- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
4777 lines
No EOL
156 KiB
Text
4777 lines
No EOL
156 KiB
Text
--
|
|
-- Copyright(C) 2003-2017 Server Technology, Inc.
|
|
--
|
|
|
|
Sentry4-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, enterprises, Integer32,
|
|
OBJECT-TYPE, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
OBJECT-GROUP, NOTIFICATION-GROUP, MODULE-COMPLIANCE FROM SNMPv2-CONF
|
|
TEXTUAL-CONVENTION, DisplayString FROM SNMPv2-TC;
|
|
|
|
|
|
sentry4 MODULE-IDENTITY
|
|
LAST-UPDATED "201706151830Z" -- 15 June 2017
|
|
ORGANIZATION "Server Technology, Inc."
|
|
CONTACT-INFO
|
|
"Server Technology, Inc.
|
|
1040 Sandhill Road
|
|
Reno, NV 89521
|
|
Tel: (775) 284-2000
|
|
Fax: (775) 284-2065
|
|
Email: mibmaster@servertech.com"
|
|
DESCRIPTION
|
|
"This is the MIB module for the fourth generation of the
|
|
Sentry product family. This includes the PRO1 and PRO2
|
|
series of Smart and Switched Cabinet Distribution Unit (CDU)
|
|
and Power Distribution Unit (PDU) products."
|
|
REVISION "201706151830Z" -- 15 June 2017
|
|
DESCRIPTION
|
|
"Added support for fan sensors, including objects for installed
|
|
count, identification, speed and status monitoring, threshold
|
|
and hysteresis configuration, and a notification for events.
|
|
Added the st4UnitOutletDisplayOrder object."
|
|
REVISION "201611182340Z" -- 18 November 2016
|
|
DESCRIPTION
|
|
"Added the st4UnitProductMfrDate object. Adjusted the upper
|
|
limit of voltage objects to 600 Volts."
|
|
REVISION "201609212300Z" -- 21 September 2016
|
|
DESCRIPTION
|
|
"Fixed the st4InputCordOutOfBalanceEvent notification
|
|
definition to include the correct objects."
|
|
REVISION "201604252140Z" -- 25 April 2016
|
|
DESCRIPTION
|
|
"Added support for the PRO1 product series. Added the
|
|
st4SystemProductSeries and st4InputCordNominalPowerFactor
|
|
objects. Adjusted the upper limit of cord and line current
|
|
objects to 600 Amps. Adjusted the lower limit of nominal
|
|
voltage objects to 0 Volts. Corrected the lower limit of
|
|
several configuration objects from -1 to 0."
|
|
REVISION "201502191000Z" -- 19 February 2015
|
|
DESCRIPTION
|
|
"Corrected the UNITS and value range of temperature sensor
|
|
threshold objects."
|
|
REVISION "201412231130Z" -- 23 December 2014
|
|
DESCRIPTION
|
|
"Initial release."
|
|
::= { serverTech 4 }
|
|
|
|
serverTech OBJECT IDENTIFIER ::= { enterprises 1718 }
|
|
|
|
|
|
-- Common Definitions
|
|
|
|
DeviceStatus ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status returned by devices."
|
|
SYNTAX INTEGER {
|
|
normal(0), -- operating properly
|
|
disabled(1), -- disabled
|
|
purged(2), -- purged
|
|
reading(5), -- read in process
|
|
settle(6), -- is settling
|
|
notFound(7), -- never connected
|
|
lost(8), -- disconnected
|
|
readError(9), -- read failure
|
|
noComm(10), -- unreachable
|
|
pwrError(11), -- power detection error
|
|
breakerTripped(12), -- breaker error
|
|
fuseBlown(13), -- fuse error
|
|
lowAlarm(14), -- under low alarm threshold
|
|
lowWarning(15), -- under low warning threshold
|
|
highWarning(16), -- over high warning threshold
|
|
highAlarm(17), -- over high alarm threshold
|
|
alarm(18), -- general alarm
|
|
underLimit(19), -- under limit alarm
|
|
overLimit(20), -- over limit alarm
|
|
nvmFail(21), -- NVM failure
|
|
profileError(22), -- profile error
|
|
conflict(23) -- conflict
|
|
}
|
|
|
|
DeviceState ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"On or off state of devices."
|
|
SYNTAX INTEGER {
|
|
unknown(0), -- on / off state is unknown
|
|
on(1), -- is on
|
|
off(2) -- is off
|
|
}
|
|
|
|
EventNotificationMethods ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bits to enable event notification methods."
|
|
SYNTAX BITS {
|
|
snmpTrap(0), -- enables notifications by SNMP traps
|
|
email(1) -- enables notifications by Email
|
|
}
|
|
|
|
-- Object Definitions
|
|
|
|
st4Objects OBJECT IDENTIFIER ::= { sentry4 1 }
|
|
|
|
-- System
|
|
|
|
st4System OBJECT IDENTIFIER ::= { st4Objects 1 }
|
|
|
|
-- System Configuration
|
|
|
|
st4SystemConfig OBJECT IDENTIFIER ::= { st4System 1 }
|
|
|
|
st4SystemProductName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The product name."
|
|
::= { st4SystemConfig 1 }
|
|
|
|
st4SystemLocation OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..63))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The location of the system."
|
|
::= { st4SystemConfig 2 }
|
|
|
|
st4SystemFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The firmware version."
|
|
::= { st4SystemConfig 3 }
|
|
|
|
st4SystemFirmwareBuildInfo OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The firmware build information."
|
|
::= { st4SystemConfig 4 }
|
|
|
|
st4SystemNICSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..8))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number of the network interface card."
|
|
::= { st4SystemConfig 5 }
|
|
|
|
st4SystemNICHardwareInfo OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..63))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Hardware information about the network interface card."
|
|
::= { st4SystemConfig 6 }
|
|
|
|
st4SystemProductSeries OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
pro1(0),
|
|
pro2(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The product series."
|
|
::= { st4SystemConfig 7 }
|
|
|
|
st4SystemFeatures OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
smartLoadShedding(0),
|
|
reserved(1),
|
|
outletControlInhibit(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The key-activated features enabled in the system."
|
|
::= { st4SystemConfig 10 }
|
|
|
|
st4SystemFeatureKey OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..19))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A valid feature key written to this object will enable a
|
|
feature in the system. A valid feature key is in the form
|
|
xxxx-xxxx-xxxx-xxxx. A read of this object returns an
|
|
empty string."
|
|
::= { st4SystemConfig 11 }
|
|
|
|
st4SystemConfigModifiedCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..2147483647)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total number of times the system configuration has changed."
|
|
::= { st4SystemConfig 20 }
|
|
|
|
st4SystemUnitCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of units in the system."
|
|
::= { st4SystemConfig 21 }
|
|
|
|
-- Units
|
|
|
|
st4Units OBJECT IDENTIFIER ::= { st4Objects 2 }
|
|
|
|
-- Unit Common Configuration
|
|
|
|
st4UnitCommonConfig OBJECT IDENTIFIER ::= { st4Units 1 }
|
|
|
|
-- Unit Configuration Table
|
|
|
|
st4UnitConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4UnitConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit configuration table."
|
|
::= { st4Units 2 }
|
|
|
|
st4UnitConfigEntry OBJECT-TYPE
|
|
SYNTAX St4UnitConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular unit."
|
|
INDEX { st4UnitIndex }
|
|
::= { st4UnitConfigTable 1 }
|
|
|
|
St4UnitConfigEntry ::= SEQUENCE {
|
|
st4UnitIndex Integer32,
|
|
st4UnitID DisplayString,
|
|
st4UnitName DisplayString,
|
|
st4UnitProductSN DisplayString,
|
|
st4UnitModel DisplayString,
|
|
st4UnitAssetTag DisplayString,
|
|
st4UnitType INTEGER,
|
|
st4UnitCapabilities BITS,
|
|
st4UnitProductMfrDate DisplayString,
|
|
st4UnitDisplayOrientation INTEGER,
|
|
st4UnitOutletSequenceOrder INTEGER,
|
|
st4UnitOutletDisplayOrder INTEGER,
|
|
st4UnitInputCordCount Integer32,
|
|
st4UnitTempSensorCount Integer32,
|
|
st4UnitHumidSensorCount Integer32,
|
|
st4UnitWaterSensorCount Integer32,
|
|
st4UnitCcSensorCount Integer32,
|
|
st4UnitAdcSensorCount Integer32,
|
|
st4UnitFanSensorCount Integer32
|
|
}
|
|
|
|
st4UnitIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..6)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit index. A=1, B=2, C=3, D=4, E=5, F=6."
|
|
::= { st4UnitConfigEntry 1 }
|
|
|
|
st4UnitID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(1))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the unit. Format=A."
|
|
::= { st4UnitConfigEntry 2 }
|
|
|
|
st4UnitName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the unit."
|
|
::= { st4UnitConfigEntry 3 }
|
|
|
|
st4UnitProductSN OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The product serial number of the unit."
|
|
::= { st4UnitConfigEntry 4 }
|
|
|
|
st4UnitModel OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The model of the unit."
|
|
::= { st4UnitConfigEntry 5 }
|
|
|
|
st4UnitAssetTag OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The asset tag of the unit."
|
|
::= { st4UnitConfigEntry 6 }
|
|
|
|
st4UnitType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
masterPdu(0),
|
|
linkPdu(1),
|
|
controller(2),
|
|
emcu(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of the unit."
|
|
::= { st4UnitConfigEntry 7 }
|
|
|
|
st4UnitCapabilities OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
dc(0), -- unit is DC
|
|
phase3(1), -- unit is 3 phase
|
|
wye(2), -- unit has Wye circuits
|
|
delta(3) -- unit has Delta circuits
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The capabilities of the unit."
|
|
::= { st4UnitConfigEntry 8 }
|
|
|
|
st4UnitProductMfrDate OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..10))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The product manufacture date in YYYY-MM-DD (ISO 8601 format) of
|
|
the unit."
|
|
::= { st4UnitConfigEntry 9 }
|
|
|
|
st4UnitDisplayOrientation OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
inverted(1),
|
|
auto(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The orientation of all displays in the unit."
|
|
::= { st4UnitConfigEntry 20 }
|
|
|
|
st4UnitOutletSequenceOrder OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
reversed(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sequencing order of all outlets in the unit."
|
|
::= { st4UnitConfigEntry 21 }
|
|
|
|
st4UnitOutletDisplayOrder OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
reversed(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The display order in the user interfaces of all outlets in the
|
|
unit."
|
|
::= { st4UnitConfigEntry 22 }
|
|
|
|
st4UnitInputCordCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of power input cords into the unit."
|
|
::= { st4UnitConfigEntry 30 }
|
|
|
|
st4UnitTempSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..2)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of external temperature sensors supported by the unit."
|
|
::= { st4UnitConfigEntry 31 }
|
|
|
|
st4UnitHumidSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..2)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of external humidity sensors supported by the unit."
|
|
::= { st4UnitConfigEntry 32 }
|
|
|
|
st4UnitWaterSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of external water sensors supported by the unit."
|
|
::= { st4UnitConfigEntry 33 }
|
|
|
|
st4UnitCcSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of external contact closure sensors supported by the
|
|
unit."
|
|
::= { st4UnitConfigEntry 34 }
|
|
|
|
st4UnitAdcSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..1)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of analog-to-digital converter sensors supported by the
|
|
unit."
|
|
::= { st4UnitConfigEntry 35 }
|
|
|
|
st4UnitFanSensorCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of fan sensors supported by the unit."
|
|
::= { st4UnitConfigEntry 36 }
|
|
|
|
-- Unit Monitor Table
|
|
|
|
st4UnitMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4UnitMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit monitor table."
|
|
::= { st4Units 3 }
|
|
|
|
st4UnitMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4UnitMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular unit."
|
|
INDEX { st4UnitIndex }
|
|
::= { st4UnitMonitorTable 1 }
|
|
|
|
St4UnitMonitorEntry ::= SEQUENCE {
|
|
st4UnitStatus DeviceStatus
|
|
}
|
|
|
|
st4UnitStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the unit."
|
|
::= { st4UnitMonitorEntry 1 }
|
|
|
|
-- Unit Event Configuration Table
|
|
|
|
st4UnitEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4UnitEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit event configuration table."
|
|
::= { st4Units 4 }
|
|
|
|
st4UnitEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4UnitEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular unit."
|
|
INDEX { st4UnitIndex }
|
|
::= { st4UnitEventConfigTable 1 }
|
|
|
|
St4UnitEventConfigEntry ::= SEQUENCE {
|
|
st4UnitNotifications EventNotificationMethods
|
|
}
|
|
|
|
st4UnitNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for unit events."
|
|
::= { st4UnitEventConfigEntry 1 }
|
|
|
|
-- Input Cords
|
|
|
|
st4InputCords OBJECT IDENTIFIER ::= { st4Objects 3 }
|
|
|
|
-- Input Cord Common Configuration
|
|
|
|
st4InputCordCommonConfig OBJECT IDENTIFIER ::= { st4InputCords 1 }
|
|
|
|
st4InputCordActivePowerHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power hysteresis of the input cord in Watts."
|
|
::= { st4InputCordCommonConfig 1 }
|
|
|
|
st4InputCordApparentPowerHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The apparent power hysteresis of the input cord in Volt-Amps."
|
|
::= { st4InputCordCommonConfig 2 }
|
|
|
|
st4InputCordPowerFactorHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..20)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power factor hysteresis of the input cord in hundredths."
|
|
::= { st4InputCordCommonConfig 3 }
|
|
|
|
st4InputCordOutOfBalanceHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..10)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 3 phase out-of-balance hysteresis of the input cord in
|
|
percent."
|
|
::= { st4InputCordCommonConfig 4 }
|
|
|
|
-- Input Cord Configuration Table
|
|
|
|
st4InputCordConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4InputCordConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord configuration table."
|
|
::= { st4InputCords 2 }
|
|
|
|
st4InputCordConfigEntry OBJECT-TYPE
|
|
SYNTAX St4InputCordConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular input cord."
|
|
INDEX { st4UnitIndex, st4InputCordIndex }
|
|
::= { st4InputCordConfigTable 1 }
|
|
|
|
St4InputCordConfigEntry ::= SEQUENCE {
|
|
st4InputCordIndex Integer32,
|
|
st4InputCordID DisplayString,
|
|
st4InputCordName DisplayString,
|
|
st4InputCordInletType DisplayString,
|
|
st4InputCordNominalVoltage Integer32,
|
|
st4InputCordNominalVoltageMin Integer32,
|
|
st4InputCordNominalVoltageMax Integer32,
|
|
st4InputCordCurrentCapacity Integer32,
|
|
st4InputCordCurrentCapacityMax Integer32,
|
|
st4InputCordPowerCapacity Integer32,
|
|
st4InputCordNominalPowerFactor Integer32,
|
|
st4InputCordLineCount Integer32,
|
|
st4InputCordPhaseCount Integer32,
|
|
st4InputCordOcpCount Integer32,
|
|
st4InputCordBranchCount Integer32,
|
|
st4InputCordOutletCount Integer32
|
|
}
|
|
|
|
st4InputCordIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord index. A=1, B=2, C=3, D=4."
|
|
::= { st4InputCordConfigEntry 1 }
|
|
|
|
st4InputCordID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(2))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the input cord. Format=AA."
|
|
::= { st4InputCordConfigEntry 2 }
|
|
|
|
st4InputCordName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the input cord."
|
|
::= { st4InputCordConfigEntry 3 }
|
|
|
|
st4InputCordInletType OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of plug on the input cord, or socket for the input cord."
|
|
::= { st4InputCordConfigEntry 6}
|
|
|
|
st4InputCordNominalVoltage OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-configured nominal voltage of the input cord in tenth
|
|
Volts."
|
|
::= { st4InputCordConfigEntry 7 }
|
|
|
|
st4InputCordNominalVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
UNITS "Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory-set minimum allowed for the user-configured nominal
|
|
voltage of the input cord in Volts."
|
|
::= { st4InputCordConfigEntry 8 }
|
|
|
|
st4InputCordNominalVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
UNITS "Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory-set maximum allowed for the user-configured nominal
|
|
voltage of the input cord in Volts."
|
|
::= { st4InputCordConfigEntry 9 }
|
|
|
|
st4InputCordCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-configured current capacity of the input cord in Amps."
|
|
::= { st4InputCordConfigEntry 10 }
|
|
|
|
st4InputCordCurrentCapacityMax OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory-set maximum allowed for the user-configured current
|
|
capacity of the input cord in Amps."
|
|
::= { st4InputCordConfigEntry 11 }
|
|
|
|
st4InputCordPowerCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power capacity of the input cord in Volt-Amps. For DC
|
|
products, this is identical to power capacity in Watts."
|
|
::= { st4InputCordConfigEntry 12 }
|
|
|
|
st4InputCordNominalPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-configured estimated nominal power factor of the input
|
|
cord in hundredths."
|
|
::= { st4InputCordConfigEntry 13 }
|
|
|
|
st4InputCordLineCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of current-carrying lines in the input cord."
|
|
::= { st4InputCordConfigEntry 20 }
|
|
|
|
st4InputCordPhaseCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..6)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of active phases from the lines in the input cord."
|
|
::= { st4InputCordConfigEntry 21 }
|
|
|
|
st4InputCordOcpCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..12)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of over-current protectors downstream from the input
|
|
cord."
|
|
::= { st4InputCordConfigEntry 22 }
|
|
|
|
st4InputCordBranchCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..12)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of branches downstream from the input cord."
|
|
::= { st4InputCordConfigEntry 23 }
|
|
|
|
st4InputCordOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..128)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of outlets powered from the input cord."
|
|
::= { st4InputCordConfigEntry 24 }
|
|
|
|
-- Input Cord Monitor Table
|
|
|
|
st4InputCordMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4InputCordMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord monitor table."
|
|
::= { st4InputCords 3 }
|
|
|
|
st4InputCordMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4InputCordMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular input cord."
|
|
INDEX { st4UnitIndex, st4InputCordIndex }
|
|
::= { st4InputCordMonitorTable 1 }
|
|
|
|
St4InputCordMonitorEntry ::= SEQUENCE {
|
|
st4InputCordState DeviceState,
|
|
st4InputCordStatus DeviceStatus,
|
|
st4InputCordActivePower Integer32,
|
|
st4InputCordActivePowerStatus DeviceStatus,
|
|
st4InputCordApparentPower Integer32,
|
|
st4InputCordApparentPowerStatus DeviceStatus,
|
|
st4InputCordPowerUtilized Integer32,
|
|
st4InputCordPowerFactor Integer32,
|
|
st4InputCordPowerFactorStatus DeviceStatus,
|
|
st4InputCordEnergy Integer32,
|
|
st4InputCordFrequency Integer32,
|
|
st4InputCordOutOfBalance Integer32,
|
|
st4InputCordOutOfBalanceStatus DeviceStatus
|
|
}
|
|
|
|
st4InputCordState OBJECT-TYPE
|
|
SYNTAX DeviceState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The on/off state of the input cord."
|
|
::= { st4InputCordMonitorEntry 1 }
|
|
|
|
st4InputCordStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the input cord."
|
|
::= { st4InputCordMonitorEntry 2 }
|
|
|
|
st4InputCordActivePower OBJECT-TYPE
|
|
SYNTAX Integer32(-1..50000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured active power of the input cord in Watts."
|
|
::= { st4InputCordMonitorEntry 3 }
|
|
|
|
st4InputCordActivePowerStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured active power of the input cord."
|
|
::= { st4InputCordMonitorEntry 4 }
|
|
|
|
st4InputCordApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32(-1..50000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured apparent power of the input cord in Volt-Amps."
|
|
::= { st4InputCordMonitorEntry 5 }
|
|
|
|
st4InputCordApparentPowerStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured apparent power of the input cord."
|
|
::= { st4InputCordMonitorEntry 6 }
|
|
|
|
st4InputCordPowerUtilized OBJECT-TYPE
|
|
SYNTAX Integer32(-1..1200)
|
|
UNITS "tenth percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of the input cord power capacity used in tenth percent.
|
|
For AC products, this is the ratio of the apparent power to the
|
|
power capacity. For DC products, this is the ratio of the active
|
|
power to the power capacity."
|
|
::= { st4InputCordMonitorEntry 7 }
|
|
|
|
st4InputCordPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32(-1..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured power factor of the input cord in hundredths."
|
|
::= { st4InputCordMonitorEntry 8 }
|
|
|
|
st4InputCordPowerFactorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured power factor of the input cord."
|
|
::= { st4InputCordMonitorEntry 9 }
|
|
|
|
st4InputCordEnergy OBJECT-TYPE
|
|
SYNTAX Integer32(-1..2147483647)
|
|
UNITS "tenth Kilowatt-Hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total energy consumption of loads through the input cord in
|
|
tenth Kilowatt-Hours."
|
|
::= { st4InputCordMonitorEntry 10 }
|
|
|
|
st4InputCordFrequency OBJECT-TYPE
|
|
SYNTAX Integer32(-1..1000)
|
|
UNITS "tenth Hertz"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The frequency of the input cord voltage in tenth Hertz."
|
|
::= { st4InputCordMonitorEntry 11 }
|
|
|
|
st4InputCordOutOfBalance OBJECT-TYPE
|
|
SYNTAX Integer32(-1..2000)
|
|
UNITS "tenth percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current imbalance on the lines of the input cord in tenth
|
|
percent."
|
|
::= { st4InputCordMonitorEntry 12 }
|
|
|
|
st4InputCordOutOfBalanceStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the current imbalance on the lines of the input
|
|
cord."
|
|
::= { st4InputCordMonitorEntry 13 }
|
|
|
|
-- Input Cord Event Configuration Table
|
|
|
|
st4InputCordEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4InputCordEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord event configuration table."
|
|
::= { st4InputCords 4 }
|
|
|
|
st4InputCordEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4InputCordEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular input cord."
|
|
INDEX { st4UnitIndex, st4InputCordIndex }
|
|
::= { st4InputCordEventConfigTable 1 }
|
|
|
|
St4InputCordEventConfigEntry ::= SEQUENCE {
|
|
st4InputCordNotifications EventNotificationMethods,
|
|
st4InputCordActivePowerLowAlarm Integer32,
|
|
st4InputCordActivePowerLowWarning Integer32,
|
|
st4InputCordActivePowerHighWarning Integer32,
|
|
st4InputCordActivePowerHighAlarm Integer32,
|
|
st4InputCordApparentPowerLowAlarm Integer32,
|
|
st4InputCordApparentPowerLowWarning Integer32,
|
|
st4InputCordApparentPowerHighWarning Integer32,
|
|
st4InputCordApparentPowerHighAlarm Integer32,
|
|
st4InputCordPowerFactorLowAlarm Integer32,
|
|
st4InputCordPowerFactorLowWarning Integer32,
|
|
st4InputCordOutOfBalanceHighWarning Integer32,
|
|
st4InputCordOutOfBalanceHighAlarm Integer32
|
|
}
|
|
|
|
st4InputCordNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for input cord events."
|
|
::= { st4InputCordEventConfigEntry 1 }
|
|
|
|
st4InputCordActivePowerLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power low alarm threshold of the input cord in Watts."
|
|
::= { st4InputCordEventConfigEntry 2 }
|
|
|
|
st4InputCordActivePowerLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power low warning threshold of the input cord in
|
|
Watts."
|
|
::= { st4InputCordEventConfigEntry 3 }
|
|
|
|
st4InputCordActivePowerHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power high warning threshold of the input cord in
|
|
Watts."
|
|
::= { st4InputCordEventConfigEntry 4 }
|
|
|
|
st4InputCordActivePowerHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power high alarm threshold of the input cord in Watts."
|
|
::= { st4InputCordEventConfigEntry 5 }
|
|
|
|
st4InputCordApparentPowerLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The apparent power low alarm threshold of the input cord in
|
|
Volt-Amps."
|
|
::= { st4InputCordEventConfigEntry 6 }
|
|
|
|
st4InputCordApparentPowerLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The apparent power low warning threshold of the input cord in
|
|
Volt-Amps."
|
|
::= { st4InputCordEventConfigEntry 7 }
|
|
|
|
st4InputCordApparentPowerHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The apparent power high warning threshold of the input cord in
|
|
Volt-Amps."
|
|
::= { st4InputCordEventConfigEntry 8 }
|
|
|
|
st4InputCordApparentPowerHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..50000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The apparent power high alarm threshold of the input cord in
|
|
Volt-Amps."
|
|
::= { st4InputCordEventConfigEntry 9 }
|
|
|
|
st4InputCordPowerFactorLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power factor low alarm threshold of the input cord in
|
|
hundredths."
|
|
::= { st4InputCordEventConfigEntry 10 }
|
|
|
|
st4InputCordPowerFactorLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power factor low warning threshold of the input cord in
|
|
hundredths."
|
|
::= { st4InputCordEventConfigEntry 11 }
|
|
|
|
st4InputCordOutOfBalanceHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 3 phase out-of-balance high warning threshold of the input
|
|
cord in percent."
|
|
::= { st4InputCordEventConfigEntry 12 }
|
|
|
|
st4InputCordOutOfBalanceHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "percent"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 3 phase out-of-balance high alarm threshold of the input cord
|
|
in percent."
|
|
::= { st4InputCordEventConfigEntry 13 }
|
|
|
|
-- Lines
|
|
|
|
st4Lines OBJECT IDENTIFIER ::= { st4Objects 4 }
|
|
|
|
-- Line Common Configuration
|
|
|
|
st4LineCommonConfig OBJECT IDENTIFIER ::= { st4Lines 1 }
|
|
|
|
st4LineCurrentHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current hysteresis of the line in tenth Amps."
|
|
::= { st4LineCommonConfig 1 }
|
|
|
|
-- Line Configuration Table
|
|
|
|
st4LineConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4LineConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line configuration table."
|
|
::= { st4Lines 2 }
|
|
|
|
st4LineConfigEntry OBJECT-TYPE
|
|
SYNTAX St4LineConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular line."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4LineIndex }
|
|
::= { st4LineConfigTable 1 }
|
|
|
|
St4LineConfigEntry ::= SEQUENCE {
|
|
st4LineIndex Integer32,
|
|
st4LineID DisplayString,
|
|
st4LineLabel DisplayString,
|
|
st4LineCurrentCapacity Integer32
|
|
}
|
|
|
|
st4LineIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line index. L1=1, L2=2, L3=3, N=4."
|
|
::= { st4LineConfigEntry 1 }
|
|
|
|
st4LineID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the line. Format=AAN."
|
|
::= { st4LineConfigEntry 2 }
|
|
|
|
st4LineLabel OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system label assigned to the line for identification."
|
|
::= { st4LineConfigEntry 4 }
|
|
|
|
st4LineCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..600)
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current capacity of the line in Amps."
|
|
::= { st4LineConfigEntry 6 }
|
|
|
|
-- Line Monitor Table
|
|
|
|
st4LineMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4LineMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line monitor table."
|
|
::= { st4Lines 3 }
|
|
|
|
st4LineMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4LineMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular line."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4LineIndex }
|
|
::= { st4LineMonitorTable 1 }
|
|
|
|
St4LineMonitorEntry ::= SEQUENCE {
|
|
st4LineState DeviceState,
|
|
st4LineStatus DeviceStatus,
|
|
st4LineCurrent Integer32,
|
|
st4LineCurrentStatus DeviceStatus,
|
|
st4LineCurrentUtilized Integer32
|
|
}
|
|
|
|
st4LineState OBJECT-TYPE
|
|
SYNTAX DeviceState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The on/off state of the line."
|
|
::= { st4LineMonitorEntry 1 }
|
|
|
|
st4LineStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the line."
|
|
::= { st4LineMonitorEntry 2 }
|
|
|
|
st4LineCurrent OBJECT-TYPE
|
|
SYNTAX Integer32(-1..60000)
|
|
UNITS "hundredth Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured current on the line in hundredth Amps."
|
|
::= { st4LineMonitorEntry 3 }
|
|
|
|
st4LineCurrentStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured current on the line."
|
|
::= { st4LineMonitorEntry 4 }
|
|
|
|
st4LineCurrentUtilized OBJECT-TYPE
|
|
SYNTAX Integer32(-1..1200)
|
|
UNITS "tenth percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of the line current capacity used in tenth percent."
|
|
::= { st4LineMonitorEntry 5 }
|
|
|
|
-- Line Event Configuration Table
|
|
|
|
st4LineEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4LineEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line event configuration table."
|
|
::= { st4Lines 4 }
|
|
|
|
st4LineEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4LineEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular line."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4LineIndex }
|
|
::= { st4LineEventConfigTable 1 }
|
|
|
|
St4LineEventConfigEntry ::= SEQUENCE {
|
|
st4LineNotifications EventNotificationMethods,
|
|
st4LineCurrentLowAlarm Integer32,
|
|
st4LineCurrentLowWarning Integer32,
|
|
st4LineCurrentHighWarning Integer32,
|
|
st4LineCurrentHighAlarm Integer32
|
|
}
|
|
|
|
st4LineNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for line events."
|
|
::= { st4LineEventConfigEntry 1 }
|
|
|
|
st4LineCurrentLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low alarm threshold of the line in tenth Amps."
|
|
::= { st4LineEventConfigEntry 2 }
|
|
|
|
st4LineCurrentLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low warning threshold of the line in tenth Amps."
|
|
::= { st4LineEventConfigEntry 3 }
|
|
|
|
st4LineCurrentHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high warning threshold of the line in tenth Amps."
|
|
::= { st4LineEventConfigEntry 4 }
|
|
|
|
st4LineCurrentHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high alarm threshold of the line in tenth Amps."
|
|
::= { st4LineEventConfigEntry 5 }
|
|
|
|
-- Phases
|
|
|
|
st4Phases OBJECT IDENTIFIER ::= { st4Objects 5 }
|
|
|
|
-- Phase Common Configuration
|
|
|
|
st4PhaseCommonConfig OBJECT IDENTIFIER ::= { st4Phases 1 }
|
|
|
|
st4PhaseVoltageHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..200)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage hysteresis of the phase in tenth Volts."
|
|
::= { st4PhaseCommonConfig 1 }
|
|
|
|
st4PhasePowerFactorHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..20)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power factor hysteresis of the phase in hundredths."
|
|
::= { st4PhaseCommonConfig 2 }
|
|
|
|
-- Phase Configuration Table
|
|
|
|
st4PhaseConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4PhaseConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase configuration table."
|
|
::= { st4Phases 2 }
|
|
|
|
st4PhaseConfigEntry OBJECT-TYPE
|
|
SYNTAX St4PhaseConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular phase."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
|
|
::= { st4PhaseConfigTable 1 }
|
|
|
|
St4PhaseConfigEntry ::= SEQUENCE {
|
|
st4PhaseIndex Integer32,
|
|
st4PhaseID DisplayString,
|
|
st4PhaseLabel DisplayString,
|
|
st4PhaseNominalVoltage Integer32,
|
|
st4PhaseBranchCount Integer32,
|
|
st4PhaseOutletCount Integer32
|
|
}
|
|
|
|
st4PhaseIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..6)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3;
|
|
Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase:
|
|
L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2,
|
|
L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6."
|
|
::= { st4PhaseConfigEntry 1 }
|
|
|
|
st4PhaseID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the phase. Format=AAN."
|
|
::= { st4PhaseConfigEntry 2 }
|
|
|
|
st4PhaseLabel OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system label assigned to the phase for identification."
|
|
::= { st4PhaseConfigEntry 4 }
|
|
|
|
st4PhaseNominalVoltage OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The nominal voltage of the phase in tenth Volts."
|
|
::= { st4PhaseConfigEntry 6 }
|
|
|
|
st4PhaseBranchCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..12)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of branches downstream from the phase."
|
|
::= { st4PhaseConfigEntry 20 }
|
|
|
|
st4PhaseOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..128)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of outlets powered from the phase."
|
|
::= { st4PhaseConfigEntry 21 }
|
|
|
|
-- Phase Monitor Table
|
|
|
|
st4PhaseMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4PhaseMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase monitor table."
|
|
::= { st4Phases 3 }
|
|
|
|
st4PhaseMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4PhaseMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular phase."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
|
|
::= { st4PhaseMonitorTable 1 }
|
|
|
|
St4PhaseMonitorEntry ::= SEQUENCE {
|
|
st4PhaseState DeviceState,
|
|
st4PhaseStatus DeviceStatus,
|
|
st4PhaseVoltage Integer32,
|
|
st4PhaseVoltageStatus DeviceStatus,
|
|
st4PhaseVoltageDeviation Integer32,
|
|
st4PhaseCurrent Integer32,
|
|
st4PhaseCurrentCrestFactor Integer32,
|
|
st4PhaseActivePower Integer32,
|
|
st4PhaseApparentPower Integer32,
|
|
st4PhasePowerFactor Integer32,
|
|
st4PhasePowerFactorStatus DeviceStatus,
|
|
st4PhaseReactance Integer32,
|
|
st4PhaseEnergy Integer32
|
|
}
|
|
|
|
st4PhaseState OBJECT-TYPE
|
|
SYNTAX DeviceState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The on/off state of the phase."
|
|
::= { st4PhaseMonitorEntry 1 }
|
|
|
|
st4PhaseStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the phase."
|
|
::= { st4PhaseMonitorEntry 2 }
|
|
|
|
st4PhaseVoltage OBJECT-TYPE
|
|
SYNTAX Integer32(-1..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured voltage on the phase in tenth Volts."
|
|
::= { st4PhaseMonitorEntry 3 }
|
|
|
|
st4PhaseVoltageStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured voltage on the phase."
|
|
::= { st4PhaseMonitorEntry 4 }
|
|
|
|
st4PhaseVoltageDeviation OBJECT-TYPE
|
|
SYNTAX Integer32(-1000..1000)
|
|
UNITS "tenth percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The deviation from the nominal voltage on the phase in tenth
|
|
percent."
|
|
::= { st4PhaseMonitorEntry 5 }
|
|
|
|
st4PhaseCurrent OBJECT-TYPE
|
|
SYNTAX Integer32(-1..30000)
|
|
UNITS "hundredth Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured current on the phase in hundredth Amps."
|
|
::= { st4PhaseMonitorEntry 6 }
|
|
|
|
st4PhaseCurrentCrestFactor OBJECT-TYPE
|
|
SYNTAX Integer32(-1..250)
|
|
UNITS "tenths"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured crest factor of the current waveform on the phase in
|
|
tenths."
|
|
::= { st4PhaseMonitorEntry 7 }
|
|
|
|
st4PhaseActivePower OBJECT-TYPE
|
|
SYNTAX Integer32(-1..25000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured active power on the phase in Watts."
|
|
::= { st4PhaseMonitorEntry 8 }
|
|
|
|
st4PhaseApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32(-1..25000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured apparent power on the phase in Volt-Amps."
|
|
::= { st4PhaseMonitorEntry 9 }
|
|
|
|
st4PhasePowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32(-1..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured power factor on the phase in hundredths."
|
|
::= { st4PhaseMonitorEntry 10 }
|
|
|
|
st4PhasePowerFactorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured power factor on the phase."
|
|
::= { st4PhaseMonitorEntry 11 }
|
|
|
|
st4PhaseReactance OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
capacitive(1),
|
|
inductive(2),
|
|
resistive(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured reactance of the phase."
|
|
::= { st4PhaseMonitorEntry 12 }
|
|
|
|
st4PhaseEnergy OBJECT-TYPE
|
|
SYNTAX Integer32(-1..2147483647)
|
|
UNITS "tenth Kilowatt-Hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total energy consumption of loads through the phase in tenth
|
|
Kilowatt-Hours."
|
|
::= { st4PhaseMonitorEntry 13 }
|
|
|
|
-- Phase Event Configuration Table
|
|
|
|
st4PhaseEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4PhaseEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase event configuration table."
|
|
::= { st4Phases 4 }
|
|
|
|
st4PhaseEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4PhaseEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular phase."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4PhaseIndex }
|
|
::= { st4PhaseEventConfigTable 1 }
|
|
|
|
St4PhaseEventConfigEntry ::= SEQUENCE {
|
|
st4PhaseNotifications EventNotificationMethods,
|
|
st4PhaseVoltageLowAlarm Integer32,
|
|
st4PhaseVoltageLowWarning Integer32,
|
|
st4PhaseVoltageHighWarning Integer32,
|
|
st4PhaseVoltageHighAlarm Integer32,
|
|
st4PhasePowerFactorLowAlarm Integer32,
|
|
st4PhasePowerFactorLowWarning Integer32
|
|
}
|
|
|
|
st4PhaseNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for phase events."
|
|
::= { st4PhaseEventConfigEntry 1 }
|
|
|
|
st4PhaseVoltageLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low alarm threshold of the phase in tenth Volts."
|
|
::= { st4PhaseEventConfigEntry 2 }
|
|
|
|
st4PhaseVoltageLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low warning threshold of the phase in tenth Volts."
|
|
::= { st4PhaseEventConfigEntry 3 }
|
|
|
|
st4PhaseVoltageHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high warning threshold of the phase in tenth Volts."
|
|
::= { st4PhaseEventConfigEntry 4 }
|
|
|
|
st4PhaseVoltageHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high alarm threshold of the phase in tenth Volts."
|
|
::= { st4PhaseEventConfigEntry 5 }
|
|
|
|
st4PhasePowerFactorLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low power factor alarm threshold of the phase in hundredths."
|
|
::= { st4PhaseEventConfigEntry 6 }
|
|
|
|
st4PhasePowerFactorLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low power factor warning threshold of the phase in
|
|
hundredths."
|
|
::= { st4PhaseEventConfigEntry 7 }
|
|
|
|
-- Over-Current Protectors
|
|
|
|
st4OverCurrentProtectors OBJECT IDENTIFIER ::= { st4Objects 6 }
|
|
|
|
-- Over-Current Protector Common Configuration
|
|
|
|
st4OcpCommonConfig OBJECT IDENTIFIER ::= { st4OverCurrentProtectors 1 }
|
|
|
|
-- Over-Current Protector Configuration Table
|
|
|
|
st4OcpConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4OcpConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over-current protector configuration table."
|
|
::= { st4OverCurrentProtectors 2 }
|
|
|
|
st4OcpConfigEntry OBJECT-TYPE
|
|
SYNTAX St4OcpConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular over-current protector."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
|
|
::= { st4OcpConfigTable 1 }
|
|
|
|
St4OcpConfigEntry ::= SEQUENCE {
|
|
st4OcpIndex Integer32,
|
|
st4OcpID DisplayString,
|
|
st4OcpLabel DisplayString,
|
|
st4OcpType INTEGER,
|
|
st4OcpCurrentCapacity Integer32,
|
|
st4OcpCurrentCapacityMax Integer32,
|
|
st4OcpBranchCount Integer32,
|
|
st4OcpOutletCount Integer32
|
|
}
|
|
|
|
st4OcpIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..64)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over-current protector index."
|
|
::= { st4OcpConfigEntry 1 }
|
|
|
|
st4OcpID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the over-current protector. Format=AAN[N]."
|
|
::= { st4OcpConfigEntry 2 }
|
|
|
|
st4OcpLabel OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system label assigned to the over-current protector for
|
|
identification."
|
|
::= { st4OcpConfigEntry 4 }
|
|
|
|
st4OcpType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
fuse(0),
|
|
breaker(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of over-current protector."
|
|
::= { st4OcpConfigEntry 6 }
|
|
|
|
st4OcpCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..125)
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user-configured current capacity of the over-current protector
|
|
in Amps."
|
|
::= { st4OcpConfigEntry 7 }
|
|
|
|
st4OcpCurrentCapacityMax OBJECT-TYPE
|
|
SYNTAX Integer32(0..125)
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The factory-set maximum allowed for the user-configured current
|
|
capacity of the over-current protector in Amps."
|
|
::= { st4OcpConfigEntry 8 }
|
|
|
|
st4OcpBranchCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..12)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of branches downstream from the over-current
|
|
protector."
|
|
::= { st4OcpConfigEntry 20 }
|
|
|
|
st4OcpOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..128)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of outlets powered from the over-current protector."
|
|
::= { st4OcpConfigEntry 21 }
|
|
|
|
-- Over-Current Protector Monitor Table
|
|
|
|
st4OcpMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4OcpMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over-current protector monitor table."
|
|
::= { st4OverCurrentProtectors 3 }
|
|
|
|
st4OcpMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4OcpMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular over-current protector."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
|
|
::= { st4OcpMonitorTable 1 }
|
|
|
|
St4OcpMonitorEntry ::= SEQUENCE {
|
|
st4OcpStatus DeviceStatus
|
|
}
|
|
|
|
st4OcpStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the over-current protector."
|
|
::= { st4OcpMonitorEntry 1 }
|
|
|
|
-- Over-Current Protector Event Configuration Table
|
|
|
|
st4OcpEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4OcpEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over-current protector event configuration table."
|
|
::= { st4OverCurrentProtectors 4 }
|
|
|
|
st4OcpEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4OcpEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular over-current
|
|
protector."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OcpIndex }
|
|
::= { st4OcpEventConfigTable 1 }
|
|
|
|
St4OcpEventConfigEntry ::= SEQUENCE {
|
|
st4OcpNotifications EventNotificationMethods
|
|
}
|
|
|
|
st4OcpNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for over-current protector
|
|
events."
|
|
::= { st4OcpEventConfigEntry 1 }
|
|
|
|
-- Branches
|
|
|
|
st4Branches OBJECT IDENTIFIER ::= { st4Objects 7 }
|
|
|
|
-- Branch Common Configuration
|
|
|
|
st4BranchCommonConfig OBJECT IDENTIFIER ::= { st4Branches 1 }
|
|
|
|
st4BranchCurrentHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current hysteresis of the branch in tenth Amps."
|
|
::= { st4BranchCommonConfig 1 }
|
|
|
|
-- Branch Configuration Table
|
|
|
|
st4BranchConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4BranchConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch configuration table."
|
|
::= { st4Branches 2 }
|
|
|
|
st4BranchConfigEntry OBJECT-TYPE
|
|
SYNTAX St4BranchConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular branch."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
|
|
::= { st4BranchConfigTable 1 }
|
|
|
|
St4BranchConfigEntry ::= SEQUENCE {
|
|
st4BranchIndex Integer32,
|
|
st4BranchID DisplayString,
|
|
st4BranchLabel DisplayString,
|
|
st4BranchCurrentCapacity Integer32,
|
|
st4BranchPhaseID DisplayString,
|
|
st4BranchOcpID DisplayString,
|
|
st4BranchOutletCount Integer32
|
|
}
|
|
|
|
st4BranchIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..64)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch index."
|
|
::= { st4BranchConfigEntry 1 }
|
|
|
|
st4BranchID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the branch. Format=AAN[N]."
|
|
::= { st4BranchConfigEntry 2 }
|
|
|
|
st4BranchLabel OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system label assigned to the branch for identification."
|
|
::= { st4BranchConfigEntry 4 }
|
|
|
|
st4BranchCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..125)
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current capacity of the branch in Amps."
|
|
::= { st4BranchConfigEntry 6 }
|
|
|
|
st4BranchPhaseID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the phase powering this branch.
|
|
Format=AAN."
|
|
::= { st4BranchConfigEntry 20 }
|
|
|
|
st4BranchOcpID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the over-current protector powering this
|
|
outlet. Format=AAN[N]."
|
|
::= { st4BranchConfigEntry 21 }
|
|
|
|
st4BranchOutletCount OBJECT-TYPE
|
|
SYNTAX Integer32(0..128)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of outlets powered from the branch."
|
|
::= { st4BranchConfigEntry 30 }
|
|
|
|
-- Branch Monitor Table
|
|
|
|
st4BranchMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4BranchMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch monitor table."
|
|
::= { st4Branches 3 }
|
|
|
|
st4BranchMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4BranchMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular branch."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
|
|
::= { st4BranchMonitorTable 1 }
|
|
|
|
St4BranchMonitorEntry ::= SEQUENCE {
|
|
st4BranchState DeviceState,
|
|
st4BranchStatus DeviceStatus,
|
|
st4BranchCurrent Integer32,
|
|
st4BranchCurrentStatus DeviceStatus,
|
|
st4BranchCurrentUtilized Integer32
|
|
}
|
|
|
|
st4BranchState OBJECT-TYPE
|
|
SYNTAX DeviceState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The on/off state of the branch."
|
|
::= { st4BranchMonitorEntry 1 }
|
|
|
|
st4BranchStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the branch."
|
|
::= { st4BranchMonitorEntry 2 }
|
|
|
|
st4BranchCurrent OBJECT-TYPE
|
|
SYNTAX Integer32(-1..12500)
|
|
UNITS "hundredth Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured current on the branch in hundredth Amps."
|
|
::= { st4BranchMonitorEntry 3 }
|
|
|
|
st4BranchCurrentStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured current on the branch."
|
|
::= { st4BranchMonitorEntry 4 }
|
|
|
|
st4BranchCurrentUtilized OBJECT-TYPE
|
|
SYNTAX Integer32(-1..1200)
|
|
UNITS "tenth percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of the branch current capacity used in tenth percent."
|
|
::= { st4BranchMonitorEntry 5 }
|
|
|
|
-- Branch Event Configuration Table
|
|
|
|
st4BranchEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4BranchEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch event configuration table."
|
|
::= { st4Branches 4 }
|
|
|
|
st4BranchEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4BranchEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular branch."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4BranchIndex }
|
|
::= { st4BranchEventConfigTable 1 }
|
|
|
|
St4BranchEventConfigEntry ::= SEQUENCE {
|
|
st4BranchNotifications EventNotificationMethods,
|
|
st4BranchCurrentLowAlarm Integer32,
|
|
st4BranchCurrentLowWarning Integer32,
|
|
st4BranchCurrentHighWarning Integer32,
|
|
st4BranchCurrentHighAlarm Integer32
|
|
}
|
|
|
|
st4BranchNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for branch events."
|
|
::= { st4BranchEventConfigEntry 1 }
|
|
|
|
st4BranchCurrentLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low alarm threshold of the branch in tenth Amps."
|
|
::= { st4BranchEventConfigEntry 2 }
|
|
|
|
st4BranchCurrentLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low warning threshold of the branch in tenth Amps."
|
|
::= { st4BranchEventConfigEntry 3 }
|
|
|
|
st4BranchCurrentHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high warning threshold of the branch in tenth Amps."
|
|
::= { st4BranchEventConfigEntry 4 }
|
|
|
|
st4BranchCurrentHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high alarm threshold of the branch in tenth Amps."
|
|
::= { st4BranchEventConfigEntry 5 }
|
|
|
|
-- Outlets
|
|
|
|
st4Outlets OBJECT IDENTIFIER ::= { st4Objects 8 }
|
|
|
|
-- Outlet Common Configuration
|
|
|
|
st4OutletCommonConfig OBJECT IDENTIFIER ::= { st4Outlets 1 }
|
|
|
|
st4OutletCurrentHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current hysteresis of the outlet in tenth Amps."
|
|
::= { st4OutletCommonConfig 1 }
|
|
|
|
st4OutletActivePowerHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..1000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power hysteresis of the outlet in Watts."
|
|
::= { st4OutletCommonConfig 2 }
|
|
|
|
st4OutletPowerFactorHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..20)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power factor hysteresis of the outlet in hundredths."
|
|
::= { st4OutletCommonConfig 3 }
|
|
|
|
st4OutletSequenceInterval OBJECT-TYPE
|
|
SYNTAX Integer32(0..15)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power-on sequencing interval for all outlets in seconds."
|
|
::= { st4OutletCommonConfig 10 }
|
|
|
|
st4OutletRebootDelay OBJECT-TYPE
|
|
SYNTAX Integer32(5..600)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reboot delay for all outlets in seconds."
|
|
::= { st4OutletCommonConfig 11 }
|
|
|
|
st4OutletStateChangeLogging OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enables or disables informational Outlet State Change event
|
|
logging."
|
|
::= { st4OutletCommonConfig 12 }
|
|
|
|
-- Outlet Configuration Table
|
|
|
|
st4OutletConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4OutletConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet configuration table."
|
|
::= { st4Outlets 2 }
|
|
|
|
st4OutletConfigEntry OBJECT-TYPE
|
|
SYNTAX St4OutletConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular outlet."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
|
::= { st4OutletConfigTable 1 }
|
|
|
|
St4OutletConfigEntry ::= SEQUENCE {
|
|
st4OutletIndex Integer32,
|
|
st4OutletID DisplayString,
|
|
st4OutletName DisplayString,
|
|
st4OutletCapabilities BITS,
|
|
st4OutletSocketType DisplayString,
|
|
st4OutletCurrentCapacity Integer32,
|
|
st4OutletPowerCapacity Integer32,
|
|
st4OutletWakeupState INTEGER,
|
|
st4OutletPostOnDelay Integer32,
|
|
st4OutletPhaseID DisplayString,
|
|
st4OutletOcpID DisplayString,
|
|
st4OutletBranchID DisplayString
|
|
}
|
|
|
|
st4OutletIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..128)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet index."
|
|
::= { st4OutletConfigEntry 1 }
|
|
|
|
st4OutletID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3..5))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the outlet. Format=AAN[N[N]]."
|
|
::= { st4OutletConfigEntry 2 }
|
|
|
|
st4OutletName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the outlet."
|
|
::= { st4OutletConfigEntry 3 }
|
|
|
|
st4OutletCapabilities OBJECT-TYPE
|
|
SYNTAX BITS {
|
|
switched(0), -- outlet supports power control
|
|
pops(1) -- outlet has pops
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The capabilities of the outlet."
|
|
::= { st4OutletConfigEntry 5 }
|
|
|
|
st4OutletSocketType OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The socket type of the outlet."
|
|
::= { st4OutletConfigEntry 6 }
|
|
|
|
st4OutletCurrentCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..125)
|
|
UNITS "Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current capacity of the outlet in Amps."
|
|
::= { st4OutletConfigEntry 7 }
|
|
|
|
st4OutletPowerCapacity OBJECT-TYPE
|
|
SYNTAX Integer32(0..10000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power capacity of the outlet in Volt-Amps. For DC products,
|
|
this is identical to power capacity in Watts."
|
|
::= { st4OutletConfigEntry 8 }
|
|
|
|
st4OutletWakeupState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(0),
|
|
off(1),
|
|
last(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The wakeup state of the outlet."
|
|
::= { st4OutletConfigEntry 20 }
|
|
|
|
st4OutletPostOnDelay OBJECT-TYPE
|
|
SYNTAX Integer32(0..900)
|
|
UNITS "seconds"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The post-on delay of the outlet in seconds."
|
|
::= { st4OutletConfigEntry 21 }
|
|
|
|
st4OutletPhaseID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the phase powering this outlet.
|
|
Format=AAN."
|
|
::= { st4OutletConfigEntry 30 }
|
|
|
|
st4OutletOcpID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the over-current protector powering this
|
|
outlet. Format=AAN[N]."
|
|
::= { st4OutletConfigEntry 31 }
|
|
|
|
st4OutletBranchID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(3..4))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the branch powering this outlet.
|
|
Format=AAN[N]."
|
|
::= { st4OutletConfigEntry 32 }
|
|
|
|
-- Outlet Monitor Table
|
|
|
|
st4OutletMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4OutletMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet monitor table."
|
|
::= { st4Outlets 3 }
|
|
|
|
st4OutletMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4OutletMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular outlet."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
|
::= { st4OutletMonitorTable 1 }
|
|
|
|
St4OutletMonitorEntry ::= SEQUENCE {
|
|
st4OutletState DeviceState,
|
|
st4OutletStatus DeviceStatus,
|
|
st4OutletCurrent Integer32,
|
|
st4OutletCurrentStatus DeviceStatus,
|
|
st4OutletCurrentUtilized Integer32,
|
|
st4OutletVoltage Integer32,
|
|
st4OutletActivePower Integer32,
|
|
st4OutletActivePowerStatus DeviceStatus,
|
|
st4OutletApparentPower Integer32,
|
|
st4OutletPowerFactor Integer32,
|
|
st4OutletPowerFactorStatus DeviceStatus,
|
|
st4OutletCurrentCrestFactor Integer32,
|
|
st4OutletReactance INTEGER,
|
|
st4OutletEnergy Integer32
|
|
}
|
|
|
|
st4OutletState OBJECT-TYPE
|
|
SYNTAX DeviceState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The on/off state of the outlet."
|
|
::= { st4OutletMonitorEntry 1 }
|
|
|
|
st4OutletStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the outlet."
|
|
::= { st4OutletMonitorEntry 2 }
|
|
|
|
st4OutletCurrent OBJECT-TYPE
|
|
SYNTAX Integer32(-1..12500)
|
|
UNITS "hundredth Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured current on the outlet in hundredth Amps."
|
|
::= { st4OutletMonitorEntry 3 }
|
|
|
|
st4OutletCurrentStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured current on the outlet."
|
|
::= { st4OutletMonitorEntry 4 }
|
|
|
|
st4OutletCurrentUtilized OBJECT-TYPE
|
|
SYNTAX Integer32(-1..1200)
|
|
UNITS "tenth percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The amount of the outlet current capacity used in tenth percent."
|
|
::= { st4OutletMonitorEntry 5 }
|
|
|
|
st4OutletVoltage OBJECT-TYPE
|
|
SYNTAX Integer32(-1..6000)
|
|
UNITS "tenth Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured voltage of the outlet in tenth Volts."
|
|
::= { st4OutletMonitorEntry 6 }
|
|
|
|
st4OutletActivePower OBJECT-TYPE
|
|
SYNTAX Integer32(-1..10000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured active power of the outlet in Watts."
|
|
::= { st4OutletMonitorEntry 7 }
|
|
|
|
st4OutletActivePowerStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured active power of the outlet."
|
|
::= { st4OutletMonitorEntry 8 }
|
|
|
|
st4OutletApparentPower OBJECT-TYPE
|
|
SYNTAX Integer32(-1..10000)
|
|
UNITS "Volt-Amps"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured apparent power of the outlet in Volt-Amps."
|
|
::= { st4OutletMonitorEntry 9 }
|
|
|
|
st4OutletPowerFactor OBJECT-TYPE
|
|
SYNTAX Integer32(-1..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured power factor of the outlet in hundredths."
|
|
::= { st4OutletMonitorEntry 10 }
|
|
|
|
st4OutletPowerFactorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured power factor of the outlet."
|
|
::= { st4OutletMonitorEntry 11 }
|
|
|
|
st4OutletCurrentCrestFactor OBJECT-TYPE
|
|
SYNTAX Integer32(-1..250)
|
|
UNITS "tenths"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured crest factor of the outlet in tenths."
|
|
::= { st4OutletMonitorEntry 12 }
|
|
|
|
st4OutletReactance OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
capacitive(1),
|
|
inductive(2),
|
|
resistive(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the measured reactance of the outlet."
|
|
::= { st4OutletMonitorEntry 13 }
|
|
|
|
st4OutletEnergy OBJECT-TYPE
|
|
SYNTAX Integer32(-1..2147483647)
|
|
UNITS "Watt-Hours"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total energy consumption of the device plugged into the outlet
|
|
in Watt-Hours."
|
|
::= { st4OutletMonitorEntry 14 }
|
|
|
|
-- Outlet Event Configuration Table
|
|
|
|
st4OutletEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4OutletEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet event configuration table."
|
|
::= { st4Outlets 4 }
|
|
|
|
st4OutletEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4OutletEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular outlet."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
|
::= { st4OutletEventConfigTable 1 }
|
|
|
|
St4OutletEventConfigEntry ::= SEQUENCE {
|
|
st4OutletNotifications EventNotificationMethods,
|
|
st4OutletCurrentLowAlarm Integer32,
|
|
st4OutletCurrentLowWarning Integer32,
|
|
st4OutletCurrentHighWarning Integer32,
|
|
st4OutletCurrentHighAlarm Integer32,
|
|
st4OutletActivePowerLowAlarm Integer32,
|
|
st4OutletActivePowerLowWarning Integer32,
|
|
st4OutletActivePowerHighWarning Integer32,
|
|
st4OutletActivePowerHighAlarm Integer32,
|
|
st4OutletPowerFactorLowAlarm Integer32,
|
|
st4OutletPowerFactorLowWarning Integer32
|
|
}
|
|
|
|
st4OutletNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for outlet events."
|
|
::= { st4OutletEventConfigEntry 1 }
|
|
|
|
st4OutletCurrentLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low alarm threshold of the outlet in tenth Amps."
|
|
::= { st4OutletEventConfigEntry 2 }
|
|
|
|
st4OutletCurrentLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current low warning threshold of the outlet in tenth Amps."
|
|
::= { st4OutletEventConfigEntry 3 }
|
|
|
|
st4OutletCurrentHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high warning threshold of the outlet in tenth Amps."
|
|
::= { st4OutletEventConfigEntry 4 }
|
|
|
|
st4OutletCurrentHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..1250)
|
|
UNITS "tenth Amps"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current high alarm threshold of the outlet in tenth Amps."
|
|
::= { st4OutletEventConfigEntry 5 }
|
|
|
|
st4OutletActivePowerLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..10000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power low alarm threshold of the outlet in Watts."
|
|
::= { st4OutletEventConfigEntry 6 }
|
|
|
|
st4OutletActivePowerLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..10000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power low warning threshold of the outlet in Watts."
|
|
::= { st4OutletEventConfigEntry 7 }
|
|
|
|
st4OutletActivePowerHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..10000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power high warning threshold of the outlet in Watts."
|
|
::= { st4OutletEventConfigEntry 8 }
|
|
|
|
st4OutletActivePowerHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..10000)
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The active power high alarm threshold of the outlet in Watts."
|
|
::= { st4OutletEventConfigEntry 9 }
|
|
|
|
st4OutletPowerFactorLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low power factor alarm threshold of the outlet in hundredths."
|
|
::= { st4OutletEventConfigEntry 10 }
|
|
|
|
st4OutletPowerFactorLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "hundredths"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low power factor warning threshold of the outlet in
|
|
hundredths."
|
|
::= { st4OutletEventConfigEntry 11 }
|
|
|
|
-- Outlet Control Table
|
|
|
|
st4OutletControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4OutletControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet control table."
|
|
::= { st4Outlets 5 }
|
|
|
|
st4OutletControlEntry OBJECT-TYPE
|
|
SYNTAX St4OutletControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects for control of a particular outlet."
|
|
INDEX { st4UnitIndex, st4InputCordIndex, st4OutletIndex }
|
|
::= { st4OutletControlTable 1 }
|
|
|
|
St4OutletControlEntry ::= SEQUENCE {
|
|
st4OutletControlState INTEGER,
|
|
st4OutletControlAction INTEGER
|
|
}
|
|
|
|
st4OutletControlState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
notSet(0), -- outlet state is unknown
|
|
fixedOn(1), -- outlet is uncontrolled (assumed on)
|
|
idleOff(2), -- outlet has defaulted to off state
|
|
idleOn(3), -- outlet has defaulted to on state
|
|
wakeOff(4), -- outlet has been set to off by wakeup
|
|
wakeOn(5), -- outlet has been set to on by wakeup
|
|
ocpOff(6), -- outlet is off due to OCP failure
|
|
ocpOn(7), -- outlet had OCP power loss
|
|
pendOn(8), -- outlet is off, but will be turning on
|
|
pendOff(9), -- outlet is on, but will be turning off
|
|
off(10), -- outlet was turned off by user
|
|
on(11), -- outlet was turned on by user or reboot event
|
|
reboot(12), -- outlet is preparing to turn on
|
|
shutdown(13), -- outlet is preparing to turn off
|
|
lockedOff(14), -- outlet was locked off by admin
|
|
lockedOn(15), -- outlet was locked on by admin
|
|
eventOff(16), -- outlet was turned off by an event
|
|
eventOn(17), -- outlet was turned on by an event
|
|
eventReboot(18), -- outlet rebooting due to an event
|
|
eventShutdown(19) -- outlet shutting down due to an event
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The control state of the outlet."
|
|
::= { st4OutletControlEntry 1 }
|
|
|
|
st4OutletControlAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
on(1),
|
|
off(2),
|
|
reboot(3),
|
|
queueOn(4),
|
|
queueOff(5),
|
|
queueReboot(6)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An action to change the control state of the outlet, or to queue
|
|
an action."
|
|
::= { st4OutletControlEntry 2 }
|
|
|
|
-- Outlet Common Control
|
|
|
|
st4OutletCommonControl OBJECT IDENTIFIER ::= { st4Outlets 6 }
|
|
|
|
st4OutletQueueControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
clear(0),
|
|
commit(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An action to clear or commit queued outlet control actions. A
|
|
read of this object returns clear(0) if queue is empty, and
|
|
commit(1) if the queue is not empty."
|
|
::= { st4OutletCommonControl 1 }
|
|
|
|
-- Temperature Sensors
|
|
|
|
st4TemperatureSensors OBJECT IDENTIFIER ::= { st4Objects 9 }
|
|
|
|
-- Temperature Sensor Common Configuration
|
|
|
|
st4TempSensorCommonConfig OBJECT IDENTIFIER ::= { st4TemperatureSensors 1 }
|
|
|
|
st4TempSensorHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..54)
|
|
UNITS "degrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature hysteresis of the sensor in degrees, using the
|
|
scale selected by st4TempSensorScale."
|
|
::= { st4TempSensorCommonConfig 1 }
|
|
|
|
st4TempSensorScale OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
celsius(0),
|
|
fahrenheit(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current scale used for all temperature values."
|
|
::= { st4TempSensorCommonConfig 10 }
|
|
|
|
-- Temperature Sensor Configuration Table
|
|
|
|
st4TempSensorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4TempSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor configuration table."
|
|
::= { st4TemperatureSensors 2 }
|
|
|
|
st4TempSensorConfigEntry OBJECT-TYPE
|
|
SYNTAX St4TempSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular temperature sensor."
|
|
INDEX { st4UnitIndex, st4TempSensorIndex }
|
|
::= { st4TempSensorConfigTable 1 }
|
|
|
|
St4TempSensorConfigEntry ::= SEQUENCE {
|
|
st4TempSensorIndex Integer32,
|
|
st4TempSensorID DisplayString,
|
|
st4TempSensorName DisplayString,
|
|
st4TempSensorValueMin Integer32,
|
|
st4TempSensorValueMax Integer32
|
|
}
|
|
|
|
st4TempSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..2)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor index."
|
|
::= { st4TempSensorConfigEntry 1 }
|
|
|
|
st4TempSensorID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(2))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the temperature sensor. Format=AN."
|
|
::= { st4TempSensorConfigEntry 2 }
|
|
|
|
st4TempSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the temperature sensor."
|
|
::= { st4TempSensorConfigEntry 3 }
|
|
|
|
st4TempSensorValueMin OBJECT-TYPE
|
|
SYNTAX Integer32(-40..253)
|
|
UNITS "degrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The minimum temperature limit of the sensor in degrees, using the
|
|
scale selected by st4TempSensorScale."
|
|
::= { st4TempSensorConfigEntry 4 }
|
|
|
|
st4TempSensorValueMax OBJECT-TYPE
|
|
SYNTAX Integer32(-40..253)
|
|
UNITS "degrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum temperature limit of the sensor in degrees, using the
|
|
scale selected by st4TempSensorScale."
|
|
::= { st4TempSensorConfigEntry 5 }
|
|
|
|
-- Temperature Sensor Monitor Table
|
|
|
|
st4TempSensorMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4TempSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor monitor table."
|
|
::= { st4TemperatureSensors 3 }
|
|
|
|
st4TempSensorMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4TempSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular temperature sensor."
|
|
INDEX { st4UnitIndex, st4TempSensorIndex }
|
|
::= { st4TempSensorMonitorTable 1 }
|
|
|
|
St4TempSensorMonitorEntry ::= SEQUENCE {
|
|
st4TempSensorValue Integer32,
|
|
st4TempSensorStatus DeviceStatus
|
|
}
|
|
|
|
st4TempSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32(-410..2540)
|
|
UNITS "tenth degrees"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured temperature on the sensor in tenth degrees using the
|
|
scale selected by st4TempSensorScale. -410 means the temperature
|
|
reading is invalid."
|
|
::= { st4TempSensorMonitorEntry 1 }
|
|
|
|
st4TempSensorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the temperature sensor."
|
|
::= { st4TempSensorMonitorEntry 2 }
|
|
|
|
-- Temperature Sensor Event Configuration Table
|
|
|
|
st4TempSensorEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4TempSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor event configuration table."
|
|
::= { st4TemperatureSensors 4 }
|
|
|
|
st4TempSensorEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4TempSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular temperature sensor."
|
|
INDEX { st4UnitIndex, st4TempSensorIndex }
|
|
::= { st4TempSensorEventConfigTable 1 }
|
|
|
|
St4TempSensorEventConfigEntry ::= SEQUENCE {
|
|
st4TempSensorNotifications EventNotificationMethods,
|
|
st4TempSensorLowAlarm Integer32,
|
|
st4TempSensorLowWarning Integer32,
|
|
st4TempSensorHighWarning Integer32,
|
|
st4TempSensorHighAlarm Integer32
|
|
}
|
|
|
|
st4TempSensorNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for temperature sensor events."
|
|
::= { st4TempSensorEventConfigEntry 1 }
|
|
|
|
st4TempSensorLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(-40..253)
|
|
UNITS "degrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low alarm threshold of the temperature sensor in degrees."
|
|
::= { st4TempSensorEventConfigEntry 2 }
|
|
|
|
st4TempSensorLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(-40..253)
|
|
UNITS "degrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low warning threshold of the temperature sensor in degrees."
|
|
::= { st4TempSensorEventConfigEntry 3 }
|
|
|
|
st4TempSensorHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(-40..253)
|
|
UNITS "degrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high warning threshold of the temperature sensor in degrees."
|
|
::= { st4TempSensorEventConfigEntry 4 }
|
|
|
|
st4TempSensorHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(-40..253)
|
|
UNITS "degrees"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high alarm threshold of the temperature sensor in degrees."
|
|
::= { st4TempSensorEventConfigEntry 5 }
|
|
|
|
-- Humidity Sensors
|
|
|
|
st4HumiditySensors OBJECT IDENTIFIER ::= { st4Objects 10 }
|
|
|
|
-- Humidity Sensor Common Configuration
|
|
|
|
st4HumidSensorCommonConfig OBJECT IDENTIFIER ::= { st4HumiditySensors 1 }
|
|
|
|
st4HumidSensorHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..20)
|
|
UNITS "percentage relative humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity hysteresis of the sensor in percent relative
|
|
humidity."
|
|
::= { st4HumidSensorCommonConfig 1 }
|
|
|
|
-- Humidity Sensor Configuration Table
|
|
|
|
st4HumidSensorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4HumidSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity sensor configuration table."
|
|
::= { st4HumiditySensors 2 }
|
|
|
|
st4HumidSensorConfigEntry OBJECT-TYPE
|
|
SYNTAX St4HumidSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular humidity sensor."
|
|
INDEX { st4UnitIndex, st4HumidSensorIndex }
|
|
::= { st4HumidSensorConfigTable 1 }
|
|
|
|
St4HumidSensorConfigEntry ::= SEQUENCE {
|
|
st4HumidSensorIndex Integer32,
|
|
st4HumidSensorID DisplayString,
|
|
st4HumidSensorName DisplayString
|
|
}
|
|
|
|
st4HumidSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..2)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity sensor index."
|
|
::= { st4HumidSensorConfigEntry 1 }
|
|
|
|
st4HumidSensorID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(2))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the humidity sensor. Format=AN."
|
|
::= { st4HumidSensorConfigEntry 2 }
|
|
|
|
st4HumidSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the humidity sensor."
|
|
::= { st4HumidSensorConfigEntry 3 }
|
|
|
|
-- Humidity Sensor Monitor Table
|
|
|
|
st4HumidSensorMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4HumidSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity sensor monitor table."
|
|
::= { st4HumiditySensors 3 }
|
|
|
|
st4HumidSensorMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4HumidSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular humidity sensor."
|
|
INDEX { st4UnitIndex, st4HumidSensorIndex }
|
|
::= { st4HumidSensorMonitorTable 1 }
|
|
|
|
St4HumidSensorMonitorEntry ::= SEQUENCE {
|
|
st4HumidSensorValue Integer32,
|
|
st4HumidSensorStatus DeviceStatus
|
|
}
|
|
|
|
st4HumidSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32(-1..100)
|
|
UNITS "percentage relative humidity"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured humidity on the sensor in percentage relative
|
|
humidity."
|
|
::= { st4HumidSensorMonitorEntry 1 }
|
|
|
|
st4HumidSensorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the humidity sensor."
|
|
::= { st4HumidSensorMonitorEntry 2 }
|
|
|
|
-- Humidity Sensor Event Configuration Table
|
|
|
|
st4HumidSensorEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4HumidSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity sensor event configuration table."
|
|
::= { st4HumiditySensors 4 }
|
|
|
|
st4HumidSensorEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4HumidSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular humidity sensor."
|
|
INDEX { st4UnitIndex, st4HumidSensorIndex }
|
|
::= { st4HumidSensorEventConfigTable 1 }
|
|
|
|
St4HumidSensorEventConfigEntry ::= SEQUENCE {
|
|
st4HumidSensorNotifications EventNotificationMethods,
|
|
st4HumidSensorLowAlarm Integer32,
|
|
st4HumidSensorLowWarning Integer32,
|
|
st4HumidSensorHighWarning Integer32,
|
|
st4HumidSensorHighAlarm Integer32
|
|
}
|
|
|
|
st4HumidSensorNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for humidity sensor events."
|
|
::= { st4HumidSensorEventConfigEntry 1 }
|
|
|
|
st4HumidSensorLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "percentage relative humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low alarm threshold of the humidity sensor in percentage
|
|
relative humidity."
|
|
::= { st4HumidSensorEventConfigEntry 2 }
|
|
|
|
st4HumidSensorLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "percentage relative humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low warning threshold of the humidity sensor in percentage
|
|
relative humidity."
|
|
::= { st4HumidSensorEventConfigEntry 3 }
|
|
|
|
st4HumidSensorHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "percentage relative humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high warning threshold of the humidity sensor in percentage
|
|
relative humidity."
|
|
::= { st4HumidSensorEventConfigEntry 4 }
|
|
|
|
st4HumidSensorHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..100)
|
|
UNITS "percentage relative humidity"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high alarm threshold of the humidity sensor in percentage
|
|
relative humidity."
|
|
::= { st4HumidSensorEventConfigEntry 5 }
|
|
|
|
-- Water Sensors
|
|
|
|
st4WaterSensors OBJECT IDENTIFIER ::= { st4Objects 11 }
|
|
|
|
-- Water Sensor Common Configuration
|
|
|
|
st4WaterSensorCommonConfig OBJECT IDENTIFIER ::= { st4WaterSensors 1 }
|
|
|
|
-- Water Sensor Configuration Table
|
|
|
|
st4WaterSensorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4WaterSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water sensor configuration table."
|
|
::= { st4WaterSensors 2 }
|
|
|
|
st4WaterSensorConfigEntry OBJECT-TYPE
|
|
SYNTAX St4WaterSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular water sensor."
|
|
INDEX { st4UnitIndex, st4WaterSensorIndex }
|
|
::= { st4WaterSensorConfigTable 1 }
|
|
|
|
St4WaterSensorConfigEntry ::= SEQUENCE {
|
|
st4WaterSensorIndex Integer32,
|
|
st4WaterSensorID DisplayString,
|
|
st4WaterSensorName DisplayString
|
|
}
|
|
|
|
st4WaterSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..1)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water sensor index."
|
|
::= { st4WaterSensorConfigEntry 1 }
|
|
|
|
st4WaterSensorID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(2))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the water sensor. Format=AN."
|
|
::= { st4WaterSensorConfigEntry 2 }
|
|
|
|
st4WaterSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the water sensor."
|
|
::= { st4WaterSensorConfigEntry 3 }
|
|
|
|
-- Water Sensor Monitor Table
|
|
|
|
st4WaterSensorMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4WaterSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water sensor monitor table."
|
|
::= { st4WaterSensors 3 }
|
|
|
|
st4WaterSensorMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4WaterSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular water sensor."
|
|
INDEX { st4UnitIndex, st4WaterSensorIndex }
|
|
::= { st4WaterSensorMonitorTable 1 }
|
|
|
|
St4WaterSensorMonitorEntry ::= SEQUENCE {
|
|
st4WaterSensorStatus DeviceStatus
|
|
}
|
|
|
|
st4WaterSensorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the water sensor."
|
|
::= { st4WaterSensorMonitorEntry 1 }
|
|
|
|
-- Water Sensor Event Configuration Table
|
|
|
|
st4WaterSensorEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4WaterSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water sensor event configuration table."
|
|
::= { st4WaterSensors 4 }
|
|
|
|
st4WaterSensorEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4WaterSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular water sensor."
|
|
INDEX { st4UnitIndex, st4WaterSensorIndex }
|
|
::= { st4WaterSensorEventConfigTable 1 }
|
|
|
|
St4WaterSensorEventConfigEntry ::= SEQUENCE {
|
|
st4WaterSensorNotifications EventNotificationMethods
|
|
}
|
|
|
|
st4WaterSensorNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for water sensor events."
|
|
::= { st4WaterSensorEventConfigEntry 1 }
|
|
|
|
-- Contact Closures Sensors
|
|
|
|
st4ContactClosureSensors OBJECT IDENTIFIER ::= { st4Objects 12 }
|
|
|
|
-- Contact Closure Sensor Common Configuration
|
|
|
|
st4CcSensorCommonConfig OBJECT IDENTIFIER ::= { st4ContactClosureSensors 1 }
|
|
|
|
-- Contact Closure Sensor Configuration Table
|
|
|
|
st4CcSensorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4CcSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact closure sensor configuration table."
|
|
::= { st4ContactClosureSensors 2 }
|
|
|
|
st4CcSensorConfigEntry OBJECT-TYPE
|
|
SYNTAX St4CcSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular contact closure sensor."
|
|
INDEX { st4UnitIndex, st4CcSensorIndex }
|
|
::= { st4CcSensorConfigTable 1 }
|
|
|
|
St4CcSensorConfigEntry ::= SEQUENCE {
|
|
st4CcSensorIndex Integer32,
|
|
st4CcSensorID DisplayString,
|
|
st4CcSensorName DisplayString
|
|
}
|
|
|
|
st4CcSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact closure sensor index."
|
|
::= { st4CcSensorConfigEntry 1 }
|
|
|
|
st4CcSensorID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(2))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the contact closure sensor. Format=AN."
|
|
::= { st4CcSensorConfigEntry 2 }
|
|
|
|
st4CcSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the contact closure sensor."
|
|
::= { st4CcSensorConfigEntry 3 }
|
|
|
|
-- Contact Closure Sensor Monitor Table
|
|
|
|
st4CcSensorMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4CcSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact closure sensor monitor table."
|
|
::= { st4ContactClosureSensors 3 }
|
|
|
|
st4CcSensorMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4CcSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular contact closure sensor."
|
|
INDEX { st4UnitIndex, st4CcSensorIndex }
|
|
::= { st4CcSensorMonitorTable 1 }
|
|
|
|
St4CcSensorMonitorEntry ::= SEQUENCE {
|
|
st4CcSensorStatus DeviceStatus
|
|
}
|
|
|
|
st4CcSensorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the contact closure."
|
|
::= { st4CcSensorMonitorEntry 1 }
|
|
|
|
-- Contact Closure Sensor Event Configuration Table
|
|
|
|
st4CcSensorEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4CcSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact closure sensor event configuration table."
|
|
::= { st4ContactClosureSensors 4 }
|
|
|
|
st4CcSensorEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4CcSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular contact closure
|
|
sensor."
|
|
INDEX { st4UnitIndex, st4CcSensorIndex }
|
|
::= { st4CcSensorEventConfigTable 1 }
|
|
|
|
St4CcSensorEventConfigEntry ::= SEQUENCE {
|
|
st4CcSensorNotifications EventNotificationMethods
|
|
}
|
|
|
|
st4CcSensorNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for contact closure sensor
|
|
events."
|
|
::= { st4CcSensorEventConfigEntry 1 }
|
|
|
|
-- Analog-to-Digital Converter Sensors
|
|
|
|
st4AnalogToDigitalConvSensors OBJECT IDENTIFIER ::= { st4Objects 13 }
|
|
|
|
-- Analog-to-Digital Converter Sensor Common Configuration
|
|
|
|
st4AdcSensorCommonConfig OBJECT IDENTIFIER ::= { st4AnalogToDigitalConvSensors 1 }
|
|
|
|
st4AdcSensorHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..20)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8-bit count hysteresis of the analog-to-digital converter
|
|
sensor."
|
|
::= { st4AdcSensorCommonConfig 1 }
|
|
|
|
-- Analog-to-Digital Converter Sensor Configuration Table
|
|
|
|
st4AdcSensorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4AdcSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog-to-digital converter sensor configuration table."
|
|
::= { st4AnalogToDigitalConvSensors 2 }
|
|
|
|
st4AdcSensorConfigEntry OBJECT-TYPE
|
|
SYNTAX St4AdcSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular analog-to-digital
|
|
converter sensor."
|
|
INDEX { st4UnitIndex, st4AdcSensorIndex }
|
|
::= { st4AdcSensorConfigTable 1 }
|
|
|
|
St4AdcSensorConfigEntry ::= SEQUENCE {
|
|
st4AdcSensorIndex Integer32,
|
|
st4AdcSensorID DisplayString,
|
|
st4AdcSensorName DisplayString
|
|
}
|
|
|
|
st4AdcSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..1)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog-to-digital converter sensor index."
|
|
::= { st4AdcSensorConfigEntry 1 }
|
|
|
|
st4AdcSensorID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(2))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the analog-to-digital converter sensor.
|
|
Format=AN."
|
|
::= { st4AdcSensorConfigEntry 2 }
|
|
|
|
st4AdcSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the analog-to-digital converter sensor."
|
|
::= { st4AdcSensorConfigEntry 3 }
|
|
|
|
-- Analog-to-Digital Converter Sensor Monitor Table
|
|
|
|
st4AdcSensorMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4AdcSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog-to-digital converter sensor monitor table."
|
|
::= { st4AnalogToDigitalConvSensors 3 }
|
|
|
|
st4AdcSensorMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4AdcSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular analog-to-digital converter
|
|
sensor."
|
|
INDEX { st4UnitIndex, st4AdcSensorIndex }
|
|
::= { st4AdcSensorMonitorTable 1 }
|
|
|
|
St4AdcSensorMonitorEntry ::= SEQUENCE {
|
|
st4AdcSensorValue Integer32,
|
|
st4AdcSensorStatus DeviceStatus
|
|
}
|
|
|
|
st4AdcSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32(-1..255)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8-bit value from the analog-to-digital converter sensor."
|
|
::= { st4AdcSensorMonitorEntry 1 }
|
|
|
|
st4AdcSensorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the analog-to-digital converter sensor."
|
|
::= { st4AdcSensorMonitorEntry 2 }
|
|
|
|
-- Analog-to-Digital Converter Sensor Event Configuration Table
|
|
|
|
st4AdcSensorEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4AdcSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog-to-digital converter sensor event configuration table."
|
|
::= { st4AnalogToDigitalConvSensors 4 }
|
|
|
|
st4AdcSensorEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4AdcSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular
|
|
analog-to-digital converter sensor."
|
|
INDEX { st4UnitIndex, st4AdcSensorIndex }
|
|
::= { st4AdcSensorEventConfigTable 1 }
|
|
|
|
St4AdcSensorEventConfigEntry ::= SEQUENCE {
|
|
st4AdcSensorNotifications EventNotificationMethods,
|
|
st4AdcSensorLowAlarm Integer32,
|
|
st4AdcSensorLowWarning Integer32,
|
|
st4AdcSensorHighWarning Integer32,
|
|
st4AdcSensorHighAlarm Integer32
|
|
}
|
|
|
|
st4AdcSensorNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for analog-to-digital converter
|
|
sensor events."
|
|
::= { st4AdcSensorEventConfigEntry 1 }
|
|
|
|
st4AdcSensorLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8-bit value for the low alarm threshold of the
|
|
analog-to-digital converter sensor."
|
|
::= { st4AdcSensorEventConfigEntry 2 }
|
|
|
|
st4AdcSensorLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8-bit value for the low warning threshold of the
|
|
analog-to-digital converter sensor."
|
|
::= { st4AdcSensorEventConfigEntry 3 }
|
|
|
|
st4AdcSensorHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8-bit value for the high warning threshold of the
|
|
analog-to-digital converter sensor."
|
|
::= { st4AdcSensorEventConfigEntry 4 }
|
|
|
|
st4AdcSensorHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..255)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8-bit value for the high alarm threshold of the
|
|
analog-to-digital converter sensor."
|
|
::= { st4AdcSensorEventConfigEntry 5 }
|
|
|
|
-- Fan Sensors
|
|
|
|
st4FanSensors OBJECT IDENTIFIER ::= { st4Objects 14 }
|
|
|
|
-- Fan Sensor Common Configuration
|
|
|
|
st4FanSensorCommonConfig OBJECT IDENTIFIER ::= { st4FanSensors 1 }
|
|
|
|
st4FanSensorHysteresis OBJECT-TYPE
|
|
SYNTAX Integer32(0..1200)
|
|
UNITS "rotations per minute"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan speed hysteresis of the sensor in rotations per minute."
|
|
::= { st4FanSensorCommonConfig 1 }
|
|
|
|
-- Fan Sensor Configuration Table
|
|
|
|
st4FanSensorConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4FanSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan sensor configuration table."
|
|
::= { st4FanSensors 2 }
|
|
|
|
st4FanSensorConfigEntry OBJECT-TYPE
|
|
SYNTAX St4FanSensorConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configuration objects for a particular fan sensor."
|
|
INDEX { st4UnitIndex, st4FanSensorIndex }
|
|
::= { st4FanSensorConfigTable 1 }
|
|
|
|
St4FanSensorConfigEntry ::= SEQUENCE {
|
|
st4FanSensorIndex Integer32,
|
|
st4FanSensorID DisplayString,
|
|
st4FanSensorName DisplayString
|
|
}
|
|
|
|
st4FanSensorIndex OBJECT-TYPE
|
|
SYNTAX Integer32(0..4)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan sensor index."
|
|
::= { st4FanSensorConfigEntry 1 }
|
|
|
|
st4FanSensorID OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(2))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal ID of the fan sensor. Format=AN."
|
|
::= { st4FanSensorConfigEntry 2 }
|
|
|
|
st4FanSensorName OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..32))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the fan sensor."
|
|
::= { st4FanSensorConfigEntry 3 }
|
|
|
|
-- Fan Sensor Monitor Table
|
|
|
|
st4FanSensorMonitorTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4FanSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan sensor monitor table."
|
|
::= { st4FanSensors 3 }
|
|
|
|
st4FanSensorMonitorEntry OBJECT-TYPE
|
|
SYNTAX St4FanSensorMonitorEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects to monitor for a particular fan sensor."
|
|
INDEX { st4UnitIndex, st4FanSensorIndex }
|
|
::= { st4FanSensorMonitorTable 1 }
|
|
|
|
St4FanSensorMonitorEntry ::= SEQUENCE {
|
|
st4FanSensorValue Integer32,
|
|
st4FanSensorStatus DeviceStatus
|
|
}
|
|
|
|
st4FanSensorValue OBJECT-TYPE
|
|
SYNTAX Integer32(-1..15300)
|
|
UNITS "rotations per minute"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured fan speed of the sensor in rotations per minute."
|
|
::= { st4FanSensorMonitorEntry 1 }
|
|
|
|
st4FanSensorStatus OBJECT-TYPE
|
|
SYNTAX DeviceStatus
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the fan sensor."
|
|
::= { st4FanSensorMonitorEntry 2 }
|
|
|
|
-- Fan Sensor Event Configuration Table
|
|
|
|
st4FanSensorEventConfigTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF St4FanSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan sensor event configuration table."
|
|
::= { st4FanSensors 4 }
|
|
|
|
st4FanSensorEventConfigEntry OBJECT-TYPE
|
|
SYNTAX St4FanSensorEventConfigEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event configuration objects for a particular fan sensor."
|
|
INDEX { st4UnitIndex, st4FanSensorIndex }
|
|
::= { st4FanSensorEventConfigTable 1 }
|
|
|
|
St4FanSensorEventConfigEntry ::= SEQUENCE {
|
|
st4FanSensorNotifications EventNotificationMethods,
|
|
st4FanSensorLowAlarm Integer32,
|
|
st4FanSensorLowWarning Integer32,
|
|
st4FanSensorHighWarning Integer32,
|
|
st4FanSensorHighAlarm Integer32
|
|
}
|
|
|
|
st4FanSensorNotifications OBJECT-TYPE
|
|
SYNTAX EventNotificationMethods
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The notification methods enabled for fan sensor events."
|
|
::= { st4FanSensorEventConfigEntry 1 }
|
|
|
|
st4FanSensorLowAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..15300)
|
|
UNITS "rotations per minute"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low alarm threshold of the fan sensor in rotations per
|
|
minute."
|
|
::= { st4FanSensorEventConfigEntry 2 }
|
|
|
|
st4FanSensorLowWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..15300)
|
|
UNITS "rotations per minute"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low warning threshold of the fan sensor in rotations per
|
|
minute."
|
|
::= { st4FanSensorEventConfigEntry 3 }
|
|
|
|
st4FanSensorHighWarning OBJECT-TYPE
|
|
SYNTAX Integer32(0..15300)
|
|
UNITS "rotations per minute"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high warning threshold of the fan sensor in rotations per
|
|
minute."
|
|
::= { st4FanSensorEventConfigEntry 4 }
|
|
|
|
st4FanSensorHighAlarm OBJECT-TYPE
|
|
SYNTAX Integer32(0..15300)
|
|
UNITS "rotations per minute"
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The high alarm threshold of the fan sensor in rotations per
|
|
minute."
|
|
::= { st4FanSensorEventConfigEntry 5 }
|
|
|
|
-- Event Information
|
|
|
|
st4EventInformation OBJECT IDENTIFIER ::= { st4Objects 99 }
|
|
|
|
st4EventStatusText OBJECT-TYPE
|
|
SYNTAX DisplayString(SIZE(0..20))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The text representation of the enumerated integer value of
|
|
the most-relevant status or state object included in a trap.
|
|
The value of this object is set only when sent with a trap.
|
|
A read of this object will return a NULL string."
|
|
::= { st4EventInformation 1 }
|
|
|
|
st4EventStatusCondition OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nonError(0),
|
|
error(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condition of the enumerated integer value of the status
|
|
object included in a trap. The value of this object is set
|
|
only when sent with a trap. A read of this object will
|
|
return zero."
|
|
::= { st4EventInformation 2 }
|
|
|
|
-- Notification Definitions
|
|
|
|
st4Notifications OBJECT IDENTIFIER ::= { sentry4 100 }
|
|
|
|
-- Events
|
|
|
|
st4Events OBJECT IDENTIFIER ::= { st4Notifications 0 }
|
|
-- The 0 is for V1 compatibility
|
|
|
|
st4UnitStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4UnitID,
|
|
st4UnitName,
|
|
st4UnitStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit status event."
|
|
--#TYPE "Sentry: Unit Status Event."
|
|
--#SUMMARY "Status of Unit '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 4 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 1 }
|
|
|
|
st4InputCordStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4InputCordID,
|
|
st4InputCordName,
|
|
st4InputCordState,
|
|
st4InputCordStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord status event."
|
|
--#TYPE "Sentry: Input Cord Status Event."
|
|
--#SUMMARY "Status of Input Cord '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 2 }
|
|
|
|
st4InputCordActivePowerEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4InputCordID,
|
|
st4InputCordName,
|
|
st4InputCordActivePower,
|
|
st4InputCordActivePowerStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord active power event."
|
|
--#TYPE "Sentry: Input Cord Active Power Event."
|
|
--#SUMMARY "Active Power Status of Input Cord '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 3 }
|
|
|
|
st4InputCordApparentPowerEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4InputCordID,
|
|
st4InputCordName,
|
|
st4InputCordApparentPower,
|
|
st4InputCordApparentPowerStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord apparent power event."
|
|
--#TYPE "Sentry: Input Cord Apparent Power Event."
|
|
--#SUMMARY "Apparent Power Status of Input Cord '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 4 }
|
|
|
|
st4InputCordPowerFactorEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4InputCordID,
|
|
st4InputCordName,
|
|
st4InputCordPowerFactor,
|
|
st4InputCordPowerFactorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord power factor event."
|
|
--#TYPE "Sentry: Input Cord Power Factor Event."
|
|
--#SUMMARY "Power Factor Status of Input Cord '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 5 }
|
|
|
|
st4InputCordOutOfBalanceEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4InputCordID,
|
|
st4InputCordName,
|
|
st4InputCordOutOfBalance,
|
|
st4InputCordOutOfBalanceStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord out-of-balance event."
|
|
--#TYPE "Sentry: Input Cord Out-of-Balance Event."
|
|
--#SUMMARY "Out-of-Balance Status of Input Cord '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 6 }
|
|
|
|
st4LineStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4LineID,
|
|
st4LineLabel,
|
|
st4LineState,
|
|
st4LineStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line status event."
|
|
--#TYPE "Sentry: Line Status Event."
|
|
--#SUMMARY "Status of Line '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 7 }
|
|
|
|
st4LineCurrentEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4LineID,
|
|
st4LineLabel,
|
|
st4LineCurrent,
|
|
st4LineCurrentStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line current event."
|
|
--#TYPE "Sentry: Line Current Event."
|
|
--#SUMMARY "Current Status of Line '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 8 }
|
|
|
|
st4PhaseStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4PhaseID,
|
|
st4PhaseLabel,
|
|
st4PhaseState,
|
|
st4PhaseStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase status event."
|
|
--#TYPE "Sentry: Phase Status Event."
|
|
--#SUMMARY "Status of Phase '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 9 }
|
|
|
|
st4PhaseVoltageEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4PhaseID,
|
|
st4PhaseLabel,
|
|
st4PhaseVoltage,
|
|
st4PhaseVoltageStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase voltage event."
|
|
--#TYPE "Sentry: Phase Voltage Event."
|
|
--#SUMMARY "Voltage Status of Phase '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 10 }
|
|
|
|
st4PhasePowerFactorEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4PhaseID,
|
|
st4PhaseLabel,
|
|
st4PhasePowerFactor,
|
|
st4PhasePowerFactorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase voltage event."
|
|
--#TYPE "Sentry: Phase Power Factor Event."
|
|
--#SUMMARY "Power Factor Status of Phase '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 11 }
|
|
|
|
st4OcpStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4OcpID,
|
|
st4OcpLabel,
|
|
st4OcpStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over-current protector status event."
|
|
--#TYPE "Sentry: Over-current Protector Status Event."
|
|
--#SUMMARY "Status of Over-current Protector '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 4 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 12 }
|
|
|
|
st4BranchStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4BranchID,
|
|
st4BranchLabel,
|
|
st4BranchState,
|
|
st4BranchStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch status event."
|
|
--#TYPE "Sentry: Branch Status Event."
|
|
--#SUMMARY "Status of Branch '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 13 }
|
|
|
|
st4BranchCurrentEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4BranchID,
|
|
st4BranchLabel,
|
|
st4BranchCurrent,
|
|
st4BranchCurrentStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch current event."
|
|
--#TYPE "Sentry: Branch Current Event."
|
|
--#SUMMARY "Current Status of Branch '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 14 }
|
|
|
|
st4OutletStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4OutletID,
|
|
st4OutletName,
|
|
st4OutletState,
|
|
st4OutletStatus,
|
|
st4OutletControlState,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet status event."
|
|
--#TYPE "Sentry: Outlet Status Event."
|
|
--#SUMMARY "Status of Outlet '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 6 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 15 }
|
|
|
|
st4OutletStateChangeEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4OutletID,
|
|
st4OutletName,
|
|
st4OutletState,
|
|
st4OutletStatus,
|
|
st4OutletControlState,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet state change event."
|
|
--#TYPE "Sentry: Outlet State Change Event."
|
|
--#SUMMARY "Outlet '%s' (%s) state has changed to '%s'."
|
|
--#ARGUMENTS { 2, 1, 6 }
|
|
--#SEVERITY INFORMATIONAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Information Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 16 }
|
|
|
|
st4OutletCurrentEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4OutletID,
|
|
st4OutletName,
|
|
st4OutletCurrent,
|
|
st4OutletCurrentStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet current event."
|
|
--#TYPE "Sentry: Outlet Current Event."
|
|
--#SUMMARY "Current Status of Outlet '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 17 }
|
|
|
|
st4OutletActivePowerEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4OutletID,
|
|
st4OutletName,
|
|
st4OutletActivePower,
|
|
st4OutletActivePowerStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet active power event."
|
|
--#TYPE "Sentry: Outlet Active Power Event."
|
|
--#SUMMARY "Active Power Status of Outlet '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 18 }
|
|
|
|
st4OutletPowerFactorEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4OutletID,
|
|
st4OutletName,
|
|
st4OutletPowerFactor,
|
|
st4OutletPowerFactorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet power factor event."
|
|
--#TYPE "Sentry: Outlet Power Factor Event."
|
|
--#SUMMARY "Power Factor Status of Outlet '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 19 }
|
|
|
|
st4TempSensorEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4TempSensorID,
|
|
st4TempSensorName,
|
|
st4TempSensorValue,
|
|
st4TempSensorStatus,
|
|
st4TempSensorScale,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor event."
|
|
--#TYPE "Sentry: Temperature Sensor Event."
|
|
--#SUMMARY "Status of Temperature Sensor '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 6 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 20 }
|
|
|
|
st4HumidSensorEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4HumidSensorID,
|
|
st4HumidSensorName,
|
|
st4HumidSensorValue,
|
|
st4HumidSensorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity sensor event."
|
|
--#TYPE "Sentry: Humidity Sensor Event."
|
|
--#SUMMARY "Status of Humidity Sensor '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 21 }
|
|
|
|
st4WaterSensorStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4WaterSensorID,
|
|
st4WaterSensorName,
|
|
st4WaterSensorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water sensor status event."
|
|
--#TYPE "Sentry: Water Sensor Status Event."
|
|
--#SUMMARY "Status of Water Sensor '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 4 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 22 }
|
|
|
|
st4CcSensorStatusEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4CcSensorID,
|
|
st4CcSensorName,
|
|
st4CcSensorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact closure sensor status event."
|
|
--#TYPE "Sentry: Contact Closure Sensor Status Event."
|
|
--#SUMMARY "Status of Contact Closure Sensor '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 4 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 23 }
|
|
|
|
st4AdcSensorEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4AdcSensorID,
|
|
st4AdcSensorName,
|
|
st4AdcSensorValue,
|
|
st4AdcSensorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog-to-digital converter sensor event."
|
|
--#TYPE "Sentry: Analog-to-Digital Converter Sensor Event."
|
|
--#SUMMARY "Status of Analog-to-Digital Converter Sensor '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 5 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 24 }
|
|
|
|
st4FanSensorEvent NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
st4SystemLocation,
|
|
st4FanSensorID,
|
|
st4FanSensorName,
|
|
st4FanSensorValue,
|
|
st4FanSensorStatus,
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan sensor event."
|
|
--#TYPE "Sentry: Fan Sensor Event."
|
|
--#SUMMARY "Status of Fan Sensor '%s' (%s) is '%s'."
|
|
--#ARGUMENTS { 2, 1, 4 }
|
|
--#SEVERITY CRITICAL
|
|
--#GENERIC 6
|
|
--#CATEGORY "Error Events"
|
|
--#SOURCE_ID "A"
|
|
--#TIMEINDEX 255
|
|
--#HELP ""
|
|
--#HELPTAG 0
|
|
--#STATE UNKNOWN
|
|
::= { st4Events 25 }
|
|
|
|
-- Conformance Definitions
|
|
|
|
st4Conformance OBJECT IDENTIFIER ::= { sentry4 200 }
|
|
|
|
-- Object/Notification Groups
|
|
|
|
st4Groups OBJECT IDENTIFIER ::= { st4Conformance 1 }
|
|
|
|
st4SystemObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4SystemProductName,
|
|
st4SystemLocation,
|
|
st4SystemFirmwareVersion,
|
|
st4SystemFirmwareBuildInfo,
|
|
st4SystemNICSerialNumber,
|
|
st4SystemNICHardwareInfo,
|
|
st4SystemProductSeries,
|
|
st4SystemFeatures,
|
|
st4SystemFeatureKey,
|
|
st4SystemConfigModifiedCount,
|
|
st4SystemUnitCount
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System objects group."
|
|
::= { st4Groups 1 }
|
|
|
|
st4UnitObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4UnitID,
|
|
st4UnitName,
|
|
st4UnitProductSN,
|
|
st4UnitModel,
|
|
st4UnitAssetTag,
|
|
st4UnitType,
|
|
st4UnitCapabilities,
|
|
st4UnitProductMfrDate,
|
|
st4UnitDisplayOrientation,
|
|
st4UnitOutletSequenceOrder,
|
|
st4UnitOutletDisplayOrder,
|
|
st4UnitInputCordCount,
|
|
st4UnitTempSensorCount,
|
|
st4UnitHumidSensorCount,
|
|
st4UnitWaterSensorCount,
|
|
st4UnitCcSensorCount,
|
|
st4UnitAdcSensorCount,
|
|
st4UnitFanSensorCount,
|
|
st4UnitStatus,
|
|
st4UnitNotifications
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit objects group."
|
|
::= { st4Groups 2 }
|
|
|
|
st4InputCordObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4InputCordActivePowerHysteresis,
|
|
st4InputCordApparentPowerHysteresis,
|
|
st4InputCordPowerFactorHysteresis,
|
|
st4InputCordOutOfBalanceHysteresis,
|
|
st4InputCordID,
|
|
st4InputCordName,
|
|
st4InputCordInletType,
|
|
st4InputCordNominalVoltage,
|
|
st4InputCordNominalVoltageMin,
|
|
st4InputCordNominalVoltageMax,
|
|
st4InputCordCurrentCapacity,
|
|
st4InputCordCurrentCapacityMax,
|
|
st4InputCordPowerCapacity,
|
|
st4InputCordNominalPowerFactor,
|
|
st4InputCordLineCount,
|
|
st4InputCordPhaseCount,
|
|
st4InputCordOcpCount,
|
|
st4InputCordBranchCount,
|
|
st4InputCordOutletCount,
|
|
st4InputCordState,
|
|
st4InputCordStatus,
|
|
st4InputCordActivePower,
|
|
st4InputCordActivePowerStatus,
|
|
st4InputCordApparentPower,
|
|
st4InputCordApparentPowerStatus,
|
|
st4InputCordPowerUtilized,
|
|
st4InputCordPowerFactor,
|
|
st4InputCordPowerFactorStatus,
|
|
st4InputCordEnergy,
|
|
st4InputCordFrequency,
|
|
st4InputCordOutOfBalance,
|
|
st4InputCordOutOfBalanceStatus,
|
|
st4InputCordNotifications,
|
|
st4InputCordActivePowerLowAlarm,
|
|
st4InputCordActivePowerLowWarning,
|
|
st4InputCordActivePowerHighWarning,
|
|
st4InputCordActivePowerHighAlarm,
|
|
st4InputCordApparentPowerLowAlarm,
|
|
st4InputCordApparentPowerLowWarning,
|
|
st4InputCordApparentPowerHighWarning,
|
|
st4InputCordApparentPowerHighAlarm,
|
|
st4InputCordPowerFactorLowAlarm,
|
|
st4InputCordPowerFactorLowWarning,
|
|
st4InputCordOutOfBalanceHighWarning,
|
|
st4InputCordOutOfBalanceHighAlarm
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input cord objects group."
|
|
::= { st4Groups 3 }
|
|
|
|
st4LineObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4LineCurrentHysteresis,
|
|
st4LineID,
|
|
st4LineLabel,
|
|
st4LineCurrentCapacity,
|
|
st4LineState,
|
|
st4LineStatus,
|
|
st4LineCurrent,
|
|
st4LineCurrentStatus,
|
|
st4LineCurrentUtilized,
|
|
st4LineNotifications,
|
|
st4LineCurrentLowAlarm,
|
|
st4LineCurrentLowWarning,
|
|
st4LineCurrentHighWarning,
|
|
st4LineCurrentHighAlarm
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Line objects group."
|
|
::= { st4Groups 4 }
|
|
|
|
st4PhaseObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4PhaseVoltageHysteresis,
|
|
st4PhasePowerFactorHysteresis,
|
|
st4PhaseID,
|
|
st4PhaseLabel,
|
|
st4PhaseNominalVoltage,
|
|
st4PhaseBranchCount,
|
|
st4PhaseOutletCount,
|
|
st4PhaseState,
|
|
st4PhaseStatus,
|
|
st4PhaseVoltage,
|
|
st4PhaseVoltageStatus,
|
|
st4PhaseVoltageDeviation,
|
|
st4PhaseCurrent,
|
|
st4PhaseCurrentCrestFactor,
|
|
st4PhaseActivePower,
|
|
st4PhaseApparentPower,
|
|
st4PhasePowerFactor,
|
|
st4PhasePowerFactorStatus,
|
|
st4PhaseReactance,
|
|
st4PhaseEnergy,
|
|
st4PhaseNotifications,
|
|
st4PhaseVoltageLowAlarm,
|
|
st4PhaseVoltageLowWarning,
|
|
st4PhaseVoltageHighWarning,
|
|
st4PhaseVoltageHighAlarm,
|
|
st4PhasePowerFactorLowAlarm,
|
|
st4PhasePowerFactorLowWarning
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Phase objects group."
|
|
::= { st4Groups 5 }
|
|
|
|
st4OcpObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4OcpID,
|
|
st4OcpLabel,
|
|
st4OcpType,
|
|
st4OcpCurrentCapacity,
|
|
st4OcpCurrentCapacityMax,
|
|
st4OcpBranchCount,
|
|
st4OcpOutletCount,
|
|
st4OcpStatus,
|
|
st4OcpNotifications
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over-current protector objects group."
|
|
::= { st4Groups 6 }
|
|
|
|
st4BranchObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4BranchCurrentHysteresis,
|
|
st4BranchID,
|
|
st4BranchLabel,
|
|
st4BranchCurrentCapacity,
|
|
st4BranchPhaseID,
|
|
st4BranchOcpID,
|
|
st4BranchOutletCount,
|
|
st4BranchState,
|
|
st4BranchStatus,
|
|
st4BranchCurrent,
|
|
st4BranchCurrentStatus,
|
|
st4BranchCurrentUtilized,
|
|
st4BranchNotifications,
|
|
st4BranchCurrentLowAlarm,
|
|
st4BranchCurrentLowWarning,
|
|
st4BranchCurrentHighWarning,
|
|
st4BranchCurrentHighAlarm
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch objects group."
|
|
::= { st4Groups 7 }
|
|
|
|
st4OutletObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4OutletCurrentHysteresis,
|
|
st4OutletActivePowerHysteresis,
|
|
st4OutletPowerFactorHysteresis,
|
|
st4OutletSequenceInterval,
|
|
st4OutletRebootDelay,
|
|
st4OutletStateChangeLogging,
|
|
st4OutletID,
|
|
st4OutletName,
|
|
st4OutletCapabilities,
|
|
st4OutletSocketType,
|
|
st4OutletCurrentCapacity,
|
|
st4OutletPowerCapacity,
|
|
st4OutletWakeupState,
|
|
st4OutletPostOnDelay,
|
|
st4OutletPhaseID,
|
|
st4OutletOcpID,
|
|
st4OutletBranchID,
|
|
st4OutletState,
|
|
st4OutletStatus,
|
|
st4OutletCurrent,
|
|
st4OutletCurrentStatus,
|
|
st4OutletCurrentUtilized,
|
|
st4OutletVoltage,
|
|
st4OutletActivePower,
|
|
st4OutletActivePowerStatus,
|
|
st4OutletApparentPower,
|
|
st4OutletPowerFactor,
|
|
st4OutletPowerFactorStatus,
|
|
st4OutletCurrentCrestFactor,
|
|
st4OutletReactance,
|
|
st4OutletEnergy,
|
|
st4OutletNotifications,
|
|
st4OutletCurrentLowAlarm,
|
|
st4OutletCurrentLowWarning,
|
|
st4OutletCurrentHighWarning,
|
|
st4OutletCurrentHighAlarm,
|
|
st4OutletActivePowerLowAlarm,
|
|
st4OutletActivePowerLowWarning,
|
|
st4OutletActivePowerHighWarning,
|
|
st4OutletActivePowerHighAlarm,
|
|
st4OutletPowerFactorLowAlarm,
|
|
st4OutletPowerFactorLowWarning,
|
|
st4OutletControlState,
|
|
st4OutletControlAction,
|
|
st4OutletQueueControl
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Outlet objects group."
|
|
::= { st4Groups 8 }
|
|
|
|
st4TempSensorObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4TempSensorHysteresis,
|
|
st4TempSensorScale,
|
|
st4TempSensorID,
|
|
st4TempSensorName,
|
|
st4TempSensorValueMin,
|
|
st4TempSensorValueMax,
|
|
st4TempSensorValue,
|
|
st4TempSensorStatus,
|
|
st4TempSensorNotifications,
|
|
st4TempSensorLowAlarm,
|
|
st4TempSensorLowWarning,
|
|
st4TempSensorHighWarning,
|
|
st4TempSensorHighAlarm
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature sensor objects group."
|
|
::= { st4Groups 9 }
|
|
|
|
st4HumidSensorObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4HumidSensorHysteresis,
|
|
st4HumidSensorID,
|
|
st4HumidSensorName,
|
|
st4HumidSensorValue,
|
|
st4HumidSensorStatus,
|
|
st4HumidSensorNotifications,
|
|
st4HumidSensorLowAlarm,
|
|
st4HumidSensorLowWarning,
|
|
st4HumidSensorHighWarning,
|
|
st4HumidSensorHighAlarm
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidity sensor objects group."
|
|
::= { st4Groups 10 }
|
|
|
|
st4WaterSensorObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4WaterSensorID,
|
|
st4WaterSensorName,
|
|
st4WaterSensorStatus,
|
|
st4WaterSensorNotifications
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water sensor objects group."
|
|
::= { st4Groups 11 }
|
|
|
|
st4CcSensorObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4CcSensorID,
|
|
st4CcSensorName,
|
|
st4CcSensorStatus,
|
|
st4CcSensorNotifications
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contact closure sensor objects group."
|
|
::= { st4Groups 12 }
|
|
|
|
st4AdcSensorObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4AdcSensorHysteresis,
|
|
st4AdcSensorID,
|
|
st4AdcSensorName,
|
|
st4AdcSensorValue,
|
|
st4AdcSensorStatus,
|
|
st4AdcSensorNotifications,
|
|
st4AdcSensorLowAlarm,
|
|
st4AdcSensorLowWarning,
|
|
st4AdcSensorHighWarning,
|
|
st4AdcSensorHighAlarm
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog-to-digital converter sensor objects group."
|
|
::= { st4Groups 13 }
|
|
|
|
st4FanSensorObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4FanSensorHysteresis,
|
|
st4FanSensorID,
|
|
st4FanSensorName,
|
|
st4FanSensorValue,
|
|
st4FanSensorStatus,
|
|
st4FanSensorNotifications,
|
|
st4FanSensorLowAlarm,
|
|
st4FanSensorLowWarning,
|
|
st4FanSensorHighWarning,
|
|
st4FanSensorHighAlarm
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan sensor objects group."
|
|
::= { st4Groups 14 }
|
|
|
|
st4EventInfoObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
st4EventStatusText,
|
|
st4EventStatusCondition
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event information objects group."
|
|
::= { st4Groups 99 }
|
|
|
|
st4EventNotificationsGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS {
|
|
st4UnitStatusEvent,
|
|
st4InputCordStatusEvent,
|
|
st4InputCordActivePowerEvent,
|
|
st4InputCordApparentPowerEvent,
|
|
st4InputCordPowerFactorEvent,
|
|
st4InputCordOutOfBalanceEvent,
|
|
st4LineStatusEvent,
|
|
st4LineCurrentEvent,
|
|
st4PhaseStatusEvent,
|
|
st4PhaseVoltageEvent,
|
|
st4PhasePowerFactorEvent,
|
|
st4OcpStatusEvent,
|
|
st4BranchStatusEvent,
|
|
st4BranchCurrentEvent,
|
|
st4OutletStatusEvent,
|
|
st4OutletStateChangeEvent,
|
|
st4OutletCurrentEvent,
|
|
st4OutletActivePowerEvent,
|
|
st4OutletPowerFactorEvent,
|
|
st4TempSensorEvent,
|
|
st4HumidSensorEvent,
|
|
st4WaterSensorStatusEvent,
|
|
st4CcSensorStatusEvent,
|
|
st4AdcSensorEvent,
|
|
st4FanSensorEvent
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event notifications group."
|
|
::= { st4Groups 100 }
|
|
|
|
-- Compliance Statements
|
|
|
|
st4Compliances OBJECT IDENTIFIER ::= { st4Conformance 2 }
|
|
|
|
st4ModuleCompliances MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The requirements for conformance to the Sentry4-MIB."
|
|
MODULE
|
|
GROUP st4SystemObjectsGroup
|
|
DESCRIPTION
|
|
"System objects group."
|
|
GROUP st4UnitObjectsGroup
|
|
DESCRIPTION
|
|
"Unit objects group."
|
|
GROUP st4InputCordObjectsGroup
|
|
DESCRIPTION
|
|
"Input cord objects group."
|
|
GROUP st4LineObjectsGroup
|
|
DESCRIPTION
|
|
"Line objects group."
|
|
GROUP st4PhaseObjectsGroup
|
|
DESCRIPTION
|
|
"Phase objects group."
|
|
GROUP st4OcpObjectsGroup
|
|
DESCRIPTION
|
|
"Over-current protector objects group."
|
|
GROUP st4BranchObjectsGroup
|
|
DESCRIPTION
|
|
"Branch objects group."
|
|
GROUP st4OutletObjectsGroup
|
|
DESCRIPTION
|
|
"Outlet objects group."
|
|
GROUP st4TempSensorObjectsGroup
|
|
DESCRIPTION
|
|
"Temperature sensor objects group."
|
|
GROUP st4HumidSensorObjectsGroup
|
|
DESCRIPTION
|
|
"Humidity sensor objects group."
|
|
GROUP st4WaterSensorObjectsGroup
|
|
DESCRIPTION
|
|
"Water sensor objects group."
|
|
GROUP st4CcSensorObjectsGroup
|
|
DESCRIPTION
|
|
"Contact closure sensor objects group."
|
|
GROUP st4AdcSensorObjectsGroup
|
|
DESCRIPTION
|
|
"Analog-to-digital converter sensor objects group."
|
|
GROUP st4FanSensorObjectsGroup
|
|
DESCRIPTION
|
|
"Fan sensor objects group."
|
|
GROUP st4EventInfoObjectsGroup
|
|
DESCRIPTION
|
|
"Event information objects group."
|
|
GROUP st4EventNotificationsGroup
|
|
DESCRIPTION
|
|
"Event notifications group."
|
|
::= { st4Compliances 1 }
|
|
|
|
END |