WebGraph-Thermometer-MIB DEFINITIONS ::= BEGIN
----------------------------------------------------------------
-- Revison: 1.26
----------------------------------------------------------------
-- 28.06.2006 New: Community String Trap
--
----------------------------------------------------------------
-- Revison: 1.25
----------------------------------------------------------------
-- 22.05.2006 Table Entry Namen korrigiert
--
----------------------------------------------------------------
-- Revison: 1.24
----------------------------------------------------------------
-- 26.07.2005 #57605, WebGraph Thermometer
-- CRON Zeitfunktion
----------------------------------------------------------------
-- Revison: 1.23
----------------------------------------------------------------
-- 14.07.2005 #57605, WebGraph Thermometer
-- FTP Funktionen
----------------------------------------------------------------
-- Revison: 1.22
----------------------------------------------------------------
-- 02.06.2005 #57605, WebGraph Thermometer
-- Trap NMS annotations
----------------------------------------------------------------
-- Revison: 1.21
----------------------------------------------------------------
-- 19.04.2005 #57605, WebGraph Themometer
-- Mail Authentication
----------------------------------------------------------------
-- Revison: 1.20
----------------------------------------------------------------
-- 05.11.2004 #57605, WebGraph Themometer
-- Neu: Syslog
--
----------------------------------------------------------------
-- Revison: 1.19
----------------------------------------------------------------
-- 27.09.2004 #57601/3/4, Webio Digital
-- Neu:
-- Eintrag AlarmHysteresis korigiert
----------------------------------------------------------------
-- Revison: 1.18
----------------------------------------------------------------
-- 21.07.2004 #57601/3/4, Webio Digital
-- Neu:
-- Diagnosis
----------------------------------------------------------------
-- Revison: 1.17
----------------------------------------------------------------
-- 28.06.2004 #57630/1/2, Webio Digital
-- Neu: Puls Mode
----------------------------------------------------------------
-- Revison: 1.16
----------------------------------------------------------------
-- 16.04.2004 neu: #57632, Webio Digital EA24x24
--
-- #57630/1, Webio Digital EA12x12
-- Neu:
-- wtWebioAn1GraphInputCounterClear
----------------------------------------------------------------
-- Revison: 1.15
----------------------------------------------------------------
-- 27.02.2004 #57630/1, Webio Digital EA12x12
-- Neu:
-- Länge erweitert auf 32 Bit:
-- wtWebioEA12x12InputValue
-- wtWebioEA12x12OutputValue
-- wtWebioEA12x12LoadControlView
-- wtWebioEA12x12LCShutDownView
-- wtWebioEA12x12SetOutput
-- wtWebioEA12x12AlarmInputTrigger
-- wtWebioEA12x12AlarmOutputTrigger
-- wtWebioEA12x12PortOutputSafetyState
----------------------------------------------------------------
-- Revison: 1.14
----------------------------------------------------------------
-- 16.02.2004 #57630/1, Webio Digital EA12x12
-- Neu:
-- Texte: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
--
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- Neu:
-- Alarm Hysterese
-- Alarm Clear Traps und Mails
----------------------------------------------------------------
-- Revison: 1.13
----------------------------------------------------------------
-- 05.02.2004 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- Neu:
-- Texte: Location, Contact
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
-- Alarm: ColdStart / WarmStart trigger
----------------------------------------------------------------
-- Revison: 1.12
----------------------------------------------------------------
-- 05.11.2003 #57601, 1xWebThermometer
-- #57603, 2xWebThermometer
-- #57604, 8xWebThermometer
-- Neu:
-- Mail Option: CSV attachment
-- Offsetkalibrierung
-- Alarm: Tcp Client mode
----------------------------------------------------------------
-- Revison: 1.11
----------------------------------------------------------------
-- 28.10.2003 #57630/1, Webio Digital EA12x12
-- Neue Feature:
-- Alarm : TCP Client mode
-- INPUTS: Pulsfilter
----------------------------------------------------------------
-- Revison: 1.10
----------------------------------------------------------------
-- 04.07.2003 #57630, Webio Digital EA12x12
-- Neuer Menübaum, neue Binärmodi
--
----------------------------------------------------------------
-- Revison: 1.09
----------------------------------------------------------------
-- 24.03.2003 Trap Enterprise (Type 1, 2) korrigiert
--
----------------------------------------------------------------
-- Revison: 1.08
----------------------------------------------------------------
-- 04.03.2003 Abgleich der Sprachversionen DE/US
--
----------------------------------------------------------------
-- Revison: 1.07
----------------------------------------------------------------
-- 25.02.2003 Korrektur US: wtWebioEA12x12LoadControl
----------------------------------------------------------------
-- Revison: 1.06
----------------------------------------------------------------
-- 24.02.2003 Neu:
-- #57630, Webio EA12x12, LoadControl Group
-- Korrektur: Trap variable Namen
----------------------------------------------------------------
-- Revison: 1.05
----------------------------------------------------------------
-- 21.01.2003 Neu:
-- #57630, Webio EA12x12
----------------------------------------------------------------
-- Revison: 1.04
----------------------------------------------------------------
-- 02.01.2003 Neu:
-- #57601, 1xWebThermometer
-- #57603, 2xWebThermometer, 8 Alarme
----------------------------------------------------------------
-- Revison: 1.03
----------------------------------------------------------------
-- 21.11.2002 Neu:
-- #57604, 2xWebThermometer, BOOTP, StartupSite
-- #57603, 8xWebThermometer, BOOTP, StartupSite
----------------------------------------------------------------
-- Revison: 1.02
----------------------------------------------------------------
-- 26.07.2002 Neu:
-- #57604, 2xWebThermometer
-- #57603, 8xWebThermometer
--
IMPORTS
OBJECT-TYPE FROM RFC-1212
TRAP-TYPE FROM RFC-1215
DisplayString, PhysAddress FROM RFC1213-MIB
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
-- IpAddress ::=
-- [APPLICATION 0]
-- IMPLICIT OCTET STRING (SIZE (4))
-- Counter ::=
-- [APPLICATION 1]
-- IMPLICIT INTEGER (0..4294967295)
-- Gauge ::=
-- [APPLICATION 2]
-- IMPLICIT INTEGER (0..4294967295)
-- TimeTicks ::=
-- [APPLICATION 3]
-- IMPLICIT INTEGER (0..4294967295)
-- DisplayString ::= OCTET STRING
-- PhysAddress ::= OCTET STRING
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
-- privat OBJECT IDENTIFIER ::= { internet 4 }
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
-- Wiesemann & Theis Com-Server MIB
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
-- wtWebio Tree
wtWebioAn1Graph OBJECT IDENTIFIER ::= { wtWebio 8 }
-- wtWebioAn1Graph Tree
wtWebioAn1GraphTemp OBJECT IDENTIFIER ::= { wtWebioAn1Graph 1 }
wtWebioAn1GraphSessCntrl OBJECT IDENTIFIER ::= { wtWebioAn1Graph 2 }
wtWebioAn1GraphConfig OBJECT IDENTIFIER ::= { wtWebioAn1Graph 3 }
wtWebioAn1GraphDiag OBJECT IDENTIFIER ::= { wtWebioAn1Graph 4 }
-- wtWebioAn1GraphConfig Tree
wtWebioAn1GraphDevice OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 1 }
wtWebioAn1GraphPorts OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 2 }
wtWebioAn1GraphManufact OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 3 }
-- wtWebioAn1GraphDevice Tree
wtWebioAn1GraphText OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 1 }
wtWebioAn1GraphTimeDate OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 2 }
wtWebioAn1GraphBasic OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 3 }
wtWebioAn1GraphDatalogger OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 4 }
wtWebioAn1GraphAlarm OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 5 }
-- wtWebioAn1GraphTimeDate Tree
wtWebioAn1GraphTimeZone OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 1 }
wtWebioAn1GraphTimeServer OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 2 }
wtWebioAn1GraphDeviceClock OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 3 }
-- wtWebioAn1GraphBasic Tree
wtWebioAn1GraphNetwork OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 1 }
wtWebioAn1GraphHTTP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 2 }
wtWebioAn1GraphMail OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 3 }
wtWebioAn1GraphSNMP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 4 }
wtWebioAn1GraphUDP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 5 }
wtWebioAn1GraphSyslog OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 6 }
wtWebioAn1GraphFTP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 7 }
-- wtWebioAn1GraphTemp Group
------------------------
wtWebioAn1GraphSensors OBJECT-TYPE
SYNTAX INTEGER (1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Anzahl der Temperatursensoren"
::= { wtWebioAn1GraphTemp 1 }
-- Interface Table
wtWebioAn1GraphSensorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Liste der Sensoren."
::= { wtWebioAn1GraphTemp 2 }
wtWebioAn1GraphSensorEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphSensorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Nummern der Temperatursensoren."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphSensorTable 1 }
WtWebioAn1GraphSensorEntry ::= SEQUENCE {
wtWebioAn1GraphSensorNo INTEGER
}
wtWebioAn1GraphSensorNo OBJECT-TYPE
SYNTAX INTEGER (1)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Nummer des Temperatursensors."
::= { wtWebioAn1GraphSensorEntry 1 }
-- wtWebioAn1GraphTempValue Table
wtWebioAn1GraphTempValueTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Liste Temperaturwerte korrespondiernd zu den Kanalnummern."
::= { wtWebioAn1GraphTemp 3 }
wtWebioAn1GraphTempValueEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Temperaturen der Sensoren."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphTempValueTable 1 }
WtWebioAn1GraphTempValueEntry ::= SEQUENCE{
wtWebioAn1GraphTempValue OCTET STRING
}
wtWebioAn1GraphTempValue OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (5))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Temperaturwert des Sensors, ASCII, 5 Zeichen lang."
::= { wtWebioAn1GraphTempValueEntry 1 }
-- wtWebioAn1GraphBinaryTempValue Table
wtWebioAn1GraphBinaryTempValueTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphBinaryTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Liste binärer Temperaturwerte korrespondiernd zu den Kanalnummern."
::= { wtWebioAn1GraphTemp 4 }
wtWebioAn1GraphBinaryTempValueEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphBinaryTempValueEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Binäre Temperaturen der Sensoren."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphBinaryTempValueTable 1 }
WtWebioAn1GraphBinaryTempValueEntry ::= SEQUENCE{
wtWebioAn1GraphBinaryTempValue INTEGER
}
wtWebioAn1GraphBinaryTempValue OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Binärer Temperaturwert des Sensors in 1/10 Grad Celcius,
vorzeichenbehaftete Zahl, der Wert 0x7FFF zeigt einen
ungültigen Messwert an."
::= { wtWebioAn1GraphBinaryTempValueEntry 1 }
-- wtWebioAn1GraphSessCntrl Group
--------------------------------
wtWebioAn1GraphSessCntrlPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Durch Eintrag diese Passworts wird eine Session eröffnet, die durch Schreiben einer 1
in wtWebioAn1GraphSessCntrlLogout beendet wird. Gelesen liefert diese Variable einen String der
Länge Null."
::= { wtWebioAn1GraphSessCntrl 1 }
wtWebioAn1GraphSessCntrlConfigMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphSessCntrl-NoSession(0),
wtWebioAn1GraphSessCntrl-Session(1)
}
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Wenn sich das Gerät im SNMP-Konfigurationsmodus befindet, wird der Wert
1 zurückgeliefert, ansonsten 0. Ist der ausgelesene Wert 0
obwohl das Passwort geschrieben wurde, befindet sich das Gerät bereits
im Configmodus und die Variablen können nur gelesen werden."
::= { wtWebioAn1GraphSessCntrl 2 }
wtWebioAn1GraphSessCntrlLogout OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Wenn sich das Gerät im Konfigurationsmodus befindet und die Session wurde
von diesem SNMP Manager eröffnet, kann durch Schreiben einer 1 in diese
Variable die Session beendet werden und alle Parameter werden gespeichert.
Durch Schreiben einer 2 werden alle Eingaben wieder verworfen.
Gelesen liefert diese Variable den Wert 0."
::= { wtWebioAn1GraphSessCntrl 3 }
wtWebioAn1GraphSessCntrlAdminPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieses Passwort schützt den Zugang der Variablen mit Administratorrechten. Es kann nur vom
Administrator verändert werden. Wurde kein Passwort vergeben so ist public das gültige Passwort.
Gelesen liefert diese Variable einen Null-Pointer."
::= { wtWebioAn1GraphSessCntrl 4 }
wtWebioAn1GraphSessCntrlConfigPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieses Passwort schützt den Zugang der Variablen mit Configuratorrechten. Es kann vom
Administrator und vom Configurator verändert werden. Wurde kein Passwort vergeben so ist
public das gültige Passwort.Gelesen liefert diese Variable einen Null-Pointer."
::= { wtWebioAn1GraphSessCntrl 5 }
-- wtWebioAn1GraphText Group
------------------------
wtWebioAn1GraphDeviceName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name des Webio's, der userdefinierbar ist."
::= { wtWebioAn1GraphText 1 }
wtWebioAn1GraphDeviceText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Beschreibung des Webio's, die userdefinierbar ist."
::= { wtWebioAn1GraphText 2 }
wtWebioAn1GraphDeviceLocation OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Aufstellort des Webio's, die userdefinierbar ist."
::= { wtWebioAn1GraphText 3 }
wtWebioAn1GraphDeviceContact OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Kontactadresse im Servicefall des Webio's, die userdefinierbar ist."
::= { wtWebioAn1GraphText 4 }
-- wtWebioAn1GraphTimeZone Group
----------------------------
wtWebioAn1GraphTzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset Stunden der Zeitzone (Winterzeit) in Bezug auf UTC."
::= { wtWebioAn1GraphTimeZone 1 }
wtWebioAn1GraphTzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset Minuten der Zeitzone (Winterzeit) in Bezug auf UTC."
::= { wtWebioAn1GraphTimeZone 2 }
wtWebioAn1GraphTzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Bedingung:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : Apply Timezone"
::= { wtWebioAn1GraphTimeZone 3 }
wtWebioAn1GraphStTzOffsetHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset Stunden der Zeitzone (Sommerzeit) in Bezug auf UTC."
::= { wtWebioAn1GraphTimeZone 4 }
wtWebioAn1GraphStTzOffsetMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset Minuten der Zeitzone (Sommerzeit) in Bezug auf UTC."
::= { wtWebioAn1GraphTimeZone 5 }
wtWebioAn1GraphStTzEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Bedingung:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : Apply Summertime"
::= { wtWebioAn1GraphTimeZone 6 }
wtWebioAn1GraphStTzStartMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStartMonth-January(1),
wtWebioAn1GraphStartMonth-February(2),
wtWebioAn1GraphStartMonth-March(3),
wtWebioAn1GraphStartMonth-April(4),
wtWebioAn1GraphStartMonth-May(5),
wtWebioAn1GraphStartMonth-June(6),
wtWebioAn1GraphStartMonth-July(7),
wtWebioAn1GraphStartMonth-August(8),
wtWebioAn1GraphStartMonth-September(9),
wtWebioAn1GraphStartMonth-October(10),
wtWebioAn1GraphStartMonth-November(11),
wtWebioAn1GraphStartMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Monat, in dem von Winterzeit auf Sommerzeit umgestellt wird."
::= { wtWebioAn1GraphTimeZone 7 }
wtWebioAn1GraphStTzStartMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStartMode-first(1),
wtWebioAn1GraphStartMode-second(2),
wtWebioAn1GraphStartMode-third(3),
wtWebioAn1GraphStartMode-fourth(4),
wtWebioAn1GraphStartMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Modus des Wochentages, bei dem von Winterzeit auf Sommerzeit umgestellt wird."
::= { wtWebioAn1GraphTimeZone 8 }
wtWebioAn1GraphStTzStartWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStartWday-Sunday(1),
wtWebioAn1GraphStartWday-Monday(2),
wtWebioAn1GraphStartWday-Tuesday(3),
wtWebioAn1GraphStartWday-Thursday(4),
wtWebioAn1GraphStartWday-Wednesday(5),
wtWebioAn1GraphStartWday-Friday(6),
wtWebioAn1GraphStartWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Wochentag, bei dem von Winterzeit auf Sommerzeit umgestellt wird"
::= { wtWebioAn1GraphTimeZone 9 }
wtWebioAn1GraphStTzStartHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Stunde, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
umgestellt wird."
::= { wtWebioAn1GraphTimeZone 10 }
wtWebioAn1GraphStTzStartMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
umgestellt wird."
::= { wtWebioAn1GraphTimeZone 11 }
wtWebioAn1GraphStTzStopMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStopMonth-January(1),
wtWebioAn1GraphStopMonth-February(2),
wtWebioAn1GraphStopMonth-March(3),
wtWebioAn1GraphStopMonth-April(4),
wtWebioAn1GraphStopMonth-May(5),
wtWebioAn1GraphStopMonth-June(6),
wtWebioAn1GraphStopMonth-July(7),
wtWebioAn1GraphStopMonth-August(8),
wtWebioAn1GraphStopMonth-September(9),
wtWebioAn1GraphStopMonth-October(10),
wtWebioAn1GraphStopMonth-November(11),
wtWebioAn1GraphStopMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Monat, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
::= { wtWebioAn1GraphTimeZone 12 }
wtWebioAn1GraphStTzStopMode OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStopMode-first(1),
wtWebioAn1GraphStopMode-second(2),
wtWebioAn1GraphStopMode-third(3),
wtWebioAn1GraphStopMode-fourth(4),
wtWebioAn1GraphStopMode-last(5)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Modus des Wochentages, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
::= { wtWebioAn1GraphTimeZone 13 }
wtWebioAn1GraphStTzStopWday OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphStopWday-Sunday(1),
wtWebioAn1GraphStopWday-Monday(2),
wtWebioAn1GraphStopWday-Tuesday(3),
wtWebioAn1GraphStopWday-Thursday(4),
wtWebioAn1GraphStopWday-Wednesday(5),
wtWebioAn1GraphStopWday-Friday(6),
wtWebioAn1GraphStopWday-Saturday(7)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Wochentage, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
::= { wtWebioAn1GraphTimeZone 14 }
wtWebioAn1GraphStTzStopHrs OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Stunde, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
umgestellt wird."
::= { wtWebioAn1GraphTimeZone 15 }
wtWebioAn1GraphStTzStopMin OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minute, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
umgestellt wird."
::= { wtWebioAn1GraphTimeZone 16 }
-- wtWebioAn1GraphTimeServer Group
----------------------------
wtWebioAn1GraphTimeServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-Adresse oder Name des 1. Time Servers in ASCII"
::= { wtWebioAn1GraphTimeServer 1 }
wtWebioAn1GraphTimeServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-Adresse oder Name des 2. Time Servers in ASCII"
::= { wtWebioAn1GraphTimeServer 2 }
wtWebioAn1GraphTsEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Bedingung:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : Apply Time Server"
::= { wtWebioAn1GraphTimeServer 3 }
wtWebioAn1GraphTsSyncTime OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Die Abfrage der Timeserver erfolgt zu dieser vollen Stunde (0-23)."
::= { wtWebioAn1GraphTimeServer 4 }
-- wtWebioAn1GraphDeviceClock Group
----------------------------
wtWebioAn1GraphClockHrs OBJECT-TYPE
SYNTAX INTEGER (0..23)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Uhrzeit Stunde, unter Berücksichtigung der Zeitzoneneinstellungen."
::= { wtWebioAn1GraphDeviceClock 1 }
wtWebioAn1GraphClockMin OBJECT-TYPE
SYNTAX INTEGER (0..59)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Uhrzeit Minute, unter Berücksichtigung der Zeitzoneneinstellungen."
::= { wtWebioAn1GraphDeviceClock 2 }
wtWebioAn1GraphClockDay OBJECT-TYPE
SYNTAX INTEGER (1..31)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Datum: Tag des Monats, unter Berücksichtigung der Zeitzoneneinstellungen."
::= { wtWebioAn1GraphDeviceClock 3 }
wtWebioAn1GraphClockMonth OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphClockMonth-January(1),
wtWebioAn1GraphClockMonth-February(2),
wtWebioAn1GraphClockMonth-March(3),
wtWebioAn1GraphClockMonth-April(4),
wtWebioAn1GraphClockMonth-May(5),
wtWebioAn1GraphClockMonth-June(6),
wtWebioAn1GraphClockMonth-July(7),
wtWebioAn1GraphClockMonth-August(8),
wtWebioAn1GraphClockMonth-September(9),
wtWebioAn1GraphClockMonth-October(10),
wtWebioAn1GraphClockMonth-November(11),
wtWebioAn1GraphClockMonth-December(12)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Datum: Monat, unter Berücksichtigung der Zeitzoneneinstellungen."
::= { wtWebioAn1GraphDeviceClock 4 }
wtWebioAn1GraphClockYear OBJECT-TYPE
SYNTAX INTEGER (0..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Datum: Jahr, unter Berücksichtigung der Zeitzoneneinstellungen."
::= { wtWebioAn1GraphDeviceClock 5 }
-- wtWebioAn1GraphNetwork Group
------------------------
wtWebioAn1GraphIpAddress OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-Adresse des Webio's"
::= { wtWebioAn1GraphNetwork 1 }
wtWebioAn1GraphSubnetMask OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Subnetmask des Webio's"
::= { wtWebioAn1GraphNetwork 2 }
wtWebioAn1GraphGateway OBJECT-TYPE
SYNTAX IpAddress
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Gateway des Webio's"
::= { wtWebioAn1GraphNetwork 3 }
wtWebioAn1GraphDnsServer1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-Adresse des 1. DNS Servers in ASCII"
::= { wtWebioAn1GraphNetwork 4 }
wtWebioAn1GraphDnsServer2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-Adresse des 2. DNS Servers in ASCII"
::= { wtWebioAn1GraphNetwork 5 }
wtWebioAn1GraphAddConfig OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Zusatzkonfiguration (1=EIN):
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0: BOOTP disable
"
::= { wtWebioAn1GraphNetwork 6 }
-- wtWebioAn1GraphHTTP Group
--------------------------------
wtWebioAn1GraphStartup OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Legt die Startseite fest, nur eine Auswahl zulässig:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 2: user.htm
Bit 1: home.htm
Bit 0: index.htm"
::= { wtWebioAn1GraphHTTP 1 }
wtWebioAn1GraphGetHeaderEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Wenn freigeschaltet, wird eine Erkennungssequenz nach
jeder GET-Anfrage der Antwort vorangestellt:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : GET Header enable"
::= { wtWebioAn1GraphHTTP 2 }
wtWebioAn1GraphHttpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"HTTP Port, an den die TCP-Anfragen gesendet werden können (Default: 80)."
::= { wtWebioAn1GraphHTTP 3 }
-- wtWebioAn1GraphMail Group
--------------------------------
wtWebioAn1GraphMailAdName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Gerätename für die Mail-Administration."
::= { wtWebioAn1GraphMail 1 }
wtWebioAn1GraphMailReply OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Reply-Adresse für den Mailserver."
::= { wtWebioAn1GraphMail 2 }
wtWebioAn1GraphMailServer OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name oder Ip-Adresse des Mailservers."
::= { wtWebioAn1GraphMail 3 }
wtWebioAn1GraphMailEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Erlaubt das versenden von Mails:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : Mail enable"
::= { wtWebioAn1GraphMail 4 }
wtWebioAn1GraphMailAuthentication OBJECT-TYPE
SYNTAX OCTET STRING (SIZE (4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Auswahl des Authenticationmodi:
die OCTETS werden bitweise interpretiert, es darf nur ein Bit gesetzt sein.
Bit 0 entspricht dem LSB.
OCTET 1: ungenutzt
OCTET 2: ungenutzt
OCTET 3: ungenutzt
OCTET 4: Bit 3-7: ungenutzt
Bit 2 : POP3 vor SMTP
Bit 1 : ESMTP, Authentifizierung
Bit 0 : SMTP, keine Authentifizierung"
::= { wtWebioAn1GraphMail 5 }
wtWebioAn1GraphMailAuthUser OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name des Postfaches / Postfachusers."
::= { wtWebioAn1GraphMail 6 }
wtWebioAn1GraphMailAuthPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Passwort zur Identifizierung des Users."
::= { wtWebioAn1GraphMail 7 }
wtWebioAn1GraphMailPop3Server OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name oder Ip-Adresse des POP3 Servers."
::= { wtWebioAn1GraphMail 8 }
-- wtWebioAn1GraphSNMP Group
--------------------------------
wtWebioAn1GraphSnmpCommunityStringRead OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read only"
::= { wtWebioAn1GraphSNMP 1 }
wtWebioAn1GraphSnmpCommunityStringReadWrite OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string read / write"
::= { wtWebioAn1GraphSNMP 2 }
wtWebioAn1GraphSystemTrapManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name oder IP-Adresse des SNMP-Managers, der den System Trap entgegen nimmt."
::= { wtWebioAn1GraphSNMP 3 }
wtWebioAn1GraphSystemTrapEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Triggerbedingungen:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2-7: ungenutzt"
::= { wtWebioAn1GraphSNMP 4 }
wtWebioAn1GraphSnmpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 schaltet SNMP frei:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : SNMP enable"
::= { wtWebioAn1GraphSNMP 5 }
wtWebioAn1GraphSnmpCommunityStringTrap OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Community string der Traps."
::= { wtWebioAn1GraphSNMP 6 }
-- wtWebioAn1GraphUDP Group
--------------------------------
wtWebioAn1GraphUdpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Udp Port, an den die Udp-Anfragen GET Single gesendet werden können"
::= { wtWebioAn1GraphUDP 1 }
wtWebioAn1GraphUdpEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Schaltet UDP frei:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : UDP enable"
::= { wtWebioAn1GraphUDP 2 }
-- wtWebioAn1GraphSyslog Group
--------------------------------
wtWebioAn1GraphSyslogServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name oder IP-Adresse des Syslog-Servers, der die Syslog-Nachricht entgegen nimmt."
::= { wtWebioAn1GraphSyslog 1 }
wtWebioAn1GraphSyslogServerPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnummer des Syslog-Servers, default ist 514."
::= { wtWebioAn1GraphSyslog 2 }
wtWebioAn1GraphSyslogSystemMessagesEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Triggerbedingungen:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0: ColdStart
Bit 1: WarmStart
Bit 2: Diag Messages
Bit 3-7: ungenutzt"
::= { wtWebioAn1GraphSyslog 3 }
wtWebioAn1GraphSyslogEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 schaltet Syslog frei:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : Syslog enable"
::= { wtWebioAn1GraphSyslog 4 }
-- wtWebioAn1GraphFTP Group
--------------------------------
wtWebioAn1GraphFTPServerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name oder IP-Adresse des FTP-Servers, der die FTP-Nachricht entgegen nimmt."
::= { wtWebioAn1GraphFTP 1 }
wtWebioAn1GraphFTPServerControlPort OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnummer des Kontrollports des FTP-Servers, default ist 21."
::= { wtWebioAn1GraphFTP 2 }
wtWebioAn1GraphFTPUserName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: Name des Anwenders."
::= { wtWebioAn1GraphFTP 3 }
wtWebioAn1GraphFTPPassword OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: Passwort des Anwenders."
::= { wtWebioAn1GraphFTP 4 }
wtWebioAn1GraphFTPAccount OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"FTP Loggin: Account-Name des Anwenderkontos."
::= { wtWebioAn1GraphFTP 5 }
wtWebioAn1GraphFTPOption OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 schaltet den FTP Server in den Passiv-Modus,
der Client kontrolliert die Datenverbindung allein:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : PASV enable"
::= { wtWebioAn1GraphFTP 6 }
wtWebioAn1GraphFTPEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 schaltet FTP frei:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : FTP enable"
::= { wtWebioAn1GraphFTP 7 }
-- wtWebioAn1GraphDatalogger Group
--------------------------------
wtWebioAn1GraphLoggerTimebase OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphDatalogger-1Min(1),
wtWebioAn1GraphDatalogger-5Min(2),
wtWebioAn1GraphDatalogger-15Min(3),
wtWebioAn1GraphDatalogger-60Min(4)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Zeitbasis des Dataloggers"
::= { wtWebioAn1GraphDatalogger 1 }
wtWebioAn1GraphLoggerSensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Triggerbedingungen:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebioAn1GraphDatalogger 2 }
wtWebioAn1GraphDisplaySensorSel OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Die hier ausgewählten Sensoren werden grafisch angezeigt:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebioAn1GraphDatalogger 3 }
-- Graph Sensor Color Table
wtWebioAn1GraphSensorColorTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphSensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Liste der Sensorfarben in der grafischen Darstellung."
::= { wtWebioAn1GraphDatalogger 4 }
wtWebioAn1GraphSensorColorEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphSensorColorEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Nummern der Sensoren."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphSensorColorTable 1 }
WtWebioAn1GraphSensorColorEntry ::= SEQUENCE {
wtWebioAn1GraphSensorColor OCTET STRING
}
wtWebioAn1GraphSensorColor OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(3))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Farbe des Sensors in der grafischen Darstellung."
::= { wtWebioAn1GraphSensorColorEntry 1 }
wtWebioAn1GraphAutoScaleEnable OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bit 0 schaltet Vertical Auto Scale frei:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 1-7: ungenutzt
Bit 0 : Auto Scale enable"
::= { wtWebioAn1GraphDatalogger 5 }
wtWebioAn1GraphVerticalUpperLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Definiert die maximal sichtbare Temperatur für die grafische Darstellung.
Temperatur in Grad mit maximal 2 Nachkommastellen."
::= { wtWebioAn1GraphDatalogger 6 }
wtWebioAn1GraphVerticalLowerLimit OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Definiert die Minal sichtbare Temperatur für die grafische Darstellung.
Temperatur in Grad mit maximal 2 Nachkommastellen."
::= { wtWebioAn1GraphDatalogger 7 }
wtWebioAn1GraphHorizontalZoom OBJECT-TYPE
SYNTAX INTEGER {
wtWebioAn1GraphZoom-25Min(1),
wtWebioAn1GraphZoom-75Min(2),
wtWebioAn1GraphZoom-5Std(3),
wtWebioAn1GraphZoom-30Std(4),
wtWebioAn1GraphZoom-5Tage(5),
wtWebioAn1GraphZoom-25Tage(6)
}
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Definiert den default Zoom."
::= { wtWebioAn1GraphDatalogger 8 }
-- wtWebioAn1GraphAlarm Group
----------------------------
wtWebioAn1GraphAlarmCount OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Anzahl der unabhängigen Alarme."
::= { wtWebioAn1GraphAlarm 1 }
-- Alarm Interface Table
wtWebioAn1GraphAlarmIfTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphAlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Liste der Alarmindizes."
::= { wtWebioAn1GraphAlarm 2 }
wtWebioAn1GraphAlarmIfEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphAlarmIfEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Nummern der Alarme."
INDEX { wtWebioAn1GraphAlarmNo }
::= { wtWebioAn1GraphAlarmIfTable 1 }
WtWebioAn1GraphAlarmIfEntry ::= SEQUENCE {
wtWebioAn1GraphAlarmNo INTEGER
}
wtWebioAn1GraphAlarmNo OBJECT-TYPE
SYNTAX INTEGER (1..8)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Nummer des Alarms."
::= { wtWebioAn1GraphAlarmIfEntry 1 }
-- Alarm Table
wtWebioAn1GraphAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphAlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Liste der Einstellungen abhängig von der Alarmnummer."
::= { wtWebioAn1GraphAlarm 3 }
wtWebioAn1GraphAlarmEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphAlarmEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Alarm-Parameter der einzelnen Alarme."
INDEX { wtWebioAn1GraphAlarmNo }
::= { wtWebioAn1GraphAlarmTable 1 }
WtWebioAn1GraphAlarmEntry ::= SEQUENCE {
wtWebioAn1GraphAlarmTrigger OCTET STRING,
wtWebioAn1GraphAlarmMin OCTET STRING,
wtWebioAn1GraphAlarmMax OCTET STRING,
wtWebioAn1GraphAlarmHysteresis OCTET STRING,
wtWebioAn1GraphAlarmDelay OCTET STRING,
wtWebioAn1GraphAlarmInterval OCTET STRING,
wtWebioAn1GraphAlarmEnable OCTET STRING,
wtWebioAn1GraphAlarmEMailAddr OCTET STRING,
wtWebioAn1GraphAlarmMailSubject OCTET STRING,
wtWebioAn1GraphAlarmMailText OCTET STRING,
wtWebioAn1GraphAlarmManagerIP OCTET STRING,
wtWebioAn1GraphAlarmTrapText OCTET STRING,
wtWebioAn1GraphAlarmMailOptions OCTET STRING,
wtWebioAn1GraphAlarmTcpIpAddr OCTET STRING,
wtWebioAn1GraphAlarmTcpPort INTEGER,
wtWebioAn1GraphAlarmTcpText OCTET STRING,
wtWebioAn1GraphAlarmClearMailSubject OCTET STRING,
wtWebioAn1GraphAlarmClearMailText OCTET STRING,
wtWebioAn1GraphAlarmClearTrapText OCTET STRING,
wtWebioAn1GraphAlarmClearTcpText OCTET STRING,
wtWebioAn1GraphAlarmSyslogIpAddr OCTET STRING,
wtWebioAn1GraphAlarmSyslogPort INTEGER,
wtWebioAn1GraphAlarmSyslogText OCTET STRING,
wtWebioAn1GraphAlarmSyslogClearText OCTET STRING,
wtWebioAn1GraphAlarmFtpDataPort OCTET STRING,
wtWebioAn1GraphAlarmFtpFileName OCTET STRING,
wtWebioAn1GraphAlarmFtpText OCTET STRING,
wtWebioAn1GraphAlarmFtpClearText OCTET STRING,
wtWebioAn1GraphAlarmFtpOption OCTET STRING,
wtWebioAn1GraphAlarmTimerCron OCTET STRING
}
wtWebioAn1GraphAlarmTrigger OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Triggerbedingungen:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3:
Bit 0: Timer
Bit 1: ColdStart
Bit 2: WarmStart
Bit 3: Sensor lost
Bit 4-7 ungenutzt
Octet 4:
Bit 0: Sensor 1
Bit 1: Sensor 2
Bit 2: Sensor 3
Bit 3: Sensor 4
Bit 4: Sensor 5
Bit 5: Sensor 6
Bit 6: Sensor 7
Bit 7: Sensor 8"
::= { wtWebioAn1GraphAlarmEntry 1 }
wtWebioAn1GraphAlarmMin OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Minimum Temperatur in Grad mit maximal 2 Nachkommastellen."
::= { wtWebioAn1GraphAlarmEntry 2 }
wtWebioAn1GraphAlarmMax OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Maximum Temperatur in Grad mit maximal 2 Nachkommastellen."
::= { wtWebioAn1GraphAlarmEntry 3 }
wtWebioAn1GraphAlarmHysteresis OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bei Überschreiten der Temperatur Min+Hyst. und Unterschreiten der Temperatur Max-Hyst.
wird der Alarm gelöscht: pos. Temperaturdifferenz in Grad mit maximal 2 Nachkommastellen."
::= { wtWebioAn1GraphAlarmEntry 4 }
wtWebioAn1GraphAlarmDelay OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Der Alarm wird erst ausgelöst, wenn für die Dauer dieser Zeit
die Alarmbedingungen erfüllt sind (Zeit in Minuten)."
::= { wtWebioAn1GraphAlarmEntry 5 }
wtWebioAn1GraphAlarmInterval OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Sendeintervall von Alarmmeldungen."
::= { wtWebioAn1GraphAlarmEntry 6 }
wtWebioAn1GraphAlarmEnable OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Alarmfreischaltung:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0: Mail Enable
Bit 1: SNMP Trap enable
Bit 2: TCP Client enable"
::= { wtWebioAn1GraphAlarmEntry 7 }
wtWebioAn1GraphAlarmEMailAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"E-Mail Adresse, an die die Alarmmail gesendet werden soll."
::= { wtWebioAn1GraphAlarmEntry 8 }
wtWebioAn1GraphAlarmMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Betreffzeile der Alarmmail."
::= { wtWebioAn1GraphAlarmEntry 9 }
wtWebioAn1GraphAlarmMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Text der Alarmmail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
<Z> liefert die aktuelle Zeit."
::= { wtWebioAn1GraphAlarmEntry 10 }
wtWebioAn1GraphAlarmManagerIP OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name oder IP-Adresse des SNMP-Managers, der den Trap entgegen nimmt."
::= { wtWebioAn1GraphAlarmEntry 11 }
wtWebioAn1GraphAlarmTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieser Text wird im Trapbody gesendet."
::= { wtWebioAn1GraphAlarmEntry 12 }
wtWebioAn1GraphAlarmMailOptions OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Optionen:
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0 : Attach Thermo.csv Enable
Bit 1 : CSV-Data_since_last_report
Bit 2-7: ungenutzt"
::= { wtWebioAn1GraphAlarmEntry 13 }
wtWebioAn1GraphAlarmTcpIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-Adresse des Gerätes, dass eine TCP-Nachricht empfangen soll."
::= { wtWebioAn1GraphAlarmEntry 14 }
wtWebioAn1GraphAlarmTcpPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnummer des Gerätes, dass eine TCP-Nachricht empfangen soll."
::= { wtWebioAn1GraphAlarmEntry 15 }
wtWebioAn1GraphAlarmTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieser Text wird im TCP Trapbody gesendet."
::= { wtWebioAn1GraphAlarmEntry 16 }
wtWebioAn1GraphAlarmClearMailSubject OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Betreffzeile der Alarm Clear Mail."
::= { wtWebioAn1GraphAlarmEntry 17 }
wtWebioAn1GraphAlarmClearMailText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Text der Alarm Clear Mail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
<Z> liefert die aktuelle Zeit."
::= { wtWebioAn1GraphAlarmEntry 18 }
wtWebioAn1GraphAlarmClearTrapText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieser Text wird im Trapbody gesendet."
::= { wtWebioAn1GraphAlarmEntry 19 }
wtWebioAn1GraphAlarmClearTcpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieser Text wird im TCP Trapbody gesendet."
::= { wtWebioAn1GraphAlarmEntry 20 }
wtWebioAn1GraphAlarmSyslogIpAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"IP-Adresse des Gerätes, dass eine Syslog-Nachricht empfangen soll."
::= { wtWebioAn1GraphAlarmEntry 21 }
wtWebioAn1GraphAlarmSyslogPort OBJECT-TYPE
SYNTAX INTEGER (1..65535)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Portnummer des Gerätes, dass eine Syslog-Nachricht empfangen soll, default Port ist 514."
::= { wtWebioAn1GraphAlarmEntry 22 }
wtWebioAn1GraphAlarmSyslogText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Jede Syslog-Nachricht beginnt mit einem Prioritätsschlüssel, einem Zeitstempel und der Host Ip-Nummer gemäß RFC3164.
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
::= { wtWebioAn1GraphAlarmEntry 23 }
wtWebioAn1GraphAlarmSyslogClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Jede Syslog-Nachricht beginnt mit einem Prioritätsschlüssel, einem Zeitstempel und der Host Ip-Nummer gemäß RFC3164.
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
::= { wtWebioAn1GraphAlarmEntry 24 }
wtWebioAn1GraphAlarmFtpDataPort OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Lokaler Datenport: 1..65535 oder AUTO: der nächste ungenutzte Port wird automatisch zugewiesen."
::= { wtWebioAn1GraphAlarmEntry 25 }
wtWebioAn1GraphAlarmFtpFileName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Der File Name kann auch Pfadinformationen enthalten."
::= { wtWebioAn1GraphAlarmEntry 26 }
wtWebioAn1GraphAlarmFtpText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieser Text wird in die angegebene Datei geschrieben."
::= { wtWebioAn1GraphAlarmEntry 27 }
wtWebioAn1GraphAlarmFtpClearText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Dieser Text wird in die angegebene Datei geschrieben."
::= { wtWebioAn1GraphAlarmEntry 28 }
wtWebioAn1GraphAlarmFtpOptions OBJECT-TYPE
SYNTAX OCTET STRING (SIZE(4))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Binär kodierte Optionen, nur eine Option darf eingeschaltet sein:
STORE = Datei ersetzen
APPEND = Nachrichten ans Dateiende anhängen
Octet 1: ungenutzt
Octet 2: ungenutzt
Octet 3: ungenutzt
Octet 4:
Bit 0 : STORE
Bit 1 : APPEND
Bit 2-7: ungenutzt"
::= { wtWebioAn1GraphAlarmEntry 29 }
wtWebioAn1GraphAlarmTimerCron OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Diser Eintrag enthält 5 Leerzeichen- oder Tab-getrente Felder zur Definition von zeitgesteuerten
Ausgabe von Alarmnachrichten. Jedes der 5 Felder muss mit der aktuelle Zeit übereinstimmen, um
das Senden einer Nachricht auszulösen, Wochentag und Monatstag werden getrennt ausgewertet.
Feld möglicher Zahlenbereich
1: Minuten 0-59
2. Stunden 0-23, 0 ist Mitternacht
3: Monatstag 1-31
4: Monat 1-12
5: Wochentag 0-6, 0 ist Sonntag
Für jedes Feld kann nun angegeben werden:
- eine ganze Zahl aus dem angegebenen Zahlenbereich
- ein Teil-Zahlenbereich (wie z.B. 1-5) innerhalb des angegebenen Zahlenbereichs
- eine mit Komma getrennte Liste von ganzen Zahlen oder Tei-Zahlenbereichen (wie z.B. 2,4-6,8,10)
- ein Stern * (deckt den gesamten erlaubten Bereich ab)
- ein / gibt die Schrittweite bei Teil-Zahlenbereichen an (z.B. 0-59/2 jede zweite Minute)."
::= { wtWebioAn1GraphAlarmEntry 30 }
-- wtWebioAn1GraphPorts Group
----------------------------
-- Table
wtWebioAn1GraphPortTable OBJECT-TYPE
SYNTAX SEQUENCE OF WtWebioAn1GraphPortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Liste der Einstellungen abhängig von der Sensornummer."
::= { wtWebioAn1GraphPorts 1 }
wtWebioAn1GraphPortEntry OBJECT-TYPE
SYNTAX WtWebioAn1GraphPortEntry
ACCESS not-accessible
STATUS mandatory
DESCRIPTION
"Sensor-Parameter der einzelnen Sensoren."
INDEX { wtWebioAn1GraphSensorNo }
::= { wtWebioAn1GraphPortTable 1 }
WtWebioAn1GraphPortEntry ::= SEQUENCE {
wtWebioAn1GraphPortName OCTET STRING,
wtWebioAn1GraphPortText OCTET STRING,
wtWebioAn1GraphPortOffset1 OCTET STRING,
wtWebioAn1GraphPortTemperature1 OCTET STRING,
wtWebioAn1GraphPortOffset2 OCTET STRING,
wtWebioAn1GraphPortTemperature2 OCTET STRING,
wtWebioAn1GraphPortComment OCTET STRING
}
wtWebioAn1GraphPortName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Name des Sensors."
::= { wtWebioAn1GraphPortEntry 1 }
wtWebioAn1GraphPortText OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Beschreibung des Sensors."
::= { wtWebioAn1GraphPortEntry 2 }
wtWebioAn1GraphPortOffset1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 1."
::= { wtWebioAn1GraphPortEntry 3 }
wtWebioAn1GraphPortTemperature1 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset-Kalibrierung: Referenztemperatur 1 in Grad mit max. 2 Nachkommastellen."
::= { wtWebioAn1GraphPortEntry 4 }
wtWebioAn1GraphPortOffset2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 2."
::= { wtWebioAn1GraphPortEntry 5 }
wtWebioAn1GraphPortTemperature2 OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset-Kalibrierung: Referenztemperatur 2 in Grad mit max. 2 Nachkommastellen."
::= { wtWebioAn1GraphPortEntry 6 }
wtWebioAn1GraphPortComment OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Offset-Kalibrierung: Angaben zu Datum, Referenzgerät, Operator."
::= { wtWebioAn1GraphPortEntry 7 }
-- wtWebioAn1GraphManufact Group
----------------------------
wtWebioAn1GraphMfName OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hersteller Firmenname"
::= { wtWebioAn1GraphManufact 1 }
wtWebioAn1GraphMfAddr OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Adresse des Herstellers."
::= { wtWebioAn1GraphManufact 2 }
wtWebioAn1GraphMfHotline OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Hotline des Herstellers."
::= { wtWebioAn1GraphManufact 3 }
wtWebioAn1GraphMfInternet OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Internet-Adresse des Herstellers."
::= { wtWebioAn1GraphManufact 4 }
wtWebioAn1GraphMfDeviceTyp OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Gerätebezeichnung (Typ) des Herstellers."
::= { wtWebioAn1GraphManufact 5 }
wtWebioAn1GraphMfOrderNo OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Bestellnummer des Gerätes des Herstellers."
::= { wtWebioAn1GraphManufact 6 }
-- wtWebioAn1GraphDiag Group
----------------------------
wtWebioAn1GraphDiagErrorCount OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Anzahl der Einträge im Fehlerspeicher."
::= { wtWebioAn1GraphDiag 1 }
wtWebioAn1GraphDiagBinaryError OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Bitweise kodierte Fehlerursachen."
::= { wtWebioAn1GraphDiag 2 }
wtWebioAn1GraphDiagErrorIndex OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Der Wert dieser Variable wird als Index für die Ausgabe
eines Fehlertextes (wtWebioAn1GraphDiagErrorMessage) verwendet.
Die Fehler im Speicher sind von 1 bis wtWebioAn1GraphDiagErrorCount durchnummeriert.
Nach dem Schreiben einens gültigen Wertes in diese Variable kann der dazugehörige Text
in wtWebioAn1GraphDiagErrorMessage ausgelesen werden."
::= { wtWebioAn1GraphDiag 3 }
wtWebioAn1GraphDiagErrorMessage OBJECT-TYPE
SYNTAX OCTET STRING
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Abhängig vom Wert wtWebioAn1GraphDiagErrorIndex wird ein Fehlertext angezeigt."
::= { wtWebioAn1GraphDiag 4 }
wtWebioAn1GraphDiagErrorClear OBJECT-TYPE
SYNTAX INTEGER
ACCESS write-only
STATUS mandatory
DESCRIPTION
"Durch Schreiben eine 1 in diese Variable, wird der Fehlerspeicher gelöscht."
::= { wtWebioAn1GraphDiag 5 }
-- TRAP DEFINITIONS
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
wtWebioAn1GraphAlert1 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 1"
--#SUMMARY "Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 31
wtWebioAn1GraphAlert2 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 2"
--#SUMMARY "Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 32
wtWebioAn1GraphAlert3 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 3"
--#SUMMARY "Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 33
wtWebioAn1GraphAlert4 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 4"
--#SUMMARY "Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 34
wtWebioAn1GraphAlert5 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 5"
--#SUMMARY "Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 35
wtWebioAn1GraphAlert6 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 6"
--#SUMMARY "Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 36
wtWebioAn1GraphAlert7 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 7"
--#SUMMARY "Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 37
wtWebioAn1GraphAlert8 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Alarm 8"
--#SUMMARY "Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 38
wtWebioAn1GraphAlert9 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 1"
--#SUMMARY "Release Alarm 1: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 91
wtWebioAn1GraphAlert10 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 2"
--#SUMMARY "Release Alarm 2: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 92
wtWebioAn1GraphAlert11 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 3"
--#SUMMARY "Release Alarm 3: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 93
wtWebioAn1GraphAlert12 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 4"
--#SUMMARY "Release Alarm 4: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 94
wtWebioAn1GraphAlert13 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 5"
--#SUMMARY "Release Alarm 5: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 95
wtWebioAn1GraphAlert14 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 6"
--#SUMMARY "Release Alarm 6: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 96
wtWebioAn1GraphAlert15 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 7"
--#SUMMARY "Release Alarm 7: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 97
wtWebioAn1GraphAlert16 TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 gelöscht wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Release Alarm 8"
--#SUMMARY "Release Alarm 8: %s"
--#ARGUMENTS {0}
--#SEVERITY INFORMATIONAL
--#TIMEINDEX 99
--#STATE OPERATIONAL
::= 98
wtWebioAn1GraphAlertDiag TRAP-TYPE
ENTERPRISE wtWebioAn1Graph
VARIABLES {
wtWebioAn1GraphDiagErrorIndex,
wtWebioAn1GraphDiagErrorMessage
}
DESCRIPTION
"Dieser SNMP-Trap wird generiert, wenn eine Diagnose/Error-Message ausgelöst wurde,
das SNMP-Trap-Enable gesetzt ist und
SNMP in Enable freigegeben ist."
-- NMS trap annotation
--#TYPE "Web-Thermograph Diagnose Error"
--#SUMMARY "Diagnose error index: %d, Message: %s."
--#ARGUMENTS {0,1}
--#SEVERITY MAJOR
--#TIMEINDEX 99
--#STATE DEGRADED
::= 110
END