- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1365 lines
47 KiB
Text
1365 lines
47 KiB
Text
PM8ECCMIB DEFINITIONS ::= BEGIN
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
AlarmType ::= INTEGER {
|
|
overValue( 10 ),
|
|
overPower( 11 ),
|
|
overReversePower( 12 ),
|
|
underValue( 20 ),
|
|
underPower( 21 ),
|
|
phaseRotationReversal( 51 ),
|
|
phaseLossVoltage( 52 ),
|
|
phaseLossCurrent( 53 ),
|
|
powerFactorLeading( 54 ),
|
|
powerFactorLagging( 55 ),
|
|
digitalInputOFFtoON( 60 ),
|
|
digitalInputONtoOFF( 61 ),
|
|
unaryEvent( 70 ),
|
|
voltageOrCurrentSwell( 80 ),
|
|
voltageOrCurrentSag( 90 ),
|
|
combinatorialAND( 100 ),
|
|
combinatorialNAND( 101 ),
|
|
combinatorialOR( 102 ),
|
|
combinatorialNOR( 103 ),
|
|
combinatorialXOR( 104 ),
|
|
combinatorialNOT( 105 ),
|
|
diagnostic( 1280 )
|
|
}
|
|
|
|
IOPointType ::= INTEGER {
|
|
digitalInput( 1 ),
|
|
digitalOutput( 2 ),
|
|
analogInput( 3 ),
|
|
analogOutput( 4 )
|
|
}
|
|
|
|
IOPointLabel ::= OCTET STRING (SIZE(0..16))
|
|
|
|
AlarmLabel ::= OCTET STRING (SIZE(0..16))
|
|
|
|
|
|
|
|
schneiderElectric OBJECT IDENTIFIER ::= { enterprises 3833 }
|
|
|
|
transparentFactoryEthernet OBJECT IDENTIFIER ::= { schneiderElectric 1 }
|
|
|
|
equipmentProfile OBJECT IDENTIFIER ::= { transparentFactoryEthernet 7 }
|
|
|
|
tfProducts OBJECT IDENTIFIER ::= { equipmentProfile 255 }
|
|
|
|
ecc OBJECT IDENTIFIER ::= { tfProducts 15 }
|
|
|
|
pm8ecc OBJECT IDENTIFIER ::= { ecc 1 }
|
|
|
|
metering OBJECT IDENTIFIER ::= { pm8ecc 1 }
|
|
|
|
systemWiringTypeTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SystemWiringTypeEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "The wiring system type of the host meter."
|
|
::= { metering 1 }
|
|
|
|
systemWiringTypeEntry OBJECT-TYPE
|
|
SYNTAX SystemWiringTypeEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter System Wiring Type"
|
|
INDEX {
|
|
swtIndex
|
|
}
|
|
::= { systemWiringTypeTable 1 }
|
|
|
|
SystemWiringTypeEntry ::= SEQUENCE {
|
|
swtIndex
|
|
INTEGER,
|
|
swtWiringType
|
|
INTEGER
|
|
}
|
|
|
|
swtIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "System Wiring Type Table Index"
|
|
::= { systemWiringTypeEntry 1 }
|
|
|
|
swtWiringType OBJECT-TYPE
|
|
SYNTAX INTEGER (10 | 11 | 12 | 30 | 31 | 32 | 40 | 42 | 44)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Single Phase Line to Neutral 2 Wire 1CT 1PT is
|
|
'10' Single Phase Line to Line 2 Wire 1CT 1PT
|
|
is '11' Single Phase 3-Wire 3 wire 2CT 2PT is
|
|
'12' Three Phase 3 Wire 2CT 2PT is '30' Three
|
|
Phase 3 Wire 3CT 2PT is '31' Three Phase 3 Wire
|
|
1CT 2PT is '32' Three Phase 4 Wire 3CT 3PT is
|
|
'40' Three Phase 4 Wire 3CT 2PT is '42' Three
|
|
Phase 4 Wire 1CT 3PT is '44'"
|
|
::= { systemWiringTypeEntry 2 }
|
|
|
|
loadCurrentTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LoadCurrentEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Load Current Table"
|
|
::= { metering 2 }
|
|
|
|
loadCurrentEntry OBJECT-TYPE
|
|
SYNTAX LoadCurrentEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Load Current Table"
|
|
INDEX {
|
|
lcIndex
|
|
}
|
|
::= { loadCurrentTable 1 }
|
|
|
|
LoadCurrentEntry ::= SEQUENCE {
|
|
lcIndex
|
|
INTEGER,
|
|
lcIa
|
|
OCTET STRING,
|
|
lcIb
|
|
OCTET STRING,
|
|
lcIc
|
|
OCTET STRING,
|
|
lcIAvg
|
|
OCTET STRING
|
|
}
|
|
|
|
lcIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Load Current Table Index"
|
|
::= { loadCurrentEntry 1 }
|
|
|
|
lcIa OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Load Current Phase A Units = A (Amps)"
|
|
::= { loadCurrentEntry 2 }
|
|
|
|
lcIb OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Load Current Phase B Units = A (Amps)"
|
|
::= { loadCurrentEntry 3 }
|
|
|
|
lcIc OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Load Current Phase C Units = A (Amps)"
|
|
::= { loadCurrentEntry 4 }
|
|
|
|
lcIAvg OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Load Current 3 Phase Average Units
|
|
= A (Amps)"
|
|
::= { loadCurrentEntry 5 }
|
|
|
|
powerTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PowerEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Table"
|
|
::= { metering 3 }
|
|
|
|
powerEntry OBJECT-TYPE
|
|
SYNTAX PowerEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Table"
|
|
INDEX {
|
|
pIndex
|
|
}
|
|
::= { powerTable 1 }
|
|
|
|
PowerEntry ::= SEQUENCE {
|
|
pIndex
|
|
INTEGER,
|
|
pReal
|
|
OCTET STRING,
|
|
pReactive
|
|
OCTET STRING,
|
|
pApparent
|
|
OCTET STRING
|
|
}
|
|
|
|
pIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Power Table Index"
|
|
::= { powerEntry 1 }
|
|
|
|
pReal OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Real Power Units = kW"
|
|
::= { powerEntry 2 }
|
|
|
|
pReactive OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Reactive Power Units = kVAR"
|
|
::= { powerEntry 3 }
|
|
|
|
pApparent OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Apparent Power Units = kVA"
|
|
::= { powerEntry 4 }
|
|
|
|
powerFactorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PowerFactorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Factor Table"
|
|
::= { metering 4 }
|
|
|
|
powerFactorEntry OBJECT-TYPE
|
|
SYNTAX PowerFactorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Factor Table"
|
|
INDEX {
|
|
pfIndex
|
|
}
|
|
::= { powerFactorTable 1 }
|
|
|
|
PowerFactorEntry ::= SEQUENCE {
|
|
pfIndex
|
|
INTEGER,
|
|
pfPowerFactorTotal
|
|
OCTET STRING,
|
|
pfPowerFactorDescription
|
|
OCTET STRING
|
|
}
|
|
|
|
pfIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Power Factor Table Index"
|
|
::= { powerFactorEntry 1 }
|
|
|
|
pfPowerFactorTotal OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter 3 Phase Total Power Factor"
|
|
::= { powerFactorEntry 2 }
|
|
|
|
pfPowerFactorDescription OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Describes the current power factor Lead/Lag for
|
|
IEEE mode Cap/Ind for IEC mode"
|
|
::= { powerFactorEntry 3 }
|
|
|
|
voltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF VoltageEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Table"
|
|
::= { metering 5 }
|
|
|
|
voltageEntry OBJECT-TYPE
|
|
SYNTAX VoltageEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Table"
|
|
INDEX {
|
|
vIndex
|
|
}
|
|
::= { voltageTable 1 }
|
|
|
|
VoltageEntry ::= SEQUENCE {
|
|
vIndex
|
|
INTEGER,
|
|
vVab
|
|
OCTET STRING,
|
|
vVbc
|
|
OCTET STRING,
|
|
vVca
|
|
OCTET STRING,
|
|
vVllAvg
|
|
OCTET STRING,
|
|
vVan
|
|
OCTET STRING,
|
|
vVbn
|
|
OCTET STRING,
|
|
vVcn
|
|
OCTET STRING,
|
|
vVlnAvg
|
|
OCTET STRING
|
|
}
|
|
|
|
vIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Voltage Table Index"
|
|
::= { voltageEntry 1 }
|
|
|
|
vVab OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line A to Line B Units = V
|
|
(Volts)"
|
|
::= { voltageEntry 2 }
|
|
|
|
vVbc OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line B to Line C Units = V
|
|
(Volts)"
|
|
::= { voltageEntry 3 }
|
|
|
|
vVca OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line C to Line A Units = V
|
|
(Volts)"
|
|
::= { voltageEntry 4 }
|
|
|
|
vVllAvg OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line to Line Average Voltage
|
|
Units = V (Volts)"
|
|
::= { voltageEntry 5 }
|
|
|
|
vVan OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line A to Neutral Units = V
|
|
(Volts)"
|
|
::= { voltageEntry 6 }
|
|
|
|
vVbn OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line B to Neutral Units = V
|
|
(Volts)"
|
|
::= { voltageEntry 7 }
|
|
|
|
vVcn OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line C to Neutral Units = V
|
|
(Volts)"
|
|
::= { voltageEntry 8 }
|
|
|
|
vVlnAvg OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Voltage Line to Neutral 3 Phase Average
|
|
Units = V (Volts)"
|
|
::= { voltageEntry 9 }
|
|
|
|
frequencyTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF FrequencyEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Frequency Table"
|
|
::= { metering 6 }
|
|
|
|
frequencyEntry OBJECT-TYPE
|
|
SYNTAX FrequencyEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Frequency Table"
|
|
INDEX {
|
|
fIndex
|
|
}
|
|
::= { frequencyTable 1 }
|
|
|
|
FrequencyEntry ::= SEQUENCE {
|
|
fIndex
|
|
INTEGER,
|
|
fFrequency
|
|
OCTET STRING
|
|
}
|
|
|
|
fIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Frequency Table Index"
|
|
::= { frequencyEntry 1 }
|
|
|
|
fFrequency OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Frequency Units = Hz"
|
|
::= { frequencyEntry 2 }
|
|
|
|
currentDemandTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF CurrentDemandEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Current Demand Table"
|
|
::= { metering 7 }
|
|
|
|
currentDemandEntry OBJECT-TYPE
|
|
SYNTAX CurrentDemandEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Current Demand Table"
|
|
INDEX {
|
|
cdPhase,
|
|
cdIndex
|
|
}
|
|
::= { currentDemandTable 1 }
|
|
|
|
CurrentDemandEntry ::= SEQUENCE {
|
|
cdIndex
|
|
INTEGER,
|
|
cdPhase
|
|
OCTET STRING,
|
|
cdPresentCurrentDemand
|
|
OCTET STRING,
|
|
cdPeakCurrentDemand
|
|
OCTET STRING,
|
|
cdLastCurrentDemand
|
|
OCTET STRING,
|
|
cdPeakDateTime
|
|
OCTET STRING,
|
|
cdResetDateTime
|
|
OCTET STRING,
|
|
cdPhaseEnum
|
|
INTEGER
|
|
}
|
|
|
|
cdIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Demand Current Table Index"
|
|
::= { currentDemandEntry 1 }
|
|
|
|
cdPhase OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(2))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Current Demand Phase Name"
|
|
::= { currentDemandEntry 2 }
|
|
|
|
cdPresentCurrentDemand OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Present Demand Current Units = A (Amps)"
|
|
::= { currentDemandEntry 3 }
|
|
|
|
cdPeakCurrentDemand OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Peak Current Demand Units = A (Amps)"
|
|
::= { currentDemandEntry 4 }
|
|
|
|
cdLastCurrentDemand OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Current Demand Last Interval Units
|
|
= A (Amps)"
|
|
::= { currentDemandEntry 5 }
|
|
|
|
cdPeakDateTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Peak Current Demand Date and Time"
|
|
::= { currentDemandEntry 6 }
|
|
|
|
cdResetDateTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Date and Time of Demand Current Reset"
|
|
::= { currentDemandEntry 7 }
|
|
|
|
cdPhaseEnum OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
currentPhaseA( 1 ),
|
|
currentPhaseB( 2 ),
|
|
currentPhaseC( 3 )
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Current Demand Phase"
|
|
::= { currentDemandEntry 8 }
|
|
|
|
powerDemandTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PowerDemandEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Demand"
|
|
::= { metering 8 }
|
|
|
|
powerDemandEntry OBJECT-TYPE
|
|
SYNTAX PowerDemandEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Demand Table"
|
|
INDEX {
|
|
pdComponent,
|
|
pdIndex
|
|
}
|
|
::= { powerDemandTable 1 }
|
|
|
|
PowerDemandEntry ::= SEQUENCE {
|
|
pdIndex
|
|
INTEGER,
|
|
pdComponent
|
|
OCTET STRING,
|
|
pdPresentPowerDemand
|
|
OCTET STRING,
|
|
pdPeakPowerDemand
|
|
OCTET STRING,
|
|
pdLastPowerDemand
|
|
OCTET STRING,
|
|
pdPeakDateTime
|
|
OCTET STRING,
|
|
pdResetDateTime
|
|
OCTET STRING,
|
|
pdComponentEnum
|
|
INTEGER
|
|
}
|
|
|
|
pdIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Power Demand Table Index"
|
|
::= { powerDemandEntry 1 }
|
|
|
|
pdComponent OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4..8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Demand Component Units: Real
|
|
= kW Reacitve = kVAR Apparent = kVA"
|
|
::= { powerDemandEntry 2 }
|
|
|
|
pdPresentPowerDemand OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Present Demand Power"
|
|
::= { powerDemandEntry 3 }
|
|
|
|
pdPeakPowerDemand OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Peak Power Demand"
|
|
::= { powerDemandEntry 4 }
|
|
|
|
pdLastPowerDemand OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Demand Last Interval"
|
|
::= { powerDemandEntry 5 }
|
|
|
|
pdPeakDateTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Peak Power Demand Date and Time"
|
|
::= { powerDemandEntry 6 }
|
|
|
|
pdResetDateTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Date and Time of Power Demand Reset"
|
|
::= { powerDemandEntry 7 }
|
|
|
|
pdComponentEnum OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
realPower( 1 ),
|
|
reactivePower( 2 ),
|
|
apparentPower( 3 )
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Power Demand Component"
|
|
::= { powerDemandEntry 8 }
|
|
|
|
energyTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EnergyEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Energy Table"
|
|
::= { metering 9 }
|
|
|
|
energyEntry OBJECT-TYPE
|
|
SYNTAX EnergyEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Energy Table"
|
|
INDEX {
|
|
eIndex
|
|
}
|
|
::= { energyTable 1 }
|
|
|
|
EnergyEntry ::= SEQUENCE {
|
|
eIndex
|
|
INTEGER,
|
|
eRealEnergy
|
|
OCTET STRING,
|
|
eDateTimeRealEnergyReset
|
|
OCTET STRING,
|
|
eReactiveEnergy
|
|
OCTET STRING,
|
|
eDateTimeReactiveEnergyReset
|
|
OCTET STRING,
|
|
eApparentEnergy
|
|
OCTET STRING,
|
|
eDateTimeApparentEnergyReset
|
|
OCTET STRING
|
|
}
|
|
|
|
eIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Energy Table Index"
|
|
::= { energyEntry 1 }
|
|
|
|
eRealEnergy OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Real Energy Units = Wh"
|
|
::= { energyEntry 2 }
|
|
|
|
eDateTimeRealEnergyReset OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Date and Time Real Energy Accumulation
|
|
was reset"
|
|
::= { energyEntry 3 }
|
|
|
|
eReactiveEnergy OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Reactive Energy Units = VARh"
|
|
::= { energyEntry 4 }
|
|
|
|
eDateTimeReactiveEnergyReset OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Date and Time Reative Energy Accumulation
|
|
was reset"
|
|
::= { energyEntry 5 }
|
|
|
|
eApparentEnergy OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Apparent Energy Units = VAh"
|
|
::= { energyEntry 6 }
|
|
|
|
eDateTimeApparentEnergyReset OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Date and Time Reactive Energy Accumulation
|
|
was reset"
|
|
::= { energyEntry 7 }
|
|
|
|
alarms OBJECT IDENTIFIER ::= { pm8ecc 2 }
|
|
|
|
alarmConfigurationTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AlarmConfigurationEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Displays the current configuration of the Host
|
|
Meter On-board alarms"
|
|
::= { alarms 1 }
|
|
|
|
alarmConfigurationEntry OBJECT-TYPE
|
|
SYNTAX AlarmConfigurationEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Contains configuration information for the Host
|
|
Meter On-board Alarms"
|
|
INDEX {
|
|
acIndex,
|
|
acPosition
|
|
}
|
|
::= { alarmConfigurationTable 1 }
|
|
|
|
AlarmConfigurationEntry ::= SEQUENCE {
|
|
acIndex
|
|
INTEGER,
|
|
acPosition
|
|
INTEGER,
|
|
acAlarmLabel
|
|
AlarmLabel,
|
|
acEnabled
|
|
INTEGER,
|
|
acStatus
|
|
INTEGER,
|
|
acCounter
|
|
INTEGER,
|
|
acPriority
|
|
INTEGER,
|
|
acType
|
|
AlarmType,
|
|
acAlarmList1
|
|
INTEGER,
|
|
acAlarmList2
|
|
INTEGER,
|
|
acAlarmList3
|
|
INTEGER,
|
|
acAlarmList4
|
|
INTEGER
|
|
}
|
|
|
|
acIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm Configuration Table Index"
|
|
::= { alarmConfigurationEntry 1 }
|
|
|
|
acPosition OBJECT-TYPE
|
|
SYNTAX INTEGER (1..74)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the position of the alarm. 1 - 74"
|
|
::= { alarmConfigurationEntry 2 }
|
|
|
|
acAlarmLabel OBJECT-TYPE
|
|
SYNTAX AlarmLabel
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The name of the alarm (user configurable)"
|
|
::= { alarmConfigurationEntry 3 }
|
|
|
|
acEnabled OBJECT-TYPE
|
|
SYNTAX INTEGER (0 | 255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates whether the alarm is enabled or not.
|
|
0 = Disabled 255 = Enabled"
|
|
::= { alarmConfigurationEntry 4 }
|
|
|
|
acStatus OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates whether the alarm is active. 0 = Inactive
|
|
1 = Active"
|
|
::= { alarmConfigurationEntry 5 }
|
|
|
|
acCounter OBJECT-TYPE
|
|
SYNTAX INTEGER (0..32767)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the number of times the alarm has been
|
|
activated. Note: This counter resets at 32767"
|
|
::= { alarmConfigurationEntry 6 }
|
|
|
|
acPriority OBJECT-TYPE
|
|
SYNTAX INTEGER (0..3)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The priority of the alarm. 0 = No Priority 1 =
|
|
Low Priority 2 = Medium Priority 3 = High Priority"
|
|
::= { alarmConfigurationEntry 7 }
|
|
|
|
acType OBJECT-TYPE
|
|
SYNTAX AlarmType
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the type of the alarm."
|
|
::= { alarmConfigurationEntry 8 }
|
|
|
|
acAlarmList1 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|
of the first alarm that is used to evaluate the
|
|
alarm state."
|
|
::= { alarmConfigurationEntry 9 }
|
|
|
|
acAlarmList2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|
of the second alarm that is used to evaluate
|
|
the alarm state."
|
|
::= { alarmConfigurationEntry 10 }
|
|
|
|
acAlarmList3 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|
of the third alarm that is used to evaluate the
|
|
alarm state."
|
|
::= { alarmConfigurationEntry 11 }
|
|
|
|
acAlarmList4 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Used for combinatorial type alarms - The position
|
|
of the fourth alarm that is used to evaluate
|
|
the alarm state."
|
|
::= { alarmConfigurationEntry 12 }
|
|
|
|
alarmSummaryBitmapsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AlarmSummaryBitmapsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the state of the Host Meter On-Board
|
|
Alarms"
|
|
::= { alarms 2 }
|
|
|
|
alarmSummaryBitmapsEntry OBJECT-TYPE
|
|
SYNTAX AlarmSummaryBitmapsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the status of the Host Meter On-Board
|
|
Alarms"
|
|
INDEX {
|
|
alSumIndex
|
|
}
|
|
::= { alarmSummaryBitmapsTable 1 }
|
|
|
|
AlarmSummaryBitmapsEntry ::= SEQUENCE {
|
|
alSumIndex
|
|
INTEGER,
|
|
alSumAlarms1to16
|
|
OCTET STRING,
|
|
alSumAlarms17to32
|
|
OCTET STRING,
|
|
alSumAlarms33to48
|
|
OCTET STRING,
|
|
alSumAlarms49to64
|
|
OCTET STRING,
|
|
alSumAlarms65to74
|
|
OCTET STRING
|
|
}
|
|
|
|
alSumIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm Summary Bitmap Table Index"
|
|
::= { alarmSummaryBitmapsEntry 1 }
|
|
|
|
alSumAlarms1to16 OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the status of Alarms 1 - 16 (16-bits,
|
|
bit-0 = Alarm 1)"
|
|
::= { alarmSummaryBitmapsEntry 2 }
|
|
|
|
alSumAlarms17to32 OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the status of Alarms 17 - 32 (16-bits,
|
|
bit-0 = Alarm 17)"
|
|
::= { alarmSummaryBitmapsEntry 3 }
|
|
|
|
alSumAlarms33to48 OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the status of Alarms 33 - 48 (16-bits,
|
|
bit-0 = Alarm 33)"
|
|
::= { alarmSummaryBitmapsEntry 4 }
|
|
|
|
alSumAlarms49to64 OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the status of Alarms 49 - 64 (16-bits,
|
|
bit-0 = Alarm 49)"
|
|
::= { alarmSummaryBitmapsEntry 5 }
|
|
|
|
alSumAlarms65to74 OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(16))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the status of Alarms 65 - 74 (16-bits,
|
|
bit-0 = Alarm 65, bit-9 = Alarm 74)"
|
|
::= { alarmSummaryBitmapsEntry 6 }
|
|
|
|
alarmCountersTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AlarmCountersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter On-Board Alarm Counters"
|
|
::= { alarms 3 }
|
|
|
|
alarmCountersEntry OBJECT-TYPE
|
|
SYNTAX AlarmCountersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter On-Board Alarm Counters"
|
|
INDEX {
|
|
alCntAlarmPosition,
|
|
alCntIndex
|
|
}
|
|
::= { alarmCountersTable 1 }
|
|
|
|
AlarmCountersEntry ::= SEQUENCE {
|
|
alCntIndex
|
|
INTEGER,
|
|
alCntAlarmPosition
|
|
INTEGER,
|
|
alCntCount
|
|
INTEGER
|
|
}
|
|
|
|
alCntIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Alarm Counters Table Index"
|
|
::= { alarmCountersEntry 1 }
|
|
|
|
alCntAlarmPosition OBJECT-TYPE
|
|
SYNTAX INTEGER (1..74)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The Host Meter Alarm Position"
|
|
::= { alarmCountersEntry 2 }
|
|
|
|
alCntCount OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The number of times the Host Meter On-Board alarm
|
|
has transitioned from an inactive state to an
|
|
active state"
|
|
::= { alarmCountersEntry 3 }
|
|
|
|
io OBJECT IDENTIFIER ::= { pm8ecc 3 }
|
|
|
|
ioOptionIDTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF IoOptionIDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "I/O Option Module Installed on the Host Meter"
|
|
::= { io 1 }
|
|
|
|
ioOptionIDEntry OBJECT-TYPE
|
|
SYNTAX IoOptionIDEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "I/O Option Card Installed On-board the Host Meter"
|
|
INDEX {
|
|
ioIDIndex
|
|
}
|
|
::= { ioOptionIDTable 1 }
|
|
|
|
IoOptionIDEntry ::= SEQUENCE {
|
|
ioIDIndex
|
|
INTEGER,
|
|
ioIDInstalledOptionSlot1
|
|
INTEGER,
|
|
ioIDInstalledOptionSlot2
|
|
INTEGER
|
|
}
|
|
|
|
ioIDIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "I/O Installed Option ID Table Index"
|
|
::= { ioOptionIDEntry 1 }
|
|
|
|
ioIDInstalledOptionSlot1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unused( 1 ),
|
|
io-22( 2 ),
|
|
io-26( 3 ),
|
|
io-2222( 4 )
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
|
|
4 = IO 2222"
|
|
::= { ioOptionIDEntry 2 }
|
|
|
|
ioIDInstalledOptionSlot2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unused( 1 ),
|
|
io-22( 2 ),
|
|
io-26( 3 ),
|
|
io-2222( 4 )
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "0 = Not Installed 1 = Unused 2 = IO22 3 = IO26
|
|
4 = IO 2222"
|
|
::= { ioOptionIDEntry 3 }
|
|
|
|
ioConfigurationTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF IoConfigurationEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Displays the current I/O configuration for each
|
|
I/O point"
|
|
::= { io 2 }
|
|
|
|
ioConfigurationEntry OBJECT-TYPE
|
|
SYNTAX IoConfigurationEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Contains configuration information for the Host
|
|
Meter On-board I/O"
|
|
INDEX {
|
|
iocIndex,
|
|
iocPointNumber
|
|
}
|
|
::= { ioConfigurationTable 1 }
|
|
|
|
IoConfigurationEntry ::= SEQUENCE {
|
|
iocIndex
|
|
INTEGER,
|
|
iocPointNumber
|
|
INTEGER,
|
|
iocLabel
|
|
IOPointLabel,
|
|
iocStateOrValue
|
|
OCTET STRING,
|
|
iocPointType
|
|
IOPointType,
|
|
iocMode
|
|
INTEGER,
|
|
iocType
|
|
INTEGER,
|
|
iocCount
|
|
OCTET STRING
|
|
}
|
|
|
|
iocIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "I/O Configuration Table Index"
|
|
::= { ioConfigurationEntry 1 }
|
|
|
|
iocPointNumber OBJECT-TYPE
|
|
SYNTAX INTEGER (1..18)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The point number for this I/O Point"
|
|
::= { ioConfigurationEntry 2 }
|
|
|
|
iocLabel OBJECT-TYPE
|
|
SYNTAX IOPointLabel
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The name of the I/O Point (user configurable)"
|
|
::= { ioConfigurationEntry 3 }
|
|
|
|
iocStateOrValue OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Displays the current value for the I/O Point Digial
|
|
I/O: 1 = Active or 0 = Inactive
|
|
|
|
Analog I/O: Scaled input/output value"
|
|
::= { ioConfigurationEntry 4 }
|
|
|
|
iocPointType OBJECT-TYPE
|
|
SYNTAX IOPointType
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The type of I/O at this point"
|
|
::= { ioConfigurationEntry 5 }
|
|
|
|
iocMode OBJECT-TYPE
|
|
SYNTAX INTEGER (0..9)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "For Digital Inputs and Outputs this object is
|
|
always 0 indicating Discrete.
|
|
|
|
For Analog Inputs and Outputs this object indicates
|
|
the range of analog I/O values (used without
|
|
units) 0 = 0 | 1 1 = 0 | 5 2 = 0 | 10 3 = 0 |
|
|
20 4 = 1 | 5 5 = 4 | 20 6 = -5 | 5 7 = -10 |
|
|
10 8 = -100 | 100 9 = User defined (values default
|
|
to 0)"
|
|
::= { ioConfigurationEntry 6 }
|
|
|
|
iocType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "For Digital Inputs this object indicates input
|
|
type 1 = Unused 2 = AC/DC
|
|
|
|
For Digital Outputs this object indicates output
|
|
type 1 = solid state relay 2 = electromechanical
|
|
relay
|
|
|
|
For Analog Inputs and Outputs this object indicates
|
|
the digital resolution of the I/O hardware. 0
|
|
= 8-Bit, unipolar 1 = 10-Bit, unipolar 2 = 12-Bit,
|
|
unipolar 3 = 14-Bit, unipolar 4 = 16-Bit, unipolar
|
|
5 = 16-Bit, bipolar with sign 6 = reserved 7
|
|
= reserved 8 = Resolution for IO2222 Voltage
|
|
range 0 - 4000 9 = Resolution for IO2222 Current
|
|
range 800 - 4000"
|
|
::= { ioConfigurationEntry 7 }
|
|
|
|
iocCount OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(8))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Number of times digital I/O point has transitioned
|
|
from OFF to ON"
|
|
::= { ioConfigurationEntry 8 }
|
|
|
|
ioStatusBitmapsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF IoStatusBitmapsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter I/O Status Bitmaps"
|
|
::= { io 3 }
|
|
|
|
ioStatusBitmapsEntry OBJECT-TYPE
|
|
SYNTAX IoStatusBitmapsEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter On-Board I/O Status Bitmaps"
|
|
INDEX {
|
|
ioStatIndex
|
|
}
|
|
::= { ioStatusBitmapsTable 1 }
|
|
|
|
IoStatusBitmapsEntry ::= SEQUENCE {
|
|
ioStatIndex
|
|
INTEGER,
|
|
ioStatSummaryBitmap
|
|
OCTET STRING
|
|
}
|
|
|
|
ioStatIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "I/O Summary Bitmaps Table Index"
|
|
::= { ioStatusBitmapsEntry 1 }
|
|
|
|
ioStatSummaryBitmap OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(18))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Indicates the Status of the Host Meter I/O Points
|
|
Bit-0 = I/O Point 1 Bit-1 = I/O Point 2 ... Bit-17
|
|
= I/O Point 18"
|
|
::= { ioStatusBitmapsEntry 2 }
|
|
|
|
meterSystem OBJECT IDENTIFIER ::= { pm8ecc 4 }
|
|
|
|
meterIdentificationTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF MeterIdentificationEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Identification"
|
|
::= { meterSystem 1 }
|
|
|
|
meterIdentificationEntry OBJECT-TYPE
|
|
SYNTAX MeterIdentificationEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Identification"
|
|
INDEX {
|
|
midIndex
|
|
}
|
|
::= { meterIdentificationTable 1 }
|
|
|
|
MeterIdentificationEntry ::= SEQUENCE {
|
|
midIndex
|
|
INTEGER,
|
|
midSerialNumber
|
|
INTEGER,
|
|
midFirmwareVersion
|
|
OCTET STRING,
|
|
midModelNumber
|
|
OCTET STRING,
|
|
midDeviceName
|
|
OCTET STRING
|
|
}
|
|
|
|
midIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..255)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Meter Identification Table Index"
|
|
::= { meterIdentificationEntry 1 }
|
|
|
|
midSerialNumber OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host meter 32 bit Serial Number"
|
|
::= { meterIdentificationEntry 2 }
|
|
|
|
midFirmwareVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Firmware Version"
|
|
::= { meterIdentificationEntry 3 }
|
|
|
|
midModelNumber OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Model Number"
|
|
::= { meterIdentificationEntry 4 }
|
|
|
|
midDeviceName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Host Meter Label plus Nameplate"
|
|
::= { meterIdentificationEntry 5 }
|
|
|
|
trapVariables OBJECT IDENTIFIER ::= { pm8ecc 5 }
|
|
|
|
alarmDateAndTime OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The Date and Time of the alarm state change."
|
|
::= { trapVariables 1 }
|
|
|
|
alarmLabel OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The Descriptive Label given to the alarm"
|
|
::= { trapVariables 2 }
|
|
|
|
alarmState OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The state of the Alarm - pickup, dropout, unary,
|
|
diagnostic"
|
|
::= { trapVariables 3 }
|
|
|
|
alarmValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The value of the alarm when it changed state."
|
|
::= { trapVariables 4 }
|
|
|
|
alarmPriority OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
highPriority( 1 ),
|
|
mediumPriority( 2 ),
|
|
lowPriority( 3 )
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The priority defined for the alarm."
|
|
::= { trapVariables 5 }
|
|
|
|
mibVersion OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "This is the current version of the MIB"
|
|
::= { pm8ecc 6 }
|
|
|
|
|
|
pm8OnBoardAlarmP1 TRAP-TYPE
|
|
ENTERPRISE pm8ecc
|
|
VARIABLES {
|
|
alarmDateAndTime,
|
|
alarmLabel,
|
|
alarmState,
|
|
alarmValue,
|
|
alarmPriority
|
|
}
|
|
DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
|
|
detected a state change of an enabled alarm with a
|
|
priority of 1"
|
|
::= 1
|
|
|
|
pm8OnBoardAlarmP2 TRAP-TYPE
|
|
ENTERPRISE pm8ecc
|
|
VARIABLES {
|
|
alarmDateAndTime,
|
|
alarmLabel,
|
|
alarmState,
|
|
alarmValue,
|
|
alarmPriority
|
|
}
|
|
DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
|
|
detected a state change of an enabled alarm with a
|
|
priority of 2"
|
|
::= 2
|
|
|
|
pm8OnBoardAlarmP3 TRAP-TYPE
|
|
ENTERPRISE pm8ecc
|
|
VARIABLES {
|
|
alarmDateAndTime,
|
|
alarmLabel,
|
|
alarmState,
|
|
alarmValue,
|
|
alarmPriority
|
|
}
|
|
DESCRIPTION "Indicates the Host Meter On-Board Alarm system has
|
|
detected a state change of an enabled alarm with a
|
|
priority of 3"
|
|
::= 3
|
|
|
|
|
|
END
|
|
|