- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
2143 lines
67 KiB
Text
2143 lines
67 KiB
Text
WebGraph-Thermometer-MIB DEFINITIONS ::= BEGIN
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.26
|
|
----------------------------------------------------------------
|
|
-- 28.06.2006 New: Community String Trap
|
|
--
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.25
|
|
----------------------------------------------------------------
|
|
-- 22.05.2006 Table Entry Namen korrigiert
|
|
--
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.24
|
|
----------------------------------------------------------------
|
|
-- 26.07.2005 #57605, WebGraph Thermometer
|
|
-- CRON Zeitfunktion
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.23
|
|
----------------------------------------------------------------
|
|
-- 14.07.2005 #57605, WebGraph Thermometer
|
|
-- FTP Funktionen
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.22
|
|
----------------------------------------------------------------
|
|
-- 02.06.2005 #57605, WebGraph Thermometer
|
|
-- Trap NMS annotations
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.21
|
|
----------------------------------------------------------------
|
|
-- 19.04.2005 #57605, WebGraph Themometer
|
|
-- Mail Authentication
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.20
|
|
----------------------------------------------------------------
|
|
-- 05.11.2004 #57605, WebGraph Themometer
|
|
-- Neu: Syslog
|
|
--
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.19
|
|
----------------------------------------------------------------
|
|
-- 27.09.2004 #57601/3/4, Webio Digital
|
|
-- Neu:
|
|
-- Eintrag AlarmHysteresis korigiert
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.18
|
|
----------------------------------------------------------------
|
|
-- 21.07.2004 #57601/3/4, Webio Digital
|
|
-- Neu:
|
|
-- Diagnosis
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.17
|
|
----------------------------------------------------------------
|
|
-- 28.06.2004 #57630/1/2, Webio Digital
|
|
-- Neu: Puls Mode
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.16
|
|
----------------------------------------------------------------
|
|
-- 16.04.2004 neu: #57632, Webio Digital EA24x24
|
|
--
|
|
-- #57630/1, Webio Digital EA12x12
|
|
-- Neu:
|
|
-- wtWebioAn1GraphInputCounterClear
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.15
|
|
----------------------------------------------------------------
|
|
-- 27.02.2004 #57630/1, Webio Digital EA12x12
|
|
-- Neu:
|
|
-- Länge erweitert auf 32 Bit:
|
|
-- wtWebioEA12x12InputValue
|
|
-- wtWebioEA12x12OutputValue
|
|
-- wtWebioEA12x12LoadControlView
|
|
-- wtWebioEA12x12LCShutDownView
|
|
-- wtWebioEA12x12SetOutput
|
|
-- wtWebioEA12x12AlarmInputTrigger
|
|
-- wtWebioEA12x12AlarmOutputTrigger
|
|
-- wtWebioEA12x12PortOutputSafetyState
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.14
|
|
----------------------------------------------------------------
|
|
-- 16.02.2004 #57630/1, Webio Digital EA12x12
|
|
-- Neu:
|
|
-- Texte: Location, Contact
|
|
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
|
|
-- Alarm: ColdStart / WarmStart trigger
|
|
--
|
|
-- #57601, 1xWebThermometer
|
|
-- #57603, 2xWebThermometer
|
|
-- #57604, 8xWebThermometer
|
|
-- Neu:
|
|
-- Alarm Hysterese
|
|
-- Alarm Clear Traps und Mails
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.13
|
|
----------------------------------------------------------------
|
|
-- 05.02.2004 #57601, 1xWebThermometer
|
|
-- #57603, 2xWebThermometer
|
|
-- #57604, 8xWebThermometer
|
|
-- Neu:
|
|
-- Texte: Location, Contact
|
|
-- SNMP: ColdStart, WarmStart, ComunityString Read/RW
|
|
-- Alarm: ColdStart / WarmStart trigger
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.12
|
|
----------------------------------------------------------------
|
|
-- 05.11.2003 #57601, 1xWebThermometer
|
|
-- #57603, 2xWebThermometer
|
|
-- #57604, 8xWebThermometer
|
|
-- Neu:
|
|
-- Mail Option: CSV attachment
|
|
-- Offsetkalibrierung
|
|
-- Alarm: Tcp Client mode
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.11
|
|
----------------------------------------------------------------
|
|
-- 28.10.2003 #57630/1, Webio Digital EA12x12
|
|
-- Neue Feature:
|
|
-- Alarm : TCP Client mode
|
|
-- INPUTS: Pulsfilter
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.10
|
|
----------------------------------------------------------------
|
|
-- 04.07.2003 #57630, Webio Digital EA12x12
|
|
-- Neuer Menübaum, neue Binärmodi
|
|
--
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.09
|
|
----------------------------------------------------------------
|
|
-- 24.03.2003 Trap Enterprise (Type 1, 2) korrigiert
|
|
--
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.08
|
|
----------------------------------------------------------------
|
|
-- 04.03.2003 Abgleich der Sprachversionen DE/US
|
|
--
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.07
|
|
----------------------------------------------------------------
|
|
-- 25.02.2003 Korrektur US: wtWebioEA12x12LoadControl
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.06
|
|
----------------------------------------------------------------
|
|
-- 24.02.2003 Neu:
|
|
-- #57630, Webio EA12x12, LoadControl Group
|
|
-- Korrektur: Trap variable Namen
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.05
|
|
----------------------------------------------------------------
|
|
-- 21.01.2003 Neu:
|
|
-- #57630, Webio EA12x12
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.04
|
|
----------------------------------------------------------------
|
|
-- 02.01.2003 Neu:
|
|
-- #57601, 1xWebThermometer
|
|
-- #57603, 2xWebThermometer, 8 Alarme
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.03
|
|
----------------------------------------------------------------
|
|
-- 21.11.2002 Neu:
|
|
-- #57604, 2xWebThermometer, BOOTP, StartupSite
|
|
-- #57603, 8xWebThermometer, BOOTP, StartupSite
|
|
----------------------------------------------------------------
|
|
-- Revison: 1.02
|
|
----------------------------------------------------------------
|
|
-- 26.07.2002 Neu:
|
|
-- #57604, 2xWebThermometer
|
|
-- #57603, 8xWebThermometer
|
|
--
|
|
|
|
IMPORTS
|
|
|
|
OBJECT-TYPE FROM RFC-1212
|
|
TRAP-TYPE FROM RFC-1215
|
|
DisplayString, PhysAddress FROM RFC1213-MIB
|
|
enterprises, TimeTicks, IpAddress, NetworkAddress FROM RFC1155-SMI;
|
|
|
|
|
|
-- IpAddress ::=
|
|
-- [APPLICATION 0]
|
|
-- IMPLICIT OCTET STRING (SIZE (4))
|
|
-- Counter ::=
|
|
-- [APPLICATION 1]
|
|
-- IMPLICIT INTEGER (0..4294967295)
|
|
-- Gauge ::=
|
|
-- [APPLICATION 2]
|
|
-- IMPLICIT INTEGER (0..4294967295)
|
|
-- TimeTicks ::=
|
|
-- [APPLICATION 3]
|
|
-- IMPLICIT INTEGER (0..4294967295)
|
|
|
|
|
|
-- DisplayString ::= OCTET STRING
|
|
-- PhysAddress ::= OCTET STRING
|
|
|
|
-- internet OBJECT IDENTIFIER ::= { iso org(3) dod(6) 1 }
|
|
-- privat OBJECT IDENTIFIER ::= { internet 4 }
|
|
-- enterprises OBJECT IDENTIFIER ::= { privat 1 }
|
|
|
|
|
|
|
|
-- Wiesemann & Theis Com-Server MIB
|
|
|
|
wut OBJECT IDENTIFIER ::= { enterprises 5040 }
|
|
wtComServer OBJECT IDENTIFIER ::= { wut 1 }
|
|
wtWebio OBJECT IDENTIFIER ::= { wtComServer 2 }
|
|
|
|
|
|
-- wtWebio Tree
|
|
|
|
wtWebioAn1Graph OBJECT IDENTIFIER ::= { wtWebio 8 }
|
|
|
|
-- wtWebioAn1Graph Tree
|
|
|
|
wtWebioAn1GraphTemp OBJECT IDENTIFIER ::= { wtWebioAn1Graph 1 }
|
|
wtWebioAn1GraphSessCntrl OBJECT IDENTIFIER ::= { wtWebioAn1Graph 2 }
|
|
wtWebioAn1GraphConfig OBJECT IDENTIFIER ::= { wtWebioAn1Graph 3 }
|
|
wtWebioAn1GraphDiag OBJECT IDENTIFIER ::= { wtWebioAn1Graph 4 }
|
|
|
|
-- wtWebioAn1GraphConfig Tree
|
|
|
|
wtWebioAn1GraphDevice OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 1 }
|
|
wtWebioAn1GraphPorts OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 2 }
|
|
wtWebioAn1GraphManufact OBJECT IDENTIFIER ::= { wtWebioAn1GraphConfig 3 }
|
|
|
|
-- wtWebioAn1GraphDevice Tree
|
|
|
|
wtWebioAn1GraphText OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 1 }
|
|
wtWebioAn1GraphTimeDate OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 2 }
|
|
wtWebioAn1GraphBasic OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 3 }
|
|
wtWebioAn1GraphDatalogger OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 4 }
|
|
wtWebioAn1GraphAlarm OBJECT IDENTIFIER ::= { wtWebioAn1GraphDevice 5 }
|
|
|
|
-- wtWebioAn1GraphTimeDate Tree
|
|
|
|
wtWebioAn1GraphTimeZone OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 1 }
|
|
wtWebioAn1GraphTimeServer OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 2 }
|
|
wtWebioAn1GraphDeviceClock OBJECT IDENTIFIER ::= { wtWebioAn1GraphTimeDate 3 }
|
|
|
|
-- wtWebioAn1GraphBasic Tree
|
|
|
|
wtWebioAn1GraphNetwork OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 1 }
|
|
wtWebioAn1GraphHTTP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 2 }
|
|
wtWebioAn1GraphMail OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 3 }
|
|
wtWebioAn1GraphSNMP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 4 }
|
|
wtWebioAn1GraphUDP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 5 }
|
|
wtWebioAn1GraphSyslog OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 6 }
|
|
wtWebioAn1GraphFTP OBJECT IDENTIFIER ::= { wtWebioAn1GraphBasic 7 }
|
|
|
|
|
|
|
|
-- wtWebioAn1GraphTemp Group
|
|
------------------------
|
|
|
|
wtWebioAn1GraphSensors OBJECT-TYPE
|
|
SYNTAX INTEGER (1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Anzahl der Temperatursensoren"
|
|
::= { wtWebioAn1GraphTemp 1 }
|
|
|
|
-- Interface Table
|
|
|
|
wtWebioAn1GraphSensorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF WtWebioAn1GraphSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Liste der Sensoren."
|
|
::= { wtWebioAn1GraphTemp 2 }
|
|
|
|
wtWebioAn1GraphSensorEntry OBJECT-TYPE
|
|
SYNTAX WtWebioAn1GraphSensorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Nummern der Temperatursensoren."
|
|
INDEX { wtWebioAn1GraphSensorNo }
|
|
::= { wtWebioAn1GraphSensorTable 1 }
|
|
|
|
WtWebioAn1GraphSensorEntry ::= SEQUENCE {
|
|
wtWebioAn1GraphSensorNo INTEGER
|
|
}
|
|
|
|
wtWebioAn1GraphSensorNo OBJECT-TYPE
|
|
SYNTAX INTEGER (1)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Nummer des Temperatursensors."
|
|
::= { wtWebioAn1GraphSensorEntry 1 }
|
|
|
|
|
|
-- wtWebioAn1GraphTempValue Table
|
|
|
|
wtWebioAn1GraphTempValueTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF WtWebioAn1GraphTempValueEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Liste Temperaturwerte korrespondiernd zu den Kanalnummern."
|
|
::= { wtWebioAn1GraphTemp 3 }
|
|
|
|
wtWebioAn1GraphTempValueEntry OBJECT-TYPE
|
|
SYNTAX WtWebioAn1GraphTempValueEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperaturen der Sensoren."
|
|
INDEX { wtWebioAn1GraphSensorNo }
|
|
::= { wtWebioAn1GraphTempValueTable 1 }
|
|
|
|
WtWebioAn1GraphTempValueEntry ::= SEQUENCE{
|
|
wtWebioAn1GraphTempValue OCTET STRING
|
|
}
|
|
|
|
wtWebioAn1GraphTempValue OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (5))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Temperaturwert des Sensors, ASCII, 5 Zeichen lang."
|
|
::= { wtWebioAn1GraphTempValueEntry 1 }
|
|
|
|
-- wtWebioAn1GraphBinaryTempValue Table
|
|
|
|
wtWebioAn1GraphBinaryTempValueTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF WtWebioAn1GraphBinaryTempValueEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Liste binärer Temperaturwerte korrespondiernd zu den Kanalnummern."
|
|
::= { wtWebioAn1GraphTemp 4 }
|
|
|
|
wtWebioAn1GraphBinaryTempValueEntry OBJECT-TYPE
|
|
SYNTAX WtWebioAn1GraphBinaryTempValueEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binäre Temperaturen der Sensoren."
|
|
INDEX { wtWebioAn1GraphSensorNo }
|
|
::= { wtWebioAn1GraphBinaryTempValueTable 1 }
|
|
|
|
WtWebioAn1GraphBinaryTempValueEntry ::= SEQUENCE{
|
|
wtWebioAn1GraphBinaryTempValue INTEGER
|
|
}
|
|
|
|
wtWebioAn1GraphBinaryTempValue OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binärer Temperaturwert des Sensors in 1/10 Grad Celcius,
|
|
vorzeichenbehaftete Zahl, der Wert 0x7FFF zeigt einen
|
|
ungültigen Messwert an."
|
|
::= { wtWebioAn1GraphBinaryTempValueEntry 1 }
|
|
|
|
-- wtWebioAn1GraphSessCntrl Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphSessCntrlPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Durch Eintrag diese Passworts wird eine Session eröffnet, die durch Schreiben einer 1
|
|
in wtWebioAn1GraphSessCntrlLogout beendet wird. Gelesen liefert diese Variable einen String der
|
|
Länge Null."
|
|
::= { wtWebioAn1GraphSessCntrl 1 }
|
|
|
|
wtWebioAn1GraphSessCntrlConfigMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphSessCntrl-NoSession(0),
|
|
wtWebioAn1GraphSessCntrl-Session(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Wenn sich das Gerät im SNMP-Konfigurationsmodus befindet, wird der Wert
|
|
1 zurückgeliefert, ansonsten 0. Ist der ausgelesene Wert 0
|
|
obwohl das Passwort geschrieben wurde, befindet sich das Gerät bereits
|
|
im Configmodus und die Variablen können nur gelesen werden."
|
|
::= { wtWebioAn1GraphSessCntrl 2 }
|
|
|
|
wtWebioAn1GraphSessCntrlLogout OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Wenn sich das Gerät im Konfigurationsmodus befindet und die Session wurde
|
|
von diesem SNMP Manager eröffnet, kann durch Schreiben einer 1 in diese
|
|
Variable die Session beendet werden und alle Parameter werden gespeichert.
|
|
Durch Schreiben einer 2 werden alle Eingaben wieder verworfen.
|
|
Gelesen liefert diese Variable den Wert 0."
|
|
::= { wtWebioAn1GraphSessCntrl 3 }
|
|
|
|
wtWebioAn1GraphSessCntrlAdminPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieses Passwort schützt den Zugang der Variablen mit Administratorrechten. Es kann nur vom
|
|
Administrator verändert werden. Wurde kein Passwort vergeben so ist public das gültige Passwort.
|
|
Gelesen liefert diese Variable einen Null-Pointer."
|
|
::= { wtWebioAn1GraphSessCntrl 4 }
|
|
|
|
wtWebioAn1GraphSessCntrlConfigPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieses Passwort schützt den Zugang der Variablen mit Configuratorrechten. Es kann vom
|
|
Administrator und vom Configurator verändert werden. Wurde kein Passwort vergeben so ist
|
|
public das gültige Passwort.Gelesen liefert diese Variable einen Null-Pointer."
|
|
::= { wtWebioAn1GraphSessCntrl 5 }
|
|
|
|
|
|
-- wtWebioAn1GraphText Group
|
|
------------------------
|
|
|
|
wtWebioAn1GraphDeviceName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name des Webio's, der userdefinierbar ist."
|
|
::= { wtWebioAn1GraphText 1 }
|
|
|
|
wtWebioAn1GraphDeviceText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Beschreibung des Webio's, die userdefinierbar ist."
|
|
::= { wtWebioAn1GraphText 2 }
|
|
|
|
wtWebioAn1GraphDeviceLocation OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Aufstellort des Webio's, die userdefinierbar ist."
|
|
::= { wtWebioAn1GraphText 3 }
|
|
|
|
wtWebioAn1GraphDeviceContact OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Kontactadresse im Servicefall des Webio's, die userdefinierbar ist."
|
|
::= { wtWebioAn1GraphText 4 }
|
|
|
|
-- wtWebioAn1GraphTimeZone Group
|
|
----------------------------
|
|
|
|
wtWebioAn1GraphTzOffsetHrs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset Stunden der Zeitzone (Winterzeit) in Bezug auf UTC."
|
|
::= { wtWebioAn1GraphTimeZone 1 }
|
|
|
|
wtWebioAn1GraphTzOffsetMin OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset Minuten der Zeitzone (Winterzeit) in Bezug auf UTC."
|
|
::= { wtWebioAn1GraphTimeZone 2 }
|
|
|
|
wtWebioAn1GraphTzEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Bedingung:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : Apply Timezone"
|
|
::= { wtWebioAn1GraphTimeZone 3 }
|
|
|
|
wtWebioAn1GraphStTzOffsetHrs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset Stunden der Zeitzone (Sommerzeit) in Bezug auf UTC."
|
|
::= { wtWebioAn1GraphTimeZone 4 }
|
|
|
|
wtWebioAn1GraphStTzOffsetMin OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset Minuten der Zeitzone (Sommerzeit) in Bezug auf UTC."
|
|
::= { wtWebioAn1GraphTimeZone 5 }
|
|
|
|
wtWebioAn1GraphStTzEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Bedingung:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : Apply Summertime"
|
|
::= { wtWebioAn1GraphTimeZone 6 }
|
|
|
|
wtWebioAn1GraphStTzStartMonth OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphStartMonth-January(1),
|
|
wtWebioAn1GraphStartMonth-February(2),
|
|
wtWebioAn1GraphStartMonth-March(3),
|
|
wtWebioAn1GraphStartMonth-April(4),
|
|
wtWebioAn1GraphStartMonth-May(5),
|
|
wtWebioAn1GraphStartMonth-June(6),
|
|
wtWebioAn1GraphStartMonth-July(7),
|
|
wtWebioAn1GraphStartMonth-August(8),
|
|
wtWebioAn1GraphStartMonth-September(9),
|
|
wtWebioAn1GraphStartMonth-October(10),
|
|
wtWebioAn1GraphStartMonth-November(11),
|
|
wtWebioAn1GraphStartMonth-December(12)
|
|
}
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Monat, in dem von Winterzeit auf Sommerzeit umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 7 }
|
|
|
|
wtWebioAn1GraphStTzStartMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphStartMode-first(1),
|
|
wtWebioAn1GraphStartMode-second(2),
|
|
wtWebioAn1GraphStartMode-third(3),
|
|
wtWebioAn1GraphStartMode-fourth(4),
|
|
wtWebioAn1GraphStartMode-last(5)
|
|
}
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Modus des Wochentages, bei dem von Winterzeit auf Sommerzeit umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 8 }
|
|
|
|
wtWebioAn1GraphStTzStartWday OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphStartWday-Sunday(1),
|
|
wtWebioAn1GraphStartWday-Monday(2),
|
|
wtWebioAn1GraphStartWday-Tuesday(3),
|
|
wtWebioAn1GraphStartWday-Thursday(4),
|
|
wtWebioAn1GraphStartWday-Wednesday(5),
|
|
wtWebioAn1GraphStartWday-Friday(6),
|
|
wtWebioAn1GraphStartWday-Saturday(7)
|
|
}
|
|
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Wochentag, bei dem von Winterzeit auf Sommerzeit umgestellt wird"
|
|
::= { wtWebioAn1GraphTimeZone 9 }
|
|
|
|
wtWebioAn1GraphStTzStartHrs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Stunde, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
|
|
umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 10 }
|
|
|
|
wtWebioAn1GraphStTzStartMin OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Minute, in der die Zeitzone von Winter auf Sommerzeit in Bezug auf UTC
|
|
umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 11 }
|
|
|
|
wtWebioAn1GraphStTzStopMonth OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphStopMonth-January(1),
|
|
wtWebioAn1GraphStopMonth-February(2),
|
|
wtWebioAn1GraphStopMonth-March(3),
|
|
wtWebioAn1GraphStopMonth-April(4),
|
|
wtWebioAn1GraphStopMonth-May(5),
|
|
wtWebioAn1GraphStopMonth-June(6),
|
|
wtWebioAn1GraphStopMonth-July(7),
|
|
wtWebioAn1GraphStopMonth-August(8),
|
|
wtWebioAn1GraphStopMonth-September(9),
|
|
wtWebioAn1GraphStopMonth-October(10),
|
|
wtWebioAn1GraphStopMonth-November(11),
|
|
wtWebioAn1GraphStopMonth-December(12)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Monat, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 12 }
|
|
|
|
wtWebioAn1GraphStTzStopMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphStopMode-first(1),
|
|
wtWebioAn1GraphStopMode-second(2),
|
|
wtWebioAn1GraphStopMode-third(3),
|
|
wtWebioAn1GraphStopMode-fourth(4),
|
|
wtWebioAn1GraphStopMode-last(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Modus des Wochentages, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 13 }
|
|
|
|
wtWebioAn1GraphStTzStopWday OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphStopWday-Sunday(1),
|
|
wtWebioAn1GraphStopWday-Monday(2),
|
|
wtWebioAn1GraphStopWday-Tuesday(3),
|
|
wtWebioAn1GraphStopWday-Thursday(4),
|
|
wtWebioAn1GraphStopWday-Wednesday(5),
|
|
wtWebioAn1GraphStopWday-Friday(6),
|
|
wtWebioAn1GraphStopWday-Saturday(7)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Wochentage, bei dem von Sommerzeit auf Winterzeit umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 14 }
|
|
|
|
wtWebioAn1GraphStTzStopHrs OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Stunde, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
|
|
umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 15 }
|
|
|
|
wtWebioAn1GraphStTzStopMin OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Minute, in der die Zeitzone von Sommer auf Winterzeit in Bezug auf UTC
|
|
umgestellt wird."
|
|
::= { wtWebioAn1GraphTimeZone 16 }
|
|
|
|
-- wtWebioAn1GraphTimeServer Group
|
|
----------------------------
|
|
|
|
wtWebioAn1GraphTimeServer1 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-Adresse oder Name des 1. Time Servers in ASCII"
|
|
::= { wtWebioAn1GraphTimeServer 1 }
|
|
|
|
wtWebioAn1GraphTimeServer2 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-Adresse oder Name des 2. Time Servers in ASCII"
|
|
::= { wtWebioAn1GraphTimeServer 2 }
|
|
|
|
wtWebioAn1GraphTsEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Bedingung:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : Apply Time Server"
|
|
::= { wtWebioAn1GraphTimeServer 3 }
|
|
|
|
wtWebioAn1GraphTsSyncTime OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Die Abfrage der Timeserver erfolgt zu dieser vollen Stunde (0-23)."
|
|
::= { wtWebioAn1GraphTimeServer 4 }
|
|
|
|
-- wtWebioAn1GraphDeviceClock Group
|
|
----------------------------
|
|
|
|
wtWebioAn1GraphClockHrs OBJECT-TYPE
|
|
SYNTAX INTEGER (0..23)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Uhrzeit Stunde, unter Berücksichtigung der Zeitzoneneinstellungen."
|
|
::= { wtWebioAn1GraphDeviceClock 1 }
|
|
|
|
wtWebioAn1GraphClockMin OBJECT-TYPE
|
|
SYNTAX INTEGER (0..59)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Uhrzeit Minute, unter Berücksichtigung der Zeitzoneneinstellungen."
|
|
::= { wtWebioAn1GraphDeviceClock 2 }
|
|
|
|
wtWebioAn1GraphClockDay OBJECT-TYPE
|
|
SYNTAX INTEGER (1..31)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Datum: Tag des Monats, unter Berücksichtigung der Zeitzoneneinstellungen."
|
|
::= { wtWebioAn1GraphDeviceClock 3 }
|
|
|
|
wtWebioAn1GraphClockMonth OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphClockMonth-January(1),
|
|
wtWebioAn1GraphClockMonth-February(2),
|
|
wtWebioAn1GraphClockMonth-March(3),
|
|
wtWebioAn1GraphClockMonth-April(4),
|
|
wtWebioAn1GraphClockMonth-May(5),
|
|
wtWebioAn1GraphClockMonth-June(6),
|
|
wtWebioAn1GraphClockMonth-July(7),
|
|
wtWebioAn1GraphClockMonth-August(8),
|
|
wtWebioAn1GraphClockMonth-September(9),
|
|
wtWebioAn1GraphClockMonth-October(10),
|
|
wtWebioAn1GraphClockMonth-November(11),
|
|
wtWebioAn1GraphClockMonth-December(12)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Datum: Monat, unter Berücksichtigung der Zeitzoneneinstellungen."
|
|
::= { wtWebioAn1GraphDeviceClock 4 }
|
|
|
|
wtWebioAn1GraphClockYear OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Datum: Jahr, unter Berücksichtigung der Zeitzoneneinstellungen."
|
|
::= { wtWebioAn1GraphDeviceClock 5 }
|
|
|
|
|
|
-- wtWebioAn1GraphNetwork Group
|
|
------------------------
|
|
|
|
wtWebioAn1GraphIpAddress OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-Adresse des Webio's"
|
|
::= { wtWebioAn1GraphNetwork 1 }
|
|
|
|
wtWebioAn1GraphSubnetMask OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Subnetmask des Webio's"
|
|
::= { wtWebioAn1GraphNetwork 2 }
|
|
|
|
wtWebioAn1GraphGateway OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Gateway des Webio's"
|
|
::= { wtWebioAn1GraphNetwork 3 }
|
|
|
|
wtWebioAn1GraphDnsServer1 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-Adresse des 1. DNS Servers in ASCII"
|
|
::= { wtWebioAn1GraphNetwork 4 }
|
|
|
|
wtWebioAn1GraphDnsServer2 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-Adresse des 2. DNS Servers in ASCII"
|
|
::= { wtWebioAn1GraphNetwork 5 }
|
|
|
|
wtWebioAn1GraphAddConfig OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Zusatzkonfiguration (1=EIN):
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0: BOOTP disable
|
|
"
|
|
::= { wtWebioAn1GraphNetwork 6 }
|
|
|
|
-- wtWebioAn1GraphHTTP Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphStartup OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Legt die Startseite fest, nur eine Auswahl zulässig:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 2: user.htm
|
|
Bit 1: home.htm
|
|
Bit 0: index.htm"
|
|
::= { wtWebioAn1GraphHTTP 1 }
|
|
|
|
wtWebioAn1GraphGetHeaderEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Wenn freigeschaltet, wird eine Erkennungssequenz nach
|
|
jeder GET-Anfrage der Antwort vorangestellt:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : GET Header enable"
|
|
::= { wtWebioAn1GraphHTTP 2 }
|
|
|
|
wtWebioAn1GraphHttpPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"HTTP Port, an den die TCP-Anfragen gesendet werden können (Default: 80)."
|
|
::= { wtWebioAn1GraphHTTP 3 }
|
|
|
|
-- wtWebioAn1GraphMail Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphMailAdName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Gerätename für die Mail-Administration."
|
|
::= { wtWebioAn1GraphMail 1 }
|
|
|
|
wtWebioAn1GraphMailReply OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Reply-Adresse für den Mailserver."
|
|
::= { wtWebioAn1GraphMail 2 }
|
|
|
|
wtWebioAn1GraphMailServer OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name oder Ip-Adresse des Mailservers."
|
|
::= { wtWebioAn1GraphMail 3 }
|
|
|
|
wtWebioAn1GraphMailEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Erlaubt das versenden von Mails:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : Mail enable"
|
|
::= { wtWebioAn1GraphMail 4 }
|
|
|
|
wtWebioAn1GraphMailAuthentication OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE (4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Auswahl des Authenticationmodi:
|
|
die OCTETS werden bitweise interpretiert, es darf nur ein Bit gesetzt sein.
|
|
Bit 0 entspricht dem LSB.
|
|
OCTET 1: ungenutzt
|
|
OCTET 2: ungenutzt
|
|
OCTET 3: ungenutzt
|
|
OCTET 4: Bit 3-7: ungenutzt
|
|
Bit 2 : POP3 vor SMTP
|
|
Bit 1 : ESMTP, Authentifizierung
|
|
Bit 0 : SMTP, keine Authentifizierung"
|
|
::= { wtWebioAn1GraphMail 5 }
|
|
|
|
wtWebioAn1GraphMailAuthUser OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name des Postfaches / Postfachusers."
|
|
::= { wtWebioAn1GraphMail 6 }
|
|
|
|
wtWebioAn1GraphMailAuthPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Passwort zur Identifizierung des Users."
|
|
::= { wtWebioAn1GraphMail 7 }
|
|
|
|
wtWebioAn1GraphMailPop3Server OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name oder Ip-Adresse des POP3 Servers."
|
|
::= { wtWebioAn1GraphMail 8 }
|
|
|
|
-- wtWebioAn1GraphSNMP Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphSnmpCommunityStringRead OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Community string read only"
|
|
::= { wtWebioAn1GraphSNMP 1 }
|
|
|
|
wtWebioAn1GraphSnmpCommunityStringReadWrite OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Community string read / write"
|
|
::= { wtWebioAn1GraphSNMP 2 }
|
|
|
|
wtWebioAn1GraphSystemTrapManagerIP OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name oder IP-Adresse des SNMP-Managers, der den System Trap entgegen nimmt."
|
|
::= { wtWebioAn1GraphSNMP 3 }
|
|
|
|
wtWebioAn1GraphSystemTrapEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Triggerbedingungen:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0: ColdStart
|
|
Bit 1: WarmStart
|
|
Bit 2-7: ungenutzt"
|
|
::= { wtWebioAn1GraphSNMP 4 }
|
|
|
|
wtWebioAn1GraphSnmpEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bit 0 schaltet SNMP frei:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : SNMP enable"
|
|
::= { wtWebioAn1GraphSNMP 5 }
|
|
|
|
wtWebioAn1GraphSnmpCommunityStringTrap OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Community string der Traps."
|
|
::= { wtWebioAn1GraphSNMP 6 }
|
|
|
|
-- wtWebioAn1GraphUDP Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphUdpPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Udp Port, an den die Udp-Anfragen GET Single gesendet werden können"
|
|
::= { wtWebioAn1GraphUDP 1 }
|
|
|
|
wtWebioAn1GraphUdpEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Schaltet UDP frei:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : UDP enable"
|
|
::= { wtWebioAn1GraphUDP 2 }
|
|
|
|
-- wtWebioAn1GraphSyslog Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphSyslogServerIP OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name oder IP-Adresse des Syslog-Servers, der die Syslog-Nachricht entgegen nimmt."
|
|
::= { wtWebioAn1GraphSyslog 1 }
|
|
|
|
wtWebioAn1GraphSyslogServerPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Portnummer des Syslog-Servers, default ist 514."
|
|
::= { wtWebioAn1GraphSyslog 2 }
|
|
|
|
wtWebioAn1GraphSyslogSystemMessagesEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Triggerbedingungen:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0: ColdStart
|
|
Bit 1: WarmStart
|
|
Bit 2: Diag Messages
|
|
Bit 3-7: ungenutzt"
|
|
::= { wtWebioAn1GraphSyslog 3 }
|
|
|
|
wtWebioAn1GraphSyslogEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bit 0 schaltet Syslog frei:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : Syslog enable"
|
|
::= { wtWebioAn1GraphSyslog 4 }
|
|
|
|
-- wtWebioAn1GraphFTP Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphFTPServerIP OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name oder IP-Adresse des FTP-Servers, der die FTP-Nachricht entgegen nimmt."
|
|
::= { wtWebioAn1GraphFTP 1 }
|
|
|
|
wtWebioAn1GraphFTPServerControlPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Portnummer des Kontrollports des FTP-Servers, default ist 21."
|
|
::= { wtWebioAn1GraphFTP 2 }
|
|
|
|
wtWebioAn1GraphFTPUserName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"FTP Loggin: Name des Anwenders."
|
|
::= { wtWebioAn1GraphFTP 3 }
|
|
|
|
wtWebioAn1GraphFTPPassword OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"FTP Loggin: Passwort des Anwenders."
|
|
::= { wtWebioAn1GraphFTP 4 }
|
|
|
|
wtWebioAn1GraphFTPAccount OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"FTP Loggin: Account-Name des Anwenderkontos."
|
|
::= { wtWebioAn1GraphFTP 5 }
|
|
|
|
wtWebioAn1GraphFTPOption OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bit 0 schaltet den FTP Server in den Passiv-Modus,
|
|
der Client kontrolliert die Datenverbindung allein:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : PASV enable"
|
|
::= { wtWebioAn1GraphFTP 6 }
|
|
|
|
wtWebioAn1GraphFTPEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bit 0 schaltet FTP frei:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : FTP enable"
|
|
::= { wtWebioAn1GraphFTP 7 }
|
|
|
|
-- wtWebioAn1GraphDatalogger Group
|
|
--------------------------------
|
|
|
|
wtWebioAn1GraphLoggerTimebase OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphDatalogger-1Min(1),
|
|
wtWebioAn1GraphDatalogger-5Min(2),
|
|
wtWebioAn1GraphDatalogger-15Min(3),
|
|
wtWebioAn1GraphDatalogger-60Min(4)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Zeitbasis des Dataloggers"
|
|
::= { wtWebioAn1GraphDatalogger 1 }
|
|
|
|
wtWebioAn1GraphLoggerSensorSel OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Triggerbedingungen:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0: Sensor 1
|
|
Bit 1: Sensor 2
|
|
Bit 2: Sensor 3
|
|
Bit 3: Sensor 4
|
|
Bit 4: Sensor 5
|
|
Bit 5: Sensor 6
|
|
Bit 6: Sensor 7
|
|
Bit 7: Sensor 8"
|
|
::= { wtWebioAn1GraphDatalogger 2 }
|
|
|
|
wtWebioAn1GraphDisplaySensorSel OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Die hier ausgewählten Sensoren werden grafisch angezeigt:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0: Sensor 1
|
|
Bit 1: Sensor 2
|
|
Bit 2: Sensor 3
|
|
Bit 3: Sensor 4
|
|
Bit 4: Sensor 5
|
|
Bit 5: Sensor 6
|
|
Bit 6: Sensor 7
|
|
Bit 7: Sensor 8"
|
|
::= { wtWebioAn1GraphDatalogger 3 }
|
|
|
|
-- Graph Sensor Color Table
|
|
|
|
wtWebioAn1GraphSensorColorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF WtWebioAn1GraphSensorColorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Liste der Sensorfarben in der grafischen Darstellung."
|
|
::= { wtWebioAn1GraphDatalogger 4 }
|
|
|
|
wtWebioAn1GraphSensorColorEntry OBJECT-TYPE
|
|
SYNTAX WtWebioAn1GraphSensorColorEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Nummern der Sensoren."
|
|
INDEX { wtWebioAn1GraphSensorNo }
|
|
::= { wtWebioAn1GraphSensorColorTable 1 }
|
|
|
|
WtWebioAn1GraphSensorColorEntry ::= SEQUENCE {
|
|
wtWebioAn1GraphSensorColor OCTET STRING
|
|
}
|
|
|
|
wtWebioAn1GraphSensorColor OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(3))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Farbe des Sensors in der grafischen Darstellung."
|
|
::= { wtWebioAn1GraphSensorColorEntry 1 }
|
|
|
|
wtWebioAn1GraphAutoScaleEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bit 0 schaltet Vertical Auto Scale frei:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 1-7: ungenutzt
|
|
Bit 0 : Auto Scale enable"
|
|
::= { wtWebioAn1GraphDatalogger 5 }
|
|
|
|
wtWebioAn1GraphVerticalUpperLimit OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Definiert die maximal sichtbare Temperatur für die grafische Darstellung.
|
|
Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|
::= { wtWebioAn1GraphDatalogger 6 }
|
|
|
|
wtWebioAn1GraphVerticalLowerLimit OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Definiert die Minal sichtbare Temperatur für die grafische Darstellung.
|
|
Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|
::= { wtWebioAn1GraphDatalogger 7 }
|
|
|
|
wtWebioAn1GraphHorizontalZoom OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
wtWebioAn1GraphZoom-25Min(1),
|
|
wtWebioAn1GraphZoom-75Min(2),
|
|
wtWebioAn1GraphZoom-5Std(3),
|
|
wtWebioAn1GraphZoom-30Std(4),
|
|
wtWebioAn1GraphZoom-5Tage(5),
|
|
wtWebioAn1GraphZoom-25Tage(6)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Definiert den default Zoom."
|
|
::= { wtWebioAn1GraphDatalogger 8 }
|
|
|
|
-- wtWebioAn1GraphAlarm Group
|
|
----------------------------
|
|
|
|
wtWebioAn1GraphAlarmCount OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Anzahl der unabhängigen Alarme."
|
|
::= { wtWebioAn1GraphAlarm 1 }
|
|
|
|
-- Alarm Interface Table
|
|
|
|
wtWebioAn1GraphAlarmIfTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF WtWebioAn1GraphAlarmIfEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Liste der Alarmindizes."
|
|
::= { wtWebioAn1GraphAlarm 2 }
|
|
|
|
wtWebioAn1GraphAlarmIfEntry OBJECT-TYPE
|
|
SYNTAX WtWebioAn1GraphAlarmIfEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Nummern der Alarme."
|
|
INDEX { wtWebioAn1GraphAlarmNo }
|
|
::= { wtWebioAn1GraphAlarmIfTable 1 }
|
|
|
|
WtWebioAn1GraphAlarmIfEntry ::= SEQUENCE {
|
|
wtWebioAn1GraphAlarmNo INTEGER
|
|
}
|
|
|
|
wtWebioAn1GraphAlarmNo OBJECT-TYPE
|
|
SYNTAX INTEGER (1..8)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Nummer des Alarms."
|
|
::= { wtWebioAn1GraphAlarmIfEntry 1 }
|
|
|
|
-- Alarm Table
|
|
|
|
wtWebioAn1GraphAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF WtWebioAn1GraphAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Liste der Einstellungen abhängig von der Alarmnummer."
|
|
::= { wtWebioAn1GraphAlarm 3 }
|
|
|
|
wtWebioAn1GraphAlarmEntry OBJECT-TYPE
|
|
SYNTAX WtWebioAn1GraphAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Alarm-Parameter der einzelnen Alarme."
|
|
INDEX { wtWebioAn1GraphAlarmNo }
|
|
::= { wtWebioAn1GraphAlarmTable 1 }
|
|
|
|
WtWebioAn1GraphAlarmEntry ::= SEQUENCE {
|
|
wtWebioAn1GraphAlarmTrigger OCTET STRING,
|
|
wtWebioAn1GraphAlarmMin OCTET STRING,
|
|
wtWebioAn1GraphAlarmMax OCTET STRING,
|
|
wtWebioAn1GraphAlarmHysteresis OCTET STRING,
|
|
wtWebioAn1GraphAlarmDelay OCTET STRING,
|
|
wtWebioAn1GraphAlarmInterval OCTET STRING,
|
|
wtWebioAn1GraphAlarmEnable OCTET STRING,
|
|
wtWebioAn1GraphAlarmEMailAddr OCTET STRING,
|
|
wtWebioAn1GraphAlarmMailSubject OCTET STRING,
|
|
wtWebioAn1GraphAlarmMailText OCTET STRING,
|
|
wtWebioAn1GraphAlarmManagerIP OCTET STRING,
|
|
wtWebioAn1GraphAlarmTrapText OCTET STRING,
|
|
wtWebioAn1GraphAlarmMailOptions OCTET STRING,
|
|
wtWebioAn1GraphAlarmTcpIpAddr OCTET STRING,
|
|
wtWebioAn1GraphAlarmTcpPort INTEGER,
|
|
wtWebioAn1GraphAlarmTcpText OCTET STRING,
|
|
wtWebioAn1GraphAlarmClearMailSubject OCTET STRING,
|
|
wtWebioAn1GraphAlarmClearMailText OCTET STRING,
|
|
wtWebioAn1GraphAlarmClearTrapText OCTET STRING,
|
|
wtWebioAn1GraphAlarmClearTcpText OCTET STRING,
|
|
wtWebioAn1GraphAlarmSyslogIpAddr OCTET STRING,
|
|
wtWebioAn1GraphAlarmSyslogPort INTEGER,
|
|
wtWebioAn1GraphAlarmSyslogText OCTET STRING,
|
|
wtWebioAn1GraphAlarmSyslogClearText OCTET STRING,
|
|
wtWebioAn1GraphAlarmFtpDataPort OCTET STRING,
|
|
wtWebioAn1GraphAlarmFtpFileName OCTET STRING,
|
|
wtWebioAn1GraphAlarmFtpText OCTET STRING,
|
|
wtWebioAn1GraphAlarmFtpClearText OCTET STRING,
|
|
wtWebioAn1GraphAlarmFtpOption OCTET STRING,
|
|
wtWebioAn1GraphAlarmTimerCron OCTET STRING
|
|
|
|
|
|
}
|
|
|
|
wtWebioAn1GraphAlarmTrigger OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Triggerbedingungen:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3:
|
|
Bit 0: Timer
|
|
Bit 1: ColdStart
|
|
Bit 2: WarmStart
|
|
Bit 3: Sensor lost
|
|
Bit 4-7 ungenutzt
|
|
Octet 4:
|
|
Bit 0: Sensor 1
|
|
Bit 1: Sensor 2
|
|
Bit 2: Sensor 3
|
|
Bit 3: Sensor 4
|
|
Bit 4: Sensor 5
|
|
Bit 5: Sensor 6
|
|
Bit 6: Sensor 7
|
|
Bit 7: Sensor 8"
|
|
::= { wtWebioAn1GraphAlarmEntry 1 }
|
|
|
|
wtWebioAn1GraphAlarmMin OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Minimum Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|
::= { wtWebioAn1GraphAlarmEntry 2 }
|
|
|
|
wtWebioAn1GraphAlarmMax OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Maximum Temperatur in Grad mit maximal 2 Nachkommastellen."
|
|
::= { wtWebioAn1GraphAlarmEntry 3 }
|
|
|
|
wtWebioAn1GraphAlarmHysteresis OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bei Überschreiten der Temperatur Min+Hyst. und Unterschreiten der Temperatur Max-Hyst.
|
|
wird der Alarm gelöscht: pos. Temperaturdifferenz in Grad mit maximal 2 Nachkommastellen."
|
|
::= { wtWebioAn1GraphAlarmEntry 4 }
|
|
|
|
wtWebioAn1GraphAlarmDelay OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Der Alarm wird erst ausgelöst, wenn für die Dauer dieser Zeit
|
|
die Alarmbedingungen erfüllt sind (Zeit in Minuten)."
|
|
::= { wtWebioAn1GraphAlarmEntry 5 }
|
|
|
|
wtWebioAn1GraphAlarmInterval OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Sendeintervall von Alarmmeldungen."
|
|
::= { wtWebioAn1GraphAlarmEntry 6 }
|
|
|
|
wtWebioAn1GraphAlarmEnable OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Alarmfreischaltung:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0: Mail Enable
|
|
Bit 1: SNMP Trap enable
|
|
Bit 2: TCP Client enable"
|
|
::= { wtWebioAn1GraphAlarmEntry 7 }
|
|
|
|
wtWebioAn1GraphAlarmEMailAddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"E-Mail Adresse, an die die Alarmmail gesendet werden soll."
|
|
::= { wtWebioAn1GraphAlarmEntry 8 }
|
|
|
|
wtWebioAn1GraphAlarmMailSubject OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Betreffzeile der Alarmmail."
|
|
::= { wtWebioAn1GraphAlarmEntry 9 }
|
|
|
|
wtWebioAn1GraphAlarmMailText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Text der Alarmmail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
|
|
<Z> liefert die aktuelle Zeit."
|
|
::= { wtWebioAn1GraphAlarmEntry 10 }
|
|
|
|
wtWebioAn1GraphAlarmManagerIP OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name oder IP-Adresse des SNMP-Managers, der den Trap entgegen nimmt."
|
|
::= { wtWebioAn1GraphAlarmEntry 11 }
|
|
|
|
wtWebioAn1GraphAlarmTrapText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieser Text wird im Trapbody gesendet."
|
|
::= { wtWebioAn1GraphAlarmEntry 12 }
|
|
|
|
wtWebioAn1GraphAlarmMailOptions OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Optionen:
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0 : Attach Thermo.csv Enable
|
|
Bit 1 : CSV-Data_since_last_report
|
|
Bit 2-7: ungenutzt"
|
|
::= { wtWebioAn1GraphAlarmEntry 13 }
|
|
|
|
wtWebioAn1GraphAlarmTcpIpAddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-Adresse des Gerätes, dass eine TCP-Nachricht empfangen soll."
|
|
::= { wtWebioAn1GraphAlarmEntry 14 }
|
|
|
|
wtWebioAn1GraphAlarmTcpPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Portnummer des Gerätes, dass eine TCP-Nachricht empfangen soll."
|
|
::= { wtWebioAn1GraphAlarmEntry 15 }
|
|
|
|
wtWebioAn1GraphAlarmTcpText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieser Text wird im TCP Trapbody gesendet."
|
|
::= { wtWebioAn1GraphAlarmEntry 16 }
|
|
|
|
wtWebioAn1GraphAlarmClearMailSubject OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Betreffzeile der Alarm Clear Mail."
|
|
::= { wtWebioAn1GraphAlarmEntry 17 }
|
|
|
|
wtWebioAn1GraphAlarmClearMailText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Text der Alarm Clear Mail: <Tn> liefert die aktuelle Temperatur; n = 1..8.
|
|
<Z> liefert die aktuelle Zeit."
|
|
::= { wtWebioAn1GraphAlarmEntry 18 }
|
|
|
|
wtWebioAn1GraphAlarmClearTrapText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieser Text wird im Trapbody gesendet."
|
|
::= { wtWebioAn1GraphAlarmEntry 19 }
|
|
|
|
wtWebioAn1GraphAlarmClearTcpText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieser Text wird im TCP Trapbody gesendet."
|
|
::= { wtWebioAn1GraphAlarmEntry 20 }
|
|
|
|
wtWebioAn1GraphAlarmSyslogIpAddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"IP-Adresse des Gerätes, dass eine Syslog-Nachricht empfangen soll."
|
|
::= { wtWebioAn1GraphAlarmEntry 21 }
|
|
|
|
wtWebioAn1GraphAlarmSyslogPort OBJECT-TYPE
|
|
SYNTAX INTEGER (1..65535)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Portnummer des Gerätes, dass eine Syslog-Nachricht empfangen soll, default Port ist 514."
|
|
::= { wtWebioAn1GraphAlarmEntry 22 }
|
|
|
|
wtWebioAn1GraphAlarmSyslogText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Jede Syslog-Nachricht beginnt mit einem Prioritätsschlüssel, einem Zeitstempel und der Host Ip-Nummer gemäß RFC3164.
|
|
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
|
|
::= { wtWebioAn1GraphAlarmEntry 23 }
|
|
|
|
wtWebioAn1GraphAlarmSyslogClearText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Jede Syslog-Nachricht beginnt mit einem Prioritätsschlüssel, einem Zeitstempel und der Host Ip-Nummer gemäß RFC3164.
|
|
Dieser Text wird im darauf folgenden Syslog-Nachrichtenteil gesendet."
|
|
::= { wtWebioAn1GraphAlarmEntry 24 }
|
|
|
|
wtWebioAn1GraphAlarmFtpDataPort OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Lokaler Datenport: 1..65535 oder AUTO: der nächste ungenutzte Port wird automatisch zugewiesen."
|
|
::= { wtWebioAn1GraphAlarmEntry 25 }
|
|
|
|
wtWebioAn1GraphAlarmFtpFileName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Der File Name kann auch Pfadinformationen enthalten."
|
|
::= { wtWebioAn1GraphAlarmEntry 26 }
|
|
|
|
wtWebioAn1GraphAlarmFtpText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieser Text wird in die angegebene Datei geschrieben."
|
|
::= { wtWebioAn1GraphAlarmEntry 27 }
|
|
|
|
wtWebioAn1GraphAlarmFtpClearText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Dieser Text wird in die angegebene Datei geschrieben."
|
|
::= { wtWebioAn1GraphAlarmEntry 28 }
|
|
|
|
wtWebioAn1GraphAlarmFtpOptions OBJECT-TYPE
|
|
SYNTAX OCTET STRING (SIZE(4))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Binär kodierte Optionen, nur eine Option darf eingeschaltet sein:
|
|
STORE = Datei ersetzen
|
|
APPEND = Nachrichten ans Dateiende anhängen
|
|
|
|
Octet 1: ungenutzt
|
|
Octet 2: ungenutzt
|
|
Octet 3: ungenutzt
|
|
Octet 4:
|
|
Bit 0 : STORE
|
|
Bit 1 : APPEND
|
|
Bit 2-7: ungenutzt"
|
|
::= { wtWebioAn1GraphAlarmEntry 29 }
|
|
|
|
wtWebioAn1GraphAlarmTimerCron OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Diser Eintrag enthält 5 Leerzeichen- oder Tab-getrente Felder zur Definition von zeitgesteuerten
|
|
Ausgabe von Alarmnachrichten. Jedes der 5 Felder muss mit der aktuelle Zeit übereinstimmen, um
|
|
das Senden einer Nachricht auszulösen, Wochentag und Monatstag werden getrennt ausgewertet.
|
|
Feld möglicher Zahlenbereich
|
|
1: Minuten 0-59
|
|
2. Stunden 0-23, 0 ist Mitternacht
|
|
3: Monatstag 1-31
|
|
4: Monat 1-12
|
|
5: Wochentag 0-6, 0 ist Sonntag
|
|
|
|
Für jedes Feld kann nun angegeben werden:
|
|
- eine ganze Zahl aus dem angegebenen Zahlenbereich
|
|
- ein Teil-Zahlenbereich (wie z.B. 1-5) innerhalb des angegebenen Zahlenbereichs
|
|
- eine mit Komma getrennte Liste von ganzen Zahlen oder Tei-Zahlenbereichen (wie z.B. 2,4-6,8,10)
|
|
- ein Stern * (deckt den gesamten erlaubten Bereich ab)
|
|
- ein / gibt die Schrittweite bei Teil-Zahlenbereichen an (z.B. 0-59/2 jede zweite Minute)."
|
|
::= { wtWebioAn1GraphAlarmEntry 30 }
|
|
|
|
-- wtWebioAn1GraphPorts Group
|
|
----------------------------
|
|
|
|
-- Table
|
|
|
|
wtWebioAn1GraphPortTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF WtWebioAn1GraphPortEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Liste der Einstellungen abhängig von der Sensornummer."
|
|
::= { wtWebioAn1GraphPorts 1 }
|
|
|
|
wtWebioAn1GraphPortEntry OBJECT-TYPE
|
|
SYNTAX WtWebioAn1GraphPortEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Sensor-Parameter der einzelnen Sensoren."
|
|
INDEX { wtWebioAn1GraphSensorNo }
|
|
::= { wtWebioAn1GraphPortTable 1 }
|
|
|
|
WtWebioAn1GraphPortEntry ::= SEQUENCE {
|
|
wtWebioAn1GraphPortName OCTET STRING,
|
|
wtWebioAn1GraphPortText OCTET STRING,
|
|
wtWebioAn1GraphPortOffset1 OCTET STRING,
|
|
wtWebioAn1GraphPortTemperature1 OCTET STRING,
|
|
wtWebioAn1GraphPortOffset2 OCTET STRING,
|
|
wtWebioAn1GraphPortTemperature2 OCTET STRING,
|
|
wtWebioAn1GraphPortComment OCTET STRING
|
|
}
|
|
|
|
wtWebioAn1GraphPortName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Name des Sensors."
|
|
::= { wtWebioAn1GraphPortEntry 1 }
|
|
|
|
wtWebioAn1GraphPortText OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Beschreibung des Sensors."
|
|
::= { wtWebioAn1GraphPortEntry 2 }
|
|
|
|
wtWebioAn1GraphPortOffset1 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 1."
|
|
::= { wtWebioAn1GraphPortEntry 3 }
|
|
|
|
wtWebioAn1GraphPortTemperature1 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset-Kalibrierung: Referenztemperatur 1 in Grad mit max. 2 Nachkommastellen."
|
|
::= { wtWebioAn1GraphPortEntry 4 }
|
|
|
|
wtWebioAn1GraphPortOffset2 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset-Kalibrierung: Offset in Grad mit max. 2 Nachkommastellen bei Temperatur 2."
|
|
::= { wtWebioAn1GraphPortEntry 5 }
|
|
|
|
wtWebioAn1GraphPortTemperature2 OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset-Kalibrierung: Referenztemperatur 2 in Grad mit max. 2 Nachkommastellen."
|
|
::= { wtWebioAn1GraphPortEntry 6 }
|
|
|
|
wtWebioAn1GraphPortComment OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Offset-Kalibrierung: Angaben zu Datum, Referenzgerät, Operator."
|
|
::= { wtWebioAn1GraphPortEntry 7 }
|
|
|
|
-- wtWebioAn1GraphManufact Group
|
|
----------------------------
|
|
|
|
wtWebioAn1GraphMfName OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hersteller Firmenname"
|
|
::= { wtWebioAn1GraphManufact 1 }
|
|
|
|
wtWebioAn1GraphMfAddr OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Adresse des Herstellers."
|
|
::= { wtWebioAn1GraphManufact 2 }
|
|
|
|
wtWebioAn1GraphMfHotline OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Hotline des Herstellers."
|
|
::= { wtWebioAn1GraphManufact 3 }
|
|
|
|
wtWebioAn1GraphMfInternet OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Internet-Adresse des Herstellers."
|
|
::= { wtWebioAn1GraphManufact 4 }
|
|
|
|
wtWebioAn1GraphMfDeviceTyp OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Gerätebezeichnung (Typ) des Herstellers."
|
|
::= { wtWebioAn1GraphManufact 5 }
|
|
|
|
wtWebioAn1GraphMfOrderNo OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bestellnummer des Gerätes des Herstellers."
|
|
::= { wtWebioAn1GraphManufact 6 }
|
|
|
|
-- wtWebioAn1GraphDiag Group
|
|
----------------------------
|
|
|
|
wtWebioAn1GraphDiagErrorCount OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Anzahl der Einträge im Fehlerspeicher."
|
|
::= { wtWebioAn1GraphDiag 1 }
|
|
|
|
wtWebioAn1GraphDiagBinaryError OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Bitweise kodierte Fehlerursachen."
|
|
::= { wtWebioAn1GraphDiag 2 }
|
|
|
|
wtWebioAn1GraphDiagErrorIndex OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Der Wert dieser Variable wird als Index für die Ausgabe
|
|
eines Fehlertextes (wtWebioAn1GraphDiagErrorMessage) verwendet.
|
|
Die Fehler im Speicher sind von 1 bis wtWebioAn1GraphDiagErrorCount durchnummeriert.
|
|
Nach dem Schreiben einens gültigen Wertes in diese Variable kann der dazugehörige Text
|
|
in wtWebioAn1GraphDiagErrorMessage ausgelesen werden."
|
|
::= { wtWebioAn1GraphDiag 3 }
|
|
|
|
wtWebioAn1GraphDiagErrorMessage OBJECT-TYPE
|
|
SYNTAX OCTET STRING
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Abhängig vom Wert wtWebioAn1GraphDiagErrorIndex wird ein Fehlertext angezeigt."
|
|
::= { wtWebioAn1GraphDiag 4 }
|
|
|
|
wtWebioAn1GraphDiagErrorClear OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS write-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Durch Schreiben eine 1 in diese Variable, wird der Fehlerspeicher gelöscht."
|
|
::= { wtWebioAn1GraphDiag 5 }
|
|
|
|
-- TRAP DEFINITIONS
|
|
|
|
-- Diese SNMP-Traps werden gesendet, wenn die Alarmtriggerbedingungen zutreffen
|
|
|
|
wtWebioAn1GraphAlert1 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 1"
|
|
--#SUMMARY "Alarm 1: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 31
|
|
|
|
wtWebioAn1GraphAlert2 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 2"
|
|
--#SUMMARY "Alarm 2: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 32
|
|
|
|
wtWebioAn1GraphAlert3 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 3"
|
|
--#SUMMARY "Alarm 3: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 33
|
|
|
|
wtWebioAn1GraphAlert4 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 4"
|
|
--#SUMMARY "Alarm 4: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 34
|
|
|
|
wtWebioAn1GraphAlert5 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 5"
|
|
--#SUMMARY "Alarm 5: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 35
|
|
|
|
wtWebioAn1GraphAlert6 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 6"
|
|
--#SUMMARY "Alarm 6: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 36
|
|
|
|
wtWebioAn1GraphAlert7 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 7"
|
|
--#SUMMARY "Alarm 7: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 37
|
|
|
|
wtWebioAn1GraphAlert8 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Alarm 8"
|
|
--#SUMMARY "Alarm 8: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 38
|
|
|
|
wtWebioAn1GraphAlert9 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 1 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 1"
|
|
--#SUMMARY "Release Alarm 1: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 91
|
|
|
|
wtWebioAn1GraphAlert10 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 2 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 2"
|
|
--#SUMMARY "Release Alarm 2: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 92
|
|
|
|
wtWebioAn1GraphAlert11 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 3 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 3"
|
|
--#SUMMARY "Release Alarm 3: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 93
|
|
|
|
wtWebioAn1GraphAlert12 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 4 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 4"
|
|
--#SUMMARY "Release Alarm 4: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 94
|
|
|
|
wtWebioAn1GraphAlert13 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 5 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 5"
|
|
--#SUMMARY "Release Alarm 5: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 95
|
|
|
|
wtWebioAn1GraphAlert14 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 6 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 6"
|
|
--#SUMMARY "Release Alarm 6: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 96
|
|
|
|
wtWebioAn1GraphAlert15 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 7 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 7"
|
|
--#SUMMARY "Release Alarm 7: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 97
|
|
|
|
wtWebioAn1GraphAlert16 TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES { wtWebioAn1GraphAlarmClearTrapText }
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn der Alarm 8 gelöscht wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Release Alarm 8"
|
|
--#SUMMARY "Release Alarm 8: %s"
|
|
--#ARGUMENTS {0}
|
|
--#SEVERITY INFORMATIONAL
|
|
--#TIMEINDEX 99
|
|
--#STATE OPERATIONAL
|
|
::= 98
|
|
|
|
wtWebioAn1GraphAlertDiag TRAP-TYPE
|
|
ENTERPRISE wtWebioAn1Graph
|
|
VARIABLES {
|
|
wtWebioAn1GraphDiagErrorIndex,
|
|
wtWebioAn1GraphDiagErrorMessage
|
|
}
|
|
DESCRIPTION
|
|
"Dieser SNMP-Trap wird generiert, wenn eine Diagnose/Error-Message ausgelöst wurde,
|
|
das SNMP-Trap-Enable gesetzt ist und
|
|
SNMP in Enable freigegeben ist."
|
|
-- NMS trap annotation
|
|
--#TYPE "Web-Thermograph Diagnose Error"
|
|
--#SUMMARY "Diagnose error index: %d, Message: %s."
|
|
--#ARGUMENTS {0,1}
|
|
--#SEVERITY MAJOR
|
|
--#TIMEINDEX 99
|
|
--#STATE DEGRADED
|
|
::= 110
|
|
|
|
|
|
END
|