- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1913 lines
64 KiB
Text
1913 lines
64 KiB
Text
UPS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
|
|
OBJECT-IDENTITY, Counter32, Gauge32, Integer32, mib-2
|
|
FROM SNMPv2-SMI
|
|
DisplayString, TimeStamp, TimeInterval, TestAndIncr,
|
|
AutonomousType, TEXTUAL-CONVENTION
|
|
FROM SNMPv2-TC
|
|
MODULE-COMPLIANCE, OBJECT-GROUP
|
|
FROM SNMPv2-CONF;
|
|
|
|
|
|
upsMIB MODULE-IDENTITY
|
|
LAST-UPDATED "9402230000Z"
|
|
ORGANIZATION "IETF UPS MIB Working Group"
|
|
CONTACT-INFO
|
|
" Jeffrey D. Case
|
|
|
|
Postal: SNMP Research, Incorporated
|
|
3001 Kimberlin Heights Road
|
|
Knoxville, TN 37920
|
|
US
|
|
|
|
Tel: +1 615 573 1434
|
|
Fax: +1 615 573 9197
|
|
|
|
E-mail: case@snmp.com"
|
|
DESCRIPTION
|
|
"The MIB module to describe Uninterruptible Power
|
|
Supplies."
|
|
::= { mib-2 33 }
|
|
|
|
PositiveInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-zero and non-negative value."
|
|
SYNTAX INTEGER (1..2147483647)
|
|
|
|
NonNegativeInteger ::= TEXTUAL-CONVENTION
|
|
DISPLAY-HINT "d"
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This data type is a non-negative value."
|
|
SYNTAX INTEGER (0..2147483647)
|
|
upsObjects OBJECT IDENTIFIER ::= { upsMIB 1 }
|
|
|
|
|
|
--
|
|
-- The Device Identification group.
|
|
-- All objects in this group except for upsIdentName and
|
|
-- upsIdentAttachedDevices are set at device initialization
|
|
-- and remain static.
|
|
--
|
|
|
|
upsIdent OBJECT IDENTIFIER ::= { upsObjects 1 }
|
|
|
|
upsIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { upsIdent 1 }
|
|
|
|
upsIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { upsIdent 2 }
|
|
|
|
upsIdentUPSSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS firmware/software version(s). This variable
|
|
may or may not have the same value as
|
|
upsIdentAgentSoftwareVersion in some implementations."
|
|
::= { upsIdent 3 }
|
|
|
|
upsIdentAgentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS agent software version. This variable may or
|
|
may not have the same value as
|
|
upsIdentUPSSoftwareVersion in some implementations."
|
|
::= { upsIdent 4 }
|
|
|
|
upsIdentName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { upsIdent 5 }
|
|
|
|
upsIdentAttachedDevices OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the UPS. This object should be set by
|
|
the administrator."
|
|
::= { upsIdent 6 }
|
|
|
|
|
|
--
|
|
-- Battery Group
|
|
--
|
|
|
|
upsBattery OBJECT IDENTIFIER ::= { upsObjects 2 }
|
|
|
|
upsBatteryStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The indication of the capacity remaining in the UPS
|
|
system's batteries. A value of batteryNormal
|
|
indicates that the remaining run-time is greater than
|
|
upsConfigLowBattTime. A value of batteryLow indicates
|
|
that the remaining battery run-time is less than or
|
|
equal to upsConfigLowBattTime. A value of
|
|
batteryDepleted indicates that the UPS will be unable
|
|
to sustain the present load when and if the utility
|
|
power is lost (including the possibility that the
|
|
utility power is currently absent and the UPS is
|
|
unable to sustain the output)."
|
|
::= { upsBattery 1 }
|
|
|
|
upsSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. Zero shall be returned
|
|
if the unit is not on battery power."
|
|
::= { upsBattery 2 }
|
|
|
|
upsEstimatedMinutesRemaining OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion
|
|
under the present load conditions if the utility power
|
|
is off and remains off, or if it were to be lost and
|
|
remain off."
|
|
::= { upsBattery 3 }
|
|
|
|
upsEstimatedChargeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { upsBattery 4 }
|
|
|
|
upsBatteryVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Volt DC"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present battery voltage."
|
|
::= { upsBattery 5 }
|
|
|
|
upsBatteryCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "0.1 Amp DC"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present battery current."
|
|
::= { upsBattery 6 }
|
|
|
|
upsBatteryTemperature OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
UNITS "degrees Centigrade"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing."
|
|
::= { upsBattery 7 }
|
|
|
|
|
|
--
|
|
-- Input Group
|
|
--
|
|
|
|
upsInput OBJECT IDENTIFIER ::= { upsObjects 3 }
|
|
|
|
upsInputLineBads OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the
|
|
manufacturer. This count is incremented by one each
|
|
time the input transitions from zero out-of-tolerance
|
|
lines to one or more input lines out-of-tolerance."
|
|
::= { upsInput 1 }
|
|
|
|
|
|
upsInputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
input table."
|
|
::= { upsInput 2 }
|
|
|
|
upsInputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputNumLines."
|
|
::= { upsInput 3 }
|
|
|
|
upsInputEntry OBJECT-TYPE
|
|
SYNTAX UpsInputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line."
|
|
INDEX { upsInputLineIndex }
|
|
::= { upsInputTable 1 }
|
|
|
|
UpsInputEntry ::= SEQUENCE {
|
|
upsInputLineIndex PositiveInteger,
|
|
upsInputFrequency NonNegativeInteger,
|
|
upsInputVoltage NonNegativeInteger,
|
|
upsInputCurrent NonNegativeInteger,
|
|
upsInputTruePower NonNegativeInteger
|
|
}
|
|
|
|
upsInputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input line identifier."
|
|
::= { upsInputEntry 1 }
|
|
|
|
upsInputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present input frequency."
|
|
::= { upsInputEntry 2 }
|
|
|
|
upsInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage."
|
|
::= { upsInputEntry 3 }
|
|
|
|
upsInputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 RMS Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input current."
|
|
::= { upsInputEntry 4 }
|
|
|
|
upsInputTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input true power."
|
|
::= { upsInputEntry 5 }
|
|
|
|
|
|
--
|
|
-- The Output group.
|
|
--
|
|
|
|
upsOutput OBJECT IDENTIFIER ::= { upsObjects 4 }
|
|
|
|
upsOutputSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker."
|
|
::= { upsOutput 1 }
|
|
|
|
upsOutputFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output frequency."
|
|
::= { upsOutput 2 }
|
|
|
|
upsOutputNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
output table."
|
|
::= { upsOutput 3 }
|
|
|
|
upsOutputTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsOutputNumLines."
|
|
::= { upsOutput 4 }
|
|
|
|
upsOutputEntry OBJECT-TYPE
|
|
SYNTAX UpsOutputEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line."
|
|
INDEX { upsOutputLineIndex }
|
|
::= { upsOutputTable 1 }
|
|
|
|
UpsOutputEntry ::= SEQUENCE {
|
|
upsOutputLineIndex PositiveInteger,
|
|
upsOutputVoltage NonNegativeInteger,
|
|
upsOutputCurrent NonNegativeInteger,
|
|
upsOutputPower NonNegativeInteger,
|
|
upsOutputPercentLoad INTEGER
|
|
}
|
|
|
|
upsOutputLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output line identifier."
|
|
::= { upsOutputEntry 1 }
|
|
|
|
upsOutputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output voltage."
|
|
::= { upsOutputEntry 2 }
|
|
|
|
upsOutputCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 RMS Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output current."
|
|
::= { upsOutputEntry 3 }
|
|
|
|
upsOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output true power."
|
|
::= { upsOutputEntry 4 }
|
|
|
|
upsOutputPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER (0..200)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line, i.e., the greater of
|
|
the percent load of true power capacity and the
|
|
percent load of VA."
|
|
::= { upsOutputEntry 5 }
|
|
|
|
--
|
|
-- The Bypass group.
|
|
--
|
|
|
|
upsBypass OBJECT IDENTIFIER ::= { upsObjects 5 }
|
|
|
|
upsBypassFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass frequency."
|
|
::= { upsBypass 1 }
|
|
|
|
upsBypassNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device.
|
|
This entry indicates the number of rows in the bypass
|
|
table."
|
|
::= { upsBypass 2 }
|
|
|
|
upsBypassTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsBypassEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of
|
|
entries is given by the value of upsBypassNumLines."
|
|
::= { upsBypass 3 }
|
|
|
|
upsBypassEntry OBJECT-TYPE
|
|
SYNTAX UpsBypassEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bypass input."
|
|
INDEX { upsBypassLineIndex }
|
|
::= { upsBypassTable 1 }
|
|
|
|
UpsBypassEntry ::= SEQUENCE {
|
|
upsBypassLineIndex PositiveInteger,
|
|
upsBypassVoltage NonNegativeInteger,
|
|
upsBypassCurrent NonNegativeInteger,
|
|
upsBypassPower NonNegativeInteger
|
|
}
|
|
|
|
upsBypassLineIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass line identifier."
|
|
::= { upsBypassEntry 1 }
|
|
|
|
upsBypassVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass voltage."
|
|
::= { upsBypassEntry 2 }
|
|
|
|
upsBypassCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 RMS Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass current."
|
|
::= { upsBypassEntry 3 }
|
|
|
|
upsBypassPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present true power conveyed by the bypass."
|
|
::= { upsBypassEntry 4 }
|
|
|
|
|
|
--
|
|
-- The Alarm group.
|
|
--
|
|
|
|
upsAlarm OBJECT IDENTIFIER ::= { upsObjects 6 }
|
|
|
|
upsAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { upsAlarm 1 }
|
|
|
|
upsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of alarm table entries. The table contains
|
|
zero, one, or many rows at any moment, depending upon
|
|
the number of alarm conditions in effect. The table
|
|
is initially empty at agent startup. The agent
|
|
creates a row in the table each time a condition is
|
|
detected and deletes that row when that condition no
|
|
longer pertains. The agent creates the first row with
|
|
upsAlarmId equal to 1, and increments the value of
|
|
upsAlarmId each time a new row is created, wrapping to
|
|
the first free value greater than or equal to 1 when
|
|
the maximum value of upsAlarmId would otherwise be
|
|
exceeded. Consequently, after multiple operations,
|
|
the table may become sparse, e.g., containing entries
|
|
for rows 95, 100, 101, and 203 and the entries should
|
|
not be assumed to be in chronological order because
|
|
upsAlarmId might have wrapped.
|
|
|
|
Alarms are named by an AutonomousType (OBJECT
|
|
IDENTIFIER), upsAlarmDescr, to allow a single table to
|
|
reflect well known alarms plus alarms defined by a
|
|
particular implementation, i.e., as documented in the
|
|
private enterprise MIB definition for the device. No
|
|
two rows will have the same value of upsAlarmDescr,
|
|
since alarms define conditions. In order to meet this
|
|
requirement, care should be taken in the definition of
|
|
alarm conditions to insure that a system cannot enter
|
|
the same condition multiple times simultaneously.
|
|
|
|
The number of rows in the table at any given time is
|
|
reflected by the value of upsAlarmsPresent."
|
|
::= { upsAlarm 2 }
|
|
|
|
upsAlarmEntry OBJECT-TYPE
|
|
SYNTAX UpsAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular alarm."
|
|
INDEX { upsAlarmId }
|
|
::= { upsAlarmTable 1 }
|
|
|
|
UpsAlarmEntry ::= SEQUENCE {
|
|
upsAlarmId PositiveInteger,
|
|
upsAlarmDescr AutonomousType,
|
|
upsAlarmTime TimeStamp
|
|
}
|
|
|
|
upsAlarmId OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition. This
|
|
value must remain constant."
|
|
::= { upsAlarmEntry 1 }
|
|
|
|
upsAlarmDescr OBJECT-TYPE
|
|
SYNTAX AutonomousType
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to an alarm description object. The
|
|
object referenced should not be accessible, but rather
|
|
be used to provide a unique description of the alarm
|
|
condition."
|
|
::= { upsAlarmEntry 2 }
|
|
|
|
upsAlarmTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was
|
|
detected. If the alarm condition was detected at the
|
|
time of agent startup and presumably existed before
|
|
agent startup, the value of upsAlarmTime shall equal
|
|
0."
|
|
::= { upsAlarmEntry 3 }
|
|
|
|
|
|
--
|
|
-- Well known alarm conditions.
|
|
--
|
|
|
|
upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm 3 }
|
|
|
|
upsAlarmBatteryBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement."
|
|
::= { upsWellKnownAlarms 1 }
|
|
|
|
upsAlarmOnBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS is drawing power from the batteries."
|
|
::= { upsWellKnownAlarms 2 }
|
|
|
|
upsAlarmLowBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remaining battery run-time is less than or equal
|
|
to upsConfigLowBattTime."
|
|
::= { upsWellKnownAlarms 3 }
|
|
|
|
|
|
upsAlarmDepletedBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will be unable to sustain the present load
|
|
when and if the utility power is lost."
|
|
::= { upsWellKnownAlarms 4 }
|
|
|
|
upsAlarmTempBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature is out of tolerance."
|
|
::= { upsWellKnownAlarms 5 }
|
|
|
|
upsAlarmInputBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input condition is out of tolerance."
|
|
::= { upsWellKnownAlarms 6 }
|
|
|
|
upsAlarmOutputBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An output condition (other than OutputOverload) is
|
|
out of tolerance."
|
|
::= { upsWellKnownAlarms 7 }
|
|
|
|
upsAlarmOutputOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity."
|
|
::= { upsWellKnownAlarms 8 }
|
|
|
|
upsAlarmOnBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is presently engaged on the UPS."
|
|
::= { upsWellKnownAlarms 9 }
|
|
|
|
upsAlarmBypassBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is out of tolerance."
|
|
::= { upsWellKnownAlarms 10 }
|
|
|
|
upsAlarmOutputOffAsRequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has shutdown as requested, i.e., the output
|
|
is off."
|
|
::= { upsWellKnownAlarms 11 }
|
|
|
|
upsAlarmUpsOffAsRequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The entire UPS has shutdown as commanded."
|
|
::= { upsWellKnownAlarms 12 }
|
|
|
|
upsAlarmChargerFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An uncorrected problem has been detected within the
|
|
UPS charger subsystem."
|
|
::= { upsWellKnownAlarms 13 }
|
|
|
|
upsAlarmUpsOutputOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output of the UPS is in the off state."
|
|
::= { upsWellKnownAlarms 14 }
|
|
|
|
upsAlarmUpsSystemOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS system is in the off state."
|
|
::= { upsWellKnownAlarms 15 }
|
|
|
|
upsAlarmFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fans in the UPS has been
|
|
detected."
|
|
::= { upsWellKnownAlarms 16 }
|
|
|
|
upsAlarmFuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected."
|
|
::= { upsWellKnownAlarms 17 }
|
|
|
|
upsAlarmGeneralFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected."
|
|
::= { upsWellKnownAlarms 18 }
|
|
|
|
upsAlarmDiagnosticTestFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a
|
|
failure."
|
|
::= { upsWellKnownAlarms 19 }
|
|
|
|
upsAlarmCommunicationsLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem has been encountered in the communications
|
|
between the agent and the UPS."
|
|
::= { upsWellKnownAlarms 20 }
|
|
|
|
upsAlarmAwaitingPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the
|
|
return of input power."
|
|
::= { upsWellKnownAlarms 21 }
|
|
|
|
upsAlarmShutdownPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway."
|
|
::= { upsWellKnownAlarms 22 }
|
|
|
|
upsAlarmShutdownImminent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will turn off power to the load in less than
|
|
5 seconds; this may be either a timed shutdown or a
|
|
low battery shutdown."
|
|
::= { upsWellKnownAlarms 23 }
|
|
|
|
upsAlarmTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A test is in progress, as initiated and indicated by
|
|
the Test Group. Tests initiated via other
|
|
implementation-specific mechanisms can indicate the
|
|
presence of the testing in the alarm table, if
|
|
desired, via a OBJECT-IDENTITY macro in the MIB
|
|
document specific to that implementation and are
|
|
outside the scope of this OBJECT-IDENTITY."
|
|
::= { upsWellKnownAlarms 24 }
|
|
|
|
|
|
--
|
|
-- The Test Group
|
|
--
|
|
|
|
upsTest OBJECT IDENTIFIER ::= { upsObjects 7 }
|
|
|
|
upsTestId OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The test is named by an OBJECT IDENTIFIER which
|
|
allows a standard mechanism for the initiation of
|
|
tests, including the well known tests identified in
|
|
this document as well as those introduced by a
|
|
particular implementation, i.e., as documented in the
|
|
private enterprise MIB definition for the device.
|
|
|
|
Setting this variable initiates the named test. Sets
|
|
to this variable require the presence of
|
|
upsTestSpinLock in the same SNMP message.
|
|
|
|
The set request will be rejected with an appropriate
|
|
error message if the requested test cannot be
|
|
performed, including attempts to start a test when
|
|
another test is already in progress. The status of
|
|
the current or last test is maintained in
|
|
upsTestResultsSummary. Tests in progress may be
|
|
aborted by setting the upsTestId variable to
|
|
upsTestAbortTestInProgress.
|
|
|
|
Read operations return the value of the name of the
|
|
test in progress if a test is in progress or the name
|
|
of the last test performed if no test is in progress,
|
|
unless no test has been run, in which case the well
|
|
known value upsTestNoTestsInitiated is returned."
|
|
::= { upsTest 1 }
|
|
|
|
-- see [6] for more information on the semantics of objects with
|
|
-- syntax of TestAndIncr
|
|
|
|
upsTestSpinLock OBJECT-TYPE
|
|
SYNTAX TestAndIncr
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A spin lock on the test subsystem. The spinlock is
|
|
used as follows.
|
|
|
|
Before starting a test, a manager-station should make
|
|
sure that a test is not in progress as follows:
|
|
|
|
try_again:
|
|
get (upsTestSpinLock)
|
|
while (upsTestResultsSummary == inProgress) {
|
|
/* loop while a test is running for another
|
|
manager */
|
|
short delay
|
|
get (upsTestSpinLock)
|
|
}
|
|
lock_value = upsTestSpinLock
|
|
/* no test in progress, start the test */
|
|
set (upsTestSpinLock = lock_value, upsTestId =
|
|
requested_test)
|
|
if (error_index == 1) { /* (upsTestSpinLock
|
|
failed) */
|
|
/* if problem is not access control, then
|
|
some other manager slipped in ahead of us
|
|
*/
|
|
goto try_again
|
|
}
|
|
if (error_index == 2) { /* (upsTestId) */
|
|
/* cannot perform the test */
|
|
give up
|
|
}
|
|
/* test started ok */
|
|
/* wait for test completion by polling
|
|
upsTestResultsSummary */
|
|
get (upsTestSpinLock, upsTestResultsSummary,
|
|
upsTestResultsDetail)
|
|
while (upsTestResultsSummary == inProgress) {
|
|
short delay
|
|
get (upsTestSpinLock, upsTestResultsSummary,
|
|
upsTestResultsDetail)
|
|
}
|
|
/* when test completes, retrieve any additional
|
|
test results */
|
|
/* if upsTestSpinLock == lock_value + 1, then
|
|
these are our test */
|
|
/* results (as opposed to another manager's */
|
|
The initial value of upsTestSpinLock at agent
|
|
initialization shall
|
|
be 1."
|
|
::= { upsTest 2 }
|
|
|
|
upsTestResultsSummary OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
donePass(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestsInitiated(6)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePass(1),
|
|
doneWarning(2), and doneError(3) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively. The value aborted(4) is
|
|
returned for tests which are aborted by setting the
|
|
value of upsTestId to upsTestAbortTestInProgress.
|
|
Tests which have not yet concluded are indicated by
|
|
inProgress(5). The value noTestsInitiated(6)
|
|
indicates that no previous test results are available,
|
|
such as is the case when no tests have been run since
|
|
the last reinitialization of the network management
|
|
subsystem and the system has no provision for non-
|
|
volatile storage of test results."
|
|
::= { upsTest 3 }
|
|
|
|
upsTestResultsDetail OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Additional information about upsTestResultsSummary.
|
|
If no additional information available, a zero length
|
|
string is returned."
|
|
::= { upsTest 4 }
|
|
|
|
upsTestStartTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime at the time the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the time the previous test was initiated. If the
|
|
value of upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestStartTime has the value 0."
|
|
::= { upsTest 5 }
|
|
|
|
upsTestElapsedTime OBJECT-TYPE
|
|
SYNTAX TimeInterval
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of time, in TimeTicks, since the test in
|
|
progress was initiated, or, if no test is in progress,
|
|
the previous test took to complete. If the value of
|
|
upsTestResultsSummary is noTestsInitiated(6),
|
|
upsTestElapsedTime has the value 0."
|
|
::= { upsTest 6 }
|
|
|
|
--
|
|
-- Well known tests.
|
|
--
|
|
|
|
upsWellKnownTests OBJECT IDENTIFIER ::= { upsTest 7 }
|
|
|
|
|
|
upsTestNoTestsInitiated OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No tests have been initiated and no test is in
|
|
progress."
|
|
::= { upsWellKnownTests 1 }
|
|
|
|
upsTestAbortTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The test in progress is to be aborted / the test in
|
|
progress was aborted."
|
|
::= { upsWellKnownTests 2 }
|
|
|
|
upsTestGeneralSystemsTest OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The manufacturer's standard test of UPS device
|
|
systems."
|
|
::= { upsWellKnownTests 3 }
|
|
|
|
upsTestQuickBatteryTest OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A test that is sufficient to determine if the battery
|
|
needs replacement."
|
|
::= { upsWellKnownTests 4 }
|
|
|
|
upsTestDeepBatteryCalibration OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is placed on battery to a discharge level,
|
|
set by the manufacturer, sufficient to determine
|
|
battery replacement and battery run-time with a high
|
|
degree of confidence. WARNING: this test will leave
|
|
the battery in a low charge state and will require
|
|
time for recharging to a level sufficient to provide
|
|
normal battery duration for the protected load."
|
|
::= { upsWellKnownTests 5 }
|
|
|
|
|
|
--
|
|
-- The Control group.
|
|
--
|
|
|
|
upsControl OBJECT IDENTIFIER ::= { upsObjects 8 }
|
|
|
|
upsShutdownType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
output(1),
|
|
system(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object determines the nature of the action to be
|
|
taken at the time when the countdown of the
|
|
upsShutdownAfterDelay and upsRebootWithDuration
|
|
objects reaches zero.
|
|
|
|
Setting this object to output(1) indicates that
|
|
shutdown requests should cause only the output of the
|
|
UPS to turn off. Setting this object to system(2)
|
|
indicates that shutdown requests will cause the entire
|
|
UPS system to turn off."
|
|
::= { upsControl 1 }
|
|
|
|
upsShutdownAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..2147483648)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will shutdown (i.e., turn off)
|
|
either the UPS output or the UPS system (as determined
|
|
by the value of upsShutdownType at the time of
|
|
shutdown) after the indicated number of seconds, or
|
|
less if the UPS batteries become depleted. Setting
|
|
this object to 0 will cause the shutdown to occur
|
|
immediately. Setting this object to -1 will abort the
|
|
countdown. If the system is already in the desired
|
|
state at the time the countdown reaches 0, then
|
|
nothing will happen. That is, there is no additional
|
|
action at that time if upsShutdownType = system and
|
|
the system is already off. Similarly, there is no
|
|
additional action at that time if upsShutdownType =
|
|
output and the output is already off. When read,
|
|
upsShutdownAfterDelay will return the number of
|
|
seconds remaining until shutdown, or -1 if no shutdown
|
|
countdown is in effect. On some systems, if the agent
|
|
is restarted while a shutdown countdown is in effect,
|
|
the countdown may be aborted. Sets to this object
|
|
override any upsShutdownAfterDelay already in effect."
|
|
::= { upsControl 2 }
|
|
|
|
upsStartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..2147483648)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds, including starting the
|
|
UPS, if necessary. Setting this object to 0 will
|
|
cause the startup to occur immediately. Setting this
|
|
object to -1 will abort the countdown. If the output
|
|
is already on at the time the countdown reaches 0,
|
|
then nothing will happen. Sets to this object
|
|
override the effect of any upsStartupAfterDelay
|
|
countdown or upsRebootWithDuration countdown in
|
|
progress. When read, upsStartupAfterDelay will return
|
|
the number of seconds until startup, or -1 if no
|
|
startup countdown is in effect. If the countdown
|
|
expires during a utility failure, the startup shall
|
|
not occur until the utility power is restored. On
|
|
some systems, if the agent is restarted while a
|
|
startup countdown is in effect, the countdown is
|
|
aborted."
|
|
::= { upsControl 3 }
|
|
|
|
upsRebootWithDuration OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..300)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will immediately shutdown (i.e.,
|
|
turn off) either the UPS output or the UPS system (as
|
|
determined by the value of upsShutdownType at the time
|
|
of shutdown) for a period equal to the indicated
|
|
number of seconds, after which time the output will be
|
|
started, including starting the UPS, if necessary. If
|
|
the number of seconds required to perform the request
|
|
is greater than the requested duration, then the
|
|
requested shutdown and startup cycle shall be
|
|
performed in the minimum time possible, but in no case
|
|
shall this require more than the requested duration
|
|
plus 60 seconds. When read, upsRebootWithDuration
|
|
shall return the number of seconds remaining in the
|
|
countdown, or -1 if no countdown is in progress. If
|
|
the startup should occur during a utility failure, the
|
|
startup shall not occur until the utility power is
|
|
restored."
|
|
::= { upsControl 4 }
|
|
|
|
upsAutoRestart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to 'on' will cause the UPS system
|
|
to restart after a shutdown if the shutdown occurred
|
|
during a power loss as a result of either a
|
|
upsShutdownAfterDelay or an internal battery depleted
|
|
condition. Setting this object to 'off' will prevent
|
|
the UPS system from restarting after a shutdown until
|
|
an operator manually or remotely explicitly restarts
|
|
it. If the UPS is in a startup or reboot countdown,
|
|
then the UPS will not restart until that delay has
|
|
been satisfied."
|
|
::= { upsControl 5 }
|
|
|
|
|
|
--
|
|
-- The Configuration group.
|
|
--
|
|
|
|
upsConfig OBJECT IDENTIFIER ::= { upsObjects 9 }
|
|
|
|
upsConfigInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal input voltage. On those
|
|
systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 1 }
|
|
|
|
upsConfigInputFreq OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal input frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 2 }
|
|
|
|
upsConfigOutputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal output voltage. On
|
|
those systems which support read-write access to this
|
|
object, if there is an attempt to set this variable to
|
|
a value that is not supported, the request must be
|
|
rejected and the agent shall respond with an
|
|
appropriate error message, i.e., badValue for SNMPv1,
|
|
or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 3 }
|
|
|
|
upsConfigOutputFreq OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Hertz"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal output frequency. On those systems which
|
|
support read-write access to this object, if there is
|
|
an attempt to set this variable to a value that is not
|
|
supported, the request must be rejected and the agent
|
|
shall respond with an appropriate error message, i.e.,
|
|
badValue for SNMPv1, or inconsistentValue for SNMPv2."
|
|
::= { upsConfig 4 }
|
|
|
|
upsConfigOutputVA OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal Volt-Amp rating."
|
|
::= { upsConfig 5 }
|
|
|
|
upsConfigOutputPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the nominal true power rating."
|
|
::= { upsConfig 6 }
|
|
|
|
upsConfigLowBattTime OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "minutes"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of upsEstimatedMinutesRemaining at which a
|
|
lowBattery condition is declared. For agents which
|
|
support only discrete (discontinuous) values, then the
|
|
agent shall round up to the next supported value. If
|
|
the requested value is larger than the largest
|
|
supported value, then the largest supported value
|
|
shall be selected."
|
|
::= { upsConfig 7 }
|
|
|
|
upsConfigAudibleStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
enabled(2),
|
|
muted(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The requested state of the audible alarm. When in
|
|
the disabled state, the audible alarm should never
|
|
sound. The enabled state is self-describing. Setting
|
|
this object to muted(3) when the audible alarm is
|
|
sounding shall temporarily silence the alarm. It will
|
|
remain muted until it would normally stop sounding and
|
|
the value returned for read operations during this
|
|
period shall equal muted(3). At the end of this
|
|
period, the value shall revert to enabled(2). Writes
|
|
of the value muted(3) when the audible alarm is not
|
|
sounding shall be accepted but otherwise shall have no
|
|
effect."
|
|
::= { upsConfig 8 }
|
|
|
|
upsConfigLowVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum input line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { upsConfig 9 }
|
|
|
|
upsConfigHighVoltageTransferPoint OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum line voltage allowed before the UPS
|
|
system transfers to battery backup."
|
|
::= { upsConfig 10 }
|
|
|
|
|
|
--
|
|
-- notifications, i.e., traps
|
|
--
|
|
upsTraps OBJECT IDENTIFIER ::= { upsMIB 2 }
|
|
|
|
-- This section defines the well-known notifications sent by
|
|
-- UPS agents.
|
|
-- Care must be taken to insure that no particular notification
|
|
-- is sent to a single receiving entity more often than once
|
|
-- every five seconds.
|
|
|
|
upsTrapOnBattery NOTIFICATION-TYPE
|
|
OBJECTS { upsEstimatedMinutesRemaining, upsSecondsOnBattery,
|
|
upsConfigLowBattTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS is operating on battery power. This trap is
|
|
persistent and is resent at one minute intervals until
|
|
the UPS either turns off or is no longer running on
|
|
battery."
|
|
::= { upsTraps 1 }
|
|
|
|
upsTrapTestCompleted NOTIFICATION-TYPE
|
|
OBJECTS { upsTestId, upsTestSpinLock,
|
|
upsTestResultsSummary, upsTestResultsDetail,
|
|
upsTestStartTime, upsTestElapsedTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent upon completion of a UPS diagnostic
|
|
test."
|
|
::= { upsTraps 2 }
|
|
|
|
upsTrapAlarmEntryAdded NOTIFICATION-TYPE
|
|
OBJECTS { upsAlarmId, upsAlarmDescr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is inserted into
|
|
to the alarm table. It is sent on the insertion of
|
|
all alarms except for upsAlarmOnBattery and
|
|
upsAlarmTestInProgress."
|
|
::= { upsTraps 3 }
|
|
|
|
upsTrapAlarmEntryRemoved NOTIFICATION-TYPE
|
|
OBJECTS { upsAlarmId, upsAlarmDescr }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is removed from
|
|
the alarm table. It is sent on the removal of all
|
|
alarms except for upsAlarmTestInProgress."
|
|
::= { upsTraps 4 }
|
|
|
|
|
|
--
|
|
-- conformance information
|
|
--
|
|
upsConformance OBJECT IDENTIFIER ::= { upsMIB 3 }
|
|
|
|
upsCompliances OBJECT IDENTIFIER ::= { upsConformance 1 }
|
|
|
|
|
|
--
|
|
-- compliance statements
|
|
--
|
|
|
|
upsSubsetCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
|
|
"The compliance statement for UPSs that only support
|
|
the two-contact communication protocol."
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS { upsSubsetIdentGroup,
|
|
upsSubsetBatteryGroup, upsSubsetInputGroup,
|
|
upsSubsetOutputGroup, upsSubsetAlarmGroup,
|
|
upsSubsetControlGroup, upsSubsetConfigGroup }
|
|
|
|
OBJECT upsBatteryStatus
|
|
SYNTAX INTEGER {
|
|
batteryNormal(2),
|
|
batteryLow(3)
|
|
}
|
|
DESCRIPTION
|
|
"Support of the values unknown(1) and
|
|
batteryDepleted(4) is not required."
|
|
|
|
OBJECT upsAlarmDescr
|
|
DESCRIPTION
|
|
"Support of all `well known' alarm types is not
|
|
required. The well known alarm types which must be
|
|
supported are: upsAlarmOnBattery, upsAlarmLowBattery,
|
|
upsAlarmInputBad, upsAlarmUpsOutputOff,
|
|
upsAlarmUpsSystemOff, and upsAlarmTestInProgress."
|
|
|
|
OBJECT upsOutputSource
|
|
SYNTAX INTEGER {
|
|
normal(2),
|
|
battery(4)
|
|
}
|
|
DESCRIPTION
|
|
"Support of the values other(1), none(2), bypass(4),
|
|
booster(6) and reducer(7) is not required."
|
|
|
|
OBJECT upsShutdownType
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required, i.e., compliant
|
|
systems need not support more than one shutdown type."
|
|
|
|
OBJECT upsAutoRestart
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required, i.e., compliant
|
|
systems need not support more than one restart type."
|
|
|
|
OBJECT upsConfigInputVoltage
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigInputFreq
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigOutputVoltage
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigOutputFreq
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
::= { upsCompliances 1 }
|
|
|
|
upsBasicCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
|
|
"The compliance statement for UPSs that support
|
|
full-featured functions, such as control."
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS { upsBasicIdentGroup,
|
|
upsBasicBatteryGroup, upsBasicInputGroup,
|
|
upsBasicOutputGroup, upsBasicAlarmGroup,
|
|
upsBasicTestGroup, upsBasicControlGroup,
|
|
upsBasicConfigGroup }
|
|
|
|
|
|
OBJECT upsAlarmDescr
|
|
DESCRIPTION
|
|
"Support of all `well known' alarm types is not
|
|
required. The well known alarm types which must be
|
|
supported are: upsAlarmOnBattery, upsAlarmLowBattery,
|
|
upsAlarmDepletedBattery, upsAlarmTempBad,
|
|
upsAlarmInputBad, upsAlarmOutputOverload,
|
|
upsAlarmOnBypass, upsAlarmBypassBad,
|
|
upsAlarmOutputOffAsRequested,
|
|
upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
|
|
upsAlarmUpsSystemOff, upsAlarmGeneralFault,
|
|
upsAlarmDiagnosticTestFailed,
|
|
upsAlarmCommunicationsLost, upsAlarmShutdownPending,
|
|
and upsAlarmTestInProgress."
|
|
|
|
OBJECT upsTestId
|
|
DESCRIPTION
|
|
"Support of all `well known' test types is not
|
|
required. If no tests are supported, then the only
|
|
well known test type which must be supported is
|
|
upsTestNoTestsInitiated."
|
|
|
|
OBJECT upsOutputSource
|
|
SYNTAX INTEGER {
|
|
normal(2),
|
|
battery(4)
|
|
}
|
|
DESCRIPTION
|
|
"Support of the values other(1), none(2), bypass(4),
|
|
booster(6) and reducer(7) is not required."
|
|
|
|
GROUP upsBasicBypassGroup
|
|
DESCRIPTION
|
|
"The upsBasicBypassGroup is only required for UPSs
|
|
that have a Bypass present."
|
|
OBJECT upsShutdownType
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required, i.e., compliant
|
|
systems need not support more than one shutdown type."
|
|
|
|
OBJECT upsAutoRestart
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required, i.e., compliant
|
|
systems need not support more than one restart type."
|
|
|
|
OBJECT upsConfigInputVoltage
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigInputFreq
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigOutputVoltage
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigOutputFreq
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigLowBattTime
|
|
DESCRIPTION
|
|
"Implementation of all possible values may be onerous
|
|
for some systems. Consequently, not all possible
|
|
values must be supported. However, at least two
|
|
different manufacturer-selected values must be
|
|
supported."
|
|
|
|
::= { upsCompliances 2 }
|
|
|
|
upsFullCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compliance statement for UPSs that support
|
|
advanced full-featured functions."
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS { upsFullIdentGroup, upsFullBatteryGroup,
|
|
upsFullInputGroup, upsFullOutputGroup,
|
|
upsFullAlarmGroup, upsFullTestGroup,
|
|
upsFullControlGroup, upsFullConfigGroup }
|
|
|
|
OBJECT upsAlarmDescr
|
|
DESCRIPTION
|
|
"Support of all `well known' alarm types is not
|
|
required. The well known alarm types which must be
|
|
supported are: upsAlarmBatteryBad, upsAlarmOnBattery,
|
|
upsAlarmLowBattery, upsAlarmDepletedBattery,
|
|
upsAlarmTempBad, upsAlarmInputBad, upsAlarmOnBypass,
|
|
upsAlarmBypassBad, upsAlarmOutputOffAsRequested,
|
|
upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
|
|
upsAlarmUpsSystemOff, upsAlarmGeneralFault,
|
|
upsAlarmDiagnosticTestFailed,
|
|
upsAlarmCommunicationsLost, upsAlarmShutdownPending,
|
|
and upsAlarmTestInProgress."
|
|
|
|
OBJECT upsTestId
|
|
DESCRIPTION
|
|
"Support of all `well known' test types is not
|
|
required. The well known test types which must be
|
|
supported are: upsTestNoTestsInitiated,
|
|
upsTestGeneralSystemsTest, and
|
|
upsTestQuickBatteryTest."
|
|
|
|
OBJECT upsOutputSource
|
|
SYNTAX INTEGER {
|
|
normal(2),
|
|
battery(4)
|
|
}
|
|
DESCRIPTION
|
|
"Support of the values other(1), none(2), bypass(4),
|
|
booster(6) and reducer(7) is not required."
|
|
|
|
GROUP upsFullBypassGroup
|
|
DESCRIPTION
|
|
"The upsFullBypassGroup is only required for UPSs that
|
|
have a Bypass present."
|
|
|
|
OBJECT upsShutdownType
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required, i.e., compliant
|
|
systems need not support more than one shutdown type."
|
|
|
|
OBJECT upsAutoRestart
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required, i.e., compliant
|
|
systems need not support more than one restart type."
|
|
|
|
OBJECT upsConfigInputVoltage
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigInputFreq
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigOutputVoltage
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigOutputFreq
|
|
MIN-ACCESS read-only
|
|
DESCRIPTION
|
|
"Read-write access is not required."
|
|
|
|
OBJECT upsConfigLowBattTime
|
|
DESCRIPTION
|
|
"Implementation of all possible values may be onerous
|
|
for some systems. Consequently, not all possible
|
|
values must be supported. However, at least two
|
|
different manufacturer-selected values must be
|
|
supported."
|
|
|
|
::= { upsCompliances 3 }
|
|
|
|
|
|
--
|
|
-- units of conformance
|
|
--
|
|
|
|
-- summary at a glance:
|
|
|
|
-- subset basic adv
|
|
--upsIdentManufacturer x x x
|
|
--upsIdentModel x x x
|
|
|
|
--upsIdentUPSSoftwareVersion x x
|
|
--upsIdentAgentSoftwareVersion x x x
|
|
--upsIdentName x x x
|
|
--upsIdentAttachedDevices x x
|
|
--
|
|
--upsBatteryStatus x x x notes
|
|
--upsSecondsOnBattery x x x
|
|
--upsEstimatedMinutesRemaining x
|
|
--upsEstimatedChargeRemaining x
|
|
--upsBatteryVoltage
|
|
--upsBatteryCurrent
|
|
--upsBatteryTemperature
|
|
--
|
|
--upsInputLineBads x x x
|
|
--upsInputNumLines x x
|
|
--upsInputFrequency x x
|
|
--upsInputVoltage x x
|
|
--upsInputCurrent
|
|
--upsInputTruePower
|
|
--
|
|
--upsOutputSource x x x notes
|
|
--upsOutputFrequency x x
|
|
--upsOutputNumLines x x
|
|
--upsOutputVoltage x x
|
|
--upsOutputCurrent x
|
|
--upsOutputPower x
|
|
--upsOutputPercentLoad x
|
|
--
|
|
--
|
|
--upsBypassFrequency x x notes
|
|
--upsBypassNumLines x x
|
|
--upsBypassVoltage x x
|
|
--upsBypassCurrent
|
|
--upsBypassPower
|
|
--
|
|
--
|
|
--upsAlarmsPresent x x x
|
|
--upsAlarmDescr x x x notes
|
|
--upsAlarmTime x x x
|
|
--
|
|
--upsTestId x x notes
|
|
--upsTestSpinLock x x
|
|
--upsTestResultsSummary x x
|
|
--upsTestResultsDetail x x
|
|
--upsTestStartTime x x
|
|
--upsTestElapsedTime x x
|
|
--
|
|
--upsShutdownType x x x notes
|
|
|
|
--upsShutdownAfterDelay x x x
|
|
--upsStartupAfterDelay x x
|
|
--upsRebootWithDuration x x
|
|
--upsAutoRestart x x x notes
|
|
--
|
|
--upsConfigInputVoltage x x x notes
|
|
--upsConfigInputFreq x x x notes
|
|
--upsConfigOutputVoltage x x x notes
|
|
--upsConfigOutputFreq x x x notes
|
|
--upsConfigOutputVA x x x
|
|
--upsConfigOutputPower x x x
|
|
--upsConfigLowBattTime x x notes
|
|
--upsConfigAudibleStatus x x
|
|
--upsConfigLowVoltageTransferPoint
|
|
--upsConfigHighVoltageTransferPoint
|
|
|
|
|
|
-- units of conformance
|
|
upsGroups OBJECT IDENTIFIER ::= { upsConformance 2 }
|
|
|
|
upsSubsetGroups OBJECT IDENTIFIER ::= { upsGroups 1 }
|
|
|
|
upsSubsetIdentGroup OBJECT-GROUP
|
|
OBJECTS { upsIdentManufacturer, upsIdentModel,
|
|
upsIdentAgentSoftwareVersion, upsIdentName,
|
|
upsIdentAttachedDevices }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsSubsetIdentGroup defines objects which are
|
|
common across all UPSs which meet subset compliance.
|
|
Most devices which conform to the upsSubsetIdentGroup
|
|
will provide access to these objects via a proxy
|
|
agent. If the proxy agent is compatible with multiple
|
|
UPS types, configuration of the proxy agent will
|
|
require specifying some of these values, either
|
|
individually, or as a group (perhaps through a table
|
|
lookup mechanism based on the UPS model number)."
|
|
::= { upsSubsetGroups 1 }
|
|
|
|
upsSubsetBatteryGroup OBJECT-GROUP
|
|
OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsSubsetBatteryGroup defines the objects that
|
|
are common to battery groups of two-contact UPSs."
|
|
::= { upsSubsetGroups 2 }
|
|
|
|
upsSubsetInputGroup OBJECT-GROUP
|
|
OBJECTS { upsInputLineBads }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsSubsetInputGroup defines the objects that are
|
|
common to the Input groups of two-contact UPSs."
|
|
::= { upsSubsetGroups 3 }
|
|
|
|
upsSubsetOutputGroup OBJECT-GROUP
|
|
OBJECTS { upsOutputSource }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsSubsetOutputGroup defines the objects that are
|
|
common to the Output groups of two-contact UPSs."
|
|
::= { upsSubsetGroups 4 }
|
|
|
|
|
|
-- { upsSubsetGroups 5 } is reserved for
|
|
-- future use (upsSubsetBypassGroup)
|
|
|
|
upsSubsetAlarmGroup OBJECT-GROUP
|
|
OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsSubsetAlarmGroup defines the objects that are
|
|
common to the Alarm groups of two-contact UPSs."
|
|
::= { upsSubsetGroups 6 }
|
|
|
|
-- { upsSubsetGroups 7 } is reserved for
|
|
-- future use (upsSubsetTestGroup)
|
|
|
|
upsSubsetControlGroup OBJECT-GROUP
|
|
OBJECTS { upsShutdownType, upsShutdownAfterDelay,
|
|
upsAutoRestart }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsSubsetControlGroup defines the objects that
|
|
are common to the Control groups of two-contact UPSs."
|
|
::= { upsSubsetGroups 8 }
|
|
|
|
upsSubsetConfigGroup OBJECT-GROUP
|
|
OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
|
|
upsConfigOutputVoltage, upsConfigOutputFreq,
|
|
upsConfigOutputVA, upsConfigOutputPower }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsSubsetConfigGroup defines the objects that are
|
|
common to the Config groups of two-contact UPSs."
|
|
::= { upsSubsetGroups 9 }
|
|
upsBasicGroups OBJECT IDENTIFIER ::= { upsGroups 2 }
|
|
|
|
upsBasicIdentGroup OBJECT-GROUP
|
|
OBJECTS { upsIdentManufacturer, upsIdentModel,
|
|
upsIdentUPSSoftwareVersion,
|
|
upsIdentAgentSoftwareVersion, upsIdentName }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicIdentGroup defines objects which are
|
|
common to the Ident group of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 1 }
|
|
|
|
upsBasicBatteryGroup OBJECT-GROUP
|
|
OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicBatteryGroup defines the objects that are
|
|
common to the battery groups of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 2 }
|
|
|
|
upsBasicInputGroup OBJECT-GROUP
|
|
OBJECTS { upsInputLineBads, upsInputNumLines,
|
|
upsInputFrequency, upsInputVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicInputGroup defines the objects that are
|
|
common to the Input groups of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 3 }
|
|
|
|
upsBasicOutputGroup OBJECT-GROUP
|
|
OBJECTS { upsOutputSource, upsOutputFrequency,
|
|
upsOutputNumLines, upsOutputVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicOutputGroup defines the objects that are
|
|
common to the Output groups of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 4 }
|
|
|
|
upsBasicBypassGroup OBJECT-GROUP
|
|
OBJECTS { upsBypassFrequency, upsBypassNumLines,
|
|
upsBypassVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicBypassGroup defines the objects that are
|
|
common to the Bypass groups of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 5 }
|
|
|
|
upsBasicAlarmGroup OBJECT-GROUP
|
|
OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
|
|
"The upsBasicAlarmGroup defines the objects that are
|
|
common to the Alarm groups of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 6 }
|
|
|
|
upsBasicTestGroup OBJECT-GROUP
|
|
OBJECTS { upsTestId, upsTestSpinLock,
|
|
upsTestResultsSummary, upsTestResultsDetail,
|
|
upsTestStartTime, upsTestElapsedTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicTestGroup defines the objects that are
|
|
common to the Test groups of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 7 }
|
|
|
|
upsBasicControlGroup OBJECT-GROUP
|
|
OBJECTS { upsShutdownType, upsShutdownAfterDelay,
|
|
upsStartupAfterDelay, upsRebootWithDuration,
|
|
upsAutoRestart }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicControlGroup defines the objects that are
|
|
common to the Control groups of compliant UPSs which
|
|
support basic functions."
|
|
::= { upsBasicGroups 8 }
|
|
|
|
upsBasicConfigGroup OBJECT-GROUP
|
|
OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
|
|
upsConfigOutputVoltage, upsConfigOutputFreq,
|
|
upsConfigOutputVA, upsConfigOutputPower,
|
|
upsConfigLowBattTime, upsConfigAudibleStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsBasicConfigGroup defines the objects that are
|
|
common to the Config groups of UPSs which support
|
|
basic functions."
|
|
::= { upsBasicGroups 9 }
|
|
upsFullGroups OBJECT IDENTIFIER ::= { upsGroups 3 }
|
|
|
|
upsFullIdentGroup OBJECT-GROUP
|
|
OBJECTS { upsIdentManufacturer, upsIdentModel,
|
|
upsIdentUPSSoftwareVersion,
|
|
upsIdentAgentSoftwareVersion, upsIdentName,
|
|
upsIdentAttachedDevices }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullIdentGroup defines objects which are
|
|
common to the Ident group of fully compliant UPSs."
|
|
::= { upsFullGroups 1 }
|
|
|
|
upsFullBatteryGroup OBJECT-GROUP
|
|
OBJECTS { upsBatteryStatus, upsSecondsOnBattery,
|
|
upsEstimatedMinutesRemaining,
|
|
upsEstimatedChargeRemaining }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullBatteryGroup defines the objects that are
|
|
common to the battery groups of fully compliant UPSs."
|
|
::= { upsFullGroups 2 }
|
|
|
|
upsFullInputGroup OBJECT-GROUP
|
|
OBJECTS { upsInputLineBads, upsInputNumLines,
|
|
upsInputFrequency, upsInputVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullInputGroup defines the objects that are
|
|
common to the Input groups of fully compliant UPSs."
|
|
::= { upsFullGroups 3 }
|
|
|
|
upsFullOutputGroup OBJECT-GROUP
|
|
OBJECTS { upsOutputSource, upsOutputFrequency,
|
|
upsOutputNumLines, upsOutputVoltage,
|
|
upsOutputCurrent, upsOutputPower,
|
|
upsOutputPercentLoad }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullOutputGroup defines the objects that are
|
|
common to the Output groups of fully compliant UPSs."
|
|
::= { upsFullGroups 4 }
|
|
|
|
upsFullBypassGroup OBJECT-GROUP
|
|
OBJECTS { upsBypassFrequency, upsBypassNumLines,
|
|
upsBypassVoltage }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullBypassGroup defines the objects that are
|
|
common to the Bypass groups of fully compliant UPSs."
|
|
::= { upsFullGroups 5 }
|
|
|
|
upsFullAlarmGroup OBJECT-GROUP
|
|
OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
|
|
"The upsFullAlarmGroup defines the objects that are
|
|
common to the Alarm groups of fully compliant UPSs."
|
|
::= { upsFullGroups 6 }
|
|
|
|
upsFullTestGroup OBJECT-GROUP
|
|
OBJECTS { upsTestId, upsTestSpinLock,
|
|
upsTestResultsSummary, upsTestResultsDetail,
|
|
upsTestStartTime, upsTestElapsedTime }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullTestGroup defines the objects that are
|
|
common to the Test groups of fully compliant UPSs."
|
|
::= { upsFullGroups 7 }
|
|
|
|
upsFullControlGroup OBJECT-GROUP
|
|
OBJECTS { upsShutdownType, upsShutdownAfterDelay,
|
|
upsStartupAfterDelay, upsRebootWithDuration,
|
|
upsAutoRestart }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullControlGroup defines the objects that are
|
|
common to the Control groups of fully compliant UPSs."
|
|
::= { upsFullGroups 8 }
|
|
|
|
upsFullConfigGroup OBJECT-GROUP
|
|
OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
|
|
upsConfigOutputVoltage, upsConfigOutputFreq,
|
|
upsConfigOutputVA, upsConfigOutputPower,
|
|
upsConfigLowBattTime, upsConfigAudibleStatus }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upsFullConfigGroup defines the objects that are
|
|
common to the Config groups of fully compliant UPSs."
|
|
::= { upsFullGroups 9 }
|
|
|
|
END
|