- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1666 lines
44 KiB
Text
1666 lines
44 KiB
Text
--Delta-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) delta(2254) ups(2) upsv4(4) }
|
|
|
|
|
|
DeltaUPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
enterprises, IpAddress
|
|
FROM RFC1155-SMI
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
|
|
delta OBJECT IDENTIFIER ::= { enterprises 2254 }
|
|
|
|
ups OBJECT IDENTIFIER ::= { delta 2 }
|
|
|
|
upsv4 OBJECT IDENTIFIER ::= { ups 4 }
|
|
|
|
dupsIdent OBJECT IDENTIFIER ::= { upsv4 1 }
|
|
dupsControl OBJECT IDENTIFIER ::= { upsv4 2 }
|
|
dupsConfig OBJECT IDENTIFIER ::= { upsv4 3 }
|
|
dupsInput OBJECT IDENTIFIER ::= { upsv4 4 }
|
|
dupsOutput OBJECT IDENTIFIER ::= { upsv4 5 }
|
|
dupsBypass OBJECT IDENTIFIER ::= { upsv4 6 }
|
|
dupsBattery OBJECT IDENTIFIER ::= { upsv4 7 }
|
|
dupsTest OBJECT IDENTIFIER ::= { upsv4 8 }
|
|
dupsAlarm OBJECT IDENTIFIER ::= { upsv4 9 }
|
|
dupsEnvironment OBJECT IDENTIFIER ::= { upsv4 10 }
|
|
dupsTraps OBJECT IDENTIFIER ::= { upsv4 20 }
|
|
|
|
|
|
----------------------
|
|
-- dups Ident group --
|
|
----------------------
|
|
dupsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..20))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { dupsIdent 1 }
|
|
|
|
dupsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { dupsIdent 2 }
|
|
|
|
dupsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not has the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { dupsIdent 3 }
|
|
|
|
dupsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not has the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations."
|
|
::= { dupsIdent 4 }
|
|
|
|
dupsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { dupsIdent 5 }
|
|
|
|
dupsAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { dupsIdent 6 }
|
|
|
|
dupsRatingOutputVA OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output VA rating."
|
|
::= { dupsIdent 7 }
|
|
|
|
dupsRatingOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage rating."
|
|
::= { dupsIdent 8 }
|
|
|
|
dupsRatingOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output frequency rating."
|
|
::= { dupsIdent 9 }
|
|
|
|
dupsRatingInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage rating."
|
|
::= { dupsIdent 10 }
|
|
|
|
dupsRatingInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input frequency rating."
|
|
::= { dupsIdent 11 }
|
|
|
|
dupsRatingBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal battery voltage rating."
|
|
::= { dupsIdent 12 }
|
|
|
|
dupsLowTransferVoltUpBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage upper bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 13 }
|
|
|
|
dupsLowTransferVoltLowBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage lower bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 14 }
|
|
|
|
dupsHighTransferVoltUpBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum input line voltage upper bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 15 }
|
|
|
|
dupsHighTransferVoltLowBound OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum input line voltage lower bound allowed
|
|
before the UPS system transfers to battery backup."
|
|
::= { dupsIdent 16 }
|
|
|
|
dupsLowBattTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Minutes, time from low battery to low battery shutdown."
|
|
::= { dupsIdent 17 }
|
|
|
|
dupsOutletRelays OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Number of outlet relay. If it is 0, the function is not
|
|
available for the UPS."
|
|
::= { dupsIdent 18 }
|
|
|
|
dupsType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on-line(1),
|
|
off-line(2),
|
|
line-interactive(3),
|
|
3phase(4),
|
|
splite-phase(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the UPS type."
|
|
::= { dupsIdent 19 }
|
|
|
|
------------------------
|
|
-- dups Control group --
|
|
------------------------
|
|
dupsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off."
|
|
::= { dupsControl 1 }
|
|
|
|
dupsAutoReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"In backup mode, the UPS may shutdown normally by SDA command,
|
|
dry-contact remote shutdown signal or low battery shutdown.
|
|
This command is used to determine the unit should restart or
|
|
not next time when the power restores"
|
|
::= { dupsControl 2 }
|
|
|
|
dupsShutdownAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the value is greater than 0 the UPS performs
|
|
shutdown action that defined by ShutdownType after
|
|
the seconds. 0, aborted."
|
|
::= { dupsControl 3 }
|
|
|
|
dupsRestartAction OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Minute"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS will restart after the indicated number of minutes.
|
|
-1, aborted."
|
|
::= { dupsControl 4 }
|
|
|
|
dupsSetOutletRelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate which outlet relay, from 1,2,3... ."
|
|
::= { dupsControl 5 }
|
|
|
|
dupsRelayOffDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turn the relay off after the seconds. The relay was indicated
|
|
by SetOutletRelay."
|
|
::= { dupsControl 6 }
|
|
|
|
dupsRelayOnDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- UNITS "Minute"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Turn the relay on after the seconds. The relay was indicated
|
|
by SetOutletRelay."
|
|
::= { dupsControl 7 }
|
|
|
|
--------------------------
|
|
-- dups Configure group --
|
|
--------------------------
|
|
dupsConfigBuzzerAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
alarm(1),
|
|
silence(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS will keep silence but will alarm again when
|
|
next power event is occurred"
|
|
::= { dupsConfig 1 }
|
|
|
|
dupsConfigBuzzerState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If it is disabled then the UPS is always muted."
|
|
::= { dupsConfig 2 }
|
|
|
|
dupsConfigSensitivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
reduced(1),
|
|
low(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The seneitivity of the UPS to utility line
|
|
abnormalities or noises."
|
|
::= { dupsConfig 3 }
|
|
|
|
dupsConfigLowVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum input line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { dupsConfig 4 }
|
|
|
|
dupsConfigHighVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Volt"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { dupsConfig 5 }
|
|
|
|
dupsConfigShutdownOSDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The operating system shutdown delay time when the
|
|
input power fail. -1 will disable this option."
|
|
::= { dupsConfig 6 }
|
|
|
|
dupsConfigUPSBootDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Second"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Delay the UPS startup after power restores. The power
|
|
quality may not stable when power restores, this
|
|
feature let the UPS wait a period of time to startup
|
|
the system."
|
|
::= { dupsConfig 7 }
|
|
|
|
dupsConfigExternalBatteryPack OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicate the number of external battery pack."
|
|
::= { dupsConfig 8 }
|
|
|
|
----------------------
|
|
-- dups Input group --
|
|
----------------------
|
|
dupsInputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device."
|
|
::= { dupsInput 1 }
|
|
|
|
dupsInputFrequency1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 1 frequency to the UPS
|
|
system in 1/10 Hz."
|
|
::= { dupsInput 2 }
|
|
|
|
dupsInputVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1 voltage of the UPS system in 1/10 V."
|
|
::= { dupsInput 3 }
|
|
|
|
dupsInputCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 1 current to the UPS system in 1/10 A."
|
|
::= { dupsInput 4 }
|
|
|
|
dupsInputFrequency2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 2 frequency to the UPS system
|
|
in 1/10 Hz."
|
|
::= { dupsInput 5 }
|
|
|
|
dupsInputVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2 voltage of the UPS system in 1/10 V."
|
|
::= { dupsInput 6 }
|
|
|
|
dupsInputCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 2 current to the UPS system in 1/10 A."
|
|
::= { dupsInput 7 }
|
|
|
|
dupsInputFrequency3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input line 3 frequency to the UPS system
|
|
in 1/10 Hz."
|
|
::= { dupsInput 8 }
|
|
|
|
dupsInputVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3 voltage of the UPS system in 1/10 V."
|
|
::= { dupsInput 9 }
|
|
|
|
dupsInputCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Input line 3 current to the UPS system in 1/10 A."
|
|
::= { dupsInput 10 }
|
|
|
|
-----------------------
|
|
-- dups Output group --
|
|
-----------------------
|
|
dupsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
battery(1),
|
|
bypass(2),
|
|
reducing(3),
|
|
boosting(4),
|
|
manualBypass(5),
|
|
other(6),
|
|
none(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(7) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker."
|
|
::= { dupsOutput 1 }
|
|
|
|
dupsOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output frequency in 1/10 Hz."
|
|
::= { dupsOutput 2 }
|
|
|
|
dupsOutputNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device."
|
|
::= { dupsOutput 3 }
|
|
|
|
dupsOutputVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 voltage of the UPS system in 1/10 V."
|
|
::= { dupsOutput 4 }
|
|
|
|
dupsOutputCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 current of the UPS system in 1/10 A."
|
|
::= { dupsOutput 5 }
|
|
|
|
dupsOutputPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 1 real power of the UPS system in watts."
|
|
::= { dupsOutput 6 }
|
|
|
|
dupsOutputLoad1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 1 load expressed in percent
|
|
of rated capacity."
|
|
::= { dupsOutput 7 }
|
|
|
|
dupsOutputVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 voltage of the UPS system in 1/10 V."
|
|
::= { dupsOutput 8 }
|
|
|
|
dupsOutputCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 current of the UPS system in 1/10 A."
|
|
::= { dupsOutput 9 }
|
|
|
|
dupsOutputPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 2 real power of the UPS system in watts."
|
|
::= { dupsOutput 10 }
|
|
|
|
dupsOutputLoad2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 2 load expressed in percent
|
|
of rated capacity."
|
|
::= { dupsOutput 11 }
|
|
|
|
dupsOutputVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 voltage of the UPS system in 1/10 V."
|
|
::= { dupsOutput 12 }
|
|
|
|
dupsOutputCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 current of the UPS system in 1/10 A."
|
|
::= { dupsOutput 13 }
|
|
|
|
dupsOutputPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Output line 3 real power of the UPS system in watts."
|
|
::= { dupsOutput 14 }
|
|
|
|
dupsOutputLoad3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS output line 3 load expressed in percent
|
|
of rated capacity."
|
|
::= { dupsOutput 15 }
|
|
|
|
-----------------------
|
|
-- dups Bypass group --
|
|
-----------------------
|
|
dupsBypassFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass frequency in 1/10 Hz."
|
|
::= { dupsBypass 1 }
|
|
|
|
dupsBypassNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device."
|
|
::= { dupsBypass 2 }
|
|
|
|
dupsBypassVoltage1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 voltage of the UPS system in 1/10 V."
|
|
::= { dupsBypass 3 }
|
|
|
|
dupsBypassCurrent1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 current of the UPS system in 1/10 A."
|
|
::= { dupsBypass 4 }
|
|
|
|
dupsBypassPower1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 1 real power of the UPS system in watts."
|
|
::= { dupsBypass 5 }
|
|
|
|
dupsBypassVoltage2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 voltage of the UPS system in 1/10 V."
|
|
::= { dupsBypass 6 }
|
|
|
|
dupsBypassCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 current of the UPS system in 1/10 A."
|
|
::= { dupsBypass 7 }
|
|
|
|
dupsBypassPower2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 2 real power of the UPS system in watts."
|
|
::= { dupsBypass 8 }
|
|
|
|
dupsBypassVoltage3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 voltage of the UPS system in 1/10 V."
|
|
::= { dupsBypass 9 }
|
|
|
|
dupsBypassCurrent3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 current of the UPS system in 1/10 A."
|
|
::= { dupsBypass 10 }
|
|
|
|
dupsBypassPower3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line 3 real power of the UPS system in watts."
|
|
::= { dupsBypass 11 }
|
|
|
|
------------------------
|
|
-- dups Battery group --
|
|
------------------------
|
|
dupsBatteryCondiction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
good(0),
|
|
weak(1),
|
|
replace(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries when AC normal."
|
|
::= { dupsBattery 1 }
|
|
|
|
dupsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(0),
|
|
low(1),
|
|
depleted(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries when AC failed. A value of ok
|
|
indicates that the remaining run-time is greater than
|
|
upsConfigLowBattTime. A value of low indicates
|
|
that the remaining battery run-time is less than or
|
|
equal to upsConfigLowBattTime. A value of
|
|
depleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility
|
|
power is lost (including the possibility that the
|
|
utility power is currently absent and the UPS is
|
|
unable to sustain the output)."
|
|
::= { dupsBattery 2 }
|
|
|
|
dupsBatteryCharge OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
floating(0),
|
|
charging(1),
|
|
resting(2),
|
|
discharging(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsBattery 3 }
|
|
|
|
dupsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power."
|
|
::= { dupsBattery 4 }
|
|
|
|
dupsBatteryEstimatedTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "minutes"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Estimated time from backup to low battery shutdown."
|
|
::= { dupsBattery 5 }
|
|
|
|
dupsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage
|
|
in 1/10 V."
|
|
::= { dupsBattery 6 }
|
|
|
|
dupsBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present battery current in 1/10 A."
|
|
::= { dupsBattery 7 }
|
|
|
|
dupsBatteryCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "percent"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { dupsBattery 8 }
|
|
|
|
dupsTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing."
|
|
::= { dupsBattery 9 }
|
|
|
|
dupsLastReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The last battery replacement date. The format is YYYYMMDD."
|
|
::= { dupsBattery 10 }
|
|
|
|
dupsNextReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The next battery replacement date. The format is YYYYMMDD."
|
|
::= { dupsBattery 11 }
|
|
|
|
-------------------
|
|
-- dups Test group
|
|
-------------------
|
|
dupsTestType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
abort(0),
|
|
generalTest(1),
|
|
batteryTest(2),
|
|
testFor10sec(3),
|
|
testUntilBattlow(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Perform the UPS Test procedure."
|
|
::= { dupsTest 1 }
|
|
|
|
dupsTestResultsSummary OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestsInitiated(0),
|
|
donePass(1),
|
|
inProgress(2),
|
|
generalTestFail(3),
|
|
batteryTestFail(4),
|
|
deepBatteryTestFail(5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
generalTestFail(3), and batteryTestFail(4) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively.Tests which have not yet
|
|
concluded are indicated by inProgress(2). The value
|
|
noTestsInitiated(0) indicates that no previous test
|
|
results are available."
|
|
::= { dupsTest 2 }
|
|
|
|
dupsTestResultsDetail OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Additional information about upsTestResultsSummary.
|
|
If no additional information available, a zero length
|
|
string is returned."
|
|
::= { dupsTest 3 }
|
|
|
|
-----------------------
|
|
-- dups Alarm group --
|
|
-----------------------
|
|
dupsAlarmDisconnect OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS disconnect?"
|
|
::= { dupsAlarm 1 }
|
|
|
|
dupsAlarmPowerFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the input power fail?"
|
|
::= { dupsAlarm 2 }
|
|
|
|
dupsAlarmBatteryLow OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Are the UPS batteries low?"
|
|
::= { dupsAlarm 3 }
|
|
|
|
dupsAlarmLoadWarning OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load percent over the load warning value?"
|
|
::= { dupsAlarm 4 }
|
|
|
|
dupsAlarmLoadSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load percent over the load severity value?"
|
|
::= { dupsAlarm 5 }
|
|
|
|
dupsAlarmLoadOnBypass OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load on bypass?"
|
|
::= { dupsAlarm 6 }
|
|
|
|
dupsAlarmUPSFault OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS general fail?"
|
|
::= { dupsAlarm 7 }
|
|
|
|
dupsAlarmBatteryGroundFault OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS battery ground fault?"
|
|
::= { dupsAlarm 8 }
|
|
|
|
dupsAlarmTestInProgress OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS test in progress?"
|
|
::= { dupsAlarm 9 }
|
|
|
|
dupsAlarmBatteryTestFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS test fail?"
|
|
::= { dupsAlarm 10 }
|
|
|
|
dupsAlarmFuseFailure OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS fuse failure?"
|
|
::= { dupsAlarm 11 }
|
|
|
|
dupsAlarmOutputOverload OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS output overload?"
|
|
::= { dupsAlarm 12 }
|
|
|
|
dupsAlarmOutputOverCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS output overcurrent?"
|
|
::= { dupsAlarm 13 }
|
|
|
|
dupsAlarmInverterAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS inverter abnormal?"
|
|
::= { dupsAlarm 14 }
|
|
|
|
dupsAlarmRectifierAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS rectifier abnormal?"
|
|
::= { dupsAlarm 15 }
|
|
|
|
dupsAlarmReserveAbnormal OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS reserve abnormal?"
|
|
::= { dupsAlarm 16 }
|
|
|
|
dupsAlarmLoadOnReserve OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS load on reserve?"
|
|
::= { dupsAlarm 17 }
|
|
|
|
dupsAlarmOverTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS over heat?"
|
|
::= { dupsAlarm 18 }
|
|
|
|
dupsAlarmOutputBad OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Is the UPS output abnormal?"
|
|
::= { dupsAlarm 19 }
|
|
|
|
dupsAlarmBypassBad OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Is the UPS bypass bad?"
|
|
::= { dupsAlarm 20 }
|
|
|
|
dupsAlarmUPSOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Is the UPS in standby mode?"
|
|
::= { dupsAlarm 21 }
|
|
|
|
dupsAlarmChargerFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS charger fail?"
|
|
::= { dupsAlarm 22 }
|
|
|
|
dupsAlarmFanFail OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the UPS fan fail?"
|
|
::= { dupsAlarm 23 }
|
|
|
|
dupsAlarmEconomicMode OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the UPS is in the economic mode."
|
|
::= { dupsAlarm 24 }
|
|
|
|
dupsAlarmOutputOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the UPS output is turned off or not."
|
|
::= { dupsAlarm 25 }
|
|
|
|
dupsAlarmSmartShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the Smart Shutdown is in progress."
|
|
::= { dupsAlarm 26 }
|
|
|
|
dupsAlarmEmergencyPowerOff OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS emergency power off."
|
|
::= { dupsAlarm 27 }
|
|
|
|
dupsAlarmUPSShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS shutdown."
|
|
::= { dupsAlarm 28 }
|
|
|
|
-----------------------
|
|
-- dups Environment group --
|
|
-----------------------
|
|
|
|
dupsEnvTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient environmental temperature."
|
|
::= { dupsEnvironment 1 }
|
|
|
|
dupsEnvHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "percentage"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The environmental humidity."
|
|
::= { dupsEnvironment 2 }
|
|
|
|
dupsEnvSetTemperatureLimit OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees Centigrade"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverTemperature on when the environmental
|
|
temperature over the value."
|
|
::= { dupsEnvironment 3 }
|
|
|
|
dupsEnvSetHumidityLimit OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "percentage"
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverHumidity on when the environmental
|
|
humidity over the value."
|
|
::= { dupsEnvironment 4 }
|
|
|
|
dupsEnvSetEnvRelay1 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 5 }
|
|
|
|
dupsEnvSetEnvRelay2 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 6 }
|
|
|
|
dupsEnvSetEnvRelay3 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 7 }
|
|
|
|
dupsEnvSetEnvRelay4 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
normalOpen(0),
|
|
normalClose(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 8 }
|
|
|
|
dupsAlarmOverEnvTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the environment over temperature?"
|
|
::= { dupsEnvironment 9 }
|
|
|
|
dupsAlarmOverEnvHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Does the environment over humidity?"
|
|
::= { dupsEnvironment 10 }
|
|
|
|
dupsAlarmEnvRelay1 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 11 }
|
|
|
|
dupsAlarmEnvRelay2 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 12 }
|
|
|
|
dupsAlarmEnvRelay3 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 13 }
|
|
|
|
dupsAlarmEnvRelay4 OBJECT-TYPE
|
|
SYNTAX INTEGER{
|
|
off(0),
|
|
on(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
""
|
|
::= { dupsEnvironment 14 }
|
|
|
|
-----------------------
|
|
-- dups Trap group --
|
|
-----------------------
|
|
|
|
dupsCommunicationLost TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: Communication with the UPS failed."
|
|
::= 1
|
|
|
|
dupsCommunicationEstablished TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the UPS reestablished."
|
|
::= 2
|
|
|
|
dupsPowerFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: Power failed! The UPS is operating on battery power."
|
|
::= 3
|
|
|
|
dupsPowerRestored TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Power restored! The utility power restored."
|
|
::= 4
|
|
|
|
dupsLowBattery TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS batteries are low and will soon be exhausted."
|
|
::= 5
|
|
|
|
dupsReturnFromLowBattery TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a low battery condition."
|
|
::= 6
|
|
|
|
dupsLoadWarning TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Loading percent of the UPS over the Load Warning value."
|
|
::= 7
|
|
|
|
dupsNoLongerLoadWarning TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Returnd from Load Warning condition."
|
|
::= 8
|
|
|
|
dupsLoadSeverity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"Warning: Loading percent of the UPS over the Load Severity value."
|
|
::= 9
|
|
|
|
dupsNoLongerLoadSeverity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Returned from Load Severity condition."
|
|
::= 10
|
|
|
|
dupsLoadOnBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS loads on bypass."
|
|
::= 11
|
|
|
|
dupsNoLongerLoadOnBypass TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is not on bypass mode."
|
|
::= 12
|
|
|
|
dupsUPSFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: A general fault caused in the UPS."
|
|
::= 13
|
|
|
|
dupsReturnFromUPSFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is returned from general fault."
|
|
::= 14
|
|
|
|
dupsBatteryGroundFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS battery ground fault."
|
|
::= 15
|
|
|
|
dupsNoLongerBatteryFault TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from battery ground fault."
|
|
::= 16
|
|
|
|
dupsTestInProgress TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS test in progress."
|
|
::= 17
|
|
|
|
dupsBatteryTestFail TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS test fail."
|
|
::= 18
|
|
|
|
dupsFuseFailure TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS fuse failed."
|
|
::= 19
|
|
|
|
dupsFuseRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS fuse recovered."
|
|
::= 20
|
|
|
|
dupsOutputOverload TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS overload!."
|
|
::= 21
|
|
|
|
dupsNoLongerOverload TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS overload."
|
|
::= 22
|
|
|
|
dupsOutputOverCurrent TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS output overcurrent."
|
|
::= 23
|
|
|
|
dupsNoLongerOutputOverCurrent TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS overcurrent."
|
|
::= 24
|
|
|
|
dupsInverterAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS inverter abnormal."
|
|
::= 25
|
|
|
|
dupsInverterRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Recovered from UPS inverter abnormal."
|
|
::= 26
|
|
|
|
dupsRectifierAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS rectifier abnormal."
|
|
::= 27
|
|
|
|
dupsRectifierRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from rectifier abnormal."
|
|
::= 28
|
|
|
|
dupsReserveAbnormal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS rectifier abnormal."
|
|
::= 29
|
|
|
|
dupsReserveRecovered TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS rectifier abnormal."
|
|
::= 30
|
|
|
|
dupsLoadOnReserve TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: The UPS load on reserve."
|
|
::= 31
|
|
|
|
dupsNoLongerLoadOnReserve TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS no longer load on reserve."
|
|
::= 32
|
|
|
|
dupsEnvOverTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: The environment overtemperature."
|
|
::= 33
|
|
|
|
dupsNoLongerEnvOverTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment recovered from overtemperature."
|
|
::= 34
|
|
|
|
dupsEnvOverHumidity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: The environment overhumidity."
|
|
::= 35
|
|
|
|
dupsNoLongerEnvOverHumidity TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment recovered from overhumidity."
|
|
::= 36
|
|
|
|
dupsEnvRelay1Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay1 is not in normal state."
|
|
::= 37
|
|
|
|
dupsEnvRelay1Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay1 is in normal state."
|
|
::= 38
|
|
|
|
dupsEnvRelay2Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay2 is not in normal state."
|
|
::= 39
|
|
|
|
dupsEnvRelay2Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay2 is in normal state."
|
|
::= 40
|
|
|
|
dupsEnvRelay3Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay3 is not in normal state."
|
|
::= 41
|
|
|
|
dupsEnvRelay3Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay3 is in normal state."
|
|
::= 42
|
|
|
|
dupsEnvRelay4Alarm TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay4 is not in normal state."
|
|
::= 43
|
|
|
|
dupsEnvRelay4Normal TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The environment relay4 is in normal state."
|
|
::= 44
|
|
|
|
dupsSmartShutdown TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: Smart Shutdown is initiated."
|
|
::= 45
|
|
|
|
dupsCancelShutdown TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: Cancel UPS Shutdown."
|
|
::= 46
|
|
|
|
dupsTestCompleted TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent upon completion of a UPS diagnostic test."
|
|
::= 47
|
|
|
|
dupsEPOON TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when emergency power off is on."
|
|
::= 48
|
|
|
|
dupsEPOOFF TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when UPS recover from emergency power off."
|
|
::= 49
|
|
|
|
dupsOverTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"SEVER: This trap is sent when the UPS is over heat."
|
|
::= 50
|
|
|
|
dupsNormalTemperature TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: This trap is sent when UPS recover from over heat."
|
|
::= 51
|
|
|
|
dupsBattReplace TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"WARNING: The battery needs to be replaced."
|
|
::= 52
|
|
|
|
dupsReturnFromBattReplace TRAP-TYPE
|
|
ENTERPRISE dupsTraps
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS recovered from battery replacement."
|
|
::= 53
|
|
END
|