DigiPower-PDU-MIB DEFINITIONS ::= BEGIN
IMPORTS
TRAP-TYPE
FROM RFC-1215
DisplayString
FROM RFC1213-MIB
OBJECT-TYPE
FROM RFC-1212
enterprises
FROM RFC1155-SMI;
digipower OBJECT IDENTIFIER ::= { enterprises 17420 }
products OBJECT IDENTIFIER ::= { digipower 1 }
devTable OBJECT IDENTIFIER ::= { products 2 }
envthreshold OBJECT IDENTIFIER ::= { products 4 }
-- DEV basic information --
devID OBJECT-TYPE
SYNTAX INTEGER (1..16)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The ID number of dev."
::= { devTable 1 }
devIP OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current IP address, netmask, default gateway, and DNS server."
::= { devTable 2 }
devMAC OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate current MAC address."
::= { devTable 3 }
devVersion OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate current firmware version."
::= { devTable 4 }
devInfo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the count of attached PDUs and their id."
::= { devTable 5 }
devValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the PDU values (currents) from PDU1 to PDU16"
::= { devTable 6 }
devTemperature OBJECT-TYPE
SYNTAX INTEGER (-50..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the PDU temperature in Celsius degree"
::= { devTable 7 }
devHumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the PDU humidity in percentage (%)"
::= { devTable 8 }
pduTable OBJECT IDENTIFIER ::= { devTable 9 }
-- PDU entries --
-- PDU01 --
pdu01Entry OBJECT IDENTIFIER ::= { pduTable 1 }
pdu01Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-01 detect."
::= { pdu01Entry 11 }
pdu01SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu01Entry 12 }
pdu01OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu01Entry 13 }
pdu01OutletConfigs OBJECT IDENTIFIER ::= { pdu01Entry 14 }
pdu01Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu01OutletConfigs 1 }
pdu01Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu01OutletConfigs 2 }
pdu01Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu01OutletConfigs 3 }
pdu01Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu01OutletConfigs 4 }
pdu01Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu01OutletConfigs 5 }
pdu01Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu01OutletConfigs 6 }
pdu01Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu01OutletConfigs 7 }
pdu01Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu01OutletConfigs 8 }
pdu01Outlet9Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet9"
::= { pdu01OutletConfigs 9 }
pdu01Outlet10Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet10"
::= { pdu01OutletConfigs 10 }
pdu01Outlet11Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet11"
::= { pdu01OutletConfigs 11 }
pdu01Outlet12Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet12"
::= { pdu01OutletConfigs 12 }
pdu01Outlet13Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet13"
::= { pdu01OutletConfigs 13 }
pdu01Outlet14Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet14"
::= { pdu01OutletConfigs 14 }
pdu01Outlet15Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet15"
::= { pdu01OutletConfigs 15 }
pdu01Outlet16Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet16"
::= { pdu01OutletConfigs 16 }
pdu01Outlet17Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet17"
::= { pdu01OutletConfigs 17 }
pdu01Outlet18Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet18"
::= { pdu01OutletConfigs 18 }
pdu01Outlet19Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet19"
::= { pdu01OutletConfigs 19 }
pdu01Outlet20Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet20"
::= { pdu01OutletConfigs 20 }
pdu01Outlet21Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet21"
::= { pdu01OutletConfigs 21 }
pdu01Outlet22Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet22"
::= { pdu01OutletConfigs 22 }
pdu01Outlet23Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet23"
::= { pdu01OutletConfigs 23 }
pdu01Outlet24Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet24"
::= { pdu01OutletConfigs 24 }
pdu01Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu01Entry 15 }
pdu01Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu01Entry 16 }
pdu01Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu01Entry 17 }
pdu01ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu01Entry 18 }
pdu01ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu01Entry 19 }
pdu01Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu01Entry 20 }
pdu01DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu01Entry 21 }
pdu01DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu01Entry 22 }
-- PDU02 --
pdu02Entry OBJECT IDENTIFIER ::= { pduTable 2 }
pdu02Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-02 detect."
::= { pdu02Entry 11 }
pdu02SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu02Entry 12 }
pdu02OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu02Entry 13 }
pdu02OutletConfigs OBJECT IDENTIFIER ::= { pdu02Entry 14 }
pdu02Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu02OutletConfigs 1 }
pdu02Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu02OutletConfigs 2 }
pdu02Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu02OutletConfigs 3 }
pdu02Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu02OutletConfigs 4 }
pdu02Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu02OutletConfigs 5 }
pdu02Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu02OutletConfigs 6 }
pdu02Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu02OutletConfigs 7 }
pdu02Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu02OutletConfigs 8 }
pdu02Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu02Entry 15 }
pdu02Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu02Entry 16 }
pdu02Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu02Entry 17 }
pdu02ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu02Entry 18 }
pdu02ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu02Entry 19 }
pdu02Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu02Entry 20 }
pdu02DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..128))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu02Entry 21 }
pdu02DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu02Entry 22 }
-- PDU03 --
pdu03Entry OBJECT IDENTIFIER ::= { pduTable 3 }
pdu03Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-03 detect."
::= { pdu03Entry 11 }
pdu03SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu03Entry 12 }
pdu03OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu03Entry 13 }
pdu03OutletConfigs OBJECT IDENTIFIER ::= { pdu03Entry 14 }
pdu03Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu03OutletConfigs 1 }
pdu03Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu03OutletConfigs 2 }
pdu03Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu03OutletConfigs 3 }
pdu03Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu03OutletConfigs 4 }
pdu03Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu03OutletConfigs 5 }
pdu03Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu03OutletConfigs 6 }
pdu03Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu03OutletConfigs 7 }
pdu03Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu03OutletConfigs 8 }
pdu03Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu03Entry 15 }
pdu03Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu03Entry 16 }
pdu03Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu03Entry 17 }
pdu03ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu03Entry 18 }
pdu03ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu03Entry 19 }
pdu03Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu03Entry 20 }
pdu03DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu03Entry 21 }
pdu03DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu03Entry 22 }
-- PDU04 --
pdu04Entry OBJECT IDENTIFIER ::= { pduTable 4 }
pdu04Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-04 detect."
::= { pdu04Entry 11 }
pdu04SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu04Entry 12 }
pdu04OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu04Entry 13 }
pdu04OutletConfigs OBJECT IDENTIFIER ::= { pdu04Entry 14 }
pdu04Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu04OutletConfigs 1 }
pdu04Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu04OutletConfigs 2 }
pdu04Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu04OutletConfigs 3 }
pdu04Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu04OutletConfigs 4 }
pdu04Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu04OutletConfigs 5 }
pdu04Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu04OutletConfigs 6 }
pdu04Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu04OutletConfigs 7 }
pdu04Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu04OutletConfigs 8 }
pdu04Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu04Entry 15 }
pdu04Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu04Entry 16 }
pdu04Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu04Entry 17 }
pdu04ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu04Entry 18 }
pdu04ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu04Entry 19 }
pdu04Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu04Entry 20 }
pdu04DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu04Entry 21 }
pdu04DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu04Entry 22 }
-- PDU05 --
pdu05Entry OBJECT IDENTIFIER ::= { pduTable 5 }
pdu05Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-05 detect."
::= { pdu05Entry 11 }
pdu05SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu05Entry 12 }
pdu05OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu05Entry 13 }
pdu05OutletConfigs OBJECT IDENTIFIER ::= { pdu05Entry 14 }
pdu05Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu05OutletConfigs 1 }
pdu05Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu05OutletConfigs 2 }
pdu05Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu05OutletConfigs 3 }
pdu05Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu05OutletConfigs 4 }
pdu05Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu05OutletConfigs 5 }
pdu05Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu05OutletConfigs 6 }
pdu05Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu05OutletConfigs 7 }
pdu05Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu05OutletConfigs 8 }
pdu05Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu05Entry 15 }
pdu05Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu05Entry 16 }
pdu05Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu05Entry 17 }
pdu05ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu05Entry 18 }
pdu05ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu05Entry 19 }
pdu05Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu05Entry 20 }
pdu05DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu05Entry 21 }
pdu05DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu05Entry 22 }
-- PDU06 --
pdu06Entry OBJECT IDENTIFIER ::= { pduTable 6 }
pdu06Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-06 detect."
::= { pdu06Entry 11 }
pdu06SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu06Entry 12 }
pdu06OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu06Entry 13 }
pdu06OutletConfigs OBJECT IDENTIFIER ::= { pdu06Entry 14 }
pdu06Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu06OutletConfigs 1 }
pdu06Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu06OutletConfigs 2 }
pdu06Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu06OutletConfigs 3 }
pdu06Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu06OutletConfigs 4 }
pdu06Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu06OutletConfigs 5 }
pdu06Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu06OutletConfigs 6 }
pdu06Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu06OutletConfigs 7 }
pdu06Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu06OutletConfigs 8 }
pdu06Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu06Entry 15 }
pdu06Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu06Entry 16 }
pdu06Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu06Entry 17 }
pdu06ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu06Entry 18 }
pdu06ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu06Entry 19 }
pdu06Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu06Entry 20 }
pdu06DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu06Entry 21 }
pdu06DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu06Entry 22 }
-- PDU07 --
pdu07Entry OBJECT IDENTIFIER ::= { pduTable 7 }
pdu07Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-07 detect."
::= { pdu07Entry 11 }
pdu07SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu07Entry 12 }
pdu07OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu07Entry 13 }
pdu07OutletConfigs OBJECT IDENTIFIER ::= { pdu07Entry 14 }
pdu07Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu07OutletConfigs 1 }
pdu07Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu07OutletConfigs 2 }
pdu07Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu07OutletConfigs 3 }
pdu07Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu07OutletConfigs 4 }
pdu07Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu07OutletConfigs 5 }
pdu07Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu07OutletConfigs 6 }
pdu07Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu07OutletConfigs 7 }
pdu07Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu07OutletConfigs 8 }
pdu07Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu07Entry 15 }
pdu07Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu07Entry 16 }
pdu07Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu07Entry 17 }
pdu07ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu07Entry 18 }
pdu07ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu07Entry 19 }
pdu07Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu07Entry 20 }
pdu07DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu07Entry 21 }
pdu07DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu07Entry 22 }
-- PDU08 --
pdu08Entry OBJECT IDENTIFIER ::= { pduTable 8 }
pdu08Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-08 detect."
::= { pdu08Entry 11 }
pdu08SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu08Entry 12 }
pdu08OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu08Entry 13 }
pdu08OutletConfigs OBJECT IDENTIFIER ::= { pdu08Entry 14 }
pdu08Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu08OutletConfigs 1 }
pdu08Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu08OutletConfigs 2 }
pdu08Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu08OutletConfigs 3 }
pdu08Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu08OutletConfigs 4 }
pdu08Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu08OutletConfigs 5 }
pdu08Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu08OutletConfigs 6 }
pdu08Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu08OutletConfigs 7 }
pdu08Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu08OutletConfigs 8 }
pdu08Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu08Entry 15 }
pdu08Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu08Entry 16 }
pdu08Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu08Entry 17 }
pdu08ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu08Entry 18 }
pdu08ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu08Entry 19 }
pdu08Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu08Entry 20 }
pdu08DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu08Entry 21 }
pdu08DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu08Entry 22 }
-- PDU09 --
pdu09Entry OBJECT IDENTIFIER ::= { pduTable 9 }
pdu09Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-09 detect."
::= { pdu09Entry 11 }
pdu09SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu09Entry 12 }
pdu09OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu09Entry 13 }
pdu09OutletConfigs OBJECT IDENTIFIER ::= { pdu09Entry 14 }
pdu09Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu09OutletConfigs 1 }
pdu09Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu09OutletConfigs 2 }
pdu09Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu09OutletConfigs 3 }
pdu09Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu09OutletConfigs 4 }
pdu09Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu09OutletConfigs 5 }
pdu09Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu09OutletConfigs 6 }
pdu09Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu09OutletConfigs 7 }
pdu09Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu09OutletConfigs 8 }
pdu09Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu09Entry 15 }
pdu09Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu09Entry 16 }
pdu09Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu09Entry 17 }
pdu09ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu09Entry 18 }
pdu09ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu09Entry 19 }
pdu09Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu09Entry 20 }
pdu09DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu09Entry 21 }
pdu09DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu09Entry 22 }
-- PDU10 --
pdu10Entry OBJECT IDENTIFIER ::= { pduTable 10 }
pdu10Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-10 detect."
::= { pdu10Entry 11 }
pdu10SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu10Entry 12 }
pdu10OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu10Entry 13 }
pdu10OutletConfigs OBJECT IDENTIFIER ::= { pdu10Entry 14 }
pdu10Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu10OutletConfigs 1 }
pdu10Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu10OutletConfigs 2 }
pdu10Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu10OutletConfigs 3 }
pdu10Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu10OutletConfigs 4 }
pdu10Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu10OutletConfigs 5 }
pdu10Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu10OutletConfigs 6 }
pdu10Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu10OutletConfigs 7 }
pdu10Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu10OutletConfigs 8 }
pdu10Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu10Entry 15 }
pdu10Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu10Entry 16 }
pdu10Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu10Entry 17 }
pdu10ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu10Entry 18 }
pdu10ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu10Entry 19 }
pdu10Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu10Entry 20 }
pdu10DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu10Entry 21 }
pdu10DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu10Entry 22 }
-- PDU11 --
pdu11Entry OBJECT IDENTIFIER ::= { pduTable 11 }
pdu11Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-11 detect."
::= { pdu11Entry 11 }
pdu11SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu11Entry 12 }
pdu11OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu11Entry 13 }
pdu11OutletConfigs OBJECT IDENTIFIER ::= { pdu11Entry 14 }
pdu11Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu11OutletConfigs 1 }
pdu11Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu11OutletConfigs 2 }
pdu11Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu11OutletConfigs 3 }
pdu11Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu11OutletConfigs 4 }
pdu11Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu11OutletConfigs 5 }
pdu11Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu11OutletConfigs 6 }
pdu11Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu11OutletConfigs 7 }
pdu11Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu11OutletConfigs 8 }
pdu11Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu11Entry 15 }
pdu11Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu11Entry 16 }
pdu11Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu11Entry 17 }
pdu11ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu11Entry 18 }
pdu11ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu11Entry 19 }
pdu11Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu11Entry 20 }
pdu11DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu11Entry 21 }
pdu11DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu11Entry 22 }
-- PDU12 --
pdu12Entry OBJECT IDENTIFIER ::= { pduTable 12 }
pdu12Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-12 detect."
::= { pdu12Entry 11 }
pdu12SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu12Entry 12 }
pdu12OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu12Entry 13 }
pdu12OutletConfigs OBJECT IDENTIFIER ::= { pdu12Entry 14 }
pdu12Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu12OutletConfigs 1 }
pdu12Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu12OutletConfigs 2 }
pdu12Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu12OutletConfigs 3 }
pdu12Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu12OutletConfigs 4 }
pdu12Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu12OutletConfigs 5 }
pdu12Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu12OutletConfigs 6 }
pdu12Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu12OutletConfigs 7 }
pdu12Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu12OutletConfigs 8 }
pdu12Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu12Entry 15 }
pdu12Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu12Entry 16 }
pdu12Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu12Entry 17 }
pdu12ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu12Entry 18 }
pdu12ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu12Entry 19 }
pdu12Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu12Entry 20 }
pdu12DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu12Entry 21 }
pdu12DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu12Entry 22 }
-- PDU13 --
pdu13Entry OBJECT IDENTIFIER ::= { pduTable 13 }
pdu13Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-13 detect."
::= { pdu13Entry 11 }
pdu13SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu13Entry 12 }
pdu13OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu13Entry 13 }
pdu13OutletConfigs OBJECT IDENTIFIER ::= { pdu13Entry 14 }
pdu13Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu13OutletConfigs 1 }
pdu13Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu13OutletConfigs 2 }
pdu13Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu13OutletConfigs 3 }
pdu13Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu13OutletConfigs 4 }
pdu13Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu13OutletConfigs 5 }
pdu13Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu13OutletConfigs 6 }
pdu13Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu13OutletConfigs 7 }
pdu13Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu13OutletConfigs 8 }
pdu13Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu13Entry 15 }
pdu13Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu13Entry 16 }
pdu13Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu13Entry 17 }
pdu13ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu13Entry 18 }
pdu13ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu13Entry 19 }
pdu13Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu13Entry 20 }
pdu13DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu13Entry 21 }
pdu13DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu13Entry 22 }
-- PDU14 --
pdu14Entry OBJECT IDENTIFIER ::= { pduTable 14 }
pdu14Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-14 detect."
::= { pdu14Entry 11 }
pdu14SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu14Entry 12 }
pdu14OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu14Entry 13 }
pdu14OutletConfigs OBJECT IDENTIFIER ::= { pdu14Entry 14 }
pdu14Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu14OutletConfigs 1 }
pdu14Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu14OutletConfigs 2 }
pdu14Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu14OutletConfigs 3 }
pdu14Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu14OutletConfigs 4 }
pdu14Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu14OutletConfigs 5 }
pdu14Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu14OutletConfigs 6 }
pdu14Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu14OutletConfigs 7 }
pdu14Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu14OutletConfigs 8 }
pdu14Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu14Entry 15 }
pdu14Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu14Entry 16 }
pdu14Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu14Entry 17 }
pdu14ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu14Entry 18 }
pdu14ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu14Entry 19 }
pdu14Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu14Entry 20 }
pdu14DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu14Entry 21 }
pdu14DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu14Entry 22 }
-- PDU15 --
pdu15Entry OBJECT IDENTIFIER ::= { pduTable 15 }
pdu15Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-15 detect."
::= { pdu15Entry 11 }
pdu15SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu15Entry 12 }
pdu15OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu15Entry 13 }
pdu15OutletConfigs OBJECT IDENTIFIER ::= { pdu15Entry 14 }
pdu15Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu15OutletConfigs 1 }
pdu15Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu15OutletConfigs 2 }
pdu15Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu15OutletConfigs 3 }
pdu15Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu15OutletConfigs 4 }
pdu15Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu15OutletConfigs 5 }
pdu15Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu15OutletConfigs 6 }
pdu15Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu15OutletConfigs 7 }
pdu15Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu15OutletConfigs 8 }
pdu15Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu15Entry 15 }
pdu15Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu15Entry 16 }
pdu15Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu15Entry 17 }
pdu15ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu15Entry 18 }
pdu15ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu15Entry 19 }
pdu15Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu15Entry 20 }
pdu15DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu15Entry 21 }
pdu15DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu15Entry 22 }
-- PDU16 --
pdu16Entry OBJECT IDENTIFIER ::= { pduTable 16 }
pdu16Value OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the current of PDU-16 detect."
::= { pdu16Entry 11 }
pdu16SubValues OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate the outlet values (currents) from Outlet1 to Outlet8"
::= { pdu16Entry 12 }
pdu16OutletStatus OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the outlet statuses (On or Off) from Outlet1 to Outlet8
1: Outlet ON
0: Outlet OFF
-1: Outlet is not available
-2: Outlet powr lost or Breaker triggered"
::= { pdu16Entry 13 }
pdu16OutletConfigs OBJECT IDENTIFIER ::= { pdu16Entry 14 }
pdu16Outlet1Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet1"
::= { pdu16OutletConfigs 1 }
pdu16Outlet2Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet2"
::= { pdu16OutletConfigs 2 }
pdu16Outlet3Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet3"
::= { pdu16OutletConfigs 3 }
pdu16Outlet4Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet4"
::= { pdu16OutletConfigs 4 }
pdu16Outlet5Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet5"
::= { pdu16OutletConfigs 5 }
pdu16Outlet6Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet6"
::= { pdu16OutletConfigs 6 }
pdu16Outlet7Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet7"
::= { pdu16OutletConfigs 7 }
pdu16Outlet8Config OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..64))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate the configuration of Outlet8"
::= { pdu16OutletConfigs 8 }
pdu16Threshold1 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 1 (warning current)."
::= { pdu16Entry 15 }
pdu16Threshold2 OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate current threshold 2 (critical current)."
::= { pdu16Entry 16 }
pdu16Voltage OBJECT-TYPE
SYNTAX INTEGER (0..999)
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate voltage of PDU."
::= { pdu16Entry 17 }
pdu16ModelName OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model name."
::= { pdu16Entry 18 }
pdu16ModelNo OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-only
STATUS mandatory
DESCRIPTION
"Indicate PDU model number."
::= { pdu16Entry 19 }
pdu16Identify OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU identify."
::= { pdu16Entry 20 }
pdu16DelayOn OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet On delay time. Unit is second "
::= { pdu16Entry 21 }
pdu16DelayOff OBJECT-TYPE
SYNTAX DisplayString (SIZE (0..32))
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate PDU Outlet Off delay time. Unit is second "
::= { pdu16Entry 22 }
-- ENV Threshold information --
tempLower OBJECT-TYPE
SYNTAX INTEGER (1..16)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate temperature lower threshold"
::= { envthreshold 42 }
tempUpper OBJECT-TYPE
SYNTAX INTEGER (1..16)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate temperature upper threshold"
::= { envthreshold 43 }
humidityLower OBJECT-TYPE
SYNTAX INTEGER (1..16)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate humidity lower threshold"
::= { envthreshold 44 }
humidityLower OBJECT-TYPE
SYNTAX INTEGER (1..16)
ACCESS read-write
STATUS mandatory
DESCRIPTION
"Indicate humidity upper threshold"
::= { envthreshold 45 }
--dev traps ----------------------------------------------------------------
--pdu01TrapEntry TRAP-TYPE
-- ENTERPRISE digipower
-- ACCESS not-accessible
-- STATUS mandatory
-- DESCRIPTION
-- "An entry containing trap information of PDU-01."
-- ::= 1
--pdu01CommunicationLost TRAP-TYPE
-- SYNTAX pdu01CommunicationLost
-- DESCRIPTION
-- "PDU-01 communication lost."
-- :: = { pdu01TrapEntry 19 }
devOutOfThreshold1 TRAP-TYPE
ENTERPRISE digipower
DESCRIPTION
"WARNING: DEV current out of threshold 1."
::= 105
devOutOfThreshold2 TRAP-TYPE
ENTERPRISE digipower
DESCRIPTION
"CRITICAL: DEV current out of threshold 2."
::= 106
--devCommunicationLost TRAP-TYPE
-- ENTERPRISE digipower
-- DESCRIPTION
-- "CRITICAL: DEV Communication lost."
-- ::= 107
devBackToNormal TRAP-TYPE
ENTERPRISE digipower
DESCRIPTION
"NORMAL: DEV back to normal states"
::= 108
END