- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
2349 lines
64 KiB
Text
2349 lines
64 KiB
Text
--PPC-MIB { iso(1) org(3) dod(6) internet(1) private(4)
|
|
-- enterprises(1) ppc(935) }
|
|
-- Title: PPC TOP LEVEL MIB
|
|
-- Date: January 07, 1994 Version 1.00
|
|
--
|
|
-- Date: January 17, 1994 Version 1.01
|
|
--
|
|
-- Date: July 14, 1994 Version 1.02
|
|
--
|
|
-- Date: May 16, 2003 Version 2.00
|
|
|
|
XPPC-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
DisplayString
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC-1212
|
|
enterprises,
|
|
IpAddress
|
|
FROM RFC1155-SMI;
|
|
|
|
|
|
ppc OBJECT IDENTIFIER
|
|
::= { enterprises 935 }
|
|
|
|
products OBJECT IDENTIFIER
|
|
::= { ppc 1 }
|
|
|
|
ppcmgmt OBJECT IDENTIFIER
|
|
::= { ppc 2 }
|
|
|
|
hardware OBJECT IDENTIFIER
|
|
::= { products 1 }
|
|
|
|
mconfig OBJECT IDENTIFIER
|
|
::= { ppcmgmt 1 }
|
|
|
|
ups OBJECT IDENTIFIER
|
|
::= { hardware 1 }
|
|
|
|
upsIdentp OBJECT IDENTIFIER
|
|
::= { ups 1 }
|
|
|
|
upsBatteryp OBJECT IDENTIFIER
|
|
::= { ups 2 }
|
|
|
|
upsInputp OBJECT IDENTIFIER
|
|
::= { ups 3 }
|
|
|
|
upsOutputp OBJECT IDENTIFIER
|
|
::= { ups 4 }
|
|
|
|
upsConfigp OBJECT IDENTIFIER
|
|
::= { ups 5 }
|
|
|
|
upsControlp OBJECT IDENTIFIER
|
|
::= { ups 6 }
|
|
|
|
upsTestp OBJECT IDENTIFIER
|
|
::= { ups 7 }
|
|
|
|
upsThreePhase OBJECT IDENTIFIER
|
|
::= { ups 8 }
|
|
|
|
upsEnvironment OBJECT IDENTIFIER
|
|
::= { ups 9 }
|
|
|
|
upsBaseIdent OBJECT IDENTIFIER
|
|
::= { upsIdentp 1 }
|
|
|
|
upsSmartIdent OBJECT IDENTIFIER
|
|
::= { upsIdentp 2 }
|
|
|
|
upsBaseBattery OBJECT IDENTIFIER
|
|
::= { upsBatteryp 1 }
|
|
|
|
upsSmartBattery OBJECT IDENTIFIER
|
|
::= { upsBatteryp 2 }
|
|
|
|
upsBaseInput OBJECT IDENTIFIER
|
|
::= { upsInputp 1 }
|
|
|
|
upsSmartInput OBJECT IDENTIFIER
|
|
::= { upsInputp 2 }
|
|
|
|
upsBaseOutput OBJECT IDENTIFIER
|
|
::= { upsOutputp 1 }
|
|
|
|
upsSmartOutput OBJECT IDENTIFIER
|
|
::= { upsOutputp 2 }
|
|
|
|
upsBaseConfig OBJECT IDENTIFIER
|
|
::= { upsConfigp 1 }
|
|
|
|
upsSmartConfig OBJECT IDENTIFIER
|
|
::= { upsConfigp 2 }
|
|
|
|
upsBaseControl OBJECT IDENTIFIER
|
|
::= { upsControlp 1 }
|
|
|
|
upsSmartControl OBJECT IDENTIFIER
|
|
::= { upsControlp 2 }
|
|
|
|
upsBaseTest OBJECT IDENTIFIER
|
|
::= { upsTestp 1 }
|
|
|
|
upsSmartTest OBJECT IDENTIFIER
|
|
::= { upsTestp 2 }
|
|
|
|
upsThreePhaseBatteryGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 1 }
|
|
|
|
upsThreePhaseInputGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 2 }
|
|
|
|
upsThreePhaseOutputGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 3 }
|
|
|
|
upsThreePhaseBypassGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 4 }
|
|
|
|
upsThreePhaseDCandRectifierStatusGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 5 }
|
|
|
|
upsThreePhaseUPSStatusGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 6 }
|
|
|
|
upsThreePhaseFaultStatusGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 7 }
|
|
|
|
upsThreePhaseRatingGrp OBJECT IDENTIFIER
|
|
::= { upsThreePhase 8 }
|
|
|
|
-- object types
|
|
-- the ppcmgmt group
|
|
-- the mconfig group
|
|
|
|
mconfigTrapsReceiversNum OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of managers to send traps to."
|
|
::= { mconfig 1 }
|
|
|
|
|
|
mconfigTrapsReceiversTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF MconfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of managers to send traps to. The number of
|
|
entries is given by the value of mconfigNumTrapReceivers"
|
|
::= { mconfig 2 }
|
|
|
|
|
|
mconfigTrapsReceiversEntry OBJECT-TYPE
|
|
SYNTAX MconfigTrapsReceiversEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The managers to send traps to."
|
|
INDEX {
|
|
trapsIndex }
|
|
::= { mconfigTrapsReceiversTable 1 }
|
|
|
|
|
|
MconfigTrapsReceiversEntry ::= SEQUENCE {
|
|
trapsIndex INTEGER,
|
|
trapsReceiverAddr IpAddress,
|
|
receiverCommunityString DisplayString,
|
|
severityLevel INTEGER,
|
|
receiverAccept INTEGER }
|
|
|
|
|
|
trapsIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index to a trap receiver entry."
|
|
::= { mconfigTrapsReceiversEntry 1 }
|
|
|
|
|
|
trapsReceiverAddr OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The IP address of the manager to send a trap to."
|
|
::= { mconfigTrapsReceiversEntry 2 }
|
|
|
|
|
|
receiverCommunityString OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The community name to use in the trap when
|
|
sent to the manager."
|
|
::= { mconfigTrapsReceiversEntry 3 }
|
|
|
|
|
|
severityLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
information(1),
|
|
warning(2),
|
|
severe(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The severity threshold of traps to send to the manager.
|
|
traps are labeled in severity as informational(1), warning(2),
|
|
severe(3). Only traps of equal or greater severity than
|
|
this value are sent to the manager."
|
|
::= { mconfigTrapsReceiversEntry 4 }
|
|
|
|
|
|
receiverAccept OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry will become active if yes, and will
|
|
be deleted if no."
|
|
::= { mconfigTrapsReceiversEntry 5 }
|
|
|
|
|
|
-- the ups group
|
|
-- the upsBaseIdent group
|
|
|
|
upsBaseIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS model name (e.g. 'Intelligent 8000E 900VA')."
|
|
::= { upsBaseIdent 1 }
|
|
|
|
|
|
upsBaseIdentUpsName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An 8 byte ID string identifying the UPS. This object
|
|
can be set by the administrator."
|
|
::= { upsBaseIdent 2 }
|
|
|
|
|
|
-- the upsSmartIdent group
|
|
|
|
upsSmartIdentFirmwareRevision OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firmware revision of the UPS system."
|
|
::= { upsSmartIdent 1 }
|
|
|
|
|
|
upsSmartIdentDateOfManufacture OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date when the UPS was manufactured in mm/dd/yy format."
|
|
::= { upsSmartIdent 2 }
|
|
|
|
|
|
upsSmartIdentUpsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An 8-character string identifying the serial number of
|
|
the UPS internal microprocessor. This number is set at
|
|
the factory. NOTE: This number does NOT correspond to
|
|
the serial number on the rear of the UPS."
|
|
::= { upsSmartIdent 3 }
|
|
|
|
|
|
upsSmartIdentAgentFirmwareRevision OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The firmware revision of the UPS SNMP Proxy agent."
|
|
::= { upsSmartIdent 4 }
|
|
|
|
|
|
-- the upsBaseBattery group
|
|
|
|
upsBaseBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The status of the UPS batteries. A batteryLow(3)
|
|
value indicates the UPS will be unable to sustain the
|
|
current load, and its services will be lost if power is
|
|
not restored. The amount of run time in reserve at the
|
|
time of low battery can be configured by the
|
|
upsSmartConfigLowBatteryRunTime."
|
|
::= { upsBaseBattery 1 }
|
|
|
|
|
|
upsBaseBatteryTimeOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The elapsed time in seconds since the UPS has switched
|
|
to battery power."
|
|
::= { upsBaseBattery 2 }
|
|
|
|
|
|
upsBaseBatteryLastReplaceDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date when the UPS system's batteries were last replaced
|
|
in mm/dd/yy format. For UPS models, this value is originally
|
|
set in the factory. When the UPS batteries are replaced,
|
|
this value should be reset by the administrator."
|
|
::= { upsBaseBattery 3 }
|
|
|
|
|
|
-- the upsSmartBattery group
|
|
|
|
upsSmartBatteryCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The remaining battery capacity expressed in
|
|
percent of full capacity."
|
|
::= { upsSmartBattery 1 }
|
|
|
|
|
|
upsSmartBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current battery voltage expressed in 1/10 VDC."
|
|
::= { upsSmartBattery 2 }
|
|
|
|
|
|
upsSmartBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current internal UPS temperature expressed in tenths of
|
|
a Celsius degree."
|
|
::= { upsSmartBattery 3 }
|
|
|
|
|
|
upsSmartBatteryRunTimeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS battery run time remaining before battery
|
|
exhaustion, in seconds."
|
|
::= { upsSmartBattery 4 }
|
|
|
|
|
|
upsSmartBatteryReplaceIndicator OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noBatteryNeedsReplacing(1),
|
|
batteryNeedsReplacing(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Indicates whether the UPS batteries need replacing."
|
|
::= { upsSmartBattery 5 }
|
|
|
|
|
|
upsSmartBatteryFullChargeVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The fully charged battery voltage of the battery system
|
|
used in the UPS, expressed in tenths of a volt."
|
|
::= { upsSmartBattery 6 }
|
|
|
|
|
|
upsSmartBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current battery current expressed in percent of
|
|
maximum current."
|
|
::= { upsSmartBattery 7 }
|
|
|
|
|
|
-- the upsBaseInput group
|
|
|
|
upsBaseInputPhase OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current AC input phase."
|
|
::= { upsBaseInput 1 }
|
|
|
|
|
|
-- the upsSmartInput group
|
|
|
|
upsSmartInputLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current utility line voltage in 1/10 VAC."
|
|
::= { upsSmartInput 1 }
|
|
|
|
|
|
upsSmartInputMaxLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum utility line voltage in 1/10 VAC over the
|
|
previous 1 minute period."
|
|
::= { upsSmartInput 2 }
|
|
|
|
|
|
upsSmartInputMinLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum utility line voltage in 1/10 VAC over the
|
|
previous 1 minute period."
|
|
::= { upsSmartInput 3 }
|
|
|
|
|
|
upsSmartInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current input frequency to the UPS system in 1/10 Hz."
|
|
::= { upsSmartInput 4 }
|
|
|
|
|
|
upsSmartInputLineFailCause OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTransfer(1),
|
|
highLineVoltage(2),
|
|
brownout(3),
|
|
blackout(4),
|
|
smallMomentarySag(5),
|
|
deepMomentarySag(6),
|
|
smallMomentarySpike(7),
|
|
largeMomentarySpike(8) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The reason for the occurrence of the last transfer
|
|
to UPS battery power. The variable is set to
|
|
noTransfer(1) if there is no transfer yet. The variable
|
|
is set to highLineVoltage(2) if the transfer to battery is
|
|
caused by an over voltage greater than the high transfer
|
|
voltage. The variable is set to brownout(3) if the duration
|
|
of the outage is greater than five seconds and the line
|
|
voltage is between 40 percent of the rated output voltage and
|
|
the low transfer voltage. The variable is set to blackout(4)
|
|
if the duration of the outage is greater than five seconds and
|
|
the line voltage is between 40 percent of the rated output voltage
|
|
and ground. The variable is set to smallMomentarySag(5)
|
|
if the duration of the outage is less than five seconds and
|
|
the line voltage is between 40 percent of the rated output voltage
|
|
and the low transfer voltage. The variable is set to
|
|
deepMomentarySag(6) if the duration of the outage is less
|
|
than five seconds and the line voltage is between 40 percent of the
|
|
rated output voltage and ground."
|
|
::= { upsSmartInput 5 }
|
|
|
|
|
|
-- the upsBaseOutput group
|
|
|
|
upsBaseOutputStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
onLine(2),
|
|
onBattery(3),
|
|
onBoost(4),
|
|
sleeping(5),
|
|
onBypass(6),
|
|
rebooting(7),
|
|
standBy(8),
|
|
onBuck(9) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current state of the UPS. If the UPS is unable
|
|
to determine the state of the UPS this variable is set
|
|
to unknown(1)."
|
|
::= { upsBaseOutput 1 }
|
|
|
|
|
|
upsBaseOutputPhase OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current output phase."
|
|
::= { upsBaseOutput 2 }
|
|
|
|
|
|
-- the upsSmartOutput group
|
|
|
|
upsSmartOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The output voltage of the UPS system in 1/10 VAC."
|
|
::= { upsSmartOutput 1 }
|
|
|
|
|
|
upsSmartOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current output frequency of the UPS system in 1/10 Hz."
|
|
::= { upsSmartOutput 2 }
|
|
|
|
|
|
upsSmartOutputLoad OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The current UPS load expressed in percent
|
|
of rated capacity."
|
|
::= { upsSmartOutput 3 }
|
|
|
|
|
|
-- the upsBaseConfig group
|
|
|
|
upsBaseConfigNumDevices OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The number of devices that are plugged into the UPS."
|
|
::= { upsBaseConfig 1 }
|
|
|
|
|
|
upsBaseConfigDeviceTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBaseConfigDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A list of devices that are plugged into the UPS. The
|
|
number of entries is given by the value of
|
|
upsBaseConfigNumDevices."
|
|
::= { upsBaseConfig 2 }
|
|
|
|
|
|
upsBaseConfigDeviceEntry OBJECT-TYPE
|
|
SYNTAX UpsBaseConfigDeviceEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The devices plugged in to the UPS."
|
|
INDEX {
|
|
indexOfDevice }
|
|
::= { upsBaseConfigDeviceTable 1 }
|
|
|
|
|
|
UpsBaseConfigDeviceEntry ::= SEQUENCE {
|
|
indexOfDevice INTEGER,
|
|
nameOfDevice DisplayString,
|
|
vaRatingOfDevice INTEGER,
|
|
deviceAccept INTEGER }
|
|
|
|
|
|
indexOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The index of the device that is plugged into the UPS."
|
|
::= { upsBaseConfigDeviceEntry 1 }
|
|
|
|
|
|
nameOfDevice OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name/description of the device plugged into the UPS."
|
|
::= { upsBaseConfigDeviceEntry 2 }
|
|
|
|
|
|
vaRatingOfDevice OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The volt-amp rating of the device plugged into the UPS."
|
|
::= { upsBaseConfigDeviceEntry 3 }
|
|
|
|
|
|
deviceAccept OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(1),
|
|
no(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"An entry is added if yes, the entry is deleted if no."
|
|
::= { upsBaseConfigDeviceEntry 4 }
|
|
|
|
|
|
-- the upsSmartConfig group
|
|
|
|
upsSmartConfigRatedOutputVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The nominal output voltage from the UPS in 1/10 VAC.
|
|
Possible values are 1000, 1200, 2080, 2200, 2250, 2300
|
|
and 2400.
|
|
|
|
NOTE: Only units that are 2200, 2250, 2300 and 2400 can
|
|
be changed. Allowable values are 2200, 2250, 2300 and
|
|
2400.
|
|
|
|
For these adjustable units, if a value other than
|
|
a supported value is provided in a set request, the
|
|
UPS interprets it as the next lower acceptable value.
|
|
If the provided value is lower than the lowest acceptable
|
|
value, the lowest acceptable value is used."
|
|
::= { upsSmartConfig 1 }
|
|
|
|
|
|
upsSmartConfigHighTransferVolt OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The maximum line voltage in 1/10 VAC allowed before the
|
|
UPS system transfers to battery backup.
|
|
|
|
Allowed value depend on the UPS used:
|
|
120 Volt units allow settings of 1290, 1320, 1350, 1380.
|
|
100 Volt units allow settings of 1080, 1100, 1120, 1140.
|
|
230 Volt units allow settings of 2530, 2640, 2710, 2800.
|
|
208 Volt units allow settings of 2240, 2290, 2340, 2390.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as the next lower
|
|
acceptable value. If the provided value is lower than
|
|
the lowest acceptable value, the lowest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 2 }
|
|
|
|
|
|
upsSmartConfigLowTransferVolt OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum line voltage in 1/10 VAC allowed before the
|
|
UPS system transfers to battery backup.
|
|
|
|
Allowable values depend on the UPS used:
|
|
120 Volt units allow settings of 970, 1000, 1030, 1060.
|
|
100 Volt units allow settings of 810, 830, 850, 870.
|
|
230 Volt units allow settings of 1880, 1960, 2040, 2080.
|
|
208 Volt units allow settings of 1680, 1720, 1770, 1820.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 3 }
|
|
|
|
|
|
upsSmartConfigAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
timed(1),
|
|
atLowBattery(2),
|
|
never(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A flag indicating how the UPS should handle audible line fail
|
|
alarms."
|
|
::= { upsSmartConfig 4 }
|
|
|
|
|
|
upsSmartConfigAlarmTimer OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in seconds after initial line failure at which the
|
|
UPS begins emitting audible alarms (beeping). This timer is
|
|
observerd only if the value of extControlAlarm is timed(2).
|
|
Allowed values are 0 or 30 seconds.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next lower
|
|
acceptable value. If the provided value is lower than
|
|
the lowest acceptable value, the lowest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 5 }
|
|
|
|
|
|
upsSmartConfigMinReturnCapacity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The minimum battery capacity as a percent of full capacity
|
|
required before the UPS will return from a low battery
|
|
shutdown condition. In other words, the UPS will not
|
|
re-energize the output until the battery capacity is equal
|
|
to this value. Allowed values are 0, 10, 25, or 90 percent.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 6 }
|
|
|
|
|
|
upsSmartConfigSensitivity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(1),
|
|
low(2),
|
|
medium(3),
|
|
high(4) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The sensitivity of the UPS to utility line abnormalities
|
|
or noises."
|
|
::= { upsSmartConfig 7 }
|
|
|
|
|
|
upsSmartConfigLowBatteryRunTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The desired run time in seconds once the low battery
|
|
condition is reached. Allowed values are 120, 300, 420,
|
|
or 600 seconds. During this time the UPS will produce a
|
|
constant warning tone which can not be disabled.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 8 }
|
|
|
|
|
|
upsSmartConfigReturnDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay in seconds after utility line power returns
|
|
before the UPS will turn on. This value is also used
|
|
when the UPS comes out of a reboot and before the UPS
|
|
wakes up from 'sleep' mode. Allowed values are 0, 60,
|
|
180 and 300 seconds.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as a the next higher
|
|
acceptable value. If the provided value is higher than
|
|
the highest acceptable value, the highest acceptable
|
|
value is used."
|
|
::= { upsSmartConfig 9 }
|
|
|
|
|
|
upsSmartConfigShutoffDelay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The delay in seconds the UPS remains on after being told
|
|
to turn off. Allowed values are 12, 18, 24, 30, 36, 42,
|
|
48, 54, 60, 120, 180, 240, 300, 360, 420, 480, 540, and
|
|
600 seconds.
|
|
|
|
If a value other than a supported value is provided in a
|
|
set request, the UPS interprets it as next higher acceptable
|
|
value. If the provided value is higher than the highest
|
|
acceptable value, the highest acceptable value is used."
|
|
::= { upsSmartConfig 10 }
|
|
|
|
|
|
upsSmartConfigUpsSleepTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The time in minutes for the UPS to go to 'sleep' when
|
|
instructed. When in sleep mode, the UPS will not provide
|
|
output power regardless of the input line state. Once the
|
|
specified time has elapsed, output power will be restored.
|
|
|
|
This is a configuration setting. The UPS will not go to
|
|
sleep until told to do so by the manager from a management
|
|
station.
|
|
|
|
Any input value is allowed, however the UPS only recognizes
|
|
0 - 9999 minutes in one minute increments.
|
|
|
|
If the provided value is higher than the highest acceptable
|
|
value, the highest acceptable value is used."
|
|
::= { upsSmartConfig 11 }
|
|
|
|
|
|
upsSmartConfigSetEEPROMDefaults OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noSetEEPROMDefaults(1),
|
|
setEEPROMDefaults(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"WRITE: Resets the UPS EEPROM variables to default values.
|
|
READ: returns 0"
|
|
::= { upsSmartConfig 12 }
|
|
|
|
|
|
-- the upsBaseControl group
|
|
|
|
upsBaseControlConserveBattery OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTurnOffUps(1),
|
|
turnUpsOffToConserveBattery(2),
|
|
turnUpsOffToConserveBatteryDelay(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to turnUpsOffToConserveBattery(2)
|
|
causes a UPS on battery to be put into 'sleep' mode immediately.
|
|
The (10) means suspending time(10 minutes) before turn off UPS.
|
|
UPS will turn back on when utility power is restored.
|
|
Attempting to turn off a UPS that is not on battery will
|
|
result in a badValue error.
|
|
|
|
Setting this value to noTurnOffUps(1) has no
|
|
effect.
|
|
|
|
The value noTurnOffUps(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsBaseControl 1 }
|
|
|
|
|
|
-- the upsSmartControl group
|
|
|
|
upsSmartControlUpsOff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTurnUpsOff(1),
|
|
turnUpsOff(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to turnUpsOff(2) causes
|
|
the UPS to shut off. When in this state, the UPS
|
|
will not provide output power regardless of the input
|
|
line state. The on/off switch on the UPS
|
|
must be toggled for the UPS to return to operation.
|
|
|
|
Setting this value to noTurnUpsOff(1) has no
|
|
effect.
|
|
|
|
The value noTurnUpsOff(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 1 }
|
|
|
|
|
|
upsSmartControlRebootUps OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noRebootUps(1),
|
|
rebootUps(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to rebootUps(2) causes the
|
|
UPS to shut off and turn back on.
|
|
|
|
Setting this value to noRebootUps(1) has no effect.
|
|
|
|
The value noRebootUps(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 2 }
|
|
|
|
|
|
upsSmartControlUpsSleep OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noPutUpsToSleep(1),
|
|
putUpsToSleep(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to putUpsToSleep(2) causes
|
|
the UPS to go to sleep for the time specified by
|
|
upsSmartConfigUpsSleepTime.
|
|
|
|
When in sleep mode, the UPS will not provide output
|
|
power regardless of the input line state. Once the
|
|
specified time has elapsed, output power will be
|
|
restored.
|
|
|
|
Setting this value to noPutUpsToSleep(1) has no
|
|
effect.
|
|
|
|
The value noPutUpsToSleep(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 3 }
|
|
|
|
|
|
upsSmartControlSimulatePowerFail OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noSimulatePowerFailure(1),
|
|
simulatePowerFailure(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to simulatePowerFailure(2) causes
|
|
the UPS switch to battery power.
|
|
|
|
Setting this value to noSimulatePowerFailure(1) has no
|
|
effect.
|
|
|
|
The value noSimulatePowerFailure(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 4 }
|
|
|
|
|
|
upsSmartControlFlashAndBeep OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noFlashAndBeep(1),
|
|
flashAndBeep(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS to identify itself by lighting all indicators
|
|
and beeping.
|
|
|
|
Setting this variable to FlashAndBeep(2) causes
|
|
the UPS lights all panel indicators and beeps.
|
|
|
|
Setting this value to noFlashAndBeep(1) has no
|
|
effect.
|
|
|
|
The value noFlashAndBeep(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartControl 5 }
|
|
|
|
|
|
upsSmartControlTurnOnUpsLoad OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noUpsSmartControlTurnOnUpsLoad(1),
|
|
upsSmartControlTurnOnUpsLoad(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to upsSmartControlTurnOnUpsLoad(2)
|
|
causes the UPS switch back to utility power if utility
|
|
power is present.
|
|
|
|
Setting this value to noUpsSmartControlTurnOnUpsLoad(1)
|
|
has no effect.
|
|
|
|
The value noUpsSmartControlTurnOnUpsLoad(1) will always
|
|
be returned when the variable is read."
|
|
::= { upsSmartControl 6 }
|
|
|
|
|
|
-- the upsBaseTest group
|
|
-- the upsSmartTest group
|
|
|
|
upsSmartTestDiagnosticSchedule OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
biweekly(2),
|
|
weekly(3),
|
|
never(4) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS system's automatic battery test schedule."
|
|
::= { upsSmartTest 1 }
|
|
|
|
|
|
upsSmartTestDiagnostics OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestDiagnostics(1),
|
|
testDiagnostics(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to testDiagnostics(2) causes
|
|
the UPS to perform a diagnostic self test.
|
|
|
|
Setting this value to noTestDiagnostics(1) has no
|
|
effect.
|
|
|
|
The value noTestDiagnostics(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartTest 2 }
|
|
|
|
|
|
upsSmartTestDiagnosticsResults OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
failed(2),
|
|
invalidTest(3),
|
|
testInProgress(4) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the last UPS diagnostics test performed."
|
|
::= { upsSmartTest 3 }
|
|
|
|
|
|
upsSmartTestLastDiagnosticsDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date the last UPS diagnostics test was performed in
|
|
mm/dd/yy format."
|
|
::= { upsSmartTest 4 }
|
|
|
|
|
|
upsSmartTestIndicators OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noTestIndicators(1),
|
|
testIndicators(2) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to testIndicators(2) causes
|
|
the UPS to perform a front panel indicator (lights) test.
|
|
|
|
Setting this value to noTestIndicators(1) has no effect.
|
|
|
|
The value noTestIndicators(1) will always be returned
|
|
when the variable is read."
|
|
::= { upsSmartTest 5 }
|
|
|
|
|
|
upsSmartTestRuntimeCalibration OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noPerformCalibration(1),
|
|
performCalibration(2),
|
|
cancelCurrentCalibration(3) }
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Setting this variable to performCalibration(2) causes
|
|
the UPS to discharge to calibrate the UPS.
|
|
The test will only start if the battery capacity is 100 percent.
|
|
The test runs until capacity is less than 25 percent.
|
|
|
|
Setting this variable to cancelCurrentCalibration(3)
|
|
after setting performCalibration(2) will cancel the
|
|
current discharge.
|
|
|
|
Setting this variable to noPerformCalibration(1)
|
|
will have no effect.
|
|
|
|
The value noPerformCalibration(1) will always be returned
|
|
when the variable is read.
|
|
|
|
The result of the calibration will be saved in
|
|
upsSmartTestCalibrationResult."
|
|
::= { upsSmartTest 6 }
|
|
|
|
|
|
upsSmartTestCalibrationResults OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ok(1),
|
|
invalidTest(2),
|
|
calibrationInProgress(3) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the last runtime calibration.
|
|
|
|
Value ok(1) means a successful runtime calibration.
|
|
|
|
Value invalidTest(2) indicates last calibration did
|
|
not take place since the battery capacity was below
|
|
100 percent.
|
|
|
|
Value calibrationInProgress(3) means a calibration
|
|
is occurring now."
|
|
::= { upsSmartTest 7 }
|
|
|
|
|
|
upsSmartTestCalibrationDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The date the last UPS runtime calibration was
|
|
performed in mm/dd/yy format."
|
|
::= { upsSmartTest 8 }
|
|
|
|
|
|
-----------------------
|
|
--ups ThreePhase group-
|
|
-----------------------
|
|
upsThreePhaseBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Voltage"
|
|
::= { upsThreePhaseBatteryGrp 1 }
|
|
|
|
|
|
upsThreePhaseBatteryCapacityPercentage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Capacity Percentage"
|
|
::= { upsThreePhaseBatteryGrp 2 }
|
|
|
|
|
|
upsThreePhaseBatteryTimeRemain OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Time Remain (unit is Minute)"
|
|
::= { upsThreePhaseBatteryGrp 3 }
|
|
|
|
|
|
upsThreePhaseBatteryCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Electric Current"
|
|
::= { upsThreePhaseBatteryGrp 4 }
|
|
|
|
|
|
upsThreePhaseBatteryTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Temperature"
|
|
::= { upsThreePhaseBatteryGrp 5 }
|
|
|
|
|
|
upsThreePhaseInputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input Frequency"
|
|
::= { upsThreePhaseInputGrp 1 }
|
|
|
|
|
|
upsThreePhaseInputVoltageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input VoltageR"
|
|
::= { upsThreePhaseInputGrp 2 }
|
|
|
|
|
|
upsThreePhaseInputVoltageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input VoltageS"
|
|
::= { upsThreePhaseInputGrp 3 }
|
|
|
|
|
|
upsThreePhaseInputVoltageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Input VoltageT"
|
|
::= { upsThreePhaseInputGrp 4 }
|
|
|
|
|
|
upsThreePhaseOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Frequency"
|
|
::= { upsThreePhaseOutputGrp 1 }
|
|
|
|
|
|
upsThreePhaseOutputVoltageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output VoltageR"
|
|
::= { upsThreePhaseOutputGrp 2 }
|
|
|
|
|
|
upsThreePhaseOutputVoltageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output VoltageS"
|
|
::= { upsThreePhaseOutputGrp 3 }
|
|
|
|
|
|
upsThreePhaseOutputVoltageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output VoltageT"
|
|
::= { upsThreePhaseOutputGrp 4 }
|
|
|
|
|
|
upsThreePhaseOutputLoadPercentageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Load PercentageR"
|
|
::= { upsThreePhaseOutputGrp 5 }
|
|
|
|
|
|
upsThreePhaseOutputLoadPercentageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Load PercentageS"
|
|
::= { upsThreePhaseOutputGrp 6 }
|
|
|
|
|
|
upsThreePhaseOutputLoadPercentageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Load PercentageT"
|
|
::= { upsThreePhaseOutputGrp 7 }
|
|
|
|
|
|
upsThreePhaseBypassSourceFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Frequency"
|
|
::= { upsThreePhaseBypassGrp 1 }
|
|
|
|
|
|
upsThreePhaseBypssSourceVoltageR OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass VoltageR"
|
|
::= { upsThreePhaseBypassGrp 2 }
|
|
|
|
|
|
upsThreePhaseBypssSourceVoltageS OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass VoltageS"
|
|
::= { upsThreePhaseBypassGrp 3 }
|
|
|
|
|
|
upsThreePhaseBypssSourceVoltageT OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass VoltageT"
|
|
::= { upsThreePhaseBypassGrp 4 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusRecRotError OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Rotation Error"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 1 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusLowBatteryShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Battery Shutdown"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 2 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusLowBattery OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Low Battery"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 3 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusInAndOut OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
threeInOneOut(2),
|
|
threeInThreeOut(3) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"In And Put"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 4 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
backup(4),
|
|
acnormal(5) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Back Status"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 5 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusChargeStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
boost(6),
|
|
float(7),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Charge Status"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 6 }
|
|
|
|
|
|
upsThreePhaseDCandRectifierStatusRecOperating OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Operating"
|
|
::= { upsThreePhaseDCandRectifierStatusGrp 7 }
|
|
|
|
|
|
upsThreePhaseUPSStatusBypassFreqFail OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Status"
|
|
::= { upsThreePhaseUPSStatusGrp 1 }
|
|
|
|
|
|
upsThreePhaseUPSStatusManualBypassBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
close(8),
|
|
open(9) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Breaker Status"
|
|
::= { upsThreePhaseUPSStatusGrp 2 }
|
|
|
|
|
|
upsThreePhaseUPSStatusACStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(10),
|
|
abnormal(11) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"AC Status"
|
|
::= { upsThreePhaseUPSStatusGrp 3 }
|
|
|
|
|
|
upsThreePhaseUPSStaticSwitchMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
invermode(12),
|
|
bypassmode(13) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Switch Mode"
|
|
::= { upsThreePhaseUPSStatusGrp 4 }
|
|
|
|
|
|
upsThreePhaseUPSStatusInverterOperating OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Operating"
|
|
::= { upsThreePhaseUPSStatusGrp 5 }
|
|
|
|
|
|
upsThreePhaseFaultStatusEmergencyStop OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Emergency Stop"
|
|
::= { upsThreePhaseFaultStatusGrp 1 }
|
|
|
|
|
|
upsThreePhaseFaultStatusHighDCShutdown OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"High DC Shutdown"
|
|
::= { upsThreePhaseFaultStatusGrp 2 }
|
|
|
|
|
|
upsThreePhaseFaultStatusBypassBreaker OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Breaker"
|
|
::= { upsThreePhaseFaultStatusGrp 3 }
|
|
|
|
|
|
upsThreePhaseFaultStatusOverLoad OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Over Load"
|
|
::= { upsThreePhaseFaultStatusGrp 4 }
|
|
|
|
|
|
upsThreePhaseFaultStatusInverterOutputFail OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Fail"
|
|
::= { upsThreePhaseFaultStatusGrp 5 }
|
|
|
|
|
|
upsThreePhaseFaultStatusOverTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Over Temperature"
|
|
::= { upsThreePhaseFaultStatusGrp 6 }
|
|
|
|
|
|
upsThreePhaseFaultStatusShortCircuit OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
yes(14),
|
|
no(16) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Short Circuit"
|
|
::= { upsThreePhaseFaultStatusGrp 7 }
|
|
|
|
|
|
upsThreePhaseRatingRectifierVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Voltage"
|
|
::= { upsThreePhaseRatingGrp 1 }
|
|
|
|
|
|
upsThreePhaseRatingRectifierFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Rectifier Frequency"
|
|
::= { upsThreePhaseRatingGrp 2 }
|
|
|
|
|
|
upsThreePhaseRatingBypassVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Voltage"
|
|
::= { upsThreePhaseRatingGrp 3 }
|
|
|
|
|
|
upsThreePhaseRatingBypassFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bypass Frequency"
|
|
::= { upsThreePhaseRatingGrp 4 }
|
|
|
|
|
|
upsThreePhaseRatingOutputVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Voltage"
|
|
::= { upsThreePhaseRatingGrp 5 }
|
|
|
|
|
|
upsThreePhaseRatingOutputFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Output Frequency"
|
|
::= { upsThreePhaseRatingGrp 6 }
|
|
|
|
|
|
upsThreePhaseRatingBatteryVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Battery Voltage"
|
|
::= { upsThreePhaseRatingGrp 7 }
|
|
|
|
|
|
upsThreePhaseRatingPower OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Power Rating"
|
|
::= { upsThreePhaseRatingGrp 8 }
|
|
|
|
|
|
-----------------------
|
|
-----------------------
|
|
|
|
upsEnvStatus OBJECT IDENTIFIER ::= { upsEnvironment 1 }
|
|
|
|
upsEnvTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The ambient environment temperature."
|
|
::= { upsEnvStatus 1 }
|
|
|
|
|
|
upsEnvHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The environment humidity."
|
|
::= { upsEnvStatus 2 }
|
|
|
|
|
|
upsEnvOverTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverTemperature on when the environment
|
|
temperature over the value."
|
|
::= { upsEnvSetting 1 }
|
|
|
|
|
|
upsEnvOverHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmOverHumidity on when the environment
|
|
humidity over the value."
|
|
::= { upsEnvSetting 3 }
|
|
|
|
|
|
upsEnvSecurity1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 5 }
|
|
|
|
|
|
upsEnvSecurity2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 6 }
|
|
|
|
|
|
upsEnvSecurity3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 7 }
|
|
|
|
|
|
upsEnvSecurity4 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 8 }
|
|
|
|
|
|
upsEnvSecurity5 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 9 }
|
|
|
|
|
|
upsEnvSecurity6 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 10 }
|
|
|
|
|
|
upsEnvSecurity7 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Security status"
|
|
::= { upsEnvStatus 11 }
|
|
|
|
|
|
upsEnvWater OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Water status"
|
|
::= { upsEnvStatus 3 }
|
|
|
|
|
|
upsEnvSmoke OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
abnormal(2) }
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Smoke status"
|
|
::= { upsEnvStatus 4 }
|
|
|
|
|
|
upsEnvSetting OBJECT IDENTIFIER ::= { upsEnvironment 2 }
|
|
|
|
upsEnvUnderTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmUnderTemperature on when the environment
|
|
temperature below the value."
|
|
::= { upsEnvSetting 2 }
|
|
|
|
|
|
upsEnvUnderHumidity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm dupsAlarmUnderHumidity on when the environment
|
|
humidity below the value."
|
|
::= { upsEnvSetting 4 }
|
|
|
|
|
|
|
|
communicationLost TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: Communication to the UPS has been lost. Steps
|
|
to reestablish communication are in progress."
|
|
--#TYPE "PPC UPS: Communication failure"
|
|
--#SUMMARY "Communication to the UPS has been lost."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 1
|
|
|
|
|
|
|
|
upsOverLoad TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS has sensed a load greater than 100 percent
|
|
of its rated capacity."
|
|
--#TYPE "PPC UPS: UPS overload"
|
|
--#SUMMARY "The UPS has sensed a load greater than 100 percent of its rated capacity."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 2
|
|
|
|
|
|
|
|
upsDiagnosticsFailed TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS failed its internal diagnostic self-test."
|
|
--#TYPE "PPC UPS: Failed self-test"
|
|
--#SUMMARY "The UPS has failed its internal diagnostic self-test."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 3
|
|
|
|
|
|
|
|
upsDischarged TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS just started a runtime calibration
|
|
discharge. The UPS batteries are being discharged."
|
|
--#TYPE "PPC UPS: Deep discharge"
|
|
--#SUMMARY "The UPS has just started a runtime calibration discharge."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 4
|
|
|
|
|
|
|
|
upsOnBattery TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has switched to battery backup power."
|
|
--#TYPE "PPC UPS: On battery"
|
|
--#SUMMARY "The UPS has switched to battery backup power."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 5
|
|
|
|
|
|
|
|
boostOn TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has enabled Boost."
|
|
--#TYPE "PPC UPS: SmartBoost"
|
|
--#SUMMARY "The UPS has enabled Boost."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MINOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 6
|
|
|
|
|
|
|
|
lowBattery TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"SEVERE: The UPS batteries are low and will soon be exhausted.
|
|
If utility power is not restored the UPS will put itself
|
|
to 'sleep' and immediately cut power to the load."
|
|
--#TYPE "PPC UPS: Low battery"
|
|
--#SUMMARY "The UPS batteries are low and will soon be exhausted."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY CRITICAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE DEGRADED
|
|
::= 7
|
|
|
|
|
|
|
|
communicationEstablished TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: Communication with the UPS has been
|
|
established."
|
|
--#TYPE "PPC UPS: Communication established"
|
|
--#SUMMARY "Communication with the UPS has been established."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 8
|
|
|
|
|
|
|
|
powerRestored TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: Utility power has been restored."
|
|
--#TYPE "PPC UPS: Utility restored"
|
|
--#SUMMARY "Normal power has been restored to the UPS."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 9
|
|
|
|
|
|
|
|
upsDiagnosticsPassed TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS passed its internal self-test."
|
|
--#TYPE "PPC UPS: Passed self-test"
|
|
--#SUMMARY "The UPS has passed its internal self-test."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 10
|
|
|
|
|
|
|
|
returnFromLowBattery TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS has returned from a low battery
|
|
condition."
|
|
--#TYPE "PPC UPS: Battery normal"
|
|
--#SUMMARY "The UPS has returned from a low battery condition."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 11
|
|
|
|
|
|
|
|
upsTurnedOff TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has been turned 'off' by the
|
|
management station."
|
|
--#TYPE "PPC UPS: Switching off"
|
|
--#SUMMARY "The UPS is being switched off by a management station."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE NONOPERATIONAL
|
|
::= 12
|
|
|
|
|
|
|
|
upsSleeping TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS is entering 'sleep' mode. Power
|
|
to the load will be cut off."
|
|
--#TYPE "PPC UPS: Going to sleep"
|
|
--#SUMMARY "The UPS is going into sleep mode."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE NONOPERATIONAL
|
|
::= 13
|
|
|
|
|
|
|
|
upsWokeUp TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The UPS woke up from 'sleep' mode. Power
|
|
to the load has been restored."
|
|
--#TYPE "PPC UPS: Wake up"
|
|
--#SUMMARY "The UPS has woke up from sleep mode."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE OPERATIONAL
|
|
::= 14
|
|
|
|
|
|
|
|
upsRebootStarted TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS has started its reboot sequence. After
|
|
the specified delay the UPS will perform a reboot."
|
|
--#TYPE "PPC UPS: Starting reboot"
|
|
--#SUMMARY "The UPS has started its reboot sequence."
|
|
--#ARGUMENTS { }
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 1
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE NONOPERATIONAL
|
|
::= 15
|
|
|
|
|
|
envOverTemperature TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment temperature exceed the normal value."
|
|
::= 16
|
|
|
|
|
|
envTemperatureNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The environment temperature is normal."
|
|
::= 17
|
|
|
|
|
|
envOverHumidity TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment humidity exceed the normal value."
|
|
::= 18
|
|
|
|
|
|
envHumidityNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: The environment humidity is normal."
|
|
::= 19
|
|
|
|
|
|
envSmokeAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Smoke is abnormal."
|
|
::= 20
|
|
|
|
|
|
envWaterAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Water is abnormal."
|
|
::= 21
|
|
|
|
|
|
envSecurityAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security is abnormal."
|
|
::= 22
|
|
|
|
|
|
--envSmokeNormal TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "INFORMATION: Smoke is normal."
|
|
-- ::= 23
|
|
|
|
|
|
envWaterNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"INFORMATION: Water is normal."
|
|
::= 24
|
|
|
|
|
|
--envSecurityNormal TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "INFORMATION: Security is normal."
|
|
-- ::= 25
|
|
|
|
|
|
envGasAbnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Gas Alarm"
|
|
::= 26
|
|
|
|
|
|
upsTemp TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Temperature Overrun"
|
|
::= 27
|
|
|
|
|
|
upsLoadNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Load Normal"
|
|
::= 28
|
|
|
|
|
|
upsTempNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS temperature Normal"
|
|
::= 29
|
|
|
|
|
|
envUnderTemperature TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment temperature below the normal value."
|
|
::= 30
|
|
|
|
|
|
envUnderHumidity TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The environment humidity below the normal value."
|
|
::= 31
|
|
|
|
|
|
upsBypass TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: The UPS is entering 'bypass' mode."
|
|
::= 32
|
|
|
|
|
|
envSecurity1 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security1 Alarm."
|
|
::= 33
|
|
|
|
|
|
envSecurity2 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security2 Alarm."
|
|
::= 34
|
|
|
|
|
|
envSecurity3 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security3 Alarm."
|
|
::= 35
|
|
|
|
|
|
envSecurity4 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security4 Alarm."
|
|
::= 36
|
|
|
|
|
|
envSecurity5 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security5 Alarm."
|
|
::= 37
|
|
|
|
|
|
envSecurity6 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security6 Alarm."
|
|
::= 38
|
|
|
|
|
|
envSecurity7 TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Security7 Alarm."
|
|
::= 39
|
|
|
|
|
|
--envSecurity1Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security1 Normal."
|
|
-- ::= 40
|
|
|
|
|
|
--envSecurity2Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security2 Normal"
|
|
-- ::= 41
|
|
|
|
|
|
--envSecurity3Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security3 Normal."
|
|
-- ::= 42
|
|
|
|
|
|
--envSecurity4Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security4 Normal."
|
|
-- ::= 43
|
|
|
|
|
|
--envSecurity5Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security5 Normal."
|
|
-- ::= 44
|
|
|
|
|
|
--envSecurity6Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security6 Normal."
|
|
-- ::= 45
|
|
|
|
|
|
--envSecurity7Return TRAP-TYPE
|
|
-- ENTERPRISE ppc
|
|
-- DESCRIPTION
|
|
-- "WARNING: Security7 Normal."
|
|
-- ::= 46
|
|
|
|
|
|
upsRecroterror TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Rectifier Rotation Error"
|
|
::= 47
|
|
|
|
|
|
upsBypassFreFail TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Bypass Frequency Fail"
|
|
::= 48
|
|
|
|
|
|
upsBypassacnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Bypass AC Normal"
|
|
::= 49
|
|
|
|
|
|
upsBypassacabnormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: Bypass AC Abnormal"
|
|
::= 50
|
|
|
|
|
|
upsTest TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Test"
|
|
::= 51
|
|
|
|
|
|
upsScheduleShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"WARNING: UPS Schedule Shutdown"
|
|
::= 52
|
|
|
|
upsBypassReturn TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS return from Bypass Mode"
|
|
::= 53
|
|
|
|
upsShortCircuitShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Short Circuit Shutdown"
|
|
::= 54
|
|
|
|
upsInverterOutputFailShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Inverter Output Fail Shutdown"
|
|
::= 55
|
|
|
|
upsBypassBreadkerOnShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Manual Bypass Breaker on Shutdown"
|
|
::= 56
|
|
|
|
upsHighDCShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS High DC Shutdown"
|
|
::= 57
|
|
|
|
upsEmergencyStop TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Emergency Stop"
|
|
::= 58
|
|
|
|
upsInverterMode TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Static Switch in Inverter Mode"
|
|
::= 59
|
|
|
|
upsBypassMode TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Static Switch in Bypass Mode"
|
|
::= 60
|
|
|
|
upsOverTemperatureShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Over Temperature Shutdown"
|
|
::= 61
|
|
|
|
upsOverLoadShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Overload Shutdown"
|
|
::= 62
|
|
|
|
upsCapacityUnderrun TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Capacity Underrun"
|
|
::= 63
|
|
|
|
upsCapacityNormal TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Capacity Normal"
|
|
::= 64
|
|
|
|
upsLowBatteryShutdown TRAP-TYPE
|
|
ENTERPRISE ppc
|
|
DESCRIPTION
|
|
"The UPS Low Battery Shutdown"
|
|
::= 67
|
|
|
|