--defines ROOMALERT7E-MIB for SNMP agent extension of Room Alert 7E
--Contents: Global Registration Module
-- Room Alert OIDs - Enterprise 20916
--Version: 2.0.3
--Date: 11 September 2007
--Developed By: AVTECH Software, Inc.
--
--Copyright (c) 2007 AVTECH Software, Inc.
--
ROOMALERT7E-MIB DEFINITIONS ::= BEGIN
IMPORTS
enterprises, IpAddress, Counter, TimeTicks
FROM RFC1155-SMI
OBJECT-TYPE
FROM RFC-1212
TRAP-TYPE
FROM RFC-1215;
avtech OBJECT IDENTIFIER ::= { enterprises 20916 }
products OBJECT IDENTIFIER ::= { avtech 1 }
roomalert7e OBJECT IDENTIFIER ::= { products 2 }
sensors OBJECT IDENTIFIER ::= { roomalert7e 1 }
traps OBJECT IDENTIFIER ::= { roomalert7e 2 }
thresholds OBJECT IDENTIFIER ::= { roomalert7e 3 }
temperature OBJECT IDENTIFIER ::= { sensors 1 }
switch OBJECT IDENTIFIER ::= { sensors 2 }
-- Room Alert 7E MIB
-- Parameters
tempreading1c OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 1 (Celsius)"
::= { temperature 1 }
tempreading2c OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 2 (Celsius)"
::= { temperature 2 }
tempreading3c OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 3 (Celsius)"
::= { temperature 3 }
tempreading4c OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 4 (Celsius)"
::= { temperature 4 }
tempreading1f OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 1 (Fahrenheit)"
::= { temperature 5 }
tempreading2f OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 2 (Fahrenheit)"
::= { temperature 6 }
tempreading3f OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 3 (Fahrenheit)"
::= { temperature 7 }
tempreading4f OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Temperature Sensor 4 (Fahrenheit)"
::= { temperature 8 }
switch1 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Switch Sensor 1 (0 = OFF, 1 = ON)"
::= { switch 1 }
switch2 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Switch Sensor 2 (0 = OFF, 1 = ON)"
::= { switch 2 }
switch3 OBJECT-TYPE
SYNTAX INTEGER(0..65535)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Switch Sensor 3 (0 = OFF, 1 = ON)"
::= { switch 3 }
alarmtemp1 OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for temperature 1
0 = temperature OK
1 = temperature too high
2 = temperature too low"
::= { traps 1 }
alarmtemp2 OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for temperature 2
0 = temperature OK
1 = temperature too high
2 = temperature too low"
::= { traps 2 }
alarmtemp3 OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for temperature 3
0 = temperature OK
1 = temperature too high
2 = temperature too low"
::= { traps 3 }
alarmtemp4 OBJECT-TYPE
SYNTAX INTEGER(0..2)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for temperature 4
0 = temperature OK
1 = temperature too high
2 = temperature too low"
::= { traps 4 }
alarmswitch1 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for switch sensor 1
0 = Switch Open
1 = Switch Closed"
::= { traps 5 }
alarmswitch2 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for switch sensor 2
0 = Switch Open
1 = Switch Closed"
::= { traps 6 }
alarmswitch3 OBJECT-TYPE
SYNTAX INTEGER(0..1)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Alarm for switch sensor 3
0 = Switch Open
1 = Switch Closed"
::= { traps 7 }
alarmmessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION "Message string to send with trap messages"
::= { traps 8 }
upperlimit1 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "High temperature threshold for temperature sensor 1"
::= { thresholds 1 }
lowerlimit1 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Low temperature threshold for temperature sensor 1"
::= { thresholds 2 }
upperlimit2 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "High temperature threshold for temperature sensor 2"
::= { thresholds 3 }
lowerlimit2 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Low temperature threshold for temperature sensor 2"
::= { thresholds 4 }
upperlimit3 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "High temperature threshold for temperature sensor 3"
::= { thresholds 5 }
lowerlimit3 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Low temperature threshold for temperature sensor 3"
::= { thresholds 6 }
upperlimit4 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "High temperature threshold for temperature sensor 4"
::= { thresholds 7 }
lowerlimit4 OBJECT-TYPE
SYNTAX INTEGER(0..15000)
ACCESS read-only
STATUS mandatory
DESCRIPTION "Low temperature threshold for temperature sensor 4"
::= { thresholds 8 }
-- ROOMALERT7E TRAPS
alarmstart1-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, tempreading1c, tempreading1f }
DESCRIPTION "A alarmstart1 trap signifies that the current
temperature on sensor 1 is outside the
defined high or low threshold."
::= 1
room-alert-7e-snmp-trap TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage }
DESCRIPTION "A room-alert-7e-snmp-trap indicates that an alarm
condition has occurred on the sensor inidcated
by the alarmmessage variable."
::= 2
alarmstart2-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, tempreading2c, tempreading2f }
DESCRIPTION "A alarmstart2 trap signifies that the current
temperature on sensor 2 is outside the
defined high or low threshold."
::= 3
alarmclear2-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, tempreading2c, tempreading2f }
DESCRIPTION "A alarmclear2 trap signifies that the current
temperature on sensor 2 has returned to a
normal condition and is within the defined
high or low threshold."
::= 4
alarmstart3-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, tempreading3c, tempreading3f }
DESCRIPTION "A alarmstart3 trap signifies that the current
temperature on sensor 3 is outside the
defined high or low threshold."
::= 5
alarmclear3-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, tempreading3c, tempreading3f }
DESCRIPTION "A alarmclear3 trap signifies that the current
temperature on sensor 3 has returned to a
normal condition and is within the defined
high or low threshold."
::= 6
alarmstart4-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, tempreading4c, tempreading4f }
DESCRIPTION "A alarmstart4 trap signifies that the current
temperature on sensor 4 is outside the
defined high or low threshold."
::= 7
alarmclear4-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, tempreading4c, tempreading4f }
DESCRIPTION "A alarmclear4 trap signifies that the current
temperature on sensor 4 has returned to a
normal condition and is within the defined
high or low threshold."
::= 8
alarmstart5-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, switch1, switch1 }
DESCRIPTION "A alarmstart5 trap signifies that the current
status of switch sensor 1 is outside the
defined threshold."
::= 9
alarmclear5-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, switch1, switch1 }
DESCRIPTION "A alarmclear5 trap signifies that the current
status of switch sensor 1 is outside the
defined threshold."
::= 10
alarmstart6-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, switch2, switch2 }
DESCRIPTION "A alarmstart6 trap signifies that the current
status of switch sensor 2 is outside the
defined threshold."
::= 11
alarmclear6-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, switch2, switch2 }
DESCRIPTION "A alarmclear6 trap signifies that the current
status of switch sensor 2 is outside the
defined threshold."
::= 12
alarmstart7-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, switch3, switch3 }
DESCRIPTION "A alarmstart7 trap signifies that the current
status of switch sensor 3 is outside the
defined threshold."
::= 13
alarmclear7-7e TRAP-TYPE
ENTERPRISE roomalert7e
VARIABLES { alarmmessage, switch3, switch3 }
DESCRIPTION "A alarmclear7 trap signifies that the current
status of switch sensor 3 is outside the
defined threshold."
::= 14
END