerEventsV2 1 }
|
||
|
||
systemUrgentAlarm NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
dcSystemDateTime,
|
||
dcNumberUrgentAlarms,
|
||
dcUrgentAlarmIdentifier,
|
||
dcUrgentAlarmValue,
|
||
dcUrgentAlarmName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The controller reports that one or more elements have changed
|
||
into urgent alarm state."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2 --
|
||
::= { controllerEventsV2 2 }
|
||
|
||
systemCriticalAlarm NOTIFICATION-TYPE
|
||
OBJECTS {
|
||
dcSystemDateTime,
|
||
dcNumberCriticalAlarms,
|
||
dcCriticalAlarmIdentifier,
|
||
dcCriticalAlarmValue,
|
||
dcCriticalAlarmName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The controller reports that one or more elements have changed
|
||
into critical alarm state."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.3 --
|
||
::= { controllerEventsV2 3 }
|
||
|
||
-- ====================================================================
|
||
-- Conformance area, containing groups and compliance specifications
|
||
-- ====================================================================
|
||
systemInfoGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcSiteName,
|
||
dcSystemName,
|
||
dcSystemDateTime,
|
||
dcSoftwareVersion }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of system info scalar objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1 --
|
||
::= { controllerGroups 1 }
|
||
|
||
systemAlarmGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcNumberUrgentAlarms,
|
||
dcNumberNonUrgentAlarms,
|
||
dcMainsFailureAlarm,
|
||
dcUrgentAlarmIdentifier,
|
||
dcUrgentAlarmValue,
|
||
dcNonUrgentAlarmIdentifier,
|
||
dcNonUrgentAlarmValue,
|
||
dcUrgentAlarmName,
|
||
dcNonUrgentAlarmName,
|
||
dcNumberCriticalAlarms,
|
||
dcCriticalAlarmIdentifier,
|
||
dcCriticalAlarmValue,
|
||
dcCriticalAlarmName }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of system alarm scalar objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2 --
|
||
::= { controllerGroups 2 }
|
||
|
||
systemMonitorGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcSystemVoltage,
|
||
dcLoadCurrent,
|
||
dcBatteryCurrent,
|
||
dcBatteryTemperature,
|
||
dcChargeState,
|
||
dcCurrentLimit,
|
||
dcRectifierCurrent,
|
||
dcSystemPower }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of system monitor scalar objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3 --
|
||
::= { controllerGroups 3 }
|
||
|
||
rectifierGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcNumberRectifiers,
|
||
dcNumberRectifiersFailure,
|
||
dcNumberRectifiersOkay,
|
||
dcEfficiencyCyclingEnabled,
|
||
dcLimitSwitchingTimes,
|
||
dcForceSwitchingOncePerMonth,
|
||
dcMaximumLoadStep,
|
||
dcMinimumLoadStep }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of rectifier scalar objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4 --
|
||
::= { controllerGroups 4 }
|
||
|
||
eventHistoryTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcEventHistoryTimestamp,
|
||
dcEventHistoryMessage }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of event history table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5 --
|
||
::= { controllerGroups 5 }
|
||
|
||
alarmTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcAlarmEventCategory,
|
||
dcAlarmEventName,
|
||
dcAlarmEventIdentifier,
|
||
dcAlarmEventValue }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of alarm table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6 --
|
||
::= { controllerGroups 6 }
|
||
|
||
rectifierTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcRectifierIdentifier,
|
||
dcRectifierStatus }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of rectifier table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7 --
|
||
::= { controllerGroups 7 }
|
||
|
||
notificationsGroup NOTIFICATION-GROUP
|
||
NOTIFICATIONS {
|
||
systemNonUrgentAlarm,
|
||
systemUrgentAlarm,
|
||
systemCriticalAlarm }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The group of all controller notifications."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8 --
|
||
::= { controllerGroups 8 }
|
||
|
||
genericAlarmTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcGenericAlarmEventIdentifier,
|
||
dcGenericAlarmEventName,
|
||
dcGenericAlarmEventValue }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Assignment of events to alarm table entries."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9 --
|
||
::= { controllerGroups 9 }
|
||
|
||
batteryGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcUsys20,
|
||
dcTempCompType,
|
||
dcSlope,
|
||
dcStartTemp,
|
||
dcStopTemp,
|
||
dcMaxVoltage,
|
||
dcLowStopVoltage,
|
||
dcLowStartTemp,
|
||
dcLowTempSlope,
|
||
dcHighStartTemp,
|
||
dcHighTempSlope,
|
||
dcHighStopVoltage,
|
||
dcRunawayTemp,
|
||
dcRunawayVoltage,
|
||
dcBatteryTestUsupport,
|
||
dcBatteryTestDuration,
|
||
dcBatteryTestInterval,
|
||
dcBatteryTestDischargeCurrent,
|
||
dcBatteryTestMinDuration,
|
||
dcBatteryTestVoltageWithinUfloat,
|
||
dcBatteryTestVoltageWithinUfloatPeriod,
|
||
dcBatteryTestTempFrom,
|
||
dcBatteryTestTempTo,
|
||
dcBatteryTestIntervalEnabled,
|
||
dcBatteryTestStartTimeFrom,
|
||
dcBatteryTestStartTimeTo,
|
||
dcBatteryTestDateTime,
|
||
dcBatteryTestResult,
|
||
dcBatteryTestEndVoltage,
|
||
dcBatteryTestControl,
|
||
dcBatteryTestStatus,
|
||
dcBatteryTestFailureEvent,
|
||
dcBatteryTestType,
|
||
dcTotalBatteryCapacity,
|
||
dcLossOfBackupTimeEnabled,
|
||
dcLossOfBackupTimeStatus,
|
||
dcExpectedBackupTime,
|
||
dcEqualizeControl,
|
||
dcEqualizeStatus,
|
||
dcEqualizeEnabled,
|
||
dcEqualizeVoltage,
|
||
dcEqualizeDuration,
|
||
dcEqualizeUseBattRoomFanEnabled,
|
||
dcEqualizeLeadTime,
|
||
dcEqualizeTimeLag,
|
||
dcEqualizeInterval,
|
||
dcEqualizeStartTimeIntervalFrom,
|
||
dcEqualizeStartTimeIntervalTo,
|
||
dcEqualizeInhibitAfterBoost,
|
||
dcBoostChargeControl,
|
||
dcBoostChargeStatus,
|
||
dcBoostChargeType,
|
||
dcBoostChargeVoltage,
|
||
dcBoostChargeMaxDuration,
|
||
dcBoostChargeUseBattRoomFanEnabled,
|
||
dcBoostChargeTimeLag,
|
||
dcBoostChargeIstart,
|
||
dcBoostChargeIstop,
|
||
dcBoostChargeInhibitTime,
|
||
dcUaMax,
|
||
dcUaMin,
|
||
dcUsMax,
|
||
dcUsMin,
|
||
dcBoD,
|
||
dcHysteresis,
|
||
dcSuppressUaLowEnabled,
|
||
dcSuppressUsLowEnabled,
|
||
dcEnableUsTempComp,
|
||
dcEvtCtrlChargeStatus,
|
||
dcEvtCtrlChargeType,
|
||
dcEvtCtrlChargeVoltage,
|
||
dcEvtCtrlChargeTempCompEnabled,
|
||
dcEvtCtrlChargeMaxIBatt,
|
||
dcHighTemp,
|
||
dcHighTempHyst }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of battery scalar objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10 --
|
||
::= { controllerGroups 10 }
|
||
|
||
controlEventTableGroup
|
||
OBJECT-GROUP
|
||
OBJECTS {
|
||
dcControlEventName,
|
||
dcControlEventIdentifier,
|
||
dcControlEventValue }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Assignment of control events to table entries."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11 --
|
||
::= { controllerGroups 11 }
|
||
|
||
trapDestinationTableGroup
|
||
OBJECT-GROUP
|
||
OBJECTS {
|
||
dcTrapDestinationIp,
|
||
dcTrapDestinationPort }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"Trap destionation table."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12 --
|
||
::= { controllerGroups 12 }
|
||
|
||
miscGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcFileProcessingStatus,
|
||
dcResendActiveAlarmTraps }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of miscellaneous objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13 --
|
||
::= { controllerGroups 13 }
|
||
|
||
rectifierGroupTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcRectifierGroupName,
|
||
dcRectifierGroupRectifierType,
|
||
dcRectifierGroupDefaultVoltage,
|
||
dcRectifierGroupDefaultCurrentLimit,
|
||
dcRectifierGroupDefaultPowerLimit,
|
||
dcRectifierGroupInputLowOff,
|
||
dcRectifierGroupInputLowOn,
|
||
dcRectifierGroupStartupVoltage,
|
||
dcRectifierGroupStartupCurrentLimit,
|
||
dcRectifierGroupStartupPowerLimit,
|
||
dcRectifierGroupStartupTimeLimit,
|
||
dcRectifierGroupPowerupDelay,
|
||
dcRectifierGroupPowerupTime,
|
||
dcRectifierGroupUmaxOff }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of rectifier group table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.14 --
|
||
::= { controllerGroups 14 }
|
||
|
||
batteryStringTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcBatteryStringName,
|
||
dcBatteryStringMaxIBatt,
|
||
dcBatteryStringCapacity }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of battery string table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.15 --
|
||
::= { controllerGroups 15 }
|
||
|
||
defaultLogEventTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcDefaultLogEventName,
|
||
dcDefaultLogEventLogged }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of default log event table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.16 --
|
||
::= { controllerGroups 16 }
|
||
|
||
eventProcessingEventTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcEventProcessingEventName,
|
||
dcEventProcessingEventAssigned,
|
||
dcEventProcessingEventType,
|
||
dcEventProcessingEventSelected }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of event processing event table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.17 --
|
||
::= { controllerGroups 17 }
|
||
|
||
lvdTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcLvdName,
|
||
dcLvdDisconnectDelay }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of LVD table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.18 --
|
||
::= { controllerGroups 18 }
|
||
|
||
powerLimitationTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcPowerLimitationEventName,
|
||
dcPowerLimitationStatus,
|
||
dcPowerLimitationType,
|
||
dcPowerLimitationLimit,
|
||
dcPowerLimitationNoBatteryDischarge }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of power limitation table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.19 --
|
||
::= { controllerGroups 19 }
|
||
|
||
measurementTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcMeasurementName,
|
||
dcMeasurementValue,
|
||
dcMeasurementScaleFactor,
|
||
dcMeasurementUnit }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of measurement table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.20 --
|
||
::= { controllerGroups 20 }
|
||
|
||
meterPanelEventTableGroup OBJECT-GROUP
|
||
OBJECTS {
|
||
dcMeterPanelEventName,
|
||
dcMeterPanelEventValue,
|
||
dcMeterPanelEventHourMeterValue }
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The collection of meter panel event table objects."
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.21 --
|
||
::= { controllerGroups 21 }
|
||
|
||
controllerBasicCompl MODULE-COMPLIANCE
|
||
STATUS current
|
||
DESCRIPTION
|
||
"The basic implementation requirements for the controller MIB."
|
||
MODULE
|
||
MANDATORY-GROUPS {
|
||
systemInfoGroup,
|
||
systemAlarmGroup,
|
||
systemMonitorGroup,
|
||
alarmTableGroup,
|
||
notificationsGroup }
|
||
-- 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1 --
|
||
::= { controllerCompl 1 }
|
||
|
||
END
|