modules:
os:
version: SITE-MONITORING-MIB::siteV1DescControllerSoftwareRevision.0
sensors:
voltage:
data:
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataDCBusBusVoltage
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.11.{{ $index }}'
descr: 'DC Bus #{{ $index }} Voltage'
charge:
data:
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataBatBatChargeCapacity
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.91.{{ $index }}'
descr: 'Battery #{{ $index }} Charge'
runtime:
data:
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataBatCalculatedAutonomy
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.92.{{ $index }}'
descr: 'Runtime'
temperature:
data:
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataBatBatTemp
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.71.{{ $index }}'
descr: 'Battery #{{ $index }} Temperature'
current:
data:
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataRectifiersRectifiersOutCurrent
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.22.{{ $index }}'
index: 'es1dc1DataRectifiersRectifiersOutCurrent.{{ $index }}'
descr: 'Output #{{ $index }} Current'
high_limit: SITE-MONITORING-MIB::es1dc1DataRectifiersRectifiersOutCurrentMax
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataLoadLoadCurrent
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.52.{{ $index }}'
index: 'es1dc1DataLoadLoadCurrent.{{ $index }}'
descr: 'Load #{{ $index }} Current'
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataBatBatInputCurrent
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.61.{{ $index }}'
index: 'es1dc1DataBatBatInputCurrent.{{ $index }}'
descr: 'Battery #{{ $index }} Input Current'
state:
data:
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataBatBatTestState
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.72.{{ $index }}'
descr: 'Battery #{{ $index }} Test Status'
state_name: 'es1dc1DataBatBatTestState'
index: 'es1dc1DataBatBatTestState.{{ $index }}'
states:
- { value: 0, descr: 'Never Tested', graph: 0, generic: 0 }
- { value: 1, descr: 'Success', graph: 0, generic: 0 }
- { value: 2, descr: 'On Going', graph: 0, generic: 1 }
- { value: 3, descr: 'Failed: Timeout', graph: 0, generic: 1 }
- { value: 4, descr: 'Failed: Vbus Too Low', graph: 0, generic: 1 }
- { value: 5, descr: 'Failed: Load Too Low', graph: 0, generic: 1 }
- { value: 6, descr: 'Failed: AC Failure', graph: 0, generic: 2 }
- { value: 7, descr: 'Failed: Canceled', graph: 0, generic: 1 }
- { value: 8, descr: 'Failed: LVD Opened', graph: 0, generic: 1 }
- { value: 9, descr: 'Failed: No Battery', graph: 0, generic: 1 }
-
oid: SITE-MONITORING-MIB::es1dc1DataList
value: SITE-MONITORING-MIB::es1dc1DataSystemDCMode
num_oid: '.1.3.6.1.4.1.26854.3.2.1.20.1.20.1.13.3.1.{{ $index }}'
descr: 'System DC #{{ $index }} Mode'
state_name: 'es1dc1DataSystemDCMode'
index: 'es1dc1DataSystemDCMode.{{ $index }}'
states:
- { value: 0, descr: 'Float', graph: 0, generic: 0 }
- { value: 1, descr: 'Equalize', graph: 0, generic: 0 }
- { value: 2, descr: 'Battery Test', graph: 0, generic: 1 }
- { value: 3, descr: 'AC Failure', graph: 0, generic: 2 }
- { value: 5, descr: 'Safe', graph: 0, generic: 0 }