678 lines
40 KiB
YAML
678 lines
40 KiB
YAML
mib: SP2-MIB
|
|
modules:
|
|
os:
|
|
hardware:
|
|
- SP2-MIB::controlUnitDescription.1
|
|
- SP2-MIB::controlUnitDescription.2
|
|
version:
|
|
- SP2-MIB::controlUnitSwVersion.1
|
|
- SP2-MIB::controlUnitSwVersion.2
|
|
serial: SP2-MIB::powerSystemSerialNumber.0
|
|
location: SP2-MIB::powerSystemSite.0
|
|
features:
|
|
- SP2-MIB::powerSystemType.0
|
|
- SP2-MIB::powerSystemModel.0
|
|
- SP2-MIB::batteryDescription.0
|
|
features_template: 'Rectifier type: {{ SP2-MIB::powerSystemType.0 }}, Rectifier model: {{ SP2-MIB::powerSystemModel.0 }}, Battery: {{ SP2-MIB::batteryDescription.0 }}'
|
|
sensors:
|
|
state:
|
|
data:
|
|
-
|
|
oid: SP2-MIB::powerSystem
|
|
value: SP2-MIB::powerSystemStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.2.1.{{ $index }}'
|
|
descr: System Status
|
|
entPhysicalIndex: '10'
|
|
state_name: powerSystemStatus
|
|
group: System
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::mains
|
|
value: SP2-MIB::mainsStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.3.1.{{ $index }}'
|
|
descr: Mains Status
|
|
entPhysicalIndex: '10'
|
|
state_name: mainsStatus
|
|
group: System
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
|
|
-
|
|
oid: SP2-MIB::mainsMainsFailure
|
|
value: SP2-MIB::mainsMainsFailureStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.3.2.1.{{ $index }}'
|
|
descr: SP2-MIB::mainsMainsFailureDescription
|
|
state_name: mainsMainsFailureStatus
|
|
group: System
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::rectifierTable
|
|
value: SP2-MIB::rectifierStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.6.1.2.{{ $index }}'
|
|
descr: '{{ SP2-MIB::rectifierType }} {{ $index }} Status'
|
|
entPhysicalIndex: '2{{ $index }}'
|
|
state_name: rectifierStatus
|
|
index: 'rectifierStatus.{{ $index }}'
|
|
group: Rectifier
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::rectifiers
|
|
value: SP2-MIB::rectifiersStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.1.{{ $index }}'
|
|
descr: Overall Rectifier Status
|
|
entPhysicalIndex: '10'
|
|
state_name: rectifiersStatus
|
|
group: Rectifier
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
|
|
-
|
|
oid: SP2-MIB::load
|
|
value: SP2-MIB::loadFusesStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.9.3.{{ $index }}'
|
|
descr: Overall Load Fuses Status
|
|
entPhysicalIndex: '10'
|
|
state_name: loadFusesStatus
|
|
group: Load Fuse
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
-
|
|
oid: SP2-MIB::loadFuseTable
|
|
value: SP2-MIB::loadFuseStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.9.7.1.1.{{ $index }}'
|
|
descr: SP2-MIB::loadFuseDescription
|
|
entPhysicalIndex: '4{{ $index }}'
|
|
state_name: loadFuseStatus
|
|
group: Load Fuse
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::battery
|
|
value: SP2-MIB::batteryStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.1.{{ $index }}'
|
|
descr: Overall Battery Status
|
|
entPhysicalIndex: '10'
|
|
state_name: batteryStatus
|
|
group: Battery
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
-
|
|
oid: SP2-MIB::batteryBankTable
|
|
value: SP2-MIB::batteryBankStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.18.2.1.2.{{ $index }}'
|
|
descr: Battery Bank {{ $index }} Status
|
|
entPhysicalIndex: '3{{ $index }}'
|
|
state_name: batteryBankStatus
|
|
group: Battery
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::batteryBankFuseTable
|
|
value: SP2-MIB::batteryFuseStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.18.5.1.2.{{ $index }}'
|
|
descr: SP2-MIB::batteryFuseDescription
|
|
state_name: batteryFuseStatus
|
|
group: Battery
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::inputControlUnitInputTable
|
|
value: SP2-MIB::inputControlUnitInputStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.11.2.1.2.{{ $index }}'
|
|
descr: 'Input {{ SP2-MIB::inputControlUnitInputDescription }}'
|
|
state_name: inputStatus
|
|
group: Alarm Input
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::outputControlUnitOutputTable
|
|
value: SP2-MIB::outputControlUnitOutputStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.12.2.1.2.{{ $index }}'
|
|
descr: 'Output {{ SP2-MIB::outputControlUnitOutputDescription }}'
|
|
state_name: outputStatus
|
|
group: Alarm Output
|
|
states:
|
|
- { descr: notenergized, graph: 0, value: 0, generic: 3 }
|
|
- { descr: energized, graph: 0, value: 1, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 2, generic: 3 }
|
|
- { descr: connected, graph: 0, value: 3, generic: 3 }
|
|
skip_values: 4
|
|
-
|
|
oid: SP2-MIB::powerSystem
|
|
value: SP2-MIB::powerSystemMode
|
|
num_oid: '.1.3.6.1.4.1.12148.10.2.3.{{ $index }}'
|
|
descr: System Mode
|
|
state_name: powerSystemMode
|
|
group: System
|
|
states:
|
|
- { descr: off, graph: 0, value: 0, generic: 0 }
|
|
- { descr: test, graph: 0, value: 1, generic: 0 }
|
|
- { descr: boost, graph: 0, value: 2, generic: 0 }
|
|
- { descr: float, graph: 0, value: 3, generic: 0 }
|
|
-
|
|
oid: SP2-MIB::inputIoUnitProgInputTable
|
|
value: SP2-MIB::inputIoUnitProgInputStatus
|
|
num_oid: '.1.3.6.1.4.1.12148.10.11.4.1.2.{{ $index }}'
|
|
descr: 'IO Input {{ SP2-MIB::inputIoUnitProgInputDescription }}'
|
|
state_name: ioInputStatus
|
|
group: IO Alarm Input
|
|
states:
|
|
- { descr: error, graph: 0, value: 0, generic: 2 }
|
|
- { descr: normal, graph: 0, value: 1, generic: 0 }
|
|
- { descr: minorAlarm, graph: 0, value: 2, generic: 1 }
|
|
- { descr: majorAlarm, graph: 0, value: 3, generic: 2 }
|
|
- { descr: disabled, graph: 0, value: 4, generic: 3 }
|
|
- { descr: disconnected, graph: 0, value: 5, generic: 3 }
|
|
- { descr: notPresent, graph: 0, value: 6, generic: 3 }
|
|
- { descr: minorAndMajor, graph: 0, value: 7, generic: 2 }
|
|
- { descr: majorLow, graph: 0, value: 8, generic: 2 }
|
|
- { descr: minorLow, graph: 0, value: 9, generic: 1 }
|
|
- { descr: majorHigh, graph: 0, value: 10, generic: 2 }
|
|
- { descr: minorHigh, graph: 0, value: 11, generic: 1 }
|
|
- { descr: event, graph: 0, value: 12, generic: 1 }
|
|
- { descr: valueVolt, graph: 0, value: 13, generic: 1 }
|
|
- { descr: valueAmp, graph: 0, value: 14, generic: 1 }
|
|
- { descr: valueTemp, graph: 0, value: 15, generic: 1 }
|
|
- { descr: valueUnit, graph: 0, value: 16, generic: 1 }
|
|
- { descr: valuePerCent, graph: 0, value: 17, generic: 1 }
|
|
- { descr: critical, graph: 0, value: 18, generic: 2 }
|
|
- { descr: warning, graph: 0, value: 19, generic: 1 }
|
|
skip_values: 4
|
|
|
|
voltage:
|
|
data:
|
|
-
|
|
oid: SP2-MIB::mainsVoltageTable
|
|
value: SP2-MIB::mainsVoltageValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.3.4.1.6.{{ $index }}'
|
|
descr: SP2-MIB::mainsVoltageDescription
|
|
index: 'mains.{{ $index }}'
|
|
group: Mains
|
|
low_limit: SP2-MIB::mainsVoltageMajorLowLevel
|
|
low_warn_limit: SP2-MIB::mainsVoltageMinorLowLevel
|
|
warn_limit: SP2-MIB::mainsVoltageMinorHighLevel
|
|
high_limit: SP2-MIB::mainsVoltageMajorHighLevel
|
|
-
|
|
oid: SP2-MIB::rectifierTable
|
|
value: SP2-MIB::rectifierInputVoltageValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.6.1.4.{{ $index }}'
|
|
descr: '{{ SP2-MIB::rectifierType }} {{ $index }} Input Voltage'
|
|
index: 'input.{{ $index }}'
|
|
entPhysicalIndex: '2{{ $index }}'
|
|
group: Rectifier
|
|
low_limit: 80
|
|
low_warn_limit: 100
|
|
warn_limit: 260
|
|
high_limit: 280
|
|
-
|
|
oid: SP2-MIB::batteryVoltage
|
|
value: SP2-MIB::batteryVoltageValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.5.5.{{ $index }}'
|
|
descr: SP2-MIB::batteryVoltageDescription
|
|
index: 'battery.{{ $index }}'
|
|
entPhysicalIndex: '100'
|
|
group: Battery
|
|
divisor: 100
|
|
low_limit: SP2-MIB::batteryVoltageMajorLowLevel
|
|
low_warn_limit: SP2-MIB::batteryVoltageMinorLowLevel
|
|
warn_limit: SP2-MIB::batteryVoltageMinorHighLevel
|
|
high_limit: SP2-MIB::batteryVoltageMajorHighLevel
|
|
-
|
|
oid: SP2-MIB::batteryBankSymmetryTable
|
|
value: SP2-MIB::batteryBankSymmetryMeasureValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.18.6.1.6.{{ $index }}'
|
|
descr: SP2-MIB::batteryBankSymmetryDescription
|
|
index: 'batteryBankSymmetry.{{ $index }}'
|
|
entPhysicalIndex: '3{{ $index }}'
|
|
group: Battery
|
|
divisor: 100
|
|
warn_limit: SP2-MIB::batteryBankSymmetryMinorAlarmLevel
|
|
high_limit: SP2-MIB::batteryBankSymmetryMajorAlarmLevel
|
|
skip_values:
|
|
-
|
|
oid: SP2-MIB::batteryBankSymmetryStatus
|
|
op: '='
|
|
value: 4
|
|
-
|
|
oid: SP2-MIB::batteryMonitorSymmetryTable
|
|
value: SP2-MIB::batteryMonitorSymmetryDeltaValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.19.6.1.7.{{ $index }}'
|
|
descr: SP2-MIB::batteryMonitorSymmetryDescription
|
|
index: 'batteryMonitorSymmetry.{{ $index }}'
|
|
group: Battery
|
|
divisor: 100
|
|
warn_limit: SP2-MIB::batteryMonitorSymmetryMinorAlarmLevel
|
|
high_limit: SP2-MIB::batteryMonitorSymmetryMajorAlarmLevel
|
|
skip_values:
|
|
-
|
|
oid: SP2-MIB::batteryMonitorSymmetryStatus
|
|
op: '='
|
|
value: 4
|
|
current:
|
|
data:
|
|
-
|
|
oid: SP2-MIB::rectifiersCurrent
|
|
value: SP2-MIB::rectifiersCurrentValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.2.5.{{ $index }}'
|
|
descr: Rectifier Output Current
|
|
index: 'current.{{ $index }}'
|
|
group: Rectifier
|
|
warn_limit: SP2-MIB::rectifiersCurrentMinorAlarmLevel
|
|
high_limit: SP2-MIB::rectifiersCurrentMajorAlarmLevel
|
|
skip_values:
|
|
-
|
|
device: hardware
|
|
op: 'regex'
|
|
value: '/^Smart[Pp]ack S.*/'
|
|
- # Smartpack S returns 10ths of an amp
|
|
oid: SP2-MIB::rectifiersCurrent
|
|
value: SP2-MIB::rectifiersCurrentValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.2.5.{{ $index }}'
|
|
descr: System Output Current
|
|
index: 'current.{{ $index }}'
|
|
group: Rectifier
|
|
divisor: 10
|
|
warn_limit: SP2-MIB::rectifiersCurrentMinorAlarmLevel
|
|
high_limit: SP2-MIB::rectifiersCurrentMajorAlarmLevel
|
|
skip_values:
|
|
- device: hardware
|
|
op: 'not_regex'
|
|
value: '/^Smart[Pp]ack S.*/'
|
|
-
|
|
oid: SP2-MIB::rectifierTable
|
|
value: SP2-MIB::rectifierOutputCurrentValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.6.1.3.{{ $index }}'
|
|
descr: '{{ SP2-MIB::rectifierType }} {{ $index }} Output Current'
|
|
index: 'output.{{ $index }}'
|
|
entPhysicalIndex: '2{{ $index }}'
|
|
group: Rectifier
|
|
divisor: 10
|
|
-
|
|
oid: SP2-MIB::batteryCurrents
|
|
value: SP2-MIB::batteryCurrentsValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.6.5.{{ $index }}'
|
|
descr: Overall Battery Current
|
|
index: 'batteryCurrent.{{ $index }}'
|
|
entPhysicalIndex: '100'
|
|
group: Battery
|
|
divisor: 10
|
|
low_limit: SP2-MIB::batteryCurrentsMinorLowLevel
|
|
low_warn_limit: SP2-MIB::batteryCurrentsMinorLowLevel
|
|
warn_limit: SP2-MIB::batteryCurrentsMinorHighLevel
|
|
high_limit: SP2-MIB::batteryCurrentsMajorHighLevel
|
|
-
|
|
oid: SP2-MIB::batteryBankCurrentTable
|
|
value: SP2-MIB::batteryCurrentValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.18.4.1.6.{{ $index }}'
|
|
descr: batteryCurrentDescription
|
|
index: 'batteryBankCurrent.{{ $index }}'
|
|
entPhysicalIndex: '3{{ $index }}'
|
|
group: Battery
|
|
divisor: 10
|
|
low_limit: SP2-MIB::batteryCurrentMinorLowLevel
|
|
low_warn_limit: SP2-MIB::batteryCurrentMinorLowLevel
|
|
warn_limit: SP2-MIB::batteryCurrentMinorHighLevel
|
|
high_limit: SP2-MIB::batteryCurrentMajorHighLevel
|
|
-
|
|
oid: SP2-MIB::loadCurrent
|
|
value: SP2-MIB::loadCurrentValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.9.2.5.{{ $index }}'
|
|
descr: SP2-MIB::loadCurrentDescription
|
|
entPhysicalIndex: '10'
|
|
index: 'load.{{ $index }}'
|
|
group: Load
|
|
divisor: 10
|
|
warn_limit: SP2-MIB::loadCurrentMinorHighLevel
|
|
high_limit: SP2-MIB::loadCurrentMajorHighLevel
|
|
temperature:
|
|
data:
|
|
-
|
|
oid: SP2-MIB::batteryTemperatures
|
|
value: SP2-MIB::batteryTemperaturesValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.7.5.{{ $index }}'
|
|
descr: Overall Battery Temperature
|
|
entPhysicalIndex: '100'
|
|
index: 'batteryTemperature.{{ $index }}'
|
|
low_limit: SP2-MIB::batteryTemperaturesMinorLowLevel
|
|
low_warn_limit: SP2-MIB::batteryTemperaturesMinorLowLevel
|
|
warn_limit: SP2-MIB::batteryTemperaturesMinorHighLevel
|
|
high_limit: SP2-MIB::batteryTemperaturesMajorHighLevel
|
|
-
|
|
oid: SP2-MIB::batteryBankTemperatureTable
|
|
value: SP2-MIB::batteryTemperatureValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.18.3.1.6.{{ $index }}'
|
|
descr: SP2-MIB::batteryTemperatureDescription
|
|
entPhysicalIndex: '3{{ $index }}'
|
|
index: 'batteryBankTemperature.{{ $index }}'
|
|
low_limit: SP2-MIB::batteryTemperatureMinorLowLevel
|
|
low_warn_limit: SP2-MIB::batteryTemperatureMinorLowLevel
|
|
warn_limit: SP2-MIB::batteryTemperatureMinorHighLevel
|
|
high_limit: SP2-MIB::batteryTemperatureMajorHighLevel
|
|
skip_values:
|
|
-
|
|
oid: SP2-MIB::batteryTemperatureStatus
|
|
op: '='
|
|
value: 4
|
|
-
|
|
oid: SP2-MIB::ambientTemperature
|
|
value: SP2-MIB::ambientTemperatureValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.13.13.5.{{ $index }}'
|
|
descr: SP2-MIB::ambientTemperatureDescription
|
|
entPhysicalIndex: '10'
|
|
index: 'ambientTemperature.{{ $index }}'
|
|
low_limit: SP2-MIB::ambientTemperatureMinorLowLevel
|
|
low_warn_limit: SP2-MIB::ambientTemperatureMinorLowLevel
|
|
warn_limit: SP2-MIB::ambientTemperatureMinorHighLevel
|
|
high_limit: SP2-MIB::ambientTemperatureMajorHighLevel
|
|
skip_values:
|
|
-
|
|
oid: SP2-MIB::ambientTemperatureStatus
|
|
op: '='
|
|
value: 4
|
|
runtime:
|
|
data:
|
|
-
|
|
oid: SP2-MIB::batteryTimeLeft
|
|
value: SP2-MIB::batteryTimeLeftValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.8.5.{{ $index }}'
|
|
descr: SP2-MIB::batteryTimeLeftDescription
|
|
entPhysicalIndex: '100'
|
|
low_warn_limit: SP2-MIB::batteryTimeLeftMinorAlarmLevel
|
|
low_limit: SP2-MIB::batteryTimeLeftMajorAlarmLevel
|
|
load:
|
|
data:
|
|
-
|
|
oid: SP2-MIB::batteryRemainingCapacity
|
|
value: SP2-MIB::batteryRemainingCapacityValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.9.5.{{ $index }}'
|
|
descr: SP2-MIB::batteryRemainingCapacityDescription
|
|
entPhysicalIndex: '100'
|
|
low_warn_limit: SP2-MIB::batteryRemainingCapacityMinorLowLevel
|
|
low_limit: SP2-MIB::batteryRemainingCapacityMajorLowLevel
|
|
index: 'batteryRemainingCapacity.{{ $index }}'
|
|
-
|
|
oid: SP2-MIB::rectifiersCapacity
|
|
value: SP2-MIB::rectifiersCapacityValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.3.5.{{ $index }}'
|
|
descr: SP2-MIB::rectifiersCapacityDescription
|
|
warn_limit: SP2-MIB::rectifiersCapacityMinorAlarmLevel
|
|
high_limit: SP2-MIB::rectifiersCapacityMajorAlarmLevel
|
|
index: 'rectifiersCapacity.{{ $index }}'
|
|
-
|
|
oid: SP2-MIB::batteryQuality
|
|
value: SP2-MIB::batteryQualityValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.12.5.{{ $index }}'
|
|
descr: SP2-MIB::batteryQualityDescription
|
|
entPhysicalIndex: '100'
|
|
low_warn_limit: SP2-MIB::batteryQualityMinorAlarmLevel
|
|
low_limit: SP2-MIB::batteryQualityMajorAlarmLevel
|
|
index: 'batteryQuality.{{ $index }}'
|
|
-
|
|
oid: SP2-MIB::batteryUsedCapacity
|
|
value: SP2-MIB::batteryUsedCapacityValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.10.5.{{ $index }}'
|
|
descr: SP2-MIB::batteryUsedCapacityDescription
|
|
entPhysicalIndex: '100'
|
|
warn_limit: SP2-MIB::batteryUsedCapacityMinorAlarmLevel
|
|
high_limit: SP2-MIB::batteryUsedCapacityMajorAlarmLevel
|
|
index: 'batteryUsedCapacity.{{ $index }}'
|
|
count:
|
|
data:
|
|
-
|
|
oid: SP2-MIB::batteryAhCharged
|
|
value: SP2-MIB::batteryAhChargedValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.23.5.{{ $index }}'
|
|
descr: SP2-MIB::batteryAhChargedDescription
|
|
entPhysicalIndex: '100'
|
|
divisor: 100
|
|
index: 'batteryAhCharged.{{ $index }}'
|
|
warn_limit: SP2-MIB::batteryAhChargedMinorHighLevel
|
|
high_limit: SP2-MIB::batteryAhChargedMajorHighLevel
|
|
-
|
|
oid: SP2-MIB::batteryTotalCapacity
|
|
value: SP2-MIB::batteryTotalCapacityValue
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.11.5.{{ $index }}'
|
|
descr: SP2-MIB::batteryTotalCapacityDescription
|
|
entPhysicalIndex: '100'
|
|
index: 'batteryTotalCapacity.{{ $index }}'
|
|
low_warn_limit: SP2-MIB::batteryTotalCapacityMinorLowLevel
|
|
low_limit: SP2-MIB::batteryTotalCapacityMajorLowLevel
|
|
-
|
|
oid: SP2-MIB::batteryBankNumberOfBanks
|
|
index: 'batteryBankNumberOfBanks.0'
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.18.1.{{ $index }}'
|
|
descr: Battery bank number of banks
|
|
-
|
|
oid: SP2-MIB::mainsNumberOfPhases
|
|
index: 'mainsNumberOfPhases.0'
|
|
num_oid: '.1.3.6.1.4.1.12148.10.3.3.{{ $index }}'
|
|
descr: Mains number of phases
|
|
-
|
|
oid: SP2-MIB::rectifiersNumberOfRectifiers
|
|
index: 'rectifiersNumberOfRectifiers.0'
|
|
num_oid: '.1.3.6.1.4.1.12148.10.5.5.{{ $index }}'
|
|
descr: Rectifiers number of rectifiers
|
|
-
|
|
oid: SP2-MIB::batteryTestNumberOfResults
|
|
index: 'batteryTestNumberOfResults.0'
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.16.3.{{ $index }}'
|
|
descr: Battery test number of results
|
|
-
|
|
oid: SP2-MIB::batteryTest.5.0
|
|
value: SP2-MIB::batteryTest
|
|
index: 'batteryTest.{{ $index }}'
|
|
num_oid: '.1.3.6.1.4.1.12148.10.10.16.5.{{ $index }}'
|
|
descr: Battery Test Max Duration (minutes)
|