- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
2620 lines
82 KiB
Text
2620 lines
82 KiB
Text
-- Ingrasys USHA MIB
|
|
-- MIB for Uninterruptible Power Supplies
|
|
--
|
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) ingrasys(2468)
|
|
-- product(1) webAppliance(2) upsAgent(1) usha(1)
|
|
-- ==============================================================================================
|
|
---
|
|
--- Revision History
|
|
---
|
|
--- v0.80 17-Apr-2000 Johnny Lin/Allion
|
|
--- Created
|
|
--
|
|
--- v0.81 27-Apr-2000 Johnny Lin/Allion
|
|
--- Add upsTest objects 8, 9 and 10
|
|
--- v1.00 09-Oct-2000 Johnny Lin/Allion
|
|
--- Fix the problems that HPOV6.0 cann't read this
|
|
--- mib file due to some incorrect ','
|
|
--- Change upsControlEvent from DisplayString to
|
|
--- enum INTEGER
|
|
--- v1.01 25-Oct-2001 Johnny Lin/Allion
|
|
--- Change ENTERPRISE name from usha to ushap
|
|
--- Add "usha" in every trap event name
|
|
--- Change object (usha, upsObjects, upsTraps) name from usha to ushap
|
|
---
|
|
--- v1.02 30-Oct-2001 Kenneth/Allion
|
|
--- 1. Import PositiveInteger and NonNegativeInteger from RFC-1628.
|
|
--- 2. Fixed: The final item of SYNTAX must not have a comma ending.
|
|
--- 3. Correct upsInputmandatory to upsInputCurrent.
|
|
--- 4. Correct upsOutputmandatory to upsOutputCurrent.
|
|
--- 5. Correct upsBypassmandatory to upsBypassCurrent.
|
|
--- 6. Fixed: SYNTAX "DisplayString" must use "SIZE()" to define its range
|
|
--- 7. Change BatteryTestScheduleEntry to UpsBatteryTestScheduleEntry
|
|
--- 8. Fixed some SYNTAX error :
|
|
--- Exp: Change "SYNTAX upsControlWeeklyScheduleEntry" to "SYNTAX
|
|
--- UpsControlWeeklyScheduleEntry". And it can avoid conflict
|
|
--- between names.
|
|
---
|
|
--- v1.03 28-Dec-2001 Johnny/Allion
|
|
--- 1. Add Simplified Chinese support for agentConfigDefaultLanguage
|
|
---
|
|
--- v1.04 03-Jan-2002 Johnny/Allion
|
|
--- 1. Fixed some typo
|
|
---
|
|
--- v1.05 16-Jul-2003 Johnny/Ingrasys
|
|
--- 1. Fixed errors of
|
|
--- "mconfigUnmpEvent" for "upsBatteryTestScheduleEntry"
|
|
--- "mconfigUnmpEvent" for "shutdownParametersEntry"
|
|
--- "mconfigScheduleIndex" for "upsControlWeeklyScheduleEntry"
|
|
--- "mconfigScheduleIndex" for "upsControlSpecialScheduleEntry"
|
|
---
|
|
--- 2. Change "read/write" to "read-write" of Access table for
|
|
--- some NMS which may not accept '/' within MIB file.
|
|
---
|
|
--- v2.00b1 20-Feb-2004 Johnny/Ingrasys
|
|
--- 1. Add EMD support, include emdStatus, emdConfig, and traps
|
|
---
|
|
---
|
|
--- v2.01 16-Jul-2004 Johnny/Ingrasys
|
|
--- 1. Change all traps Enterprise from ushap to upsTraps
|
|
---
|
|
---
|
|
--- v2.02 05-Jan-2007 Kevin/Ingrasys
|
|
--- 1. Modified MIB error issuse for http://www.simpleweb.org/ietf/mibs/validate/ web site
|
|
--- 2. Included RFC1628.MIB
|
|
---
|
|
--- v2.03 5-Jan-2007 Kevin/Ingrasys
|
|
--- 1. Modified MIB error issue for http://www.simpleweb.org/ietf/mibs/validate/ web side.
|
|
---
|
|
--- v2.04 20-Sep-2007 Kevin/Ingrasys
|
|
--- 1. Added IpAddress type.
|
|
---
|
|
--- v2.05 23-Jan-2008 Kenneth/Ingrasys
|
|
--- 1. Add upsBatteryTestScheduleSpecialDay and upsBatteryTestScheduleTestWithTime to upsBatteryTestScheduleTable.
|
|
--- 2. Add emdTemperatureOverThreshold(7), emdAlarm1(8) and emdAlarm2(9) to upsControlEvent.
|
|
--- 3. Add timeOfConnectionTime and timeOfConnectionTimeout to upsDevicesTable.
|
|
--- 4. Change "allion" string to "ingrasys".
|
|
--- 5. change for http://wwwsnmp.cs.utwente.nl/ietf/mibs/validate/ Level:4
|
|
--- 6. Change "shutdownParametersEntry/ShutdownParametersEntry" strings to "upsControlShutdownParametersEntry/UpsControlShutdownParametersEntry".
|
|
---
|
|
--- v2.06 04-Feb-2008 Figo/Ingrasys
|
|
--- 1. Fixed MIB Object description(upsControlWeeklyShutdownTime upsControlWeeklyRestartTime upsControlSpecialShutdownTime upsControlSpecialRestartTime) to hh:mm format.
|
|
---
|
|
--- v2.07 25-Feb-2008 Figo/Ingrasys
|
|
--- 1. Change upsBatteryTestScheduleTable order list.
|
|
---
|
|
--- v2.08 30-May-2008 Figo/Ingrasys
|
|
--- 1. Fixed upsBatteryGroupSecondsOnBattery DESCRIPTION"0 shall be returned if the unit is not on battery power.".
|
|
---
|
|
--- v2.09 02-Sep-2008 Figo/Ingrasys
|
|
--- 1. Change "ushaUpsOverTemperature" and "ushaUpsOverLoad" trap level from "WARNING" to "SEVERE".
|
|
--- 2. Add Q6 warning code definition in trap group.
|
|
---
|
|
--- v2.10 16-Sep-2008 Figo/Ingrasys
|
|
--- 1. Rearrange order for Q6 warning code in trap group.
|
|
--- 2. Define Q6 warning code recover trap.
|
|
---
|
|
--- v2.11 23-Sep-2008 Figo/Ingrasys
|
|
--- 1. Modified trap1~38 description in coincidence with FW.
|
|
---
|
|
|
|
USHA-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises,Counter,IpAddress
|
|
FROM RFC1155-SMI
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
PositiveInteger,NonNegativeInteger
|
|
FROM UPS-MIB;
|
|
|
|
ingrasys OBJECT IDENTIFIER ::= { enterprises 2468 }
|
|
product OBJECT IDENTIFIER ::= { ingrasys 1 }
|
|
upsAgent OBJECT IDENTIFIER ::= { product 2 }
|
|
ushap OBJECT IDENTIFIER ::= { upsAgent 1 }
|
|
upsObjectGroup OBJECT IDENTIFIER ::= { ushap 1 }
|
|
upsTrapGroup OBJECT IDENTIFIER ::= { ushap 2 }
|
|
|
|
upsIdentGroup OBJECT IDENTIFIER ::= { upsObjectGroup 1 }
|
|
upsBatteryGroup OBJECT IDENTIFIER ::= { upsObjectGroup 2 }
|
|
upsInputGroup OBJECT IDENTIFIER ::= { upsObjectGroup 3 }
|
|
upsOutputGroup OBJECT IDENTIFIER ::= { upsObjectGroup 4 }
|
|
upsBypassGroup OBJECT IDENTIFIER ::= { upsObjectGroup 5 }
|
|
upsTestGroup OBJECT IDENTIFIER ::= { upsObjectGroup 6 }
|
|
upsControlGroup OBJECT IDENTIFIER ::= { upsObjectGroup 7 }
|
|
upsConfigGroup OBJECT IDENTIFIER ::= { upsObjectGroup 8 }
|
|
upsClients OBJECT IDENTIFIER ::= { upsObjectGroup 9 }
|
|
agentConfig OBJECT IDENTIFIER ::= { upsObjectGroup 10 }
|
|
emdStatus OBJECT IDENTIFIER ::= { upsObjectGroup 11 }
|
|
emdConfig OBJECT IDENTIFIER ::= { upsObjectGroup 12 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- upsIdentification
|
|
--
|
|
-- All objects in this group except for upsIdentGroupName and
|
|
-- upsIdentGroupAttachedDevices are set at device initialization
|
|
-- and remain static.
|
|
--
|
|
-- ===========================================================================
|
|
|
|
upsIdentGroupManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { upsIdentGroup 1 }
|
|
|
|
upsIdentGroupModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { upsIdentGroup 2 }
|
|
|
|
upsIdentGroupUPSFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not have the same value as
|
|
upsIdentGroupAgentSoftwareVersion in some implementations."
|
|
::= { upsIdentGroup 3 }
|
|
|
|
upsIdentGroupAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The USHA software/firmware version. This variable may or
|
|
may not have the same value as
|
|
upsIdentGroupUPSSoftwareVersion in some implementations."
|
|
::= { upsIdentGroup 4 }
|
|
|
|
upsIdentGroupName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { upsIdentGroup 5 }
|
|
|
|
upsIdentGroupAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { upsIdentGroup 6 }
|
|
|
|
upsIdentGroupUpsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS serial no."
|
|
::= { upsIdentGroup 7 }
|
|
|
|
-- ===========================================================================
|
|
-- upsBatteryGroup
|
|
--
|
|
-- The Battery group.
|
|
-- ===========================================================================
|
|
|
|
upsBatteryGroupStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4),
|
|
batteryDischarging(5),
|
|
batteryFailure(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the status in the UPS system's batteries."
|
|
::= { upsBatteryGroup 1 }
|
|
|
|
upsBatteryGroupSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. 0 shall be returned
|
|
if the unit is not on battery power."
|
|
::= { upsBatteryGroup 2 }
|
|
|
|
upsBatteryGroupEstimatedMinutesRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion
|
|
under the present load conditions if the utility power
|
|
is off and remains off, or if it were to be lost and
|
|
remain off."
|
|
::= { upsBatteryGroup 3 }
|
|
|
|
upsBatteryGroupEstimatedChargeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { upsBatteryGroup 4 }
|
|
|
|
upsBatteryGroupVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage in 0.1 Volt DC."
|
|
::= { upsBatteryGroup 5 }
|
|
|
|
upsBatteryGroupMandatory OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present battery mandatory."
|
|
::= { upsBatteryGroup 6 }
|
|
|
|
upsBatteryGroupTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
-- "degrees 0.1 Centigrade"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing."
|
|
::= { upsBatteryGroup 7 }
|
|
|
|
-- ===========================================================================
|
|
-- upsInputGroup
|
|
--
|
|
-- Input group.
|
|
-- ===========================================================================
|
|
|
|
upsInputGroupLineBads OBJECT-TYPE
|
|
SYNTAX Counter
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the
|
|
manufacturer. This count is incremented by one each
|
|
time the input transitions from zero out-of-tolerance
|
|
lines to one or more input lines out-of-tolerance."
|
|
::= { upsInputGroup 1 }
|
|
|
|
upsInputGroupNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
input table."
|
|
::= { upsInputGroup 2 }
|
|
|
|
upsInputGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInputGroupEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputGroupNumLines."
|
|
::= { upsInputGroup 3 }
|
|
|
|
upsInputGroupEntry OBJECT-TYPE
|
|
SYNTAX UpsInputGroupEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line."
|
|
INDEX { upsInputGroupLineIndex }
|
|
::= { upsInputGroupTable 1 }
|
|
|
|
UpsInputGroupEntry ::=
|
|
SEQUENCE {
|
|
upsInputGroupLineIndex PositiveInteger,
|
|
upsInputGroupFrequency NonNegativeInteger,
|
|
upsInputGroupVoltage NonNegativeInteger,
|
|
upsInputGroupCurrent NonNegativeInteger,
|
|
upsInputGroupTruePower NonNegativeInteger,
|
|
upsInputGroupVoltageMax NonNegativeInteger,
|
|
upsInputGroupVoltageMin NonNegativeInteger
|
|
}
|
|
|
|
upsInputGroupLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of UpsInputGroupEntry."
|
|
::= { upsInputGroupEntry 1 }
|
|
|
|
upsInputGroupFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
-- "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present input frequency."
|
|
::= { upsInputGroupEntry 2 }
|
|
|
|
upsInputGroupVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The input utility line voltage in 0.1 volts."
|
|
::= { upsInputGroupEntry 3 }
|
|
|
|
upsInputGroupCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input current in 0.1 A."
|
|
::= { upsInputGroupEntry 4 }
|
|
|
|
upsInputGroupTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
-- "Watts"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the present input true power."
|
|
::= { upsInputGroupEntry 5 }
|
|
|
|
upsInputGroupVoltageMax OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum utility line voltage in 0.1 VAC for last 1 minute."
|
|
::= { upsInputGroupEntry 6 }
|
|
|
|
upsInputGroupVoltageMin OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum utility line voltage in 0.1 VAC for last 1 minute."
|
|
::= { upsInputGroupEntry 7 }
|
|
|
|
-- ===========================================================================
|
|
-- upsOutputGroup
|
|
--
|
|
-- Output group
|
|
-- ===========================================================================
|
|
|
|
upsOutputGroupSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker."
|
|
::= { upsOutputGroup 1 }
|
|
|
|
upsOutputGroupFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current output frequency of the UPS system in 0.1 of HZ."
|
|
::= { upsOutputGroup 2 }
|
|
|
|
upsOutputGroupNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
output table."
|
|
::= { upsOutputGroup 3 }
|
|
|
|
upsOutputGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutputGroupEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsOutputGroupNumLines."
|
|
::= { upsOutputGroup 4 }
|
|
|
|
upsOutputGroupEntry OBJECT-TYPE
|
|
SYNTAX UpsOutputGroupEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line."
|
|
INDEX { upsOutputGroupLineIndex }
|
|
::= { upsOutputGroupTable 1 }
|
|
|
|
UpsOutputGroupEntry ::=
|
|
SEQUENCE {
|
|
upsOutputGroupLineIndex PositiveInteger,
|
|
upsOutputGroupVoltage NonNegativeInteger,
|
|
upsOutputGroupCurrent NonNegativeInteger,
|
|
upsOutputGroupPower NonNegativeInteger,
|
|
upsOutputGroupPercentLoad INTEGER
|
|
}
|
|
|
|
upsOutputGroupLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output line identifier."
|
|
::= { upsOutputGroupEntry 1 }
|
|
|
|
upsOutputGroupVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output voltage of the UPS system in 0.1 volts."
|
|
::= { upsOutputGroupEntry 2 }
|
|
|
|
upsOutputGroupCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output current of the UPS system in 0.1 Amps."
|
|
::= { upsOutputGroupEntry 3 }
|
|
|
|
upsOutputGroupPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
-- "Watts"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present output true power."
|
|
::= { upsOutputGroupEntry 4 }
|
|
|
|
upsOutputGroupPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line, i.e., the greater of
|
|
the percent load of true power capacity and the
|
|
percent load of VA."
|
|
::= { upsOutputGroupEntry 5 }
|
|
|
|
-- ===========================================================================
|
|
-- upsBypassGroup
|
|
-- ===========================================================================
|
|
|
|
upsBypassGroupFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass frequency."
|
|
::= { upsBypassGroup 1 }
|
|
|
|
upsBypassGroupNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device.
|
|
This entry indicates the number of rows in the bypass
|
|
table."
|
|
::= { upsBypassGroup 2 }
|
|
|
|
upsBypassGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBypassGroupEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of
|
|
entries is given by the value of upsBypassGroupNumLines."
|
|
::= { upsBypassGroup 3 }
|
|
|
|
upsBypassGroupEntry OBJECT-TYPE
|
|
SYNTAX UpsBypassGroupEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bypass input."
|
|
INDEX { upsBypassGroupLineIndex }
|
|
::= { upsBypassGroupTable 1 }
|
|
|
|
UpsBypassGroupEntry ::=
|
|
SEQUENCE {
|
|
upsBypassGroupLineIndex PositiveInteger,
|
|
upsBypassGroupVoltage NonNegativeInteger,
|
|
upsBypassGroupCurrent NonNegativeInteger,
|
|
upsBypassGroupPower NonNegativeInteger
|
|
}
|
|
|
|
upsBypassGroupLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The bypass line identifier."
|
|
::= { upsBypassGroupEntry 1 }
|
|
|
|
upsBypassGroupVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass voltage."
|
|
::= { upsBypassGroupEntry 2 }
|
|
|
|
upsBypassGroupCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present bypass current."
|
|
::= { upsBypassGroupEntry 3 }
|
|
|
|
upsBypassGroupPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
-- "Watts"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The present true power conveyed by the bypass."
|
|
::= { upsBypassGroupEntry 4 }
|
|
|
|
-- ===========================================================================
|
|
-- upsTestGroup
|
|
--
|
|
-- ===========================================================================
|
|
|
|
upsTestBatteryTestSettingTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The object specify the test time for battery test."
|
|
::= { upsTestGroup 1 }
|
|
|
|
upsBatteryTest OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
battTest10sec(2),
|
|
battTestUntilLow(3),
|
|
battTestWithTime(4),
|
|
battTestCancelTest(5),
|
|
battTestClearInfo(6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"This object specify the battery test type and initiate
|
|
battery test. If battTestWithTime selected, the test
|
|
time is refer to upsTestBatteryTestTime."
|
|
::= { upsTestGroup 2 }
|
|
|
|
upsTestBatteryTestResult OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
donePassed(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestsInitiated(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePassed(1),
|
|
doneWarning(2), and doneError(3) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively. The value aborted(4) is
|
|
returned for tests which are aborted by setting the
|
|
value of upsTestId to upsTestAbortTestInProgress.
|
|
Tests which have not yet concluded are indicated by
|
|
inProgress(5). The value noTestsInitiated(6)
|
|
indicates that no previous test results are available,
|
|
such as is the case when no tests have been run since
|
|
the last reinitialization of the network management
|
|
subsystem and the system has no provision for non-
|
|
volatile storage of test results."
|
|
::= { upsTestGroup 3 }
|
|
|
|
upsTestBatteryTestStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(1..19))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The value of the time the test in progress was initiated,
|
|
or, if no test is in progress, the time the previous test
|
|
was initiated. If the value of upsTestBatteryTestResult
|
|
is noTestsInitiated(6), upsTestStartTime has the value
|
|
01/01/1970 00:00:00."
|
|
::= { upsTestGroup 4 }
|
|
|
|
upsTestBatteryTestElapsedTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(11..11))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The amount of time, in TimeTicks, since the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the previous test took to complete. If the value of
|
|
upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestElapsedTime has the value 00:00:00.00."
|
|
::= { upsTestGroup 5 }
|
|
|
|
upsBatteryTestScheduleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBatteryTestScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table which describes the schedule for automatically battery
|
|
test."
|
|
::= { upsTestGroup 6 }
|
|
|
|
upsBatteryTestScheduleEntry OBJECT-TYPE
|
|
SYNTAX UpsBatteryTestScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION ""
|
|
INDEX { upsBatteryTestScheduleIndex }
|
|
::= { upsBatteryTestScheduleTable 1 }
|
|
|
|
UpsBatteryTestScheduleEntry ::= SEQUENCE {
|
|
upsBatteryTestScheduleIndex
|
|
INTEGER,
|
|
upsBatteryTestScheduleDay
|
|
INTEGER,
|
|
upsBatteryTestScheduleTime
|
|
DisplayString,
|
|
upsBatteryTestScheduleType
|
|
INTEGER,
|
|
upsBatteryTestScheduleTestWithTime
|
|
INTEGER,
|
|
upsBatteryTestScheduleSpecialDay
|
|
DisplayString
|
|
}
|
|
|
|
upsBatteryTestScheduleIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of battery test scheduled."
|
|
::= { upsBatteryTestScheduleEntry 1 }
|
|
|
|
upsBatteryTestScheduleDay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday(1),
|
|
monday(2),
|
|
tuesday(3),
|
|
wednesday(4),
|
|
thursday(5),
|
|
friday(6),
|
|
saturday(7),
|
|
specialDay(8),
|
|
none(9)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The weekday on which the UPS should start battery test."
|
|
::= { upsBatteryTestScheduleEntry 2 }
|
|
|
|
upsBatteryTestScheduleTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(5..5))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time that the battery test will be initiated in hh:mm format."
|
|
::= { upsBatteryTestScheduleEntry 3 }
|
|
|
|
upsBatteryTestScheduleType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
battTest10sec(2),
|
|
battTestUntilLow(3),
|
|
battTestWithTime(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The type of battery test."
|
|
::= { upsBatteryTestScheduleEntry 4 }
|
|
|
|
upsBatteryTestScheduleTestWithTime OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
supported(1),
|
|
notSupported(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The battTestWithTime of battery test is supported or not."
|
|
::= { upsBatteryTestScheduleEntry 5 }
|
|
|
|
upsBatteryTestScheduleSpecialDay OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(10..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The special day that the battery test will be initiated in dd/mm/yyyy format."
|
|
::= { upsBatteryTestScheduleEntry 6 }
|
|
|
|
-- ===========================================================================
|
|
-- upsControlGroup
|
|
--
|
|
-- ===========================================================================
|
|
|
|
upsControlUpsShutdownDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay in seconds the UPS remains on after being told
|
|
to turn off."
|
|
::= { upsControlGroup 1 }
|
|
|
|
upsControlUpsSleepTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in minutes for the UPS to go to sleep when
|
|
instructed. When in sleep mode, the UPS will not provide
|
|
output power regardless of the input line state. Once the
|
|
specified time has elapsed, output power will be restored.
|
|
|
|
This is a configuration setting. The UPS will not go to
|
|
sleep until told to do so by the manager from a management
|
|
station.
|
|
|
|
Any input value is allowed, however the UPS only recognizes
|
|
0 - 9999 minutes in one minute increments.
|
|
|
|
If the provided value is higher than the highest acceptable
|
|
value, the highest acceptable value is used."
|
|
::= { upsControlGroup 2 }
|
|
|
|
upsControlUpsOnOffControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnUpsOff(1),
|
|
putUpsToSleep(2),
|
|
turnOnUpsOrCancelShutdown(3),
|
|
none(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to control UPS output status.
|
|
turnUpsOff(1) will set UPS turn off output after
|
|
upsControlUpsShutdownDelay period expired.
|
|
putUpsToSleep(2) will set UPS turn off output after
|
|
upsControlUpsShutdownDelay period expired, UPS output
|
|
will stay off with the period defined by
|
|
upsControlUpsSleepTime, then turn output on.
|
|
turnOnUpsOrCancelShutdown(3) can used to turn on UPS
|
|
output, or cancel any shutdown process."
|
|
::= { upsControlGroup 3 }
|
|
|
|
upsControlShutdownParametersTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsControlShutdownParametersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Table which describes the parametes for shutdown process
|
|
when shutdown event occurs"
|
|
::= { upsControlGroup 4 }
|
|
|
|
upsControlShutdownParametersEntry OBJECT-TYPE
|
|
SYNTAX UpsControlShutdownParametersEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION ""
|
|
INDEX { upsControlEvent }
|
|
::= { upsControlShutdownParametersTable 1 }
|
|
|
|
UpsControlShutdownParametersEntry ::= SEQUENCE {
|
|
upsControlEvent INTEGER,
|
|
upsControlEventStatus INTEGER,
|
|
upsControlDelay INTEGER,
|
|
upsControlFirstWarning INTEGER,
|
|
upsControlWarningInterval INTEGER
|
|
}
|
|
|
|
upsControlEvent OBJECT-TYPE
|
|
-- SYNTAX DisplayString
|
|
SYNTAX INTEGER {
|
|
acFail(1),
|
|
batteryLow (2),
|
|
upsOverload (3),
|
|
upsOverTempeature (4),
|
|
weeklySchedule (5),
|
|
specialDaySchedule (6),
|
|
emdTemperatureOverThreshold (7),
|
|
emdAlarm1 (8),
|
|
emdAlarm2 (9)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The shutdown event identification "
|
|
::= { upsControlShutdownParametersEntry 1 }
|
|
|
|
upsControlEventStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
-- enable(1),
|
|
-- disable(2)
|
|
disable(1),
|
|
warning(2),
|
|
clientShutdown(3),
|
|
upsTurnOff(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Status of the corresponding shutdown Event.
|
|
When set to disable(), shutdown process will not start when
|
|
corresponding event occured."
|
|
::= { upsControlShutdownParametersEntry 2 }
|
|
|
|
upsControlDelay OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10080)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The Delay after the occurance of the curresponding shutdown
|
|
event that USHA should issue shutdown request to
|
|
connected clients. For WeeklyScheduledShutdown and
|
|
SpecialScheduledShutdown, this is the time before the
|
|
configured Shutdowntime when USHA will start sending the
|
|
warning message to the connected clients. The value is in
|
|
units of minutes."
|
|
::= { upsControlShutdownParametersEntry 3 }
|
|
|
|
upsControlFirstWarning OBJECT-TYPE
|
|
SYNTAX INTEGER (0..3600)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay after the occurance of the curresponding shutdown
|
|
event that the USHA will start sending the warning
|
|
message to the connected clients. The value is in units of
|
|
seconds"
|
|
::= { upsControlShutdownParametersEntry 4 }
|
|
|
|
upsControlWarningInterval OBJECT-TYPE
|
|
SYNTAX INTEGER (0..3600)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The frequency of sending warning messages to the connected
|
|
clients when the curresponding shutdown event occurs.
|
|
The value is in units of seconds."
|
|
::= { upsControlShutdownParametersEntry 5 }
|
|
|
|
upsControlWeeklyScheduleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsControlWeeklyScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The table to schedule shutting down the ups by weekly."
|
|
::= { upsControlGroup 5 }
|
|
|
|
upsControlWeeklyScheduleEntry OBJECT-TYPE
|
|
SYNTAX UpsControlWeeklyScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entries for each day."
|
|
INDEX { upsControlWeeklyIndex }
|
|
::= {upsControlWeeklyScheduleTable 1 }
|
|
|
|
UpsControlWeeklyScheduleEntry ::= SEQUENCE {
|
|
upsControlWeeklyIndex
|
|
INTEGER,
|
|
upsControlWeeklyShutdownDay
|
|
INTEGER,
|
|
upsControlWeeklyShutdownTime
|
|
DisplayString,
|
|
upsControlWeeklyRestartDay
|
|
INTEGER,
|
|
upsControlWeeklyRestartTime
|
|
DisplayString
|
|
}
|
|
|
|
upsControlWeeklyIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of scheduled events."
|
|
::= { upsControlWeeklyScheduleEntry 1 }
|
|
|
|
upsControlWeeklyShutdownDay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday(1),
|
|
monday(2),
|
|
tuesday(3),
|
|
wednesday(4),
|
|
thursday(5),
|
|
friday(6),
|
|
saturday(7),
|
|
none(8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The weekday on which the UPS should shut down."
|
|
::= { upsControlWeeklyScheduleEntry 2 }
|
|
|
|
upsControlWeeklyShutdownTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(5..5))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time that the process of shutting down the UPS will be initiated
|
|
in hh:mm format."
|
|
::= { upsControlWeeklyScheduleEntry 3 }
|
|
|
|
upsControlWeeklyRestartDay OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
sunday(1),
|
|
monday(2),
|
|
tuesday(3),
|
|
wednesday(4),
|
|
thursday(5),
|
|
friday(6),
|
|
saturday(7),
|
|
none(8)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The weekday on which the UPS should restart"
|
|
|
|
::= { upsControlWeeklyScheduleEntry 4 }
|
|
|
|
upsControlWeeklyRestartTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(5..5))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time the UPS will restart in hh:mm format."
|
|
::= { upsControlWeeklyScheduleEntry 5 }
|
|
|
|
upsControlSpecialScheduleTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsControlSpecialScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The table to schedule shutting down the ups."
|
|
::= { upsControlGroup 6 }
|
|
|
|
upsControlSpecialScheduleEntry OBJECT-TYPE
|
|
SYNTAX UpsControlSpecialScheduleEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The entries for each day."
|
|
INDEX { upsControlSpecialIndex }
|
|
::= {upsControlSpecialScheduleTable 1 }
|
|
|
|
UpsControlSpecialScheduleEntry ::= SEQUENCE {
|
|
upsControlSpecialIndex
|
|
INTEGER,
|
|
upsControlSpecialShutdownDay
|
|
DisplayString,
|
|
upsControlSpecialShutdownTime
|
|
DisplayString,
|
|
upsControlSpecialRestartDay
|
|
DisplayString,
|
|
upsControlSpecialRestartTime
|
|
DisplayString
|
|
}
|
|
|
|
upsControlSpecialIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of scheduled events."
|
|
::= { upsControlSpecialScheduleEntry 1 }
|
|
|
|
upsControlSpecialShutdownDay OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(10..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date on which the UPS should shut down in dd/mm/yyyy
|
|
format."
|
|
::= { upsControlSpecialScheduleEntry 2 }
|
|
|
|
upsControlSpecialShutdownTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(5..5))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time that the process of shutting down the UPS will be initiated
|
|
in hh:mm format"
|
|
::= { upsControlSpecialScheduleEntry 3 }
|
|
|
|
upsControlSpecialRestartDay OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(10..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date on which the UPS should restart in dd/mm/yyyy format"
|
|
|
|
::= { upsControlSpecialScheduleEntry 4 }
|
|
|
|
upsControlSpecialRestartTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(5..5))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time the UPS will restart in hh:mm format."
|
|
::= { upsControlSpecialScheduleEntry 5 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- upsConfigGroup
|
|
--
|
|
-- ===========================================================================
|
|
|
|
upsConfigGroupInputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage. On those
|
|
systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfigGroup 1 }
|
|
|
|
upsConfigGroupInputFreq OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal input frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfigGroup 2 }
|
|
|
|
upsConfigGroupOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage. On
|
|
those systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfigGroup 3 }
|
|
|
|
upsConfigGroupOutputFreq OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal output frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfigGroup 4 }
|
|
|
|
upsConfigGroupOutputVA OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
-- "Volt-Amps"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal Volt-Amp rating."
|
|
::= { upsConfigGroup 5 }
|
|
|
|
upsConfigGroupOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
-- "Watts"
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The magnitude of the nominal true power rating."
|
|
::= { upsConfigGroup 6 }
|
|
|
|
upsConfigGroupOverTemperatureSetPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger (10..70)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum temperature allowed before the UPS
|
|
operation temperature is too high."
|
|
::= { upsConfigGroup 7 }
|
|
|
|
upsConfigGroupOverLoadSetPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger (0..120)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum output load allowed before the load is
|
|
too high for UPS operation."
|
|
::= { upsConfigGroup 8 }
|
|
|
|
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- upsClients
|
|
--
|
|
-- ===========================================================================
|
|
|
|
upsClientsConnectedNum OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The count of clients which have resgistered for UPS
|
|
shutdown control."
|
|
::= { upsClients 1 }
|
|
|
|
upsDevicesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsDevicesEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The devices powered by UPS and registered to USHA"
|
|
-- INDEX { indexOfDevice }
|
|
::= { upsClients 2 }
|
|
|
|
upsDevicesEntry OBJECT-TYPE
|
|
SYNTAX UpsDevicesEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The devices protected by USHA"
|
|
-- INDEX { trapsIndex}
|
|
INDEX { indexOfDevice}
|
|
::= { upsDevicesTable 1 }
|
|
|
|
UpsDevicesEntry ::=
|
|
SEQUENCE {
|
|
indexOfDevice
|
|
NonNegativeInteger,
|
|
addrOfDevice
|
|
IpAddress,
|
|
nameOfDevice
|
|
DisplayString,
|
|
timeOfConnection
|
|
DisplayString,
|
|
timeOfConnectionTime
|
|
DisplayString,
|
|
timeOfConnectionTimeout
|
|
INTEGER
|
|
}
|
|
|
|
indexOfDevice OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of the device that is plugged into the UPS."
|
|
::= { upsDevicesEntry 1 }
|
|
|
|
addrOfDevice OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ip address of the device."
|
|
::= { upsDevicesEntry 2 }
|
|
|
|
nameOfDevice OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name/description of the device plugged into the UPS."
|
|
::= { upsDevicesEntry 3 }
|
|
|
|
timeOfConnection OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The device registered to USHA"
|
|
::= { upsDevicesEntry 4 }
|
|
|
|
timeOfConnectionTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The device registered time to USHA."
|
|
::= { upsDevicesEntry 5 }
|
|
|
|
timeOfConnectionTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The device timeout counter. Unit: 10 seconds"
|
|
::= { upsDevicesEntry 6 }
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- agentConfig
|
|
--
|
|
-- ===========================================================================
|
|
|
|
agentConfigIpaddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The ip address that NMS can identify the managed
|
|
device"
|
|
::= { agentConfig 1}
|
|
|
|
agentConfigGateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The default gateway that allow device managed
|
|
through routers "
|
|
::= { agentConfig 2}
|
|
|
|
agentConfigSubnetMask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" Internet address subnet mask"
|
|
::= { agentConfig 3}
|
|
|
|
agentConfigDate OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (10..10))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date in agent, format is (dd/mm/yyyy)"
|
|
::= { agentConfig 4}
|
|
|
|
agentConfigTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (8..8))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in agent, format is (hh:mm:ss)"
|
|
::= { agentConfig 5}
|
|
|
|
agentConfigPrimaryTimeServer OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The primary time server is responsible for sending the
|
|
correct time to the agent."
|
|
::= { agentConfig 6 }
|
|
|
|
agentConfigSecondaryTimeServer OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The secondary time server is responsible for sending the
|
|
correct time to the agent."
|
|
::= { agentConfig 7 }
|
|
|
|
agentConfigHistoryLogFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (5..28800) -- in seconds
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The frequency of the updation of the history log. The value
|
|
is in seconds"
|
|
::= { agentConfig 8 }
|
|
|
|
agentConfigExtHistoryLogFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (1..10080) -- in minutes
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ups parameters are sampled at the rate governed by the
|
|
mconfigHistroyLogFrequency. These sampled values are further
|
|
conslidated over period of time which is determined by this
|
|
object."
|
|
::= { agentConfig 9 }
|
|
|
|
agentConfigPollRate OBJECT-TYPE
|
|
SYNTAX INTEGER (1..999) -- in seconds
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
" The frequency that proxy agent polls the connected
|
|
UPS in JBUS protocol. (unit : second)"
|
|
::= { agentConfig 10}
|
|
|
|
agentConfigBaudRate OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The serial port communication speed. only 9600 allowed"
|
|
::= { agentConfig 11}
|
|
|
|
agentConfigDhcpStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable DHCP/BootP capability"
|
|
::= { agentConfig 12}
|
|
|
|
agentConfigTelnetStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable telnet access"
|
|
::= { agentConfig 13}
|
|
|
|
agentConfigTftpStatue OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable network upgrade capability"
|
|
::= { agentConfig 14}
|
|
|
|
agentConfigResetToDefault OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
reset(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reset all parameters of USHA to default value"
|
|
::= { agentConfig 15}
|
|
|
|
agentConfigRestart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
restart(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Restart USHA"
|
|
::= { agentConfig 16}
|
|
|
|
agentConfigClearAgentLog OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
clear(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Clear agent log data"
|
|
::= { agentConfig 17}
|
|
|
|
agentConfigClearEventLog OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
clear(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Clear event log data"
|
|
::= { agentConfig 18}
|
|
|
|
agentConfigClearExtHistoryLog OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
clear(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Clear extented history log data"
|
|
::= { agentConfig 19}
|
|
|
|
agentConfigClearHistoryLog OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
clear(1),
|
|
nothing(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Clear history log data"
|
|
::= { agentConfig 20}
|
|
|
|
agentConfigTrapRetryCount OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The count of repeat traps to send to NMS before trap
|
|
acknowledge received."
|
|
::= { agentConfig 21}
|
|
|
|
agentConfigTrapRetryTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time between retry traps sned to NMS."
|
|
::= { agentConfig 22}
|
|
|
|
agentConfigTrapAckSignature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The signature of trap acknowledge."
|
|
::= { agentConfig 23}
|
|
|
|
agentConfigMibVersion OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The version of MIB spec."
|
|
::= { agentConfig 24 }
|
|
|
|
agentConfigTrapsReceiversTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AgentConfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send traps to. The number of
|
|
entries is given by the value of agentConfigNumTrapReceivers"
|
|
::= { agentConfig 25}
|
|
|
|
agentConfigTrapsReceiversEntry OBJECT-TYPE
|
|
SYNTAX AgentConfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers to send traps to."
|
|
INDEX { trapsIndex}
|
|
::= { agentConfigTrapsReceiversTable 1 }
|
|
|
|
AgentConfigTrapsReceiversEntry ::=
|
|
SEQUENCE {
|
|
trapsIndex
|
|
INTEGER,
|
|
trapsReceiverAddr
|
|
IpAddress,
|
|
receiverCommunityString
|
|
DisplayString,
|
|
receiverNmsType
|
|
INTEGER,
|
|
receiverSeverityLevel
|
|
INTEGER,
|
|
receiverDescription
|
|
DisplayString
|
|
}
|
|
|
|
trapsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a trap receiver entry."
|
|
::= { agentConfigTrapsReceiversEntry 1 }
|
|
|
|
trapsReceiverAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to send a trap to."
|
|
::= { agentConfigTrapsReceiversEntry 2 }
|
|
|
|
receiverCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..19))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use in the trap when
|
|
sent to the manager."
|
|
::= { agentConfigTrapsReceiversEntry 3 }
|
|
|
|
receiverNmsType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
rfc1628-trap(2),
|
|
usha-trap(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The trap group that NMS desired."
|
|
::= { agentConfigTrapsReceiversEntry 4 }
|
|
|
|
receiverSeverityLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
informational(1),
|
|
warning(2),
|
|
severe(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The severity level of traps to be received by this manager."
|
|
::= { agentConfigTrapsReceiversEntry 5 }
|
|
|
|
receiverDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of trap receivers"
|
|
::= { agentConfigTrapsReceiversEntry 6 }
|
|
|
|
agentConfigAccessControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AgentConfigAccessControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers which can access USHA with private
|
|
community string."
|
|
::= { agentConfig 26}
|
|
|
|
agentConfigAccessControlEntry OBJECT-TYPE
|
|
SYNTAX AgentConfigAccessControlEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers."
|
|
INDEX { trapsIndex}
|
|
::= { agentConfigAccessControlTable 1 }
|
|
|
|
AgentConfigAccessControlEntry ::=
|
|
SEQUENCE {
|
|
accessIndex
|
|
INTEGER,
|
|
accessControlAddr
|
|
IpAddress,
|
|
accessCommunityString
|
|
DisplayString,
|
|
accessControlMode
|
|
INTEGER
|
|
}
|
|
|
|
accessIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a access control entry."
|
|
::= { agentConfigAccessControlEntry 1 }
|
|
|
|
accessControlAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to access USHA"
|
|
::= { agentConfigAccessControlEntry 2 }
|
|
|
|
accessCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..19))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use in the manager when
|
|
access USHA"
|
|
::= { agentConfigAccessControlEntry 3 }
|
|
|
|
accessControlMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
readOnly (1),
|
|
readWrite (2),
|
|
notAccess (3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Access type, only read/Write access type can change parameter
|
|
of USHA"
|
|
::= { agentConfigAccessControlEntry 4 }
|
|
|
|
agentConfigDefaultLanguage OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(1),
|
|
english(2),
|
|
traditionalChinese(3),
|
|
simplifiedChinese(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The default languauge for browser, when set to auto(1)
|
|
USHA will send page in the language depends on the
|
|
request language of browser."
|
|
::= { agentConfig 27 }
|
|
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- emdStatus
|
|
--
|
|
-- ===========================================================================
|
|
|
|
emdSatatusEmdType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
disabled(2),
|
|
emdHT(3),
|
|
emdT(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The type of EMD plugged into the port."
|
|
::= { emdStatus 1}
|
|
|
|
emdSatatusTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The measurement of EMD temperature, in 0.1 degree"
|
|
::= { emdStatus 2}
|
|
|
|
emdSatatusHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The measurement of EMD humidity, in 0.1 degree"
|
|
::= { emdStatus 3}
|
|
|
|
emdSatatusAlarm1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknow(1),
|
|
disabled(2),
|
|
active(3),
|
|
inactive(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The EMD alarm-1 status"
|
|
::= { emdStatus 4}
|
|
|
|
emdSatatusAlarm2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknow(1),
|
|
disabled(2),
|
|
active(3),
|
|
inactive(4)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The EMD alarm-2 status"
|
|
::= { emdStatus 5}
|
|
|
|
|
|
-- ===========================================================================
|
|
--
|
|
-- emdConfig
|
|
--
|
|
-- ===========================================================================
|
|
|
|
usahEmdConfigEmdConfig OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
auto(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Enable or disable to detect presence of EMD"
|
|
::= { emdConfig 1}
|
|
|
|
emdConfigEmdName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of EMD"
|
|
::= { emdConfig 2}
|
|
|
|
emdConfigTemperature OBJECT IDENTIFIER ::= { emdConfig 3 }
|
|
|
|
emdConfigTempName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of EMD temperature sensor"
|
|
::= { emdConfigTemperature 1}
|
|
|
|
emdConfigTempHighSetPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point for high temperature warning, in degrees"
|
|
::= { emdConfigTemperature 2}
|
|
|
|
emdConfigTempHighStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To enable/disable high set point check with emd temperature."
|
|
::= { emdConfigTemperature 3}
|
|
|
|
emdConfigTempLowSetPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point for low temperature warning, in degrees"
|
|
::= { emdConfigTemperature 4}
|
|
|
|
emdConfigTempLowStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To enable/disable low set point check with emd temperature."
|
|
::= { emdConfigTemperature 5}
|
|
|
|
emdConfigTempOffset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The offset to calibrate temperature of EMD, in degrees"
|
|
::= { emdConfigTemperature 6}
|
|
|
|
emdConfigHumidity OBJECT IDENTIFIER ::= { emdConfig 4 }
|
|
|
|
emdConfigHumidityName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of EMD humidity sensor"
|
|
::= { emdConfigHumidity 1}
|
|
|
|
emdConfigHumidityHighSetPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point for high humidity warning, in %"
|
|
::= { emdConfigHumidity 2}
|
|
|
|
emdConfigHumidityLowStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To enable/disable high set point check with emd humidity."
|
|
::= { emdConfigHumidity 3}
|
|
|
|
emdConfigHumidityLowSetPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The set point for low humidity warning, in %"
|
|
::= { emdConfigHumidity 4}
|
|
|
|
emdConfigHumidityHighStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"To enable/disable low set point check with emd humidity."
|
|
::= { emdConfigHumidity 5}
|
|
|
|
emdConfigHumidityOffset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The offset to calibrate humidity of EMD, in %"
|
|
::= { emdConfigHumidity 6}
|
|
|
|
emdConfigAlarm1 OBJECT IDENTIFIER ::= { emdConfig 5 }
|
|
|
|
emdConfigAlarm1Name OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of EMD alarm-1"
|
|
::= { emdConfigAlarm1 1}
|
|
|
|
emdConfigAlarm1Type OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
nomralOpen(2),
|
|
normalClose(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm-1 operation type"
|
|
::= { emdConfigAlarm1 2 }
|
|
|
|
emdConfigAlarm2 OBJECT IDENTIFIER ::= { emdConfig 6 }
|
|
|
|
emdConfigAlarm2Name OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..15))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Description of EMD alarm-2"
|
|
::= { emdConfigAlarm2 1}
|
|
|
|
emdConfigAlarm2Type OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
nomralOpen(2),
|
|
normalClose(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The alarm-1 operation type"
|
|
::= { emdConfigAlarm2 2 }
|
|
|
|
-- ===========================================================================
|
|
-- upsTrapGroup
|
|
--
|
|
-- Traps group
|
|
-- ===========================================================================
|
|
|
|
-- This section defines the well-known notifications sent by
|
|
-- UPS agents.
|
|
-- Care must be taken to insure that no particular notification
|
|
-- is sent to a single receiving entity more often than once
|
|
-- every five seconds.
|
|
|
|
ushaPowerRestored TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Utility power has been restore."
|
|
::= 1
|
|
|
|
ushaPowerFail TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Utility power not available."
|
|
::= 2
|
|
|
|
ushaReturnFromLowBattery TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has return from a low battery condition."
|
|
::= 3
|
|
|
|
ushaLowBattery TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"SEVERE: The UPS batteries are low and will soon be exhausted."
|
|
::= 4
|
|
|
|
ushaUpsOk TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The ups is working fine."
|
|
::= 5
|
|
|
|
ushaUpsFailed TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"SEVERE: The ups is not working fine."
|
|
::= 6
|
|
|
|
ushaUpsNotOnBattery TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is not on battery power."
|
|
::= 7
|
|
|
|
ushaUpsOnBattery TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
upsBatteryGroupEstimatedChargeRemaining,
|
|
upsBatteryGroupVoltage,
|
|
upsBatteryGroupSecondsOnBattery
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: The UPS has switched to battery backup power."
|
|
::= 8
|
|
|
|
ushaTestOver TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
upsBatteryTest,
|
|
upsTestBatteryTestSettingTime,
|
|
upsTestBatteryTestResult,
|
|
upsTestBatteryTestStartTime,
|
|
upsTestBatteryTestElapsedTime
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: The testing of UPS is completed."
|
|
::= 9
|
|
|
|
ushaTestInProgress TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The testing is going on ups."
|
|
::= 10
|
|
|
|
ushaBypassOn TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has enabled bypass."
|
|
::= 11
|
|
|
|
ushaUpsOnline TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is not on Bypass and return to normal status."
|
|
::= 12
|
|
|
|
ushaCommunicationLost TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"SEVERE: Communication to the UPS has been lost."
|
|
::= 13
|
|
|
|
ushaCommunicationEstablished TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the UPS has been established."
|
|
::= 14
|
|
|
|
ushaUpsGoingDown TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: The ups has been given shutdown command."
|
|
::= 15
|
|
|
|
ushaUpsTurnedOff TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: UPS turn off."
|
|
::= 16
|
|
|
|
ushaUpsSleeping TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
upsControlUpsSleepTime
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: UPS has entered sleep mode."
|
|
::= 17
|
|
|
|
ushaUpsWokeUp TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS woke up from sleep mode."
|
|
::= 18
|
|
|
|
ushaUpsRebooted TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS is reboot."
|
|
::= 19
|
|
|
|
ushaUpsShutdownCancelled TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS shutdown process had been cancelled."
|
|
::= 20
|
|
|
|
ushaUpsNotOverTemperature TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
upsBatteryGroupTemperature,
|
|
upsConfigGroupOverTemperatureSetPoint
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS internal temperature return to normal."
|
|
::= 21
|
|
|
|
ushaUpsOverTemperature TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
upsBatteryGroupTemperature,
|
|
upsConfigGroupOverTemperatureSetPoint
|
|
}
|
|
DESCRIPTION
|
|
"SEVERE: The UPS temperature is too high."
|
|
::= 22
|
|
|
|
ushaUpsNotOverLoad TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
upsOutputGroupPercentLoad,
|
|
upsConfigGroupOverLoadSetPoint
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS load return from overload."
|
|
::= 23
|
|
|
|
ushaUpsOverLoad TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
upsOutputGroupPercentLoad,
|
|
upsConfigGroupOverLoadSetPoint
|
|
}
|
|
DESCRIPTION
|
|
"SEVERE: The UPS is overload."
|
|
::= 24
|
|
|
|
ushaUpsModuleInserted TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: UPS Battery Module plug-in."
|
|
::= 25
|
|
|
|
ushaUpsModuleRemoved TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: UPS Battery Module unplug."
|
|
::= 26
|
|
|
|
emdTemperatureNotHigh TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusTemperature,
|
|
emdConfigTempHighSetPoint,
|
|
emdConfigTempName
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: EMD Temperature not over high Set point."
|
|
::= 27
|
|
|
|
emdTemperatureTooHigh TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusTemperature,
|
|
emdConfigTempHighSetPoint,
|
|
emdConfigTempName
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: EMD Temperature over high Set point."
|
|
::= 28
|
|
|
|
emdTemperatureNotLow TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusTemperature,
|
|
emdConfigTempLowSetPoint,
|
|
emdConfigTempName
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: EMD Temperature not under low Set point."
|
|
::= 29
|
|
|
|
emdTemperatureTooLow TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusTemperature,
|
|
emdConfigTempLowSetPoint,
|
|
emdConfigTempName
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: EMD Temperature under low Set point."
|
|
::= 30
|
|
|
|
emdHumidityNotHigh TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusHumidity,
|
|
emdConfigHumidityHighSetPoint,
|
|
emdConfigHumidityName
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: EMD Humidity not over high Set point."
|
|
::= 31
|
|
|
|
emdHumidityTooHigh TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusHumidity,
|
|
emdConfigHumidityHighSetPoint,
|
|
emdConfigHumidityName
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: EMD Humidity over high Set point."
|
|
::= 32
|
|
|
|
emdHumidityNotLow TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusHumidity,
|
|
emdConfigHumidityLowSetPoint,
|
|
emdConfigHumidityName
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: EMD Humidity not under low Set point."
|
|
::= 33
|
|
|
|
emdHumidityTooLow TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdSatatusHumidity,
|
|
emdConfigHumidityLowSetPoint,
|
|
emdConfigHumidityName
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: EMD Humidity under low Set point."
|
|
::= 34
|
|
|
|
emdAlarm1Normal TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdConfigAlarm1Type,
|
|
emdConfigAlarm1Name
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: EMD Alarm-1 not active."
|
|
::= 35
|
|
|
|
emdAlarm1Active TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdConfigAlarm1Type,
|
|
emdConfigAlarm1Name
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: EMD Alarm-1 activated."
|
|
::= 36
|
|
|
|
emdAlarm2Normal TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdConfigAlarm2Type,
|
|
emdConfigAlarm2Name
|
|
}
|
|
DESCRIPTION
|
|
"INFORMATION: EMD Alarm-2 not active."
|
|
::= 37
|
|
|
|
emdAlarm2Active TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
VARIABLES {
|
|
emdConfigAlarm2Type,
|
|
emdConfigAlarm2Name
|
|
}
|
|
DESCRIPTION
|
|
"WARNING: EMD Alarm-2 activated."
|
|
::= 38
|
|
|
|
ushaUpsInternalwarning TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Internal warning."
|
|
::= 39
|
|
|
|
ushaUpsReturnFromInternalwarning TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Internal warning."
|
|
::= 40
|
|
|
|
ushaUpsEPOActive TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: EPO Active."
|
|
::= 41
|
|
|
|
ushaUpsReturnFromEPOActive TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from EPO Active."
|
|
::= 42
|
|
|
|
ushaUpsModuleUnlock TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Module Unlock."
|
|
::= 43
|
|
|
|
ushaUpsReturnFromModuleUnlock TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Module Unlock."
|
|
::= 44
|
|
|
|
ushaUpsMain1Neutralloss TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Main 1 Neutral loss."
|
|
::= 45
|
|
|
|
ushaUpsReturnFromMain1Neutralloss TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Main 1 Neutral loss."
|
|
::= 46
|
|
|
|
ushaUpsMain1phaseerror TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Main 1 phase error."
|
|
::= 47
|
|
|
|
ushaUpsReturnFromMain1phaseerror TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Main 1 phase error."
|
|
::= 48
|
|
|
|
ushaUpsSitefault TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Site fault."
|
|
::= 49
|
|
|
|
ushaUpsReturnFromSitefault TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Site fault."
|
|
::= 50
|
|
|
|
ushaUpsBypassAbnormal TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Bypass Abnormal."
|
|
::= 51
|
|
|
|
ushaUpsReturnFromBypassAbnormal TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Bypass Abnormal."
|
|
::= 52
|
|
|
|
ushaUpsBypassPhaseError TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Bypass Phase Error."
|
|
::= 53
|
|
|
|
ushaUpsReturnFromBypassPhaseError TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Bypass Phase Error."
|
|
::= 54
|
|
|
|
ushaUpsBatteryOpen TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Battery Open."
|
|
::= 55
|
|
|
|
ushaUpsReturnFromBatteryOpen TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Battery Open."
|
|
::= 56
|
|
|
|
ushaUpsBatteryOverCharge TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Battery Over Charge."
|
|
::= 57
|
|
|
|
ushaUpsReturnFromBatteryOverCharge TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Battery Over Charge."
|
|
::= 58
|
|
|
|
ushaUpsBatteryReverse TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Battery Reverse."
|
|
::= 59
|
|
|
|
ushaUpsReturnFromBatteryReverse TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Battery Reverse."
|
|
::= 60
|
|
|
|
ushaUpsOverloadforewarning TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Overload forewarning."
|
|
::= 61
|
|
|
|
ushaUpsReturnFromOverloadforewarning TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Overload forewarning."
|
|
::= 62
|
|
|
|
ushaUpsOverloadWarning TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Overload Warning."
|
|
::= 63
|
|
|
|
ushaUpsReturnFromOverloadWarning TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Overload Warning."
|
|
::= 64
|
|
|
|
ushaUpsFanLock TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Fan Lock."
|
|
::= 65
|
|
|
|
ushaUpsReturnFromFanLock TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Fan Lock."
|
|
::= 66
|
|
|
|
ushaUpsMaintaincoverisopen TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Maintain cover is open."
|
|
::= 67
|
|
|
|
ushaUpsReturnFromMaintaincoverisopen TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Maintain cover is open."
|
|
::= 68
|
|
|
|
ushaUpsChargerfault TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Charger fault."
|
|
::= 69
|
|
|
|
ushaUpsReturnFromChargerfault TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Charger fault."
|
|
::= 70
|
|
|
|
ushaUpsModulelocationerror TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Module location error."
|
|
::= 71
|
|
|
|
ushaUpsReturnFromModulelocationerror TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Module location error."
|
|
::= 72
|
|
|
|
ushaUpsTurnonabnormal TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Turn on abnormal."
|
|
::= 73
|
|
|
|
ushaUpsReturnFromTurnonabnormal TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Turn on abnormal."
|
|
::= 74
|
|
|
|
ushaUpsRedundancyloss TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Redundancy loss."
|
|
::= 75
|
|
|
|
ushaUpsReturnFromRedundancyloss TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Redundancy loss."
|
|
::= 76
|
|
|
|
ushaUpsHotSwapActived TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Hot Swap Actived."
|
|
::= 77
|
|
|
|
ushaUpsReturnFromHotSwapActived TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Hot Swap Actived."
|
|
::= 78
|
|
|
|
ushaUpsBatteryInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Battery Inform."
|
|
::= 79
|
|
|
|
ushaUpsReturnFromBatteryInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Battery Inform."
|
|
::= 80
|
|
|
|
ushaUpsInspectionInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Inspection Inform."
|
|
::= 81
|
|
|
|
ushaUpsReturnFromInspectionInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Inspection Inform."
|
|
::= 82
|
|
|
|
ushaUpsGuaranteeInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Guarantee Inform."
|
|
::= 83
|
|
|
|
ushaUpsReturnFromGuaranteeInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Guarantee Inform."
|
|
::= 84
|
|
|
|
ushaUpsTemperatureLow TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Temperature Low."
|
|
::= 85
|
|
|
|
ushaUpsReturnFromTemperatureLow TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Temperature Low."
|
|
::= 86
|
|
|
|
ushaUpsTemperatureHigh TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Temperature High."
|
|
::= 87
|
|
|
|
ushaUpsReturnFromTemperatureHigh TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Temperature High."
|
|
::= 88
|
|
|
|
ushaUpsBatteryOverTemperature TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Battery Over Temperature."
|
|
::= 89
|
|
|
|
ushaUpsReturnFromBatteryOverTemperature TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Battery Over Temperature."
|
|
::= 90
|
|
|
|
ushaUpsFanMaintainInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Fan Maintain Inform."
|
|
::= 91
|
|
|
|
ushaUpsReturnFromFanMaintainInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Fan Maintain Inform."
|
|
::= 92
|
|
|
|
ushaUpsBusCapacitanceMaintainInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: Bus Capacitance Maintain Inform."
|
|
::= 93
|
|
|
|
ushaUpsReturnFromBusCapacitanceMaintainInform TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from Bus Capacitance Maintain Inform."
|
|
::= 94
|
|
|
|
ushaUpsSystemOverCapacity TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"WARNING: System Over Capacity."
|
|
::= 95
|
|
|
|
ushaUpsReturnFromSystemOverCapacity TRAP-TYPE
|
|
ENTERPRISE upsTrapGroup
|
|
DESCRIPTION
|
|
"INFORMATION: Return from System Over Capacity."
|
|
::= 96
|
|
|
|
END
|