-- TRIPP LITE PRODUCTS MIB
-- Copyright (c) 1999-2021 Tripp Lite
-- All rights reserved
-- ------------------------------------------------------
TRIPPLITE-PRODUCTS DEFINITIONS ::= BEGIN
IMPORTS
DisplayString,
TruthValue,
TimeStamp,
RowStatus
FROM SNMPv2-TC
sysUpTime
FROM SNMPv2-MIB
OBJECT-GROUP,
NOTIFICATION-GROUP
FROM SNMPv2-CONF
MODULE-IDENTITY,
OBJECT-IDENTITY,
OBJECT-TYPE,
NOTIFICATION-TYPE,
Gauge32,
Integer32,
Unsigned32,
enterprises,
IpAddress,
TimeTicks
FROM SNMPv2-SMI
tripplite
FROM TRIPPLITE;
tlpProducts MODULE-IDENTITY
LAST-UPDATED "202105120000Z"
ORGANIZATION "Tripp Lite"
CONTACT-INFO
"Software Engineering
Tripp Lite
1111 W. 35th St.
Chicago, IL 60609"
DESCRIPTION
"This MIB module defines MIB objects which provide mechanisms for
remote management capabilities of Tripp Lite PowerAlert and related
software."
REVISION "202105120000Z"
DESCRIPTION
"Modifications to support additional device protocols (20.0.1)"
REVISION "202102020000Z"
DESCRIPTION
"Modifications to support PADM 20"
REVISION "201911010000Z"
DESCRIPTION
"Consolidated modifications from PADM 15"
::= { tripplite 1 }
-- tlpProducts OBJECT IDENTIFIER ::= { tripplite 1 }
tlpHardware OBJECT IDENTIFIER ::= { tlpProducts 1 }
tlpSoftware OBJECT IDENTIFIER ::= { tlpProducts 2 }
tlpAlarms OBJECT IDENTIFIER ::= { tlpProducts 3 }
tlpNotify OBJECT IDENTIFIER ::= { tlpProducts 4 }
tlpDevice OBJECT IDENTIFIER ::= { tlpHardware 1 }
tlpDeviceDetail OBJECT IDENTIFIER ::= { tlpHardware 2 }
tlpDeviceTypes OBJECT IDENTIFIER ::= { tlpHardware 3 }
tlpUps OBJECT IDENTIFIER ::= { tlpDeviceTypes 1 }
tlpPdu OBJECT IDENTIFIER ::= { tlpDeviceTypes 2 }
tlpEnvirosense OBJECT IDENTIFIER ::= { tlpDeviceTypes 3 }
tlpAts OBJECT IDENTIFIER ::= { tlpDeviceTypes 4 }
tlpCooling OBJECT IDENTIFIER ::= { tlpDeviceTypes 5 }
tlpKvm OBJECT IDENTIFIER ::= { tlpDeviceTypes 6 }
tlpRackTrack OBJECT IDENTIFIER ::= { tlpDeviceTypes 7 }
tlpSwitch OBJECT IDENTIFIER ::= { tlpDeviceTypes 8 }
tlpUpsIdent OBJECT IDENTIFIER ::= { tlpUps 1 }
tlpUpsDevice OBJECT IDENTIFIER ::= { tlpUps 2 }
tlpUpsDetail OBJECT IDENTIFIER ::= { tlpUps 3 }
tlpUpsControl OBJECT IDENTIFIER ::= { tlpUps 4 }
tlpUpsConfig OBJECT IDENTIFIER ::= { tlpUps 5 }
tlpUpsBattery OBJECT IDENTIFIER ::= { tlpUpsDetail 1 }
tlpUpsInput OBJECT IDENTIFIER ::= { tlpUpsDetail 2 }
tlpUpsOutput OBJECT IDENTIFIER ::= { tlpUpsDetail 3 }
tlpUpsBypass OBJECT IDENTIFIER ::= { tlpUpsDetail 4 }
tlpUpsOutlet OBJECT IDENTIFIER ::= { tlpUpsDetail 5 }
tlpUpsWatchdog OBJECT IDENTIFIER ::= { tlpUpsDetail 6 }
tlpUpsFan OBJECT IDENTIFIER ::= { tlpUpsDetail 7 }
tlpUpsHeatsink OBJECT IDENTIFIER ::= { tlpUpsDetail 8 }
tlpUpsContact OBJECT IDENTIFIER ::= { tlpUpsDetail 9 }
tlpUpsInputContact OBJECT IDENTIFIER ::= { tlpUpsContact 1 }
tlpUpsOutputContact OBJECT IDENTIFIER ::= { tlpUpsContact 2 }
tlpPduIdent OBJECT IDENTIFIER ::= { tlpPdu 1 }
tlpPduDevice OBJECT IDENTIFIER ::= { tlpPdu 2 }
tlpPduDetail OBJECT IDENTIFIER ::= { tlpPdu 3 }
tlpPduControl OBJECT IDENTIFIER ::= { tlpPdu 4 }
tlpPduConfig OBJECT IDENTIFIER ::= { tlpPdu 5 }
tlpPduInput OBJECT IDENTIFIER ::= { tlpPduDetail 1 }
tlpPduOutput OBJECT IDENTIFIER ::= { tlpPduDetail 2 }
tlpPduOutlet OBJECT IDENTIFIER ::= { tlpPduDetail 3 }
tlpPduCircuit OBJECT IDENTIFIER ::= { tlpPduDetail 4 }
tlpPduBreaker OBJECT IDENTIFIER ::= { tlpPduDetail 5 }
tlpPduHeatsink OBJECT IDENTIFIER ::= { tlpPduDetail 6 }
tlpEnvIdent OBJECT IDENTIFIER ::= { tlpEnvirosense 1 }
-- tlpEnvDevice OBJECT IDENTIFIER ::= { tlpEnvirosense 2 }
tlpEnvDetail OBJECT IDENTIFIER ::= { tlpEnvirosense 3 }
tlpEnvControl OBJECT IDENTIFIER ::= { tlpEnvirosense 4 }
tlpEnvConfig OBJECT IDENTIFIER ::= { tlpEnvirosense 5 }
tlpAtsIdent OBJECT IDENTIFIER ::= { tlpAts 1 }
tlpAtsDevice OBJECT IDENTIFIER ::= { tlpAts 2 }
tlpAtsDetail OBJECT IDENTIFIER ::= { tlpAts 3 }
tlpAtsControl OBJECT IDENTIFIER ::= { tlpAts 4 }
tlpAtsConfig OBJECT IDENTIFIER ::= { tlpAts 5 }
tlpAtsInput OBJECT IDENTIFIER ::= { tlpAtsDetail 1 }
tlpAtsOutput OBJECT IDENTIFIER ::= { tlpAtsDetail 2 }
tlpAtsOutlet OBJECT IDENTIFIER ::= { tlpAtsDetail 3 }
tlpAtsCircuit OBJECT IDENTIFIER ::= { tlpAtsDetail 4 }
tlpAtsBreaker OBJECT IDENTIFIER ::= { tlpAtsDetail 5 }
tlpAtsHeatsink OBJECT IDENTIFIER ::= { tlpAtsDetail 6 }
tlpCoolingIdent OBJECT IDENTIFIER ::= { tlpCooling 1 }
tlpCoolingDevice OBJECT IDENTIFIER ::= { tlpCooling 2 }
tlpCoolingDetail OBJECT IDENTIFIER ::= { tlpCooling 3 }
tlpCoolingControl OBJECT IDENTIFIER ::= { tlpCooling 4 }
tlpCoolingConfig OBJECT IDENTIFIER ::= { tlpCooling 5 }
tlpCoolingTemperature OBJECT IDENTIFIER ::= { tlpCoolingDetail 1 }
tlpCoolingPressure OBJECT IDENTIFIER ::= { tlpCoolingDetail 2 }
tlpKvmIdent OBJECT IDENTIFIER ::= { tlpKvm 1 }
tlpKvmDevice OBJECT IDENTIFIER ::= { tlpKvm 2 }
tlpKvmDetail OBJECT IDENTIFIER ::= { tlpKvm 3 }
tlpKvmControl OBJECT IDENTIFIER ::= { tlpKvm 4 }
tlpKvmConfig OBJECT IDENTIFIER ::= { tlpKvm 5 }
tlpRackTrackIdent OBJECT IDENTIFIER ::= { tlpRackTrack 1 }
tlpRackTrackDevice OBJECT IDENTIFIER ::= { tlpRackTrack 2 }
tlpRackTrackDetail OBJECT IDENTIFIER ::= { tlpRackTrack 3 }
tlpRackTrackControl OBJECT IDENTIFIER ::= { tlpRackTrack 4 }
tlpRackTrackConfig OBJECT IDENTIFIER ::= { tlpRackTrack 5 }
tlpSwitchIdent OBJECT IDENTIFIER ::= { tlpSwitch 1 }
tlpSwitchDevice OBJECT IDENTIFIER ::= { tlpSwitch 2 }
tlpSwitchDetail OBJECT IDENTIFIER ::= { tlpSwitch 3 }
tlpSwitchControl OBJECT IDENTIFIER ::= { tlpSwitch 4 }
tlpSwitchConfig OBJECT IDENTIFIER ::= { tlpSwitch 5 }
tlpAgentDetails OBJECT IDENTIFIER ::= { tlpSoftware 1 }
tlpAgentSettings OBJECT IDENTIFIER ::= { tlpSoftware 2 }
tlpAgentContacts OBJECT IDENTIFIER ::= { tlpSoftware 3 }
tlpAgentAutoProbe OBJECT IDENTIFIER ::= { tlpSoftware 4 }
tlpAgentIdent OBJECT IDENTIFIER ::= { tlpAgentDetails 1}
tlpAgentAttributes OBJECT IDENTIFIER ::= { tlpAgentDetails 2}
tlpAgentAddresses OBJECT IDENTIFIER ::= { tlpAgentDetails 3}
tlpAgentConfig OBJECT IDENTIFIER ::= { tlpAgentSettings 1}
tlpAgentEmailContacts OBJECT IDENTIFIER ::= { tlpAgentContacts 1}
tlpAgentSnmpContacts OBJECT IDENTIFIER ::= { tlpAgentContacts 2}
tlpAgentSmsContacts OBJECT IDENTIFIER ::= { tlpAgentContacts 3}
tlpAlarmsWellKnown OBJECT IDENTIFIER ::= { tlpAlarms 3 }
tlpAlarmControl OBJECT IDENTIFIER ::= { tlpAlarms 4 }
tlpAgentAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 1 }
tlpDeviceAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 2 }
tlpUpsAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 3 }
tlpPduAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 4 }
tlpEnvAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 5 }
tlpAtsAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 6 }
tlpCoolingAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 7 }
tlpKvmAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 8 }
tlpRackTrackAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 9 }
tlpSwitchAlarms OBJECT IDENTIFIER ::= { tlpAlarmsWellKnown 10 }
tlpNotifications OBJECT IDENTIFIER ::= { tlpNotify 1 }
tlpNotificationsEvent OBJECT IDENTIFIER ::= { tlpNotify 2 }
tlpNotificationsEventParameters OBJECT IDENTIFIER ::= { tlpNotify 3 }
tlpDeviceNumDevices OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of devices that this agent is currently managing."
::= { tlpDevice 1 }
tlpDeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of device table entries. The number of entries
is given by the value of tlpDevicesNumDevices."
::= { tlpDevice 2 }
tlpDeviceEntry OBJECT-TYPE
SYNTAX TlpDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular device
managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpDeviceTable 1 }
TlpDeviceEntry ::= SEQUENCE {
tlpDeviceIndex Unsigned32,
tlpDeviceRowStatus RowStatus,
tlpDeviceType OBJECT IDENTIFIER,
tlpDeviceManufacturer DisplayString,
tlpDeviceModel DisplayString,
tlpDeviceName DisplayString,
tlpDeviceID INTEGER,
tlpDeviceLocation DisplayString,
tlpDeviceRegion DisplayString,
tlpDeviceStatus INTEGER,
tlpDeviceAssetTag DisplayString }
tlpDeviceIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the device."
::= { tlpDeviceEntry 1 }
tlpDeviceRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Used with table edits to indicate the status of a given row in
tlpDeviceTable."
::= { tlpDeviceEntry 2 }
tlpDeviceType OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of device. One of the appropriate hardware types:
ups, pdu, envirosense, etc."
::= { tlpDeviceEntry 3 }
tlpDeviceManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the manufacturer."
::= { tlpDeviceEntry 4 }
tlpDeviceModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The model designation."
::= { tlpDeviceEntry 5 }
tlpDeviceName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-supplied name for the device."
::= { tlpDeviceEntry 6 }
tlpDeviceID OBJECT-TYPE
SYNTAX INTEGER (0..65535)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-supplied numeric identifier for the device. The range of this
value accommodates all devices; however, some devices support a smaller
range and return an error when setting to a value outside the supported
range."
::= { tlpDeviceEntry 7 }
tlpDeviceLocation OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-supplied location for the device."
::= { tlpDeviceEntry 8 }
tlpDeviceRegion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-supplied region for the device."
::= { tlpDeviceEntry 9 }
tlpDeviceStatus OBJECT-TYPE
SYNTAX INTEGER {
none(0),
critical(1),
warning(2),
info(3),
status(4),
offline(5),
custom(6),
configuration(7) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The currently most critical alarm status for the device."
::= { tlpDeviceEntry 10 }
tlpDeviceAssetTag OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-supplied textual identifier for the device."
::= { tlpDeviceEntry 11 }
tlpDeviceIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpDeviceIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The identity details of each device in device table. The number
of entries is given by the value of tlpDevicesNumDevices."
::= { tlpDeviceDetail 1 }
tlpDeviceIdentEntry OBJECT-TYPE
SYNTAX TlpDeviceIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing details for a particular device."
INDEX { tlpDeviceIndex }
::= { tlpDeviceIdentTable 1 }
TlpDeviceIdentEntry ::= SEQUENCE {
tlpDeviceIdentProtocol DisplayString,
tlpDeviceIdentCommPortType INTEGER,
tlpDeviceIdentCommPortName DisplayString,
tlpDeviceIdentFirmwareVersion DisplayString,
tlpDeviceIdentSerialNum DisplayString,
tlpDeviceIdentDateInstalled DisplayString,
tlpDeviceIdentHardwareVersion DisplayString,
tlpDeviceIdentCurrentUptime DisplayString,
tlpDeviceIdentTotalUptime DisplayString,
tlpDeviceIdentFirmwareVersion2 DisplayString,
tlpDeviceIdentFirmwareVersion3 DisplayString,
tlpDeviceIdentNvrID DisplayString }
tlpDeviceIdentProtocol OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The Tripplite protocol used to communicate with the device."
::= { tlpDeviceIdentEntry 1 }
tlpDeviceIdentCommPortType OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
serial(1),
usb(2),
hid(3),
simulated(4),
unittest(5) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of communications port used to connect with the device."
::= { tlpDeviceIdentEntry 2 }
tlpDeviceIdentCommPortName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the communications port."
::= { tlpDeviceIdentEntry 3 }
tlpDeviceIdentFirmwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware version of the device."
::= { tlpDeviceIdentEntry 4 }
tlpDeviceIdentSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of the device."
::= { tlpDeviceIdentEntry 5 }
tlpDeviceIdentDateInstalled OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The installation date for this device in the format of yyyy-mm-dd."
::= { tlpDeviceIdentEntry 6 }
tlpDeviceIdentHardwareVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The hardware revision of the device. This value will return ERROR_NO_SUCH_NAME
if not supported by the device."
::= { tlpDeviceIdentEntry 7 }
tlpDeviceIdentCurrentUptime OBJECT-TYPE
SYNTAX DisplayString
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The device uptime since its last startup. A device returning a single, numeric
value reports uptime in hours. This value will return ERROR_NO_SUCH_NAME if
not supported by the device."
::= { tlpDeviceIdentEntry 8 }
tlpDeviceIdentTotalUptime OBJECT-TYPE
SYNTAX DisplayString
UNITS "days"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The cumulative (total) uptime for the device. A device returning a single,
numeric value reports total uptime in days. This value will return
ERROR_NO_SUCH_NAME if not supported by the device."
::= { tlpDeviceIdentEntry 9 }
tlpDeviceIdentFirmwareVersion2 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware version of second IC on the device. This value will return
ERROR_NO_SUCH_NAME if not supported by the device."
::= { tlpDeviceIdentEntry 10 }
tlpDeviceIdentFirmwareVersion3 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware version of third IC on the device. This value will return
ERROR_NO_SUCH_NAME if not supported by the device."
::= { tlpDeviceIdentEntry 11 }
tlpDeviceIdentNvrID OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The id of NVRAM. This value will return ERROR_NO_SUCH_NAME if not supported by the device."
::= { tlpDeviceIdentEntry 12 }
-- ups
tlpUpsIdentNumUps OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of ups devices that this agent is currently managing."
::= { tlpUpsIdent 1 }
tlpUpsIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The identity details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss."
::= { tlpUpsIdent 2 }
tlpUpsIdentEntry OBJECT-TYPE
SYNTAX TlpUpsIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing details for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsIdentTable 1 }
TlpUpsIdentEntry ::= SEQUENCE {
tlpUpsIdentNumInputs Unsigned32,
tlpUpsIdentNumOutputs Unsigned32,
tlpUpsIdentNumBypass Unsigned32,
tlpUpsIdentNumPhases Unsigned32,
tlpUpsIdentNumOutlets Unsigned32,
tlpUpsIdentNumOutletGroups Unsigned32,
tlpUpsIdentNumBatteries Unsigned32,
tlpUpsIdentNumFans Unsigned32,
tlpUpsIdentNumHeatsinks Unsigned32,
tlpUpsIdentNumInputContacts Unsigned32,
tlpUpsIdentNumOutputContacts Unsigned32,
tlpUpsIdentNumActiveControlModules Unsigned32,
tlpUpsIdentNumRedundantControlModules Unsigned32 }
tlpUpsIdentNumInputs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input lines supported by the ups."
::= { tlpUpsIdentEntry 1 }
tlpUpsIdentNumOutputs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of output lines supported by the ups."
::= { tlpUpsIdentEntry 2 }
tlpUpsIdentNumBypass OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of bypass lines supported by the ups."
::= { tlpUpsIdentEntry 3 }
tlpUpsIdentNumPhases OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of phases supported by the ups."
::= { tlpUpsIdentEntry 4 }
tlpUpsIdentNumOutlets OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of receptacles supported by the ups."
::= { tlpUpsIdentEntry 5 }
tlpUpsIdentNumOutletGroups OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of user-defined receptacle groups created for the
ups."
::= { tlpUpsIdentEntry 6 }
tlpUpsIdentNumBatteries OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of batteries, internal and external combined, connected
to the ups."
::= { tlpUpsIdentEntry 7 }
tlpUpsIdentNumFans OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of fans supported by the ups."
::= { tlpUpsIdentEntry 8 }
tlpUpsIdentNumHeatsinks OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of heatsink thermistors supported by the ups."
::= { tlpUpsIdentEntry 9 }
tlpUpsIdentNumInputContacts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input contacts supported by the ups."
::= { tlpUpsIdentEntry 10 }
tlpUpsIdentNumOutputContacts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of output contacts supported by the ups."
::= { tlpUpsIdentEntry 11 }
tlpUpsIdentNumActiveControlModules OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of active control modules supported by the ups."
::= { tlpUpsIdentEntry 12 }
tlpUpsIdentNumRedundantControlModules OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of redundant control modules supported by the ups."
::= { tlpUpsIdentEntry 13 }
tlpUpsSupportsTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsSupportsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The supported details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss."
::= { tlpUpsIdent 3 }
tlpUpsSupportsEntry OBJECT-TYPE
SYNTAX TlpUpsSupportsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing supported details for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsSupportsTable 1 }
TlpUpsSupportsEntry ::= SEQUENCE {
tlpUpsSupportsEnergywise TruthValue,
tlpUpsSupportsRampShed TruthValue,
tlpUpsSupportsOutletGroup TruthValue,
tlpUpsSupportsOutletCurrent TruthValue,
tlpUpsSupportsOutletVoltage TruthValue,
tlpUpsSupportsOutletActivePower TruthValue }
tlpUpsSupportsEnergywise OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Indicates whether the ups supports Cisco EnergyWise."
::= { tlpUpsSupportsEntry 1 }
tlpUpsSupportsRampShed OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ups supports ramping and shedding."
::= { tlpUpsSupportsEntry 2 }
tlpUpsSupportsOutletGroup OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ups supports outlet groups."
::= { tlpUpsSupportsEntry 3 }
tlpUpsSupportsOutletCurrent OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ups reports individual receptacle current
measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpUpsOutletCurrent."
::= { tlpUpsSupportsEntry 4 }
tlpUpsSupportsOutletVoltage OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ups reports individual receptacle voltage
measurements. Devices that do not support individual receptacle
measurements will always return ERROR_NO_SUCH_NAME for
tlpUpsOutletVoltage."
::= { tlpUpsSupportsEntry 5 }
tlpUpsSupportsOutletActivePower OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ups reports individual receptacle
power measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpUpsOutletActivePower."
::= { tlpUpsSupportsEntry 6 }
tlpUpsDeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The device details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss."
::= { tlpUpsDevice 1 }
tlpUpsDeviceEntry OBJECT-TYPE
SYNTAX TlpUpsDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing device details for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsDeviceTable 1 }
TlpUpsDeviceEntry ::= SEQUENCE {
tlpUpsDeviceMainLoadState INTEGER,
tlpUpsDeviceMainLoadControllable TruthValue,
tlpUpsDeviceMainLoadCommand INTEGER,
tlpUpsDevicePowerOnDelay Integer32,
tlpUpsDeviceTestDate DisplayString,
tlpUpsDeviceTestResultsStatus INTEGER,
tlpUpsDeviceTemperatureC Integer32,
tlpUpsDeviceTemperatureF Integer32,
tlpUpsDeviceLastACFailureReason INTEGER,
tlpUpsDeviceLastShutdownReason INTEGER,
tlpUpsDeviceOutputCurrentPrecision INTEGER,
tlpUpsDeviceOutputActivePowerTotal Unsigned32,
tlpUpsDeviceAggregatePowerFactor Unsigned32,
tlpUpsDeviceGeneralFault TruthValue,
tlpUpsDeviceUpsType INTEGER,
tlpUpsDeviceLastBypassReason INTEGER,
tlpUpsDeviceBuzzerStatus INTEGER }
tlpUpsDeviceMainLoadState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the main output of the device."
::= { tlpUpsDeviceEntry 1 }
tlpUpsDeviceMainLoadControllable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the main output is controllable, and whether
the ups can be turned off and on."
::= { tlpUpsDeviceEntry 2 }
tlpUpsDeviceMainLoadCommand OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value to
turnOff(1) will turn off the main output of the ups. Setting this
value to turnOn(2) will turn on the main output of the ups. Setting
this value to cycle(3) will turn off the main output, then turn it
back on."
::= { tlpUpsDeviceEntry 3 }
tlpUpsDevicePowerOnDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "Seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configurable delay value, which sets the amount of additional
time a given device will wait before it connects to a valid AC
source. By default the delay value is set to 0."
::= { tlpUpsDeviceEntry 4 }
tlpUpsDeviceTestDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The date of the last self-test run on the ups, in the format yyyy-mm-dd.
The test date is not valid under certain circumstances, such as when no
test has been performed, tlpUpsDeviceTestResultsStatus is noTest(0). The
agent will always return ERROR_NO_SUCH_NAME when the test date is not
valid or not supported."
::= { tlpUpsDeviceEntry 5 }
tlpUpsDeviceTestResultsStatus OBJECT-TYPE
SYNTAX INTEGER {
noTest(0),
doneAndPassed(1),
doneAndWarning(2),
doneAndError(3),
aborted(4),
inProgress(5),
noTestInitiatedDeprecated(6),
badBattery(7),
overCurrent(8),
batteryFailed(9) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The result of the last self-test run on the ups. The noTestInitiated(6)
result is a duplicate of noTest(0) and was deprecated in agent v20. All
untested self tests, where supported, will return noTest(0)."
::= { tlpUpsDeviceEntry 6 }
tlpUpsDeviceTemperatureC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the ups casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsDeviceEntry 7 }
tlpUpsDeviceTemperatureF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the ups casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsDeviceEntry 8 }
tlpUpsDeviceLastACFailureReason OBJECT-TYPE
SYNTAX INTEGER {
noACFailureSinceReset(0),
blackout(1),
instantaneousHighLineFrequency(2),
highLineVoltage(3),
lowLineVoltage(4),
averageFrequencyFault(5),
instantaneousLowLineFrequency(6),
delayedBrownout(7) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The last reason for ac failure."
::= { tlpUpsDeviceEntry 9 }
tlpUpsDeviceLastShutdownReason OBJECT-TYPE
SYNTAX INTEGER {
noShutdownSinceReset(0),
onOffButtonShutdown(1),
averageVbattSmallerThenLVCShutdown(2),
fastVbattKeepaliveVoltageFastShutdown(3),
averageCurrentLimitShutdown(4),
fastCurrentLimitShutdown(5),
heavyLoadThermalTimeLimitShutdown(6),
fixedInvertModeTimeLimitShutdown(7),
highBatteryVoltageFault(8),
averageVbattKeepaliveVoltageShutdown(9),
shutdownCommandWithAutorestartEnabled(10),
shutdownCommandWithoutAutorestartEnabled(11),
lineConnectRelayFault(12),
epoInvertMode(13),
epoRestartMode(14),
invalidLineStandbyMode(15),
chargerLimitMinBatteryVoltage(16),
chargerLimitMaxBatteryVoltage(17),
invalidLineDelayedWakeupAutorestartEnabled(18),
invalidLineDelayedWakeupAutorestartDisabled(19),
minBatteryVoltagePriorDelayedWakeupAutorestartEnabled(20),
minBatteryVoltagePriorDelayedWakeupAutorestartDisabled(21),
lvcShutdownAutorestartEnabled(22),
lvcShutdownAutorestartDisabled(23),
overloadShutdownAutorestartEnabled(24),
overloadShutdownAutorestartDisabled(25),
overTemperatureShutdownAutorestartEnabled(26),
overTemperatureShutdownAutorestartDisabled(27),
onOffButtonShutdownAutorestartEnabled(28),
onOffButtonShutdownAutorestartDisabled(29),
batteryReportedFault(30),
batteryCommunicationLost(31),
batteryJumpStartChargerTimeoutError(32) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The last reason for device shut down."
::= { tlpUpsDeviceEntry 10 }
tlpUpsDeviceOutputCurrentPrecision OBJECT-TYPE
SYNTAX INTEGER {
wholeNumber(0),
tenths(1),
hundredths(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output current is reported by tlpUpsOutputLineCurrent, tlpUpsOutputLineCurrentMin and
tlpUpsOutputLineCurrentMax. These values are all reported in hundredths(0.01A),which
accommodates all models; however, on any given device the actual precision may vary. This
value describes the actual precision, which can be used as a divisor against the output current
values to obtain the true output current measurement. For example, if tlpUpsOutputLineCurrent reports
530 and tlpUpsDeviceOutputCurrentPrecision is tenths(1), then the actual output current is 5.3."
::= { tlpUpsDeviceEntry 11 }
tlpUpsDeviceOutputActivePowerTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC output total power for all circuits. If not supported, this value will
always return ERROR_NO_SUCH_NAME."
::= { tlpUpsDeviceEntry 12 }
tlpUpsDeviceAggregatePowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The aggregate power factor of all phases. If not supported, this value will
always return ERROR_NO_SUCH_NAME."
::= { tlpUpsDeviceEntry 13 }
tlpUpsDeviceGeneralFault OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the ups is in a fault condition. When the ups is in such
a fault condition, the condition can be cleared with tlpUpsControlResetGeneralFault.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsDeviceEntry 14 }
tlpUpsDeviceUpsType OBJECT-TYPE
SYNTAX INTEGER {
onLine(0),
offLine(1),
lineInteractive(2),
threePhase(3),
splitPhase(4),
others(5),
splitPhaseOld(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of ups."
::= { tlpUpsDeviceEntry 15 }
tlpUpsDeviceLastBypassReason OBJECT-TYPE
SYNTAX INTEGER {
noBypassSinceReset(0),
overLoad(1),
overTemperature(2),
dcBusAbnormal(3),
inverterStsFailure(4),
inverterVoltageAbnormal(5),
fuseOpen(6),
internalCommunicationsFailure(7),
softStartFailure(8) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The last reason the ups went into bypass mode."
::= { tlpUpsDeviceEntry 16 }
tlpUpsDeviceBuzzerStatus OBJECT-TYPE
SYNTAX INTEGER {
silent(0),
buzzing(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present state of the audible alarm. When buzzing(1), use
tlpUpsControlMuteBuzzer to temporarily silence the buzzer until the
current alarm state is cleared. Use tlpUpsConfigAudibleStatus to
permanently disable the audible alarm from sounding when entering
any alarm state."
::= { tlpUpsDeviceEntry 17 }
tlpUpsBatterySummaryTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsBatterySummaryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The battery system summary of each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss managed by
the agent as reported by tlpUpsIdentNumUps."
::= { tlpUpsBattery 1 }
tlpUpsBatterySummaryEntry OBJECT-TYPE
SYNTAX TlpUpsBatterySummaryEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
battery system managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpUpsBatterySummaryTable 1 }
TlpUpsBatterySummaryEntry ::= SEQUENCE {
tlpUpsBatteryStatus INTEGER,
tlpUpsSecondsOnBattery Unsigned32,
tlpUpsEstimatedMinutesRemaining Unsigned32,
tlpUpsEstimatedChargeRemaining INTEGER,
tlpUpsBatteryRunTimeRemaining TimeTicks,
tlpUpsBatteryTotalMinutesOnBattery Unsigned32 }
tlpUpsBatteryStatus OBJECT-TYPE
SYNTAX INTEGER {
unknown(1),
batteryNormal(2),
batteryLow(3),
batteryDepleted(4) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The indication of the capacity remaining in the ups system's
batteries. A value of batteryNormal indicates that the
remaining run-time is greater than tlpUpsConfigLowBattTime. A
value of batteryLow indicates that the remaining battery run-time
is less than or equal to tlpUpsConfigLowBattTime. A value of
batteryDepleted indicates that the ups will be unable to sustain
the present load when and if the utility power is lost (including
the possibility that the utility power is currently absent and
the ups is unable to sustain the output)."
::= { tlpUpsBatterySummaryEntry 1 }
tlpUpsSecondsOnBattery OBJECT-TYPE
SYNTAX Unsigned32
UNITS "seconds"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"If the unit is on battery power, the elapsed time since the ups
last switched to battery power, or the time since the network
management subsystem was last restarted, whichever is less. Zero
shall be returned if the unit is not on battery power."
::= { tlpUpsBatterySummaryEntry 2 }
tlpUpsEstimatedMinutesRemaining OBJECT-TYPE
SYNTAX Unsigned32
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An estimate of the time to battery charge depletion
under the present load conditions if the utility power
is off and remains off, or if it were to be lost and
remain off."
::= { tlpUpsBatterySummaryEntry 3 }
tlpUpsEstimatedChargeRemaining OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"An estimate of the battery charge remaining expressed
as a percent of full charge."
::= { tlpUpsBatterySummaryEntry 4 }
tlpUpsBatteryRunTimeRemaining OBJECT-TYPE
SYNTAX TimeTicks
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The run time remaining before batteries are exhausted. If the device
does not support run time remaining, then the agent reports
ERROR_NO_SUCH_NAME."
::= { tlpUpsBatterySummaryEntry 5 }
tlpUpsBatteryTotalMinutesOnBattery OBJECT-TYPE
SYNTAX Unsigned32
UNITS "minutes"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total accumulative minutes the ups has run on the battery."
::= { tlpUpsBatterySummaryEntry 6 }
tlpUpsBatteryDetailTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsBatteryDetailEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The battery detail of each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumUps."
::= { tlpUpsBattery 2 }
tlpUpsBatteryDetailEntry OBJECT-TYPE
SYNTAX TlpUpsBatteryDetailEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
battery system managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpUpsBatteryDetailTable 1 }
TlpUpsBatteryDetailEntry ::= SEQUENCE {
tlpUpsBatteryDetailVoltage Unsigned32,
tlpUpsBatteryDetailCurrent Integer32,
tlpUpsBatteryDetailCapacity INTEGER,
tlpUpsBatteryDetailCharge INTEGER,
tlpUpsBatteryDetailChargerStatus INTEGER,
tlpUpsBatteryDetailNominalVoltage Unsigned32,
tlpUpsBatteryDetailFullyCharged TruthValue,
tlpUpsBatteryDetailOvercharged TruthValue,
tlpUpsBatteryDetailVoltageNegative Unsigned32,
tlpUpsBatteryDetailVoltagePositive Unsigned32,
tlpUpsBatteryDetailMaxChargerCurrent INTEGER
}
tlpUpsBatteryDetailVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volt DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present battery voltage."
::= { tlpUpsBatteryDetailEntry 1 }
tlpUpsBatteryDetailCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present battery current."
::= { tlpUpsBatteryDetailEntry 2 }
tlpUpsBatteryDetailCapacity OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The estimated remaining battery capacity expressed as a percent of
full capacity."
::= { tlpUpsBatteryDetailEntry 3 }
tlpUpsBatteryDetailCharge OBJECT-TYPE
SYNTAX INTEGER {
floating(0),
charging(1),
resting(2),
discharging(3),
normal(4),
standby(5) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the charge state of the battery."
::= { tlpUpsBatteryDetailEntry 4 }
tlpUpsBatteryDetailChargerStatus OBJECT-TYPE
SYNTAX INTEGER {
ok(0),
inFaultCondition(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The status of the battery charger. This value may not be supported
on all models. If not supported, this agent will return ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryDetailEntry 5 }
tlpUpsBatteryDetailNominalVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the battery voltage. This value may not
be supported on all models. If not supported, this agent will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryDetailEntry 6 }
tlpUpsBatteryDetailFullyCharged OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether the battery is fully charged. This value may not
be supported on all models. If not supported, this agent will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryDetailEntry 7 }
tlpUpsBatteryDetailOvercharged OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether the battery is over charged. This value may not
be supported on all models. If not supported, this agent will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryDetailEntry 8 }
tlpUpsBatteryDetailVoltageNegative OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volt DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present negative battery voltage."
::= { tlpUpsBatteryDetailEntry 9 }
tlpUpsBatteryDetailVoltagePositive OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volt DC"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present positive battery voltage."
::= { tlpUpsBatteryDetailEntry 10 }
tlpUpsBatteryDetailMaxChargerCurrent OBJECT-TYPE
SYNTAX INTEGER (0..255)
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum charging current for the battery. This value may not
be supported on all models. If not supported, this agent will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryDetailEntry 11 }
tlpUpsBatteryPackIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsBatteryIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The battery identification details for each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss managed by the
agent as reported by upsIdentNumUps and the number of battery
battery packs per each as reported by tlpUpsNumBatteryPacks."
::= { tlpUpsBattery 3 }
tlpUpsBatteryPackIdentEntry OBJECT-TYPE
SYNTAX TlpUpsBatteryIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
battery pack managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsBatteryPackIdentIndex }
::= { tlpUpsBatteryPackIdentTable 1 }
TlpUpsBatteryIdentEntry ::= SEQUENCE {
tlpUpsBatteryPackIdentIndex Unsigned32,
tlpUpsBatteryPackIdentManufacturer DisplayString,
tlpUpsBatteryPackIdentModel DisplayString,
tlpUpsBatteryPackIdentSerialNum DisplayString,
tlpUpsBatteryPackIdentFirmware DisplayString,
tlpUpsBatteryPackIdentSKU DisplayString }
tlpUpsBatteryPackIdentIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups battery pack."
::= { tlpUpsBatteryPackIdentEntry 1 }
tlpUpsBatteryPackIdentManufacturer OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The manufacturer of the battery pack. If the device does not
support this value, then the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackIdentEntry 2 }
tlpUpsBatteryPackIdentModel OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The model or device name of the battery pack. If the device does not
support this value, then the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackIdentEntry 3 }
tlpUpsBatteryPackIdentSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The serial number of the battery pack. If the device does not support
this value, then the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackIdentEntry 4 }
tlpUpsBatteryPackIdentFirmware OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The firmware of the battery pack. If the device does not support this
value, then the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackIdentEntry 5 }
tlpUpsBatteryPackIdentSKU OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The SKU of the battery pack. If the device does not support this value,
then the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackIdentEntry 6 }
tlpUpsBatteryPackConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsBatteryConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The battery configuration details for each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss managed by the
agent as reported by upsIdentNumUps and the number of battery
battery packs per each as reported by tlpUpsNumBatteryPacks."
::= { tlpUpsBattery 4 }
tlpUpsBatteryPackConfigEntry OBJECT-TYPE
SYNTAX TlpUpsBatteryConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
battery pack managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsBatteryPackIdentIndex }
::= { tlpUpsBatteryPackConfigTable 1 }
TlpUpsBatteryConfigEntry ::= SEQUENCE {
tlpUpsBatteryPackConfigChemistry INTEGER,
tlpUpsBatteryPackConfigStyle INTEGER,
tlpUpsBatteryPackConfigLocation INTEGER,
tlpUpsBatteryPackConfigStrings Unsigned32,
tlpUpsBatteryPackConfigBatteriesPerString Unsigned32,
tlpUpsBatteryPackConfigCellsPerBattery INTEGER,
tlpUpsBatteryPackConfigNumBatteries Unsigned32,
tlpUpsBatteryPackConfigCapacityUnits INTEGER,
tlpUpsBatteryPackConfigDesignCapacity Unsigned32,
tlpUpsBatteryPackConfigCellCapacity Unsigned32,
tlpUpsBatteryPackConfigMinCellVoltage Unsigned32,
tlpUpsBatteryPackConfigMaxCellVoltage Unsigned32,
tlpUpsBatteryPackConfigRechargeable TruthValue,
tlpUpsBatteryPackConfigFullChargeCapacity Unsigned32 }
tlpUpsBatteryPackConfigChemistry OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
leadAcid(1),
nickelCadmium(2),
lithiumIon(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of battery pack."
::= { tlpUpsBatteryPackConfigEntry 1 }
tlpUpsBatteryPackConfigStyle OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
nonsmart(1),
smart(2),
bms(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The style of battery pack."
::= { tlpUpsBatteryPackConfigEntry 2 }
tlpUpsBatteryPackConfigLocation OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
internal(1),
external(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The location of the battery pack."
::= { tlpUpsBatteryPackConfigEntry 3 }
tlpUpsBatteryPackConfigStrings OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of series strings in parallel contained in the battery
pack. If the device does not support this value, then the agent will
report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 4 }
tlpUpsBatteryPackConfigBatteriesPerString OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of battery per each string in the battery pack. If the
device does not support this value, then the agent will report
ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 5 }
tlpUpsBatteryPackConfigCellsPerBattery OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of cells per battery.."
::= { tlpUpsBatteryPackConfigEntry 6 }
tlpUpsBatteryPackConfigNumBatteries OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total number of batteries contained in the battery pack. If the device
does not support this value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 7 }
tlpUpsBatteryPackConfigCapacityUnits OBJECT-TYPE
SYNTAX INTEGER {
mAHr(0),
mWHr(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The units of measurement used for tlpUpsBatteryPackConfigDesignCapacity and
tlpUpsBatteryPackConfigCellCapacity. If supported, this value will report either
mAHR(1), amps per hour, or mWhr(1), watts per hour. If the device does not
support this value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 8 }
tlpUpsBatteryPackConfigDesignCapacity OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The theoretical or nominal capacity of a new battery pack in the measurement
defined by tlpUpsBatteryPackConfigCapacityUnits. If the device does not support
this value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 9 }
tlpUpsBatteryPackConfigCellCapacity OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The capacity of the batteries in the measurement defined by
tlpUpsBatteryPackConfigCapacityUnits. If the device does not support this value,
then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 10 }
tlpUpsBatteryPackConfigMinCellVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum cell voltage for the batteries. If the device does not support
this value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 11 }
tlpUpsBatteryPackConfigMaxCellVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum cell voltage for the batteries. If the device does not support
this value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 12 }
tlpUpsBatteryPackConfigRechargeable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether this battery pack is rechargeable."
::= { tlpUpsBatteryPackConfigEntry 13 }
tlpUpsBatteryPackConfigFullChargeCapacity OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The predicted capacity of the battery pack when fully charged in the measurement
defined by tlpUpsBatteryPackConfigCapacityUnits. If the device does not support
this value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackConfigEntry 14 }
tlpUpsBatteryPackDetailTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsBatteryPackDetailEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The details of each battery pack for each ups in the device
table. This is a sparse dependent table, and will contain the
number of entries based upon the number of upss and battery
packs managed by the agent as reported by tlpUpsIdentNumUps
and tlpUpsIdentNumBatteryPacks."
::= { tlpUpsBattery 5 }
tlpUpsBatteryPackDetailEntry OBJECT-TYPE
SYNTAX TlpUpsBatteryPackDetailEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
battery system managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsBatteryPackIdentIndex }
::= { tlpUpsBatteryPackDetailTable 1 }
TlpUpsBatteryPackDetailEntry ::= SEQUENCE {
tlpUpsBatteryPackDetailCondition INTEGER,
tlpUpsBatteryPackDetailTemperatureC Unsigned32,
tlpUpsBatteryPackDetailTemperatureF Unsigned32,
tlpUpsBatteryPackDetailAge Unsigned32,
tlpUpsBatteryPackDetailLastReplaceDate DisplayString,
tlpUpsBatteryPackDetailNextReplaceDate DisplayString,
tlpUpsBatteryPackDetailCycleCount Unsigned32 }
tlpUpsBatteryPackDetailCondition OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
good(1),
weak(2),
bad(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The condition of the battery. A bad battery should be replaced."
::= { tlpUpsBatteryPackDetailEntry 1 }
tlpUpsBatteryPackDetailTemperatureC OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the ups Battery casing."
::= { tlpUpsBatteryPackDetailEntry 2 }
tlpUpsBatteryPackDetailTemperatureF OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the ups Battery casing."
::= { tlpUpsBatteryPackDetailEntry 3 }
tlpUpsBatteryPackDetailAge OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Years"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The age of the battery in tenths of years. This is equal to the current
date minus tlpUpsBatteryPackDetailLastReplaceDate."
::= { tlpUpsBatteryPackDetailEntry 4 }
tlpUpsBatteryPackDetailLastReplaceDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The date when the batteries were last replaced in yyyy-mm-dd format."
::= { tlpUpsBatteryPackDetailEntry 5 }
tlpUpsBatteryPackDetailNextReplaceDate OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The date when the batteries should next be replaced in yyyy-mm-dd
format."
::= { tlpUpsBatteryPackDetailEntry 6 }
tlpUpsBatteryPackDetailCycleCount OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of times the battery went into invert mode. This number
is incremented by 1 each time the unit goes on battery mode (with
the exception of Self Test mode). If the device does not support this
value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsBatteryPackDetailEntry 7 }
tlpUpsInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps."
::= { tlpUpsInput 1 }
tlpUpsInputEntry OBJECT-TYPE
SYNTAX TlpUpsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to all input lines per
each ups managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpUpsInputTable 1 }
TlpUpsInputEntry ::= SEQUENCE {
tlpUpsInputLineBads INTEGER,
tlpUpsInputNominalVoltage Unsigned32,
tlpUpsInputNominalFrequency Unsigned32,
tlpUpsInputLowTransferVoltage Unsigned32,
tlpUpsInputLowTransferVoltageLowerBound Unsigned32,
tlpUpsInputLowTransferVoltageUpperBound Unsigned32,
tlpUpsInputHighTransferVoltage Unsigned32,
tlpUpsInputHighTransferVoltageLowerBound Unsigned32,
tlpUpsInputHighTransferVoltageUpperBound Unsigned32,
tlpUpsInputCurrentTotal Unsigned32,
tlpUpsInputLowTransferVoltageResetTolerance Unsigned32,
tlpUpsInputHighTransferVoltageResetTolerance Unsigned32,
tlpUpsInputTransformerStatus INTEGER,
tlpUpsInputAvrTransitionCount Unsigned32,
tlpUpsInputSource INTEGER }
tlpUpsInputLineBads OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A count of the number of times the input entered an out-of-tolerance
condition as defined by the manufacturer. This count is incremented
by one each time the input transitions from zero out-of-tolerance
lines to one or more input lines out-of-tolerance. This value is not
supported on all units. If the ups does not support this value, then
the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsInputEntry 1 }
tlpUpsInputNominalVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsInputEntry 2 }
tlpUpsInputNominalFrequency OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line frequency. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsInputEntry 3 }
tlpUpsInputLowTransferVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum line voltage allowed before the ups transfers to battery
backup."
::= { tlpUpsInputEntry 4 }
tlpUpsInputLowTransferVoltageLowerBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lower boundary value of tlpUpsInputLowTransferVoltage as dictated
by the hardware of the unit."
::= { tlpUpsInputEntry 5 }
tlpUpsInputLowTransferVoltageUpperBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The upper boundary value of tlpUpsInputLowTransferVoltage as dictated
by the hardware of the unit."
::= { tlpUpsInputEntry 6 }
tlpUpsInputHighTransferVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum line voltage allowed before the ups system transfers to
battery backup."
::= { tlpUpsInputEntry 7 }
tlpUpsInputHighTransferVoltageLowerBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lower boundary value of tlpUpsInputHighTransferVoltage as dictated
by the hardware of the unit."
::= { tlpUpsInputEntry 8 }
tlpUpsInputHighTransferVoltageUpperBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The upper boundary value of tlpUpsInputHighTransferVoltage as dictated
by the hardware of the unit."
::= { tlpUpsInputEntry 9 }
tlpUpsInputCurrentTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The aggregate total of conductor currents. If the ups does not support this value,
then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsInputEntry 10 }
tlpUpsInputLowTransferVoltageResetTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"If a unit is transferred to battery backup due to under-voltage, the
line voltage has to rise above this value from tlpUpsConfigLowVoltageTransfer,
before the unit switched back to the AC input."
::= { tlpUpsInputEntry 11 }
tlpUpsInputHighTransferVoltageResetTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"If an input transferred to battery backup due to over-voltage, the line voltage
on the input source has to fall below this value from tlpUpsConfigHighVoltageTransfer,
before the unit switched back to the AC input."
::= { tlpUpsInputEntry 12 }
tlpUpsInputTransformerStatus OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
reducing(1),
boosting(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the status of the transformer as to whether it is presently reducing or
boosting the input."
::= { tlpUpsInputEntry 13 }
tlpUpsInputAvrTransitionCount OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of times the automatic voltage regulating transformer transitions from
a normal state to either boosting or reducing. This number is incremented by 1 each
time a transition occurs. Use tlpUpsControlResetAvrTransitionCount to reset the count.
If the ups does not support this value, then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpUpsInputEntry 14 }
tlpUpsInputSource OBJECT-TYPE
SYNTAX INTEGER {
utility(0),
battery(1),
other(2),
none(3),
testing(4) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes the current input source for the ups."
::= { tlpUpsInputEntry 15 }
tlpUpsInputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input phase details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps and tlpUpsIdentNumPhases."
::= { tlpUpsInput 2 }
tlpUpsInputPhaseEntry OBJECT-TYPE
SYNTAX TlpUpsInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
input phase managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsInputPhaseIndex }
::= { tlpUpsInputPhaseTable 1 }
TlpUpsInputPhaseEntry ::= SEQUENCE {
tlpUpsInputPhaseIndex Unsigned32,
tlpUpsInputPhaseFrequency Unsigned32,
tlpUpsInputPhaseVoltage Unsigned32,
tlpUpsInputPhaseVoltageMin Unsigned32,
tlpUpsInputPhaseVoltageMax Unsigned32,
tlpUpsInputPhaseCurrent Unsigned32,
tlpUpsInputPhasePower Unsigned32 }
tlpUpsInputPhaseIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups input phase."
::= { tlpUpsInputPhaseEntry 1 }
tlpUpsInputPhaseFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present input frequency for a given input line."
::= { tlpUpsInputPhaseEntry 2 }
tlpUpsInputPhaseVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input voltage for a given input line."
::= { tlpUpsInputPhaseEntry 3 }
tlpUpsInputPhaseVoltageMin OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpUpsInputPhaseVoltageMin or tlpUpsInputPhaseVoltageMax using
agent version below 20, both will be reset to their appropriate
minimum and maximum values. Writes are deprecated as of agent
version 20. Use tlpUpsControlResetInputVoltageMinMax to reset
this value."
::= { tlpUpsInputPhaseEntry 4 }
tlpUpsInputPhaseVoltageMax OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpUpsInputPhaseVoltageMin or tlpUpsInputPhaseVoltageMax using
agent version below 20, both will be reset to their appropriate
minimum and maximum values. Writes are deprecated as of agent
version 20. Use tlpUpsControlResetInputVoltageMinMax to reset
this value."
::= { tlpUpsInputPhaseEntry 5 }
tlpUpsInputPhaseCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input current."
::= { tlpUpsInputPhaseEntry 6 }
tlpUpsInputPhasePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input true power."
::= { tlpUpsInputPhaseEntry 7 }
tlpUpsOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output details of each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumUps."
::= { tlpUpsOutput 1 }
tlpUpsOutputEntry OBJECT-TYPE
SYNTAX TlpUpsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
output line managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpUpsOutputTable 1 }
TlpUpsOutputEntry ::= SEQUENCE {
tlpUpsOutputSource INTEGER,
tlpUpsOutputNominalVoltage Unsigned32,
tlpUpsOutputFrequency Unsigned32,
tlpUpsOutputVARating Unsigned32,
tlpUpsOutputPowerFactor Unsigned32,
tlpUpsOutputTotalUtilization INTEGER,
tlpUpsOutputPowerRating Unsigned32,
tlpUpsOutputChargerCurrent Unsigned32,
tlpUpsOutputCurrentRating Unsigned32,
tlpUpsOutputEfficiency INTEGER }
tlpUpsOutputSource OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
other(1),
none(2),
normal(3),
bypass(4),
battery(5),
boosting(6),
reducing(7),
second(8),
economy(9),
testing(10) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power. The enumeration none(2) indicates
that there is no source of output power (and therefore no output power),
for example, the device has an open circuit breaker."
::= { tlpUpsOutputEntry 1 }
tlpUpsOutputNominalVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the output voltage. This value may not be
supported on all models. If not supported, the agent reports
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputEntry 2 }
tlpUpsOutputFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output frequency. The output frequency on most ups
devices is common across all output lines. Some ups devices, however,
maintain the output frequency per each line. If a common frequency is
supported by the ups, then this frequency will contain the common
frequency value. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputEntry 3 }
tlpUpsOutputVARating OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The VA Rating of the ups. This value may not be
supported on all models. If not supported, the agent reports
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputEntry 4 }
tlpUpsOutputPowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of output power factor."
::= { tlpUpsOutputEntry 5 }
tlpUpsOutputTotalUtilization OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total percentage of the ups power capacity presently being
used on the ups measured in hundredths of a percent."
::= { tlpUpsOutputEntry 6 }
tlpUpsOutputPowerRating OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ac output apparent power rating. This value may not be
supported on all models. If not supported, the agent reports
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputEntry 7 }
tlpUpsOutputChargerCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The charger current. If not supported, this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputEntry 8 }
tlpUpsOutputCurrentRating OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output current rating. If not supported, this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputEntry 9 }
tlpUpsOutputEfficiency OBJECT-TYPE
SYNTAX INTEGER
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present measurement of efficiency of output power conversion. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputEntry 10 }
tlpUpsOutputLineTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsOutputLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output line details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps."
::= { tlpUpsOutput 2 }
tlpUpsOutputLineEntry OBJECT-TYPE
SYNTAX TlpUpsOutputLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
output line managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsOutputLineIndex }
::= { tlpUpsOutputLineTable 1 }
TlpUpsOutputLineEntry ::= SEQUENCE {
tlpUpsOutputLineIndex Unsigned32,
tlpUpsOutputLineVoltage Unsigned32,
tlpUpsOutputLineCurrent Unsigned32,
tlpUpsOutputLineActivePower Unsigned32,
tlpUpsOutputLineUtilization INTEGER,
tlpUpsOutputLineFrequency Unsigned32,
tlpUpsOutputLineCurrentMin Unsigned32,
tlpUpsOutputLineCurrentMax Unsigned32,
tlpUpsOutputLineApparentPower Unsigned32,
tlpUpsOutputLinePowerKVA Unsigned32,
tlpUpsOutputLinePowerKW Unsigned32,
tlpUpsOutputLine24hrEnergy Unsigned32,
tlpUpsOutputLineWattHours Unsigned32,
tlpUpsOutputLinePeakPower Unsigned32 }
tlpUpsOutputLineIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups output line."
::= { tlpUpsOutputLineEntry 1 }
tlpUpsOutputLineVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present output voltage for a given output line."
::= { tlpUpsOutputLineEntry 2 }
tlpUpsOutputLineCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output current, in hundredths of amps, for a given line. The actual
precision of this value, whether a whole number, tenths or hundredths, is
returned by tlpUpsDeviceOutputCurrentPrecision."
::= { tlpUpsOutputLineEntry 3 }
tlpUpsOutputLineActivePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output true power."
::= { tlpUpsOutputLineEntry 4 }
tlpUpsOutputLineUtilization OBJECT-TYPE
SYNTAX INTEGER (0..200)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the ups power capacity presently being used on
this output line, i.e., the greater of the percent load of true
power capacity and the percent load of VA."
::= { tlpUpsOutputLineEntry 5 }
tlpUpsOutputLineFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output frequency on this output line. The output frequency on
most ups devices is common across all output lines. Some ups devices, however,
maintain the output frequency per each line. If a per line frequency is
supported by the ups, then this frequency value will reports the value of this
line. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputLineEntry 6 }
tlpUpsOutputLineCurrentMin OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpUpsDeviceOutputCurrentPrecision. Use
tlpUpsControlResetOutputCurrentMinMax to reset this value."
::= { tlpUpsOutputLineEntry 7 }
tlpUpsOutputLineCurrentMax OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpUpsDeviceOutputCurrentPrecision. Use
tlpUpsControlResetOutputCurrentMinMax to reset this value."
::= { tlpUpsOutputLineEntry 8 }
tlpUpsOutputLineApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output apparent power."
::= { tlpUpsOutputLineEntry 9 }
tlpUpsOutputLinePowerKVA OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of apparent power being used."
::= { tlpUpsOutputLineEntry 10 }
tlpUpsOutputLinePowerKW OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of active power being used."
::= { tlpUpsOutputLineEntry 11 }
tlpUpsOutputLine24hrEnergy OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption using present value
of tlpUpsOutputLinePowerKW."
::= { tlpUpsOutputLineEntry 12 }
tlpUpsOutputLineWattHours OBJECT-TYPE
SYNTAX Unsigned32
UNITS "WH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of watt hours of energy utilized in the past 24 hours. Use
tlpUpsControlResetWattHours to reset the watt hours calculation algorithm."
::= { tlpUpsOutputLineEntry 13 }
tlpUpsOutputLinePeakPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum 1 second average power value since the last reset. Use
tlpUpsControlResetPeakPower to reset the peak power calculations."
::= { tlpUpsOutputLineEntry 14 }
tlpUpsBypassTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsBypassEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The bypass details of each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumUps."
::= { tlpUpsBypass 1 }
tlpUpsBypassEntry OBJECT-TYPE
SYNTAX TlpUpsBypassEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to all input lines per
each ups managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpUpsBypassTable 1 }
TlpUpsBypassEntry ::= SEQUENCE {
tlpUpsBypassFrequency Unsigned32,
tlpUpsBypassNominalFrequency Unsigned32 }
tlpUpsBypassFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass frequency."
::= { tlpUpsBypassEntry 1 }
tlpUpsBypassNominalFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the battery frequency. This value may not
be supported on all models. If not supported, this agent will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsBypassEntry 2 }
tlpUpsBypassLineTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsBypassLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The bypass line details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps."
::= { tlpUpsBypass 2 }
tlpUpsBypassLineEntry OBJECT-TYPE
SYNTAX TlpUpsBypassLineEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular
bypass line managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsBypassLineIndex }
::= { tlpUpsBypassLineTable 1 }
TlpUpsBypassLineEntry ::= SEQUENCE {
tlpUpsBypassLineIndex Unsigned32,
tlpUpsBypassLineVoltage Unsigned32,
tlpUpsBypassLineCurrent Unsigned32,
tlpUpsBypassLinePower Unsigned32 }
tlpUpsBypassLineIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The bypass line identifier."
::= { tlpUpsBypassLineEntry 1 }
tlpUpsBypassLineVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass voltage."
::= { tlpUpsBypassLineEntry 2 }
tlpUpsBypassLineCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present bypass current."
::= { tlpUpsBypassLineEntry 3 }
tlpUpsBypassLinePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present true power conveyed by the bypass."
::= { tlpUpsBypassLineEntry 4 }
tlpUpsOutletTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The details of each ups outlet in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported
by tlpUpsIdentNumUps."
::= { tlpUpsOutlet 1 }
tlpUpsOutletEntry OBJECT-TYPE
SYNTAX TlpUpsOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular outlet
managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsOutletIndex }
::= { tlpUpsOutletTable 1 }
TlpUpsOutletEntry ::= SEQUENCE {
tlpUpsOutletIndex Unsigned32,
tlpUpsOutletName DisplayString,
tlpUpsOutletDescription DisplayString,
tlpUpsOutletState INTEGER,
tlpUpsOutletControllable TruthValue,
tlpUpsOutletCommand INTEGER,
tlpUpsOutletVoltage Unsigned32,
tlpUpsOutletCurrent Unsigned32,
tlpUpsOutletActivePower Unsigned32,
tlpUpsOutletRampAction INTEGER,
tlpUpsOutletRampDelay Integer32,
tlpUpsOutletShedAction INTEGER,
tlpUpsOutletShedDelay Integer32,
tlpUpsOutletGroup Integer32,
tlpUpsOutletBank Integer32,
tlpUpsOutletCircuit Integer32,
tlpUpsOutletPhase INTEGER,
tlpUpsOutletReceptacleType INTEGER,
tlpUpsOutletPowerFactor INTEGER,
tlpUpsOutletApparentPower Unsigned32,
tlpUpsOutletReactivePower Integer32,
tlpUpsOutletFrequency Unsigned32,
tlpUpsOutletUtilization Unsigned32,
tlpUpsOutlet24hrEnergy Unsigned32,
tlpUpsOutletOvercurrent TruthValue }
tlpUpsOutletIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups outlet."
::= { tlpUpsOutletEntry 1 }
tlpUpsOutletName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-definable string identifying the name of the outlet."
::= { tlpUpsOutletEntry 2 }
tlpUpsOutletDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-definable string identifying the device(s) connected to
the given outlet."
::= { tlpUpsOutletEntry 3 }
tlpUpsOutletState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the outlet."
::= { tlpUpsOutletEntry 4 }
tlpUpsOutletControllable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether this outlet is controllable."
::= { tlpUpsOutletEntry 5 }
tlpUpsOutletCommand OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value
to turnOff(1) will turn off the outlet. Setting this value
to turnOn(2) will turn on the outlet. Setting this value to
cycle(3) will turn the outlet off, then turn it back on."
::= { tlpUpsOutletEntry 6 }
tlpUpsOutletVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will always return ERROR_NO_SUCH_NAME.
Device-wide support for receptacle voltage measurements is denoted
by tlpUpsSupportsOutletVoltage."
::= { tlpUpsOutletEntry 7 }
tlpUpsOutletCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will always return ERROR_NO_SUCH_NAME.
Device-wide support for receptacle current measurements is denoted
by tlpUpsSupportsCurrent."
::= { tlpUpsOutletEntry 8 }
tlpUpsOutletActivePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output power of a given outlet. If the power measurement is
not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this value will
always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle
power measurements is denoted by tlpUpsSupportsPower."
::= { tlpUpsOutletEntry 9 }
tlpUpsOutletRampAction OBJECT-TYPE
SYNTAX INTEGER {
remainOff(0),
turnOnAfterDelay(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutletEntry 10 }
tlpUpsOutletRampDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutletEntry 11 }
tlpUpsOutletShedAction OBJECT-TYPE
SYNTAX INTEGER {
remainOn(0),
turnOffAfterDelay(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutletEntry 12 }
tlpUpsOutletShedDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpUpsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsOutletEntry 13 }
tlpUpsOutletGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The tlpUpsOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped."
::= { tlpUpsOutletEntry 14 }
tlpUpsOutletBank OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"This is reported as a bank number, but it is rather an internal
number unrelated to a bank as silk-screened on many devices and is
unrelated to and often confused with tlpUpsOutletCircuit. The value
reported is of no commercial use and was deprecated in agent
version 20."
::= { tlpUpsOutletEntry 15 }
tlpUpsOutletCircuit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which circuit the given outlet is wired."
::= { tlpUpsOutletEntry 16 }
tlpUpsOutletPhase OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
phase1(1),
phase2(2),
phase3(3),
phase1-2(4),
phase2-3(5),
phase3-1(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which phase or phases the given outlet is
associated. For single phase devices, this object will
always return phase1(1). For 3-phase devices with outlets
wired to a single phase, this object will return phase1(1),
phase2(2) or phase3(3). For 3-phase devices with outlets
wired to two phases, this object will return phase1-2(4)
for phases 1 and 2, phase2-3(5) for phases 2 and 3, and
phase3-1(6) for phases 3 and 1. Devices that do not report
phase connections will return unknown(0)."
::= { tlpUpsOutletEntry 17 }
tlpUpsOutletReceptacleType OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
nema-515R(1),
nema-520R(2),
nema-530R(3),
nema-L515R(4),
nema-L520R(5),
nema-L530R(6),
nema-L615R(7),
nema-L620R(8),
nema-L630R(9),
nema-L1430R(10),
nema-L1520R(11),
nema-L1530R(12),
nema-L2120R(13),
nema-L2130R(14),
nema-L2230R(15),
iec-309-1620(16),
iec-309-3032(17),
iec-309-6063(18),
iec-320-C13(19),
iec-320-C14(20),
iec-320-C15(21),
iec-320-C17(22),
iec-320-C19(23),
iec-320-C20(24) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of receptacle for this outlet. Not all devices report
receptacle types. The value will return unknown(0) when not supported."
::= { tlpUpsOutletEntry 18 }
tlpUpsOutletPowerFactor OBJECT-TYPE
SYNTAX INTEGER (0..200)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor for this outlet."
::= { tlpUpsOutletEntry 19 }
tlpUpsOutletApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The apparent power of this outlet."
::= { tlpUpsOutletEntry 20 }
tlpUpsOutletReactivePower OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reactive power of this outlet."
::= { tlpUpsOutletEntry 21 }
tlpUpsOutletFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The frequency of this outlet."
::= { tlpUpsOutletEntry 22 }
tlpUpsOutletUtilization OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of utilization of this outlet."
::= { tlpUpsOutletEntry 23 }
tlpUpsOutlet24hrEnergy OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption of this outlet."
::= { tlpUpsOutletEntry 24 }
tlpUpsOutletOvercurrent OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether this outlet is in an overcurrent condition."
::= { tlpUpsOutletEntry 25 }
tlpUpsOutletGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The receptacle grouping details of each ups in device table.
This is a sparse dependent table, and will contain the number
of entries based upon the value of tlpUpsIdentNumOutletGroups per
each device."
::= { tlpUpsOutlet 2 }
tlpUpsOutletGroupEntry OBJECT-TYPE
SYNTAX TlpUpsOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular outlet
group managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsOutletGroupIndex }
::= { tlpUpsOutletGroupTable 1 }
TlpUpsOutletGroupEntry ::= SEQUENCE {
tlpUpsOutletGroupIndex Unsigned32,
tlpUpsOutletGroupRowStatus RowStatus,
tlpUpsOutletGroupName DisplayString,
tlpUpsOutletGroupDescription DisplayString,
tlpUpsOutletGroupState INTEGER,
tlpUpsOutletGroupCommand INTEGER }
tlpUpsOutletGroupIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups outlet group."
::= { tlpUpsOutletGroupEntry 1 }
tlpUpsOutletGroupRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Row status for the tlpUpsOutletGroupTable"
::= { tlpUpsOutletGroupEntry 2 }
tlpUpsOutletGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of this outlet group."
::= { tlpUpsOutletGroupEntry 3 }
tlpUpsOutletGroupDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A description for this outlet group."
::= { tlpUpsOutletGroupEntry 4 }
tlpUpsOutletGroupState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2),
mixed(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the outlet group. This value will report
off(1) if all outlets in the group are off, on(2) if all outlets
in the group are on, mixed(3) if some outlets in the group are
off and others are on, or unknown(0) if the state of the outlets
cannot be determined."
::= { tlpUpsOutletGroupEntry 5 }
tlpUpsOutletGroupCommand OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value to
turnOff(1) will turn off every outlet associated with the group.
Setting this value to turnOn(2) will turn on every outlet associated
with the group. Setting this value to cycle(3) will turn off every
outlet associated with the group, then turn each outlet back on."
::= { tlpUpsOutletGroupEntry 6 }
tlpUpsWatchdogTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsWatchdogEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The watchdog details of each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss."
::= { tlpUpsWatchdog 1 }
tlpUpsWatchdogEntry OBJECT-TYPE
SYNTAX TlpUpsWatchdogEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing watchdog details for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsWatchdogTable 1 }
TlpUpsWatchdogEntry ::= SEQUENCE {
tlpUpsWatchdogSupported TruthValue,
tlpUpsWatchdogSecsBeforeRestart Unsigned32,
tlpUpsWatchdogRestartAlarm INTEGER,
tlpUpsWatchdogStatus INTEGER,
tlpUpsWatchdogRetry INTEGER }
tlpUpsWatchdogSupported OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not this ups supports a watchdog restart."
::= { tlpUpsWatchdogEntry 1 }
tlpUpsWatchdogSecsBeforeRestart OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum number of seconds that can expire between polls that
the engine makes to the ups for data. If this time runs out, then
the ups will cycle its outputs. Set this to zero to turns disable
this feature."
::= { tlpUpsWatchdogEntry 2 }
tlpUpsWatchdogRestartAlarm OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates whether an optional alarm should sound when the Watchdog
function is triggered and cycle the ups receptacles."
::= { tlpUpsWatchdogEntry 3 }
tlpUpsWatchdogStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates whether the ups should monitor rs232 communications so as
to cycle the ups receptacles when a loss of communications occurs."
::= { tlpUpsWatchdogEntry 4 }
tlpUpsWatchdogRetry OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If enabled, the ups will automatically reset the watchdog timer when
it times out. This automatic re-arm of the watchdog function will only
occur up to 2 times if communications are not established before each
restart. The result will be if watchdog is enabled and communications
are lost, the ups will automatically reboot up to 3 times until
communications are re-established."
::= { tlpUpsWatchdogEntry 5 }
tlpUpsFanTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsFanEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The fan details for each ups in the device table. This is a sparse
dependent table, and will contain the number of entries based upon the
number of upss managed by the agent as reported by tlpUpsIdentNumFans."
::= { tlpUpsFan 1 }
tlpUpsFanEntry OBJECT-TYPE
SYNTAX TlpUpsFanEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular fan
managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsFanIndex }
::= { tlpUpsFanTable 1 }
TlpUpsFanEntry ::= SEQUENCE {
tlpUpsFanIndex Unsigned32,
tlpUpsFanLocation INTEGER,
tlpUpsFanStatus INTEGER,
tlpUpsFanSpeed Unsigned32,
tlpUpsFanActivationTemperatureDegF Integer32,
tlpUpsFanActivationTemperatureDegC Integer32 }
tlpUpsFanIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups fan."
::= { tlpUpsFanEntry 1 }
tlpUpsFanLocation OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
internal(1),
external(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The location of the fan."
::= { tlpUpsFanEntry 2 }
tlpUpsFanStatus OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operational status of the fan. This status is not supported on
all models with fans. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsFanEntry 3 }
tlpUpsFanSpeed OBJECT-TYPE
SYNTAX Unsigned32
UNITS "RPM"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The fan speed in rotations per minute. Fan speed is not supported on
all models with fans. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpUpsFanEntry 4 }
tlpUpsFanActivationTemperatureDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at which point the ups will turn on the fan. This value is
configured using tlpUpsConfigExternalFanActivationTemperatureDegF. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsFanEntry 5 }
tlpUpsFanActivationTemperatureDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at which point the ups will turn on the fan. This value is
configured using tlpUpsConfigExternalFanActivationTemperatureDegC. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsFanEntry 6 }
tlpUpsHeatsinkTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsHeatsinkEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of ups heatsink thermistor table entries. The number of entries
is given by the value of tlpUpsIdentNumHeatsinks."
::= { tlpUpsHeatsink 1 }
tlpUpsHeatsinkEntry OBJECT-TYPE
SYNTAX TlpUpsHeatsinkEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular heatsink
managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsHeatsinkIndex }
::= { tlpUpsHeatsinkTable 1 }
TlpUpsHeatsinkEntry ::= SEQUENCE {
tlpUpsHeatsinkIndex Unsigned32,
tlpUpsHeatsinkTemperatureC Integer32,
tlpUpsHeatsinkTemperatureF Integer32 }
tlpUpsHeatsinkIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups heatsink."
::= { tlpUpsHeatsinkEntry 1 }
tlpUpsHeatsinkTemperatureC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at the heatsink thermistor in tenths degrees Celsius.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsHeatsinkEntry 2 }
tlpUpsHeatsinkTemperatureF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at the heatsink thermistor in tenths degrees Fahrenheit.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsHeatsinkEntry 3 }
tlpUpsInputContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsInputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input contact details of each ups in the device table. The number of entries
is given by the value of tlpUpsIdentNumInputContacts."
::= { tlpUpsInputContact 1 }
tlpUpsInputContactEntry OBJECT-TYPE
SYNTAX TlpUpsInputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing input contact details for a particular ups."
INDEX { tlpDeviceIndex, tlpUpsInputContactIndex }
::= { tlpUpsInputContactTable 1 }
TlpUpsInputContactEntry ::= SEQUENCE {
tlpUpsInputContactIndex Unsigned32,
tlpUpsInputContactInAlarm INTEGER }
tlpUpsInputContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups input contact details."
::= { tlpUpsInputContactEntry 1 }
tlpUpsInputContactInAlarm OBJECT-TYPE
SYNTAX INTEGER {
notInAlarm(0),
inAlarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The alarm status of the input contact. Input contacts are not supported on
all models. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsInputContactEntry 2 }
tlpUpsOutputContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output contact details of each ups in the device table. The number of entries
is given by the value of tlpUpsIdentNumOuputContacts."
::= { tlpUpsOutputContact 1 }
tlpUpsOutputContactEntry OBJECT-TYPE
SYNTAX TlpUpsOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing output contact details for a particular ups."
INDEX { tlpDeviceIndex, tlpUpsOutputContactIndex }
::= { tlpUpsOutputContactTable 1 }
TlpUpsOutputContactEntry ::= SEQUENCE {
tlpUpsOutputContactIndex Unsigned32,
tlpUpsOutputContactInAlarm INTEGER }
tlpUpsOutputContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups output contact details."
::= { tlpUpsOutputContactEntry 1 }
tlpUpsOutputContactInAlarm OBJECT-TYPE
SYNTAX INTEGER {
notInAlarm(0),
inAlarm(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The alarm status of the output contact. Output contacts are not supported on
all models. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsOutputContactEntry 2 }
tlpUpsControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable controls for each ups in device table. This is a
sparse dependent table, and will contain some subset of devices
that are upss."
::= { tlpUpsControl 1 }
tlpUpsControlEntry OBJECT-TYPE
SYNTAX TlpUpsControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing controls for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsControlTable 1 }
TlpUpsControlEntry ::= SEQUENCE {
tlpUpsControlSelfTest TruthValue,
tlpUpsControlRamp TruthValue,
tlpUpsControlShed TruthValue,
tlpUpsControlUpsOn TruthValue,
tlpUpsControlUpsOff TruthValue,
tlpUpsControlUpsRestart TruthValue,
tlpUpsControlBypass INTEGER,
tlpUpsControlResetWattHours TruthValue,
tlpUpsControlCancelSelfTest TruthValue,
tlpUpsControlResetAllParameters TruthValue,
tlpUpsControlMuteBuzzer TruthValue,
tlpUpsControlResetBatteryTransitionCount TruthValue,
tlpUpsControlResetLastReasonForBypass TruthValue,
tlpUpsControlResetLastReasonStats TruthValue,
tlpUpsControlResetAvrTransitionCount TruthValue,
tlpUpsControlResetPeakPower TruthValue,
tlpUpsControlClearEventLog TruthValue }
tlpUpsControlSelfTest OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate a self test on the ups."
::= { tlpUpsControlEntry 1 }
tlpUpsControlRamp OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate the pre-designated ramp
sequence on the ups."
::= { tlpUpsControlEntry 2 }
tlpUpsControlShed OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate the pre-designated shed
sequence on the ups."
::= { tlpUpsControlEntry 3 }
tlpUpsControlUpsOn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the ups on."
::= { tlpUpsControlEntry 4 }
tlpUpsControlUpsOff OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the ups off."
::= { tlpUpsControlEntry 5 }
tlpUpsControlUpsRestart OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to restart the ups."
::= { tlpUpsControlEntry 6 }
tlpUpsControlBypass OBJECT-TYPE
SYNTAX INTEGER {
disable(0),
enable(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This switches the ups in and out of bypass mode. This value returns
the current bypass mode: disable(0) if the ups is not in bypass mode,
enable(1) if the ups is in bypass mode. Set to disable(0) to exit
bypass mode, or enable(1) to enter bypass mode. If switching bypass
mode is not supported, this value will return ERROR_NO_SUCH_NAME."
::= { tlpUpsControlEntry 7 }
tlpUpsControlResetWattHours OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the tlpUpsDeviceWattHoursTotal and
tlpUpsOutputLineWattHours calculation algorithms."
::= { tlpUpsControlEntry 8 }
tlpUpsControlCancelSelfTest OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to cancel the self test in progress."
::= { tlpUpsControlEntry 9 }
tlpUpsControlResetAllParameters OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset all configuration settings to the default values."
::= { tlpUpsControlEntry 10 }
tlpUpsControlMuteBuzzer OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to temporarily mute the audible alarm. This control is only
viable when tlpUpsConfigAudibleStatus is enabled(1) and the audible alarm is
sounding. The audible alarm will be muted and will reset when the active
alarm state clears. The audible alarm will sound again when the ups enters
a new alarm state. Set tlpUpsConfigAudibleStatus to disabled(0) if permanently
preventing the audible alarm from sounding is the desired outcome."
::= { tlpUpsControlEntry 11 }
tlpUpsControlResetBatteryTransitionCount OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the number of times the battery went into invert mode
as reported by tlpUpsBatteryPackDetailCycleCount."
::= { tlpUpsControlEntry 12 }
tlpUpsControlResetLastReasonForBypass OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset/clear the last reason the ups went into bypass."
::= { tlpUpsControlEntry 13 }
tlpUpsControlResetLastReasonStats OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset/clear the last reason for ac failure and last reason
for shutdown statistics."
::= { tlpUpsControlEntry 14 }
tlpUpsControlResetAvrTransitionCount OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset tlpUpsInputAvrTransitionCount."
::= { tlpUpsControlEntry 15 }
tlpUpsControlResetPeakPower OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the tlpUpsOutputLinePeakPower calculation algorithm."
::= { tlpUpsControlEntry 16 }
tlpUpsControlClearEventLog OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to clear the event log retained by the ups."
::= { tlpUpsControlEntry 17 }
tlpUpsControlOutputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsControlOutputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable output phase-specific controls for each ups in device
table. This is a sparse dependent table, and will contain some subset of
devices that are upss."
::= { tlpUpsControl 2 }
tlpUpsControlOutputPhaseEntry OBJECT-TYPE
SYNTAX TlpUpsControlOutputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular output
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsOutputLineIndex }
::= { tlpUpsControlOutputPhaseTable 1 }
TlpUpsControlOutputPhaseEntry ::= SEQUENCE {
tlpUpsControlResetOutputCurrentMinMax TruthValue }
tlpUpsControlResetOutputCurrentMinMax OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset tlpUpsOutputLineCurrentMin and tlpUpsOutputLineCurrentMax
to their appropriate minimum and maximum values. This value will return
ERROR_NO_SUCH_NAME if not supported."
::= { tlpUpsControlOutputPhaseEntry 1 }
tlpUpsControlInputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsControlInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable input phase-specific controls for each ups in device
table. This is a sparse dependent table, and will contain some subset of
devices that are upss."
::= { tlpUpsControl 3 }
tlpUpsControlInputPhaseEntry OBJECT-TYPE
SYNTAX TlpUpsControlInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular input
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsInputPhaseIndex }
::= { tlpUpsControlInputPhaseTable 1 }
TlpUpsControlInputPhaseEntry ::= SEQUENCE {
tlpUpsControlResetInputVoltageMinMax TruthValue }
tlpUpsControlResetInputVoltageMinMax OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset tlpUpsInputPhaseVoltageMin and tlpUpsInputPhaseVoltageMax
to their appropriate minimum and maximum values. Resetting the minimum and maximum
values for one phase on some devices will reset the values for all phases. This
value will return ERROR_NO_SUCH_NAME if not supported."
::= { tlpUpsControlInputPhaseEntry 1 }
tlpUpsConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration details of each ups in the device table. This is
a sparse dependent table, and will contain the number of entries
based upon the number of upss managed by the agent as reported by
tlpUpsIdentNumUps."
::= { tlpUpsConfig 1 }
tlpUpsConfigEntry OBJECT-TYPE
SYNTAX TlpUpsConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to all input lines per
each ups managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigTable 1 }
TlpUpsConfigEntry ::= SEQUENCE {
tlpUpsConfigInputVoltage Unsigned32,
tlpUpsConfigInputFrequency Unsigned32,
tlpUpsConfigOutputVoltage Unsigned32,
tlpUpsConfigOutputFrequency Unsigned32,
tlpUpsConfigAudibleStatus INTEGER,
tlpUpsConfigAutoBatteryTest INTEGER,
tlpUpsConfigAutoRestartAfterShutdown INTEGER,
tlpUpsConfigAutoRampOnTransition INTEGER,
tlpUpsConfigAutoShedOnTransition INTEGER,
tlpUpsConfigBypassLowerLimitPercent INTEGER,
tlpUpsConfigBypassUpperLimitPercent INTEGER,
tlpUpsConfigBypassLowerLimitVoltage Unsigned32,
tlpUpsConfigBypassUpperLimitVoltage Unsigned32,
tlpUpsConfigColdStart INTEGER,
tlpUpsConfigPowerStrategy INTEGER,
tlpUpsConfigFaultAction INTEGER,
tlpUpsConfigOffMode INTEGER,
tlpUpsConfigLineSensitivity INTEGER,
tlpUpsConfigLineQualifyTime Unsigned32,
tlpUpsConfigACPowerSenseType INTEGER,
tlpUpsConfigAcPresentStartMode INTEGER,
tlpUpsConfigBatteryCapacityCoefficient INTEGER,
tlpUpsConfigBatteryTemperatureCompensation INTEGER,
tlpUpsConfigBatteryTimedShutdownStatus INTEGER,
tlpUpsConfigBatteryTimedShutdownSeconds Unsigned32,
tlpUpsConfigBatteryMinCapacityToRestart INTEGER,
tlpUpsConfigShutdownCompletionBehavior INTEGER,
tlpUpsConfigEmergencyPowerOff INTEGER,
tlpUpsConfigEnergySavingSetting INTEGER,
tlpUpsConfigFrequencyConvertMode INTEGER,
tlpUpsConfigBatteryCapacityConfiguration INTEGER,
tlpUpsConfigAutoBatteryTestMinutes INTEGER,
tlpUpsConfigMaxBatteryChargerCurrent INTEGER }
tlpUpsConfigInputVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the value will be rejected and an appropriate error
message will be returned."
::= { tlpUpsConfigEntry 1 }
tlpUpsConfigInputFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal input frequency. On those devices which support read-write
access to this object, if there is an attempt to set this variable to a
value that is not supported, the request must be rejected and the agent
shall respond with an appropriate error message, i.e., badValue for
SNMPv1, or inconsistentValue for SNMPv2."
::= { tlpUpsConfigEntry 2 }
tlpUpsConfigOutputVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal value of the output voltage. This value may not be
supported on all models. If not supported, the agent reports
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the value will be rejected and an appropriate error
message will be returned."
::= { tlpUpsConfigEntry 3 }
tlpUpsConfigOutputFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal output frequency. On those devices which support read-write
access to this object, if there is an attempt to set this variable to a
value that is not supported, the request will be rejected and the agent
will respond with an appropriate error message."
::= { tlpUpsConfigEntry 4 }
tlpUpsConfigAudibleStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(1),
enabled(2),
muted(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The requested state of the audible alarm. When in the disabled state,
the audible alarm should never sound. The enabled state is self-
describing. Setting this object to muted(3) when the audible alarm is
sounding shall temporarily silence the alarm. It will remain muted until
it would normally stop sounding and the value returned for read operations
during this period shall equal muted(3). At the end of this period, the
value shall revert to enabled(2). Writes of the value muted(3) when the
audible alarm is not sounding shall be accepted but otherwise shall have no
effect."
::= { tlpUpsConfigEntry 5 }
tlpUpsConfigAutoBatteryTest OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
daily(1),
weekly(2),
biweekly(3),
monthly(4),
quarterly(5),
semiannually(6) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When disabled(0), the ups will not perform an automatic battery selftest.
When set to another value, the ups will perform an automatic selftest in
the approximate period defined by each respective enumerated value. This
feature is generally not recommended."
::= { tlpUpsConfigEntry 6 }
tlpUpsConfigAutoRestartAfterShutdown OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When enabled(1), the ups should autorestart after a shutdown from battery
mode if valid AC is applied. When disabled(0), the ups should not autorestart
when AC is restored and instead power up into standby mode."
::= { tlpUpsConfigEntry 7 }
tlpUpsConfigAutoRampOnTransition OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When enabled(1), the ups should perform its preconfigured ramp sequence when
valid AC is restored while in battery mode. If this value is not supported by
the ups, then this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 8 }
tlpUpsConfigAutoShedOnTransition OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When enabled(1), the ups should perform its preconfigured shed sequence when
valid AC is lost causing the ups to enter battery mode. If this value is not
supported by the ups, then this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 9 }
tlpUpsConfigBypassLowerLimitPercent OBJECT-TYPE
SYNTAX INTEGER (-20..-5)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lowest AC input voltage allowed to be output to the load while in bypass
mode. This setting is expressed as a percentage from nominal voltage. If this
value is not supported by the ups, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 10 }
tlpUpsConfigBypassUpperLimitPercent OBJECT-TYPE
SYNTAX INTEGER (5..20)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The highest AC input voltage allowed to be output to the load while in bypass
mode. This setting is expressed as a percentage from nominal voltage. If this
value is not supported by the ups, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 11 }
tlpUpsConfigBypassLowerLimitVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lowest AC input voltage allowed to be output to the load while in bypass
mode. If this value is not supported by the ups, then this value will always
return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 12 }
tlpUpsConfigBypassUpperLimitVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The highest AC input voltage allowed to be output to the load while in bypass
mode. If this value is not supported by the ups, then this value will always
return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 13 }
tlpUpsConfigColdStart OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option enables or disables the ability to turn the ups on without AC
supplied. If this value is not supported by the ups, then this value will
always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 14 }
tlpUpsConfigPowerStrategy OBJECT-TYPE
SYNTAX INTEGER {
maximumQuality(0),
maximumEfficiency(1),
constant50Hz(2),
constant60Hz(3),
constantAuto(4),
autoAdaptive(5) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configurable economic mode options for the ups. The online(0) mode is
the default configuration of most upss, which is synonymous as having the
economic mode disabled. The maximumEfficiency(1) mode is the typical configuration
to run in economy mode, which is synonymous as having the economic mode enabled.
Constant50Hz(2) is a power strategy, which fixes the output frequency at 50Hz.
Constant60Hz(3) is a power strategy, which fixes the output frequency at 60Hz.
ConstantAuto(4) regulates the output frequency at nominal input frequency.
AutoAdaptive(5) mode will cause the ups to automatically switch between
online(0), maximum quality, and maximumEfficiency(1), maximum efficiency, to improve
efficiency during stable utility periods and improve output regulation during
unstable utility periods. Not all values are supported by all upss. Most upss,
if supportive of economic mode, only supports online(0) and maximumEfficiency(1).
If the ups does not support economic mode, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 15 }
tlpUpsConfigFaultAction OBJECT-TYPE
SYNTAX INTEGER {
bypass(0),
standby(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines the action to take if the output needs to be shut down due to a
fault condition, limited by the type of fault incurred. When configured for
bypass(0), the ups will go to bypass on a fault condition. When configured
for standby(1), the ups will go to standby mode on a fault condition. Either
configuration will be valid as long as AC input is within normal line voltage
and frequency limits when the fault condition occurs. If the line is outside
these limits, the ups will turn off. If this value is not supported by the ups,
then this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 16 }
tlpUpsConfigOffMode OBJECT-TYPE
SYNTAX INTEGER {
standby(0),
bypass(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option governs what mode the ups should go into when AC input is
available, but the load is either off or not battery backed up. If this
setting is configured for bypass(1), the intention is that any time the ups
would normally go into standby mode, it would instead go into bypass mode. Note
that this setting does not dictate the mode for fault conditions, which is
governed by tlpUpsConfigFaultAction. If this value is not supported by the ups,
then this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 17 }
tlpUpsConfigLineSensitivity OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
reduced(1),
fullyReduced(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Adjusts the AC line voltage sensitivity setting. If this value is not supported
by the ups, then this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 18 }
tlpUpsConfigLineQualifyTime OBJECT-TYPE
SYNTAX Unsigned32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The amount of time the ups monitors line power quality for stability before ac power
is restored. If there is an attempt to set this variable to a
value that is not supported, the request will be rejected and the agent
will respond with an appropriate error message."
::= { tlpUpsConfigEntry 19 }
tlpUpsConfigACPowerSenseType OBJECT-TYPE
SYNTAX INTEGER {
generator(1),
ups(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option enables configuration of ups AC power sensing to maximize ups
operation for standard line power AC and generator power applications.
If this value is not supported by the ups, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 20 }
tlpUpsConfigAcPresentStartMode OBJECT-TYPE
SYNTAX INTEGER {
alwaysOff(0),
alwaysTurnOn(1),
lastState(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures how the ups will turn on when ac is present. alwaysOff will cause the
ups to NEVER autostart regardless of how it was shut down or the state of
tlpUpsConfigAutoRestartInverterShutdown. alwaysOn will cause the ups to ALWAYS
autostart regardless of how it was shut down or the state of
tlpUpsConfigAutoRestartInverterShutdown. lastState will cause the ups to autostart
based on the method used last subject to tlpUpsConfigAutoRestartInverterShutdown. The
agent will always return ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 21 }
tlpUpsConfigBatteryCapacityCoefficient OBJECT-TYPE
SYNTAX INTEGER (5..20)
UNITS "0.1"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Used to adjust the battery capacity as the battery ages."
::= { tlpUpsConfigEntry 22 }
tlpUpsConfigBatteryTemperatureCompensation OBJECT-TYPE
SYNTAX INTEGER {
twoAndOneHalf(5),
three(6),
threeAndOneHalf(7),
four(8) }
UNITS "mV"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option reduces related float voltages during high temperature conditions. If
this value is not supported by the ups, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigEntry 23 }
tlpUpsConfigBatteryTimedShutdownStatus OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables the ups device shutdown after tlpUpsConfigBatteryTimedShutdownSeconds seconds.
This shutdown occurs by the ups itself rather than by the LX card when installed. Whenever
enabled, tlpUpsConfigBatteryTimedShutdownSeconds will always revert to zero(0). The agent
will always return ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 24 }
tlpUpsConfigBatteryTimedShutdownSeconds OBJECT-TYPE
SYNTAX Unsigned32 (15..65534)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Enables the ups device shutdown after the specified number of seconds. Whenever set,
tlpUpsConfigBatteryTimedShutdownStatus will always become enabled. The agent will always
return ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 25 }
tlpUpsConfigBatteryMinCapacityToRestart OBJECT-TYPE
SYNTAX INTEGER (0..90)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Restart the ups with ac returns and tlpUpsConfigAutoRestartAfterShutdown is enabled, if
the battery capacity is more than the percentage (%) specified. The agent will always
return ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 26 }
tlpUpsConfigShutdownCompletionBehavior OBJECT-TYPE
SYNTAX INTEGER {
complete(0),
cancel(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures whether the ups should reboot the output if ac returns before a delay before
shutdown expires. The agent will always return ERROR_NO_SUCH_NAME when this feature is not
supported by the ups."
::= { tlpUpsConfigEntry 27 }
tlpUpsConfigEmergencyPowerOff OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures emergency power off (epo) functionality via the communications port."
::= { tlpUpsConfigEntry 28 }
tlpUpsConfigEnergySavingSetting OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the ups to shut down if the load level is less than the percent indicated after
five minutes in invert mode. A value less than five percent disables this feature whereas any
value five percent or greater enables this feature. The agent will always return
ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 29 }
tlpUpsConfigFrequencyConvertMode OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the frequency convert mode for the ups. The agent will always return
ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 30 }
tlpUpsConfigBatteryCapacityConfiguration OBJECT-TYPE
SYNTAX INTEGER (7..100)
UNITS "AH"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the ups battery capacity. Depending on the ups, not all values in the range apply.
The agent will always return ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 31 }
tlpUpsConfigAutoBatteryTestMinutes OBJECT-TYPE
SYNTAX INTEGER (1..255)
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the number of minutes a ups battery will be tested when a test occurs. The agent will
always return ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 32 }
tlpUpsConfigMaxBatteryChargerCurrent OBJECT-TYPE
SYNTAX INTEGER (0..255)
UNITS "Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the maximum charging current for ups battery. The agent will
always return ERROR_NO_SUCH_NAME when this feature is not supported by the ups."
::= { tlpUpsConfigEntry 33 }
tlpUpsConfigAutoRestartTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigAutoRestartEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configurable automatic restart options of each ups in device table.
This is a sparse dependent table, and will contain some subset of devices
that are upss. Not all options are available on all upss."
::= { tlpUpsConfig 2 }
tlpUpsConfigAutoRestartEntry OBJECT-TYPE
SYNTAX TlpUpsConfigAutoRestartEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing configurable automatic restart options for a particular
ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigAutoRestartTable 1 }
TlpUpsConfigAutoRestartEntry ::= SEQUENCE {
tlpUpsConfigAutoRestartInverterShutdown INTEGER,
tlpUpsConfigAutoRestartDelayedWakeup INTEGER,
tlpUpsConfigAutoRestartLowVoltageCutoff INTEGER,
tlpUpsConfigAutoRestartOverLoad INTEGER,
tlpUpsConfigAutoRestartOverTemperature INTEGER }
tlpUpsConfigAutoRestartInverterShutdown OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If enabled(1) and the ups is turned off from invert mode (via user
interaction), if line becomes valid, the ups will automatically go to line
mode. If disabled(0), the ups will turn back on and go to standby mode
instead."
::= { tlpUpsConfigAutoRestartEntry 1 }
tlpUpsConfigAutoRestartDelayedWakeup OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If enabled(1) and power fails during a DelayBeforeStartup and line remains
invalid after the timeout expires, the ups will be set to turn back on
automatically. If disabled(0), the ups will turn back on and go to standby
mode instead."
::= { tlpUpsConfigAutoRestartEntry 2 }
tlpUpsConfigAutoRestartLowVoltageCutoff OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If enabled(1) and the ups is turned off from invert mode (via low voltage
cutoff), if line becomes valid, the ups will automatically go to line mode.
If disabled(0), the ups will turn back on and go to standby mode instead."
::= { tlpUpsConfigAutoRestartEntry 3 }
tlpUpsConfigAutoRestartOverLoad OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If enabled(1) and the ups is turned off from invert mode (via overload), if
line becomes valid, the ups will automatically go to line mode. If disabled(0),
the ups will turn back on and go to standby mode instead."
::= { tlpUpsConfigAutoRestartEntry 4 }
tlpUpsConfigAutoRestartOverTemperature OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If enabled(1) and the ups is turned off from invert mode (via over temperature),
if line becomes valid, the ups will automatically go to line mode. If disabled(0),
the ups will turn back on and go to standby mode instead."
::= { tlpUpsConfigAutoRestartEntry 5 }
tlpUpsConfigThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configurable threshold options of each ups in device table. This
is a sparse dependent table, and will contain some subset of devices that
are upss. Not all options are available on all upss."
::= { tlpUpsConfig 3 }
tlpUpsConfigThresholdEntry OBJECT-TYPE
SYNTAX TlpUpsConfigThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing configurable threshold options for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigThresholdTable 1 }
TlpUpsConfigThresholdEntry ::= SEQUENCE {
tlpUpsConfigBatteryAgeThreshold Unsigned32,
tlpUpsConfigLowBatteryThreshold INTEGER,
tlpUpsConfigLowBatteryTime Unsigned32,
tlpUpsConfigOverLoadThreshold INTEGER,
tlpUpsConfigLowBatteryCriticalThreshold INTEGER,
tlpUpsConfigBatteryAgeWarningThreshold INTEGER,
tlpUpsConfigBatteryAgeCriticalThreshold INTEGER,
tlpUpsConfigLowBatteryRuntimeWarningThreshold Unsigned32,
tlpUpsConfigLowBatteryRuntimeCriticalThreshold Unsigned32 }
tlpUpsConfigBatteryAgeThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "months"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The number of months for a battery to be in service. The battery age alarm,
tlpUpsAlarmBatteryAgeAboveThreshold, is triggered when the current date
exceeds tlpUpsBatteryPackDetailLastReplaceDate by tlpUpsConfigBatteryAgeThreshold
months. This value was deprecated as of agent v2 and has become read-only. It
is superseded by tlpUpsConfigBatteryAgeWarningThreshold and expected to become
obsolete and not supported in a future release. All usages of this oid should be
modified to use tlpUpsConfigBatteryAgeWarningThreshold instead."
::= { tlpUpsConfigThresholdEntry 1 }
tlpUpsConfigLowBatteryThreshold OBJECT-TYPE
SYNTAX INTEGER (11..90)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value denotes the percentage of battery capacity remaining warning
level. The low battery alarm, tlpUpsAlarmLowBattery, is triggered when
tlpUpsEstimatedChargeRemaining drops below this value. This value must be
greater than tlpUpsConfigLowBatteryCriticalThreshold."
::= { tlpUpsConfigThresholdEntry 2 }
tlpUpsConfigLowBatteryTime OBJECT-TYPE
SYNTAX Unsigned32
UNITS "seconds"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The value in seconds of tlpUpsEstimatedMinutesRemaining at which a lowBattery
condition is declared. For agents which support only discrete (discontinuous)
values, then the agent shall round up to the next supported value. If the
requested value is larger than the largest supported value, then the largest
supported value shall be selected. This oid was deprecated in agent v20 and
superceded by tlpUpsConfigLowBatteryRuntimeWarningThreshold."
::= { tlpUpsConfigThresholdEntry 3 }
tlpUpsConfigOverLoadThreshold OBJECT-TYPE
SYNTAX INTEGER (5..105)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value denotes the percentage of load at which the overload condition
occurs. The overload alarm, tlpUpsAlarmOutputOverload, is triggered when the
percentage of output load exceeds this value. This value must be greater than
tlpUpsConfigOutputUtilizationWarningThreshold."
::= { tlpUpsConfigThresholdEntry 4 }
tlpUpsConfigLowBatteryCriticalThreshold OBJECT-TYPE
SYNTAX INTEGER (10..89)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value denotes the percentage of battery capacity remaining critical
level. This value must be less than tlpUpsConfigLowBatteryThreshold."
::= { tlpUpsConfigThresholdEntry 5 }
tlpUpsConfigBatteryAgeWarningThreshold OBJECT-TYPE
SYNTAX INTEGER (0..50)
UNITS "0.1 years"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of years for a battery to be in service, represented in tenths of years. The
battery age alarm, tlpUpsAlarmBatteryAgeAboveThreshold, is triggered when the current date
exceeds tlpUpsBatteryPackDetailLastReplaceDate by tlpUpsConfigBatteryAgeWarningThreshold
years. This value must be less than tlpUpsConfigBatteryAgeCriticalThreshold."
::= { tlpUpsConfigThresholdEntry 6 }
tlpUpsConfigBatteryAgeCriticalThreshold OBJECT-TYPE
SYNTAX INTEGER (0..50)
UNITS "0.1 years"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of years for a battery in service to be deemed critical, represented in tenths
of years. This value must be greater than tlpUpsConfigBatteryAgeWarningThreshold."
::= { tlpUpsConfigThresholdEntry 7 }
tlpUpsConfigLowBatteryRuntimeWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value in minutes of tlpUpsEstimatedMinutesRemaining at which a lowBattery
condition is declared. For agents which support only discrete (discontinuous)
values, then the agent shall round up to the next supported value. If the
requested value is larger than the largest supported value, then the largest
supported value shall be selected."
::= { tlpUpsConfigThresholdEntry 8 }
tlpUpsConfigLowBatteryRuntimeCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "minutes"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value in minutes of tlpUpsEstimatedMinutesRemaining at which a critical
lowBattery condition is declared. For agents which support only discrete
(discontinuous) values, then the agent shall round up to the next supported
value. If the requested value is larger than the largest supported value, then
the largest supported value shall be selected."
::= { tlpUpsConfigThresholdEntry 9 }
tlpUpsConfigVoltageTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigVoltageEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The voltage configuration details for each ups in device table. This
is a sparse dependent table, and will contain some subset of devices
that are upss. Not all options are available on all upss."
::= { tlpUpsConfig 4 }
tlpUpsConfigVoltageEntry OBJECT-TYPE
SYNTAX TlpUpsConfigVoltageEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing voltage configuration options for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigVoltageTable 1 }
TlpUpsConfigVoltageEntry ::= SEQUENCE {
tlpUpsConfigHighVoltageTransfer Unsigned32,
tlpUpsConfigHighVoltageResetTolerance Unsigned32,
tlpUpsConfigHighVoltageReset Unsigned32,
tlpUpsConfigLowVoltageTransfer Unsigned32,
tlpUpsConfigLowVoltageResetTolerance Unsigned32,
tlpUpsConfigLowVoltageReset Unsigned32 }
tlpUpsConfigHighVoltageTransfer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum line voltage allowed on the input source before the unit
disconnects the AC input connection."
::= { tlpUpsConfigVoltageEntry 1 }
tlpUpsConfigHighVoltageResetTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If an input connection is disconnected due to over-voltage, the line voltage on the input source
has to fall below tlpUpsConfigHighVoltageTransfer less tlpUpsConfigHighVoltageTransferResetTolerance
before the unit reconnects the AC input to input source."
::= { tlpUpsConfigVoltageEntry 2 }
tlpUpsConfigHighVoltageReset OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If an input connection is disconnected due to over-voltage, the line voltage on the input source
has to fall below tlpUpsConfigHighVoltageReset before the unit reconnects the AC input to input source."
::= { tlpUpsConfigVoltageEntry 3 }
tlpUpsConfigLowVoltageTransfer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum line voltage allowed before the unit disconnects the AC input
connection."
::= { tlpUpsConfigVoltageEntry 4 }
tlpUpsConfigLowVoltageResetTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If a unit is disconnected due to under-voltage or is not powered up yet, the line voltage
has to rise above tlpUpsConfigLowVoltageTransfer plus tlpUpsConfigLowVoltageTransferResetTolerance
before the unit reconnect the AC input to input source."
::= { tlpUpsConfigVoltageEntry 5 }
tlpUpsConfigLowVoltageReset OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If a unit is disconnected due to under-voltage or is not powered up yet, the line voltage
has to rise above tlpUpsConfigLowVoltageReset before the unit reconnect the AC input to input source."
::= { tlpUpsConfigVoltageEntry 6 }
tlpUpsConfigContact OBJECT IDENTIFIER::= { tlpUpsConfig 5 }
tlpUpsConfigContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each ups in device table. This
is a sparse dependent table, and will contain some subset of
devices that are upss. Not all options are available on all
upss."
::= { tlpUpsConfigContact 1 }
tlpUpsConfigContactEntry OBJECT-TYPE
SYNTAX TlpUpsConfigContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing contact configuration options for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigContactTable 1 }
TlpUpsConfigContactEntry ::= SEQUENCE {
tlpUpsConfigOutputContactBackupTimer Unsigned32 }
tlpUpsConfigOutputContactBackupTimer OBJECT-TYPE
SYNTAX Unsigned32 (0..480)
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This is the amount of runtime the ups supports in battery mode before sending
a configured output contact notification. Output contacts are not supported on all
models. If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigContactEntry 1 }
tlpUpsConfigInputContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigInputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input contact details of each ups in device table. the number of entries is
given by tlpUpsIdentNumInputContacts. This is a sparse dependent table, and will
contain some subset of devices that are upss. Not all options are available on all
upss."
::= { tlpUpsConfigContact 2 }
tlpUpsConfigInputContactEntry OBJECT-TYPE
SYNTAX TlpUpsConfigInputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing input contact details for a particular ups."
INDEX { tlpDeviceIndex, tlpUpsConfigInputContactIndex }
::= { tlpUpsConfigInputContactTable 1 }
TlpUpsConfigInputContactEntry ::= SEQUENCE {
tlpUpsConfigInputContactIndex Unsigned32,
tlpUpsConfigInputContactSetup INTEGER }
tlpUpsConfigInputContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups input contact details."
::= { tlpUpsConfigInputContactEntry 1 }
tlpUpsConfigInputContactSetup OBJECT-TYPE
SYNTAX INTEGER {
userDefined(0),
externalAlarm(1),
externalBatteryAlarm(2),
externalFanFailed(3),
doorUnlock(4)}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Input contact configuration options. Input contacts are not supported on
all models. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigInputContactEntry 2 }
tlpUpsConfigOutputContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Output contact details of each ups in device table. The number of entries is
given by tlpUpsIdentNumOutputContacts. This is a sparse dependent table, and
will contain some subset of devices that are upss. Not all options are available
on all upss."
::= { tlpUpsConfigContact 3 }
tlpUpsConfigOutputContactEntry OBJECT-TYPE
SYNTAX TlpUpsConfigOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing output contact details for a particular ups."
INDEX { tlpDeviceIndex, tlpUpsConfigOutputContactIndex }
::= { tlpUpsConfigOutputContactTable 1 }
TlpUpsConfigOutputContactEntry ::= SEQUENCE {
tlpUpsConfigOutputContactIndex Unsigned32,
tlpUpsConfigOutputContactSetup INTEGER }
tlpUpsConfigOutputContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ups output contact details."
::= { tlpUpsConfigOutputContactEntry 1 }
tlpUpsConfigOutputContactSetup OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
onBattery(1),
batteryLow(2),
timer(3),
alarm(4),
fault(5),
outputOff(6) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Output contact configuration options. Output contacts are not supported on
all models. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigOutputContactEntry 2 }
tlpUpsConfigDb9 OBJECT IDENTIFIER::= { tlpUpsConfig 6 }
tlpUpsConfigDb9InputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigDb9InputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each ups in device table. This
is a sparse dependent table, and will contain some subset of
devices that are upss. Not all options are available on all
upss."
::= { tlpUpsConfigDb9 1 }
tlpUpsConfigDb9InputEntry OBJECT-TYPE
SYNTAX TlpUpsConfigDb9InputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing contact configuration options for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigDb9InputTable 1 }
TlpUpsConfigDb9InputEntry ::= SEQUENCE {
tlpUpsConfigDb9InputPins3and9 INTEGER }
tlpUpsConfigDb9InputPins3and9 OBJECT-TYPE
SYNTAX INTEGER {
shutdown(0),
outputOff(1),
reboot(2),
outputOn(3),
powerToggle(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the ups detects a short between pin 3 and 9 for a certain amount of time, the
ups will perform the action as specified. If not supported, this value returned is
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigDb9InputEntry 1 }
tlpUpsConfigDb9OutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigDb9OutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each ups in device table. This
is a sparse dependent table, and will contain some subset of
devices that are upss. Not all options are available on all
upss."
::= { tlpUpsConfigDb9 2 }
tlpUpsConfigDb9OutputEntry OBJECT-TYPE
SYNTAX TlpUpsConfigDb9OutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing contact configuration options for a particular ups."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigDb9OutputTable 1 }
TlpUpsConfigDb9OutputEntry ::= SEQUENCE {
tlpUpsConfigDb9OutputPins1and5 INTEGER,
tlpUpsConfigDb9OutputPins8and5 INTEGER}
tlpUpsConfigDb9OutputPins1and5 OBJECT-TYPE
SYNTAX INTEGER {
onBattery(0),
onBypass(1),
outputOn(2),
lowBattery(3),
summaryAlarm(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the selected option is met, the ups will send a signal by bridging
pins 1 and 5 on the db9 port. If not supported, this value returned is
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigDb9OutputEntry 1 }
tlpUpsConfigDb9OutputPins8and5 OBJECT-TYPE
SYNTAX INTEGER {
onBattery(0),
onBypass(1),
outputOn(2),
lowBattery(3),
summaryAlarm(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When the selected option is met, the ups will send a signal by bridging
pins 8 and 5 on the db9 port. If not supported, this value returned is
ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigDb9OutputEntry 2 }
tlpUpsConfigOutputPhaseThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigOutputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output phase configuration details for each ups in device table.
This is a sparse dependent table, and will contain the number of
entries based on the number of upss managed by the agent as reported
by tlpUpsIdentNumUps and tlpUpsIdentNumPhases. Not all options are
available on all upss."
::= { tlpUpsConfig 7 }
tlpUpsConfigOutputPhaseThresholdEntry OBJECT-TYPE
SYNTAX TlpUpsConfigOutputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular output
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsOutputLineIndex }
::= { tlpUpsConfigOutputPhaseThresholdTable 1 }
TlpUpsConfigOutputPhaseThresholdEntry ::= SEQUENCE {
tlpUpsConfigOutputCurrentThresholdTolerance Unsigned32,
tlpUpsConfigOutputCurrentHighThreshold Unsigned32,
tlpUpsConfigOutputCurrentLowThreshold Unsigned32,
tlpUpsConfigOutputVoltageThresholdTolerance Unsigned32,
tlpUpsConfigOutputVoltageHighCriticalThreshold Unsigned32,
tlpUpsConfigOutputVoltageHighWarningThreshold Unsigned32,
tlpUpsConfigOutputVoltageLowWarningThreshold Unsigned32,
tlpUpsConfigOutputVoltageLowCriticalThreshold Unsigned32,
tlpUpsConfigOutputUtilizationThresholdTolerance Unsigned32,
tlpUpsConfigOutputUtilizationWarningThreshold INTEGER }
tlpUpsConfigOutputCurrentThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output current high/low
threshold to evaluate output current high/low condition."
::= { tlpUpsConfigOutputPhaseThresholdEntry 1 }
tlpUpsConfigOutputCurrentHighThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which an output current high condition is declared."
::= { tlpUpsConfigOutputPhaseThresholdEntry 2 }
tlpUpsConfigOutputCurrentLowThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which an output current low condition is declared."
::= { tlpUpsConfigOutputPhaseThresholdEntry 3 }
tlpUpsConfigOutputVoltageThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output voltage high/low
threshold to evaluate output voltage high/low condition."
::= { tlpUpsConfigOutputPhaseThresholdEntry 4 }
tlpUpsConfigOutputVoltageHighCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage high critical condition is declared."
::= { tlpUpsConfigOutputPhaseThresholdEntry 5 }
tlpUpsConfigOutputVoltageHighWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage high warning condition is declared."
::= { tlpUpsConfigOutputPhaseThresholdEntry 6 }
tlpUpsConfigOutputVoltageLowWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage low warning condition is declared."
::= { tlpUpsConfigOutputPhaseThresholdEntry 7 }
tlpUpsConfigOutputVoltageLowCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage low critical condition is declared."
::= { tlpUpsConfigOutputPhaseThresholdEntry 8 }
tlpUpsConfigOutputUtilizationThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The tolerance value used together with tlpUpsConfigOutputUtilizationWarningThreshold
to evaluate tlpUpsAlarmLoadLevelAboveThreshold condition."
::= { tlpUpsConfigOutputPhaseThresholdEntry 9 }
tlpUpsConfigOutputUtilizationWarningThreshold OBJECT-TYPE
SYNTAX INTEGER (5..105)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value denotes the percentage of load at which the load warning condition
occurs. The load warning alarm, tlpUpsAlarmLoadLevelAboveThreshold, is
triggered when the percentage of output load exceeds this value. This threshold value
must be less than tlpUpsConfigOverLoadThreshold when supported."
::= { tlpUpsConfigOutputPhaseThresholdEntry 10 }
-- reserved
-- tlpUpsConfigOutputUtilizationCriticalThreshold OBJECT-TYPE
-- ::= { tlpUpsConfigOutputPhaseThresholdEntry 11 }
tlpUpsConfigInputPhaseThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigInputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input phase configuration details for each ups in device table.
This is a sparse dependent table, and will contain the number of
entries based on the number of upss managed by the agent as reported
by tlpUpsIdentNumUps and tlpUpsIdentNumPhases. Not all options are
available on all upss."
::= { tlpUpsConfig 8 }
tlpUpsConfigInputPhaseThresholdEntry OBJECT-TYPE
SYNTAX TlpUpsConfigInputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular input
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpUpsInputPhaseIndex }
::= { tlpUpsConfigInputPhaseThresholdTable 1 }
TlpUpsConfigInputPhaseThresholdEntry ::= SEQUENCE {
tlpUpsConfigInputVoltageThresholdTolerance Unsigned32,
tlpUpsConfigInputVoltageHighCriticalThreshold Unsigned32,
tlpUpsConfigInputVoltageHighWarningThreshold Unsigned32,
tlpUpsConfigInputVoltageLowWarningThreshold Unsigned32,
tlpUpsConfigInputVoltageLowCriticalThreshold Unsigned32 }
tlpUpsConfigInputVoltageThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output voltage high/low
threshold to evaluate output voltage high/low condition."
::= { tlpUpsConfigInputPhaseThresholdEntry 1 }
tlpUpsConfigInputVoltageHighCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage high critical condition is declared."
::= { tlpUpsConfigInputPhaseThresholdEntry 2 }
tlpUpsConfigInputVoltageHighWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage high warning condition is declared."
::= { tlpUpsConfigInputPhaseThresholdEntry 3 }
tlpUpsConfigInputVoltageLowWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage low warning condition is declared."
::= { tlpUpsConfigInputPhaseThresholdEntry 4 }
tlpUpsConfigInputVoltageLowCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage low critical condition is declared."
::= { tlpUpsConfigInputPhaseThresholdEntry 5 }
tlpUpsConfigTemperatureFahrenheitTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigTemperatureFahrenheitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The temperature configuration details for each ups device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are ups device. Not all options are available on all
ups devices."
::= { tlpUpsConfig 9 }
tlpUpsConfigTemperatureFahrenheitEntry OBJECT-TYPE
SYNTAX TlpUpsConfigTemperatureFahrenheitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing temperature configuration details for a particular ups device."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigTemperatureFahrenheitTable 1 }
TlpUpsConfigTemperatureFahrenheitEntry ::= SEQUENCE {
tlpUpsConfigExternalFanActivationTemperatureDegF Integer32 }
tlpUpsConfigExternalFanActivationTemperatureDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the temperature at which point the ups will turn on the external fan.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigTemperatureFahrenheitEntry 1 }
tlpUpsConfigTemperatureCelsiusTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpUpsConfigTemperatureCelsiusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration details for each each ups device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are ups device. Not all options are available on all
ups devices."
::= { tlpUpsConfig 10 }
tlpUpsConfigTemperatureCelsiusEntry OBJECT-TYPE
SYNTAX TlpUpsConfigTemperatureCelsiusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing temperature configuration details for a particular ups device."
INDEX { tlpDeviceIndex }
::= { tlpUpsConfigTemperatureCelsiusTable 1 }
TlpUpsConfigTemperatureCelsiusEntry ::= SEQUENCE {
tlpUpsConfigExternalFanActivationTemperatureDegC Integer32 }
tlpUpsConfigExternalFanActivationTemperatureDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Configures the temperature at which point the ups will turn on the external fan.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpUpsConfigTemperatureCelsiusEntry 1 }
-- pdu
tlpPduIdentNumPdu OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of pdu devices that this agent is currently managing."
::= { tlpPduIdent 1 }
tlpPduIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The identity details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus."
::= { tlpPduIdent 2 }
tlpPduIdentEntry OBJECT-TYPE
SYNTAX TlpPduIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing details for a particular pdu."
INDEX { tlpDeviceIndex }
::= { tlpPduIdentTable 1 }
TlpPduIdentEntry ::= SEQUENCE {
tlpPduIdentNumInputs Unsigned32,
tlpPduIdentNumOutputs Unsigned32,
tlpPduIdentNumPhases Unsigned32,
tlpPduIdentNumOutlets Unsigned32,
tlpPduIdentNumOutletGroups Unsigned32,
tlpPduIdentNumCircuits Unsigned32,
tlpPduIdentNumBreakers Unsigned32,
tlpPduIdentNumHeatsinks Unsigned32 }
tlpPduIdentNumInputs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input lines supported by the pdu."
::= { tlpPduIdentEntry 1 }
tlpPduIdentNumOutputs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of output lines supported by the pdu."
::= { tlpPduIdentEntry 2 }
tlpPduIdentNumPhases OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of phases supported by the pdu."
::= { tlpPduIdentEntry 3 }
tlpPduIdentNumOutlets OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of receptacles supported by the pdu."
::= { tlpPduIdentEntry 4 }
tlpPduIdentNumOutletGroups OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of user-defined receptacle groups created for the
pdu."
::= { tlpPduIdentEntry 5 }
tlpPduIdentNumCircuits OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of circuits supported by the pdu."
::= { tlpPduIdentEntry 6 }
tlpPduIdentNumBreakers OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of monitored circuit breakers supported by the pdu.
If the pdu has breakers that are not monitored by the device,
the value of zero(0) will be returned."
::= { tlpPduIdentEntry 7 }
tlpPduIdentNumHeatsinks OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of heatsink thermistors supported by the pdu."
::= { tlpPduIdentEntry 8 }
tlpPduSupportsTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduSupportsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The supported details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus."
::= { tlpPduIdent 3 }
tlpPduSupportsEntry OBJECT-TYPE
SYNTAX TlpPduSupportsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing supported details for a particular pdu."
INDEX { tlpDeviceIndex }
::= { tlpPduSupportsTable 1 }
TlpPduSupportsEntry ::= SEQUENCE {
tlpPduSupportsEnergywise TruthValue,
tlpPduSupportsRampShed TruthValue,
tlpPduSupportsOutletGroup TruthValue,
tlpPduSupportsOutletCurrent TruthValue,
tlpPduSupportsOutletVoltage TruthValue,
tlpPduSupportsOutletActivePower TruthValue }
tlpPduSupportsEnergywise OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Indicates whether the pdu supports Cisco EnergyWise."
::= { tlpPduSupportsEntry 1 }
tlpPduSupportsRampShed OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the pdu supports ramping and shedding."
::= { tlpPduSupportsEntry 2 }
tlpPduSupportsOutletGroup OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the pdu supports outlet groups."
::= { tlpPduSupportsEntry 3 }
tlpPduSupportsOutletCurrent OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the pdu reports individual receptacle
current measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpPduOutletCurrent."
::= { tlpPduSupportsEntry 4 }
tlpPduSupportsOutletVoltage OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the pdu reports individual receptacle voltage
measurements. Devices that do not support individual receptacle
measurements will always return ERROR_NO_SUCH_NAME for
tlpPduOutletVoltage."
::= { tlpPduSupportsEntry 5 }
tlpPduSupportsOutletActivePower OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the pdu reports individual receptacle power
measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpPduOutletActivePower."
::= { tlpPduSupportsEntry 6 }
tlpPduDisplayTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduDisplayEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"The display details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus."
::= { tlpPduIdent 4 }
tlpPduDisplayEntry OBJECT-TYPE
SYNTAX TlpPduDisplayEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"An entry containing display details for a particular pdu."
INDEX { tlpDeviceIndex }
::= { tlpPduDisplayTable 1 }
TlpPduDisplayEntry ::= SEQUENCE {
tlpPduDisplayScheme INTEGER,
tlpPduDisplayOrientation INTEGER,
tlpPduDisplayAutoScroll INTEGER,
tlpPduDisplayIntensity INTEGER,
tlpPduDisplayUnits INTEGER }
tlpPduDisplayScheme OBJECT-TYPE
SYNTAX INTEGER {
schemeReverse(0),
schemeNormal(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the display scheme of the LED display. The value
schemeReverse(0) indicates the tricolor LED indicator uses an
alternate pattern. The value schemeNormal(1) indicates the
LED indicator uses the standard pattern. This value may not
be supported on all models. If not supported, the value will
always return schemeNormal(1)."
::= { tlpPduDisplayEntry 1 }
tlpPduDisplayOrientation OBJECT-TYPE
SYNTAX INTEGER {
displayNormal(0),
displayReverse(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the physical orientation of the LED display. The value
displayNormal(0) indicates the display is right-side-up (normal).
The value displayReverse(1) indicates the display is upside-down.
This value may not be supported on all models. If not supported,
the value will always return displayNormal(0)."
::= { tlpPduDisplayEntry 2 }
tlpPduDisplayAutoScroll OBJECT-TYPE
SYNTAX INTEGER {
scrollDisabled(0),
scrollEnabled(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates whether the LED display automatically scrolls through
displaying status values."
::= { tlpPduDisplayEntry 3 }
tlpPduDisplayIntensity OBJECT-TYPE
SYNTAX INTEGER {
intensity25(1),
intensity50(2),
intensity75(3),
intensity100(4) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the intensity, as a percentage, of the LED display. The
value intensity100(4) indicates the display is at 100% intensity.
The other values indicate the display is at a lesser intensity based
upon the respective percentage denoted."
::= { tlpPduDisplayEntry 4 }
tlpPduDisplayUnits OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
metric(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the units of measurement displayed on the LED display.
The value normal(0) indicates that a temperature value, for example,
is displayed in degrees Fahrenheit. The value metric(1) indicates a
temperature value is displayed in degrees Celsius."
::= { tlpPduDisplayEntry 5 }
tlpPduDeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The device details of each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus."
::= { tlpPduDevice 1 }
tlpPduDeviceEntry OBJECT-TYPE
SYNTAX TlpPduDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing device details for a particular pdu."
INDEX { tlpDeviceIndex }
::= { tlpPduDeviceTable 1 }
TlpPduDeviceEntry ::= SEQUENCE {
tlpPduDeviceMainLoadState INTEGER,
tlpPduDeviceMainLoadControllable TruthValue,
tlpPduDeviceMainLoadCommand INTEGER,
tlpPduDevicePowerOnDelay Integer32,
tlpPduDeviceTotalInputPowerRating Integer32,
tlpPduDeviceTemperatureC Integer32,
tlpPduDeviceTemperatureF Integer32,
tlpPduDevicePhaseImbalance INTEGER,
tlpPduDeviceOutputActivePowerTotal Unsigned32,
tlpPduDeviceAggregatePowerFactor Unsigned32,
tlpPduDeviceOutputCurrentPrecision INTEGER,
tlpPduDeviceGeneralFault TruthValue,
tlpPduDeviceTotalOutputUtilization INTEGER,
tlpPduDeviceOutputApparentPowerTotal Unsigned32,
tlpPduDeviceOutputReactivePowerTotal Integer32,
tlpPduDeviceOutputCurrentTotal Unsigned32,
tlpPduDeviceWattHoursTotal Unsigned32,
tlpPduDevicePeakPowerTotal Unsigned32,
tlpPduDevice24hrEnergyTotal Unsigned32 }
tlpPduDeviceMainLoadState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the main output of the device."
::= { tlpPduDeviceEntry 1 }
tlpPduDeviceMainLoadControllable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the main output is controllable, and whether
the ups can be turned off and on."
::= { tlpPduDeviceEntry 2 }
tlpPduDeviceMainLoadCommand OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value to
turnOff(1) will turn off the main output of the ups. Setting this
value to turnOn(2) will turn on the main output of the ups. Setting
this value to cycle(3) will turn off the main output, then turn it
back on."
::= { tlpPduDeviceEntry 3 }
tlpPduDevicePowerOnDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "Seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configurable delay value, which sets the amount of additional
time a given device will wait before it connects to a valid AC
source. By default the delay value is set to 0. For devices with
multiple AC input sources, this delay only applies to the primary
input source."
::= { tlpPduDeviceEntry 4 }
tlpPduDeviceTotalInputPowerRating OBJECT-TYPE
SYNTAX Integer32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total input power rating of all phases on the device. This
value may not be supported on all models. If not supported, this
value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduDeviceEntry 5 }
tlpPduDeviceTemperatureC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the pdu casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduDeviceEntry 6 }
tlpPduDeviceTemperatureF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the pdu casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduDeviceEntry 7 }
tlpPduDevicePhaseImbalance OBJECT-TYPE
SYNTAX INTEGER (0..200)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of imbalance of the three phases. This value is in
the range from 0% imbalance to 100% imbalance. The lower the value,
the better balanced the phases are. If all load is on a single phase,
the imbalance is defined as 100%."
::= { tlpPduDeviceEntry 8 }
tlpPduDeviceOutputActivePowerTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC output total true power for all circuits."
::= { tlpPduDeviceEntry 9 }
tlpPduDeviceAggregatePowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The aggregate power factor of all phases."
::= { tlpPduDeviceEntry 10 }
tlpPduDeviceOutputCurrentPrecision OBJECT-TYPE
SYNTAX INTEGER {
wholeNumber(0),
tenths(1),
hundredths(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output current is reported by tlpPduOutputCurrent, tlpPduOutputCurrentMin
and tlpPduOutputCurrentMax. These values are all reported in hundredths(0.01A),
which accommodates all models; however, on any given device the actual precision
may vary. All current values must be divided by 100 to obtain the actual value.
For example, if tlpPduOutputCurrent reports 500, then the actual output current
is 5.00. This tlpPduDeviceOutputCurrentPrecision defines the actual resolution
of that value: wholeNumber(0) is 5, tenths(1) is 5.0 and hundredths(2) is 5.00."
::= { tlpPduDeviceEntry 11 }
tlpPduDeviceGeneralFault OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the pdu is in a fault condition. When the pdu is in such
a fault condition, the condition can be cleared with tlpPduControlResetGeneralFault."
::= { tlpPduDeviceEntry 12 }
tlpPduDeviceTotalOutputUtilization OBJECT-TYPE
SYNTAX INTEGER
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total percentage of the pdu power capacity presently being used on the pdu.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduDeviceEntry 13 }
tlpPduDeviceOutputApparentPowerTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC output total apparent power for all circuits. If not supported, this
value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduDeviceEntry 14 }
tlpPduDeviceOutputReactivePowerTotal OBJECT-TYPE
SYNTAX Integer32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC output total reactive power for all circuits. If not supported, this
value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduDeviceEntry 15 }
tlpPduDeviceOutputCurrentTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total output current, in hundredths of amps.The actual precision of
this value, whether a whole number, tenths or hundredths, is returned
by tlpPduDeviceOutputCurrentPrecision."
::= { tlpPduDeviceEntry 16 }
tlpPduDeviceWattHoursTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "WH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of watt hours of energy utilized in the past 24 hours. Use
tlpPduControlResetWattHours to reset the watt hours calculation algorithm."
::= { tlpPduDeviceEntry 17 }
tlpPduDevicePeakPowerTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum 1 second average power value since the last reset. Use
tlpPduControlResetPeakPower to reset the peak power calculations."
::= { tlpPduDeviceEntry 18 }
tlpPduDevice24hrEnergyTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption using present value
of tlpPduOutputPowerKW."
::= { tlpPduDeviceEntry 19 }
tlpPduInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input details of each pdu in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the number of pdus managed by the agent as reported by tlpPduIdentNumPdus."
::= { tlpPduInput 1 }
tlpPduInputEntry OBJECT-TYPE
SYNTAX TlpPduInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular pdu managed
by this agent."
INDEX { tlpDeviceIndex }
::= { tlpPduInputTable 1 }
TlpPduInputEntry ::= SEQUENCE {
tlpPduInputNominalVoltage Unsigned32,
tlpPduInputNominalVoltagePhaseToPhase Unsigned32,
tlpPduInputNominalVoltagePhaseToNeutral Unsigned32,
tlpPduInputLowTransferVoltage Unsigned32,
tlpPduInputLowTransferVoltageLowerBound Unsigned32,
tlpPduInputLowTransferVoltageUpperBound Unsigned32,
tlpPduInputHighTransferVoltage Unsigned32,
tlpPduInputHighTransferVoltageLowerBound Unsigned32,
tlpPduInputHighTransferVoltageUpperBound Unsigned32,
tlpPduInputCurrentLimit Unsigned32,
tlpPduInputCurrentTotal Unsigned32 }
tlpPduInputNominalVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpPduInputEntry 1 }
tlpPduInputNominalVoltagePhaseToPhase OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line voltage as measured from
phase to phase. This value may not be supported on all models.
If not supported, this value will always return zero."
::= { tlpPduInputEntry 2 }
tlpPduInputNominalVoltagePhaseToNeutral OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line voltage as measured from
phase to neutral. This value may not be supported on all models.
If not supported, this value will always return zero."
::= { tlpPduInputEntry 3 }
tlpPduInputLowTransferVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum line voltage allowed before the unit disconnects the
AC input connection. This value may not be writable on all models.
If not writable, the value will be rejected and an appropriate error
message will be returned. When supported, the minimum and maximum
values allowed are dictated by tlpPduInputLowTransferVoltageLowerBound
and tlpPduInputLowTransferVoltageUpperBound respectively."
::= { tlpPduInputEntry 4 }
tlpPduInputLowTransferVoltageLowerBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lower boundary value of tlpPduInputLowTransferVoltage as dictated
by the hardware of the unit."
::= { tlpPduInputEntry 5 }
tlpPduInputLowTransferVoltageUpperBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The upper boundary value of tlpPduInputLowTransferVoltage as dictated
by the hardware of the unit."
::= { tlpPduInputEntry 6 }
tlpPduInputHighTransferVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum line voltage allowed before the unit disconnects the
AC input connection. This value may not be writable on all models.
If not writable, the value will be rejected and an appropriate error
message will be returned. When supported, the minimum and maximum
values allowed are dictated by tlpPduInputHighTransferVoltageLowerBound
and tlpPduInputHighTransferVoltageUpperBound respectively."
::= { tlpPduInputEntry 7 }
tlpPduInputHighTransferVoltageLowerBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lower boundary value of tlpPduInputHighTransferVoltage as dictated
by the hardware of the unit."
::= { tlpPduInputEntry 8 }
tlpPduInputHighTransferVoltageUpperBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The upper boundary value of tlpPduInputHighTransferVoltage as dictated
by the hardware of the unit."
::= { tlpPduInputEntry 9 }
tlpPduInputCurrentLimit OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The capacity of each phase conductor in the pdu limited by the AC input
cord or any other potential limiting factors unique to a given unit."
::= { tlpPduInputEntry 10 }
tlpPduInputCurrentTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The aggregate total of conductor currents. If the pdu does not support this value,
then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpPduInputEntry 11 }
tlpPduInputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input phase details of each pdu in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpPduIdentNumInputs and tlpPduIdentNumPhases per each
device."
::= { tlpPduInput 2 }
tlpPduInputPhaseEntry OBJECT-TYPE
SYNTAX TlpPduInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular input
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpPduInputPhaseIndex }
::= { tlpPduInputPhaseTable 1 }
TlpPduInputPhaseEntry ::= SEQUENCE {
tlpPduInputPhaseIndex Unsigned32,
tlpPduInputPhasePhaseType INTEGER,
tlpPduInputPhaseFrequency Unsigned32,
tlpPduInputPhaseVoltage Unsigned32,
tlpPduInputPhaseVoltageMin Unsigned32,
tlpPduInputPhaseVoltageMax Unsigned32,
tlpPduInputPhaseCurrent Unsigned32,
tlpPduInputPhasePower Unsigned32,
tlpPduInputPhaseThdVoltage Unsigned32 }
tlpPduInputPhaseIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the pdu phase."
::= { tlpPduInputPhaseEntry 1 }
tlpPduInputPhasePhaseType OBJECT-TYPE
SYNTAX INTEGER {
phaseToNeutral(0),
phaseToPhase(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether measurements are phase to neutral(0) or phase
to phase(1)."
::= { tlpPduInputPhaseEntry 2 }
tlpPduInputPhaseFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present input frequency for a given phase."
::= { tlpPduInputPhaseEntry 3 }
tlpPduInputPhaseVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input voltage for a given phase."
::= { tlpPduInputPhaseEntry 4 }
tlpPduInputPhaseVoltageMin OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpPduInputPhaseVoltageMin or tlpPduInputPhaseVoltageMax using
agent version below 20, both will be reset to their appropriate
minimum and maximum values. Writes are deprecated as of agent
version 20. Use tlpPduControlResetInputVoltageMinMax to reset
this value."
::= { tlpPduInputPhaseEntry 5 }
tlpPduInputPhaseVoltageMax OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpPduInputPhaseVoltageMin or tlpPduInputPhaseVoltageMax using
agent version below 20, both will be reset to their appropriate
minimum and maximum values. Writes are deprecated as of agent
version 20. Use tlpPduControlResetInputVoltageMinMax to reset
this value."
::= { tlpPduInputPhaseEntry 6 }
tlpPduInputPhaseCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input current for a given phase."
::= { tlpPduInputPhaseEntry 7 }
tlpPduInputPhasePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input true power."
::= { tlpPduInputPhaseEntry 8 }
tlpPduInputPhaseThdVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The voltage thd (total harmonic distortion) for this phase in hundredths
of a percent."
::= { tlpPduInputPhaseEntry 9 }
tlpPduOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output details of each pdu in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpPduIdentNumOutputs per each device."
::= { tlpPduOutput 1 }
tlpPduOutputEntry OBJECT-TYPE
SYNTAX TlpPduOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing output information applicable to a particular
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpPduOutputIndex }
::= { tlpPduOutputTable 1 }
TlpPduOutputEntry ::= SEQUENCE {
tlpPduOutputIndex Unsigned32,
tlpPduOutputPhase INTEGER,
tlpPduOutputPhaseType INTEGER,
tlpPduOutputVoltage Unsigned32,
tlpPduOutputCurrent Unsigned32,
tlpPduOutputCurrentMin Unsigned32,
tlpPduOutputCurrentMax Unsigned32,
tlpPduOutputActivePower Unsigned32,
tlpPduOutputPowerFactor INTEGER,
tlpPduOutputSource INTEGER,
tlpPduOutputFrequency Unsigned32,
tlpPduOutputPowerKVA Unsigned32,
tlpPduOutputPowerKW Unsigned32,
tlpPduOutput24hrEnergy Unsigned32,
tlpPduOutputApparentPower Unsigned32,
tlpPduOutputReactivePower Integer32,
tlpPduOutputUtilization Unsigned32,
tlpPduOutputWattHours Unsigned32,
tlpPduOutputPeakPower Unsigned32 }
tlpPduOutputIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the pdu phase."
::= { tlpPduOutputEntry 1 }
tlpPduOutputPhase OBJECT-TYPE
SYNTAX INTEGER {
phase1(1),
phase2(2),
phase3(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the phase associated with the output line."
::= { tlpPduOutputEntry 2 }
tlpPduOutputPhaseType OBJECT-TYPE
SYNTAX INTEGER {
phaseToNeutral(0),
phaseToPhase(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether measurements are phase to neutral(0) or phase
to phase(1)."
::= { tlpPduOutputEntry 3 }
tlpPduOutputVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present output voltage for a given output line."
::= { tlpPduOutputEntry 4 }
tlpPduOutputCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output current, in hundredths of amps, for a given phase.
The actual precision of this value, whether a whole number, tenths
or hundredths, is returned by tlpPduDeviceOutputCurrentPrecision."
::= { tlpPduOutputEntry 5 }
tlpPduOutputCurrentMin OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpPduDeviceOutputCurrentPrecision. Use
tlpPduControlResetOutputCurrentMinMax to reset this value."
::= { tlpPduOutputEntry 6 }
tlpPduOutputCurrentMax OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpPduDeviceOutputCurrentPrecision. Use
tlpPduControlResetOutputCurrentMinMax to reset this value."
::= { tlpPduOutputEntry 7 }
tlpPduOutputActivePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output power for a given phase."
::= { tlpPduOutputEntry 8 }
tlpPduOutputPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output power factor ratio for a given phase."
::= { tlpPduOutputEntry 9 }
tlpPduOutputSource OBJECT-TYPE
SYNTAX INTEGER {
none(0),
normal(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power. The enumeration none(0) indicates
that there is no source of output power (and therefore no output power),
for example, the pdu has an open circuit breaker."
::= { tlpPduOutputEntry 10 }
tlpPduOutputFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output frequency. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpPduOutputEntry 11 }
tlpPduOutputPowerKVA OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of active power being used."
::= { tlpPduOutputEntry 12 }
tlpPduOutputPowerKW OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of active power being used."
::= { tlpPduOutputEntry 13 }
tlpPduOutput24hrEnergy OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption using present value
of tlpPduOutputPowerKW."
::= { tlpPduOutputEntry 14 }
tlpPduOutputApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of apparent power being used."
::= { tlpPduOutputEntry 15 }
tlpPduOutputReactivePower OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of reactive power being used."
::= { tlpPduOutputEntry 16 }
tlpPduOutputUtilization OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the ats power capacity presently being used on
this output line."
::= { tlpPduOutputEntry 17 }
tlpPduOutputWattHours OBJECT-TYPE
SYNTAX Unsigned32
UNITS "WH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of watt hours of energy utilized in the past 24 hours. Use
tlpPduControlResetWattHours to reset the watt hours calculation algorithm."
::= { tlpPduOutputEntry 18 }
tlpPduOutputPeakPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum 1 second average power value since the last reset. Use
tlpPduControlResetPeakPower to reset the peak power calculations."
::= { tlpPduOutputEntry 19 }
tlpPduOutletTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The receptacle status details of each pdu in device table. This
is a sparse dependent table, and will contain the number of entries
based upon the value of tlpPduIdentNumOutlets per each device."
::= { tlpPduOutlet 1 }
tlpPduOutletEntry OBJECT-TYPE
SYNTAX TlpPduOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular outlet
managed by this agent."
INDEX { tlpDeviceIndex, tlpPduOutletIndex }
::= { tlpPduOutletTable 1 }
TlpPduOutletEntry ::= SEQUENCE {
tlpPduOutletIndex Unsigned32,
tlpPduOutletName DisplayString,
tlpPduOutletDescription DisplayString,
tlpPduOutletState INTEGER,
tlpPduOutletControllable TruthValue,
tlpPduOutletCommand INTEGER,
tlpPduOutletVoltage Unsigned32,
tlpPduOutletCurrent Unsigned32,
tlpPduOutletActivePower Unsigned32,
tlpPduOutletRampAction INTEGER,
tlpPduOutletRampDelay Integer32,
tlpPduOutletShedAction INTEGER,
tlpPduOutletShedDelay Integer32,
tlpPduOutletGroup Integer32,
tlpPduOutletBank Integer32,
tlpPduOutletCircuit Integer32,
tlpPduOutletPhase INTEGER,
tlpPduOutletReceptacleType INTEGER,
tlpPduOutletPowerFactor INTEGER,
tlpPduOutletApparentPower Unsigned32,
tlpPduOutletReactivePower Integer32,
tlpPduOutletFrequency Unsigned32,
tlpPduOutletUtilization Unsigned32,
tlpPduOutlet24hrEnergy Unsigned32,
tlpPduOutletOvercurrent TruthValue }
tlpPduOutletIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the pdu outlet."
::= { tlpPduOutletEntry 1 }
tlpPduOutletName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-definable string identifying the name of the outlet."
::= { tlpPduOutletEntry 2 }
tlpPduOutletDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-definable string identifying the device(s) connected to
the given outlet."
::= { tlpPduOutletEntry 3 }
tlpPduOutletState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the outlet."
::= { tlpPduOutletEntry 4 }
tlpPduOutletControllable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether this outlet is controllable."
::= { tlpPduOutletEntry 5 }
tlpPduOutletCommand OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value
to turnOff(1) will turn off the outlet. Setting this value
to turnOn(2) will turn on the outlet. Setting this value to
cycle(3) will turn the outlet off, then turn it back on."
::= { tlpPduOutletEntry 6 }
tlpPduOutletVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will always return ERROR_NO_SUCH_NAME.
Device-wide support for receptacle voltage measurements is denoted
by tlpPduSupportsOutletVoltage."
::= { tlpPduOutletEntry 7 }
tlpPduOutletCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will always return ERROR_NO_SUCH_NAME.
Device-wide support for receptacle current measurements is denoted
by tlpPduSupportsOutletCurrent."
::= { tlpPduOutletEntry 8 }
tlpPduOutletActivePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output active power of a given outlet. If the power measurement
is not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this value will
always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle
power measurements is denoted by tlpPduSupportsOutletActivePower."
::= { tlpPduOutletEntry 9 }
tlpPduOutletRampAction OBJECT-TYPE
SYNTAX INTEGER {
remainOff(0),
turnOnAfterDelay(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpPduOutletEntry 10 }
tlpPduOutletRampDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpPduOutletEntry 11 }
tlpPduOutletShedAction OBJECT-TYPE
SYNTAX INTEGER {
remainOn(0),
turnOffAfterDelay(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpPduOutletEntry 12 }
tlpPduOutletShedDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpPduOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpPduOutletEntry 13 }
tlpPduOutletGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The tlpPduOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped."
::= { tlpPduOutletEntry 14 }
tlpPduOutletBank OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"This is reported as a bank number, but it is rather an internal
number unrelated to a bank as silk-screened on many devices and is
unrelated to and often confused with tlpPduOutletCircuit. The value
reported is of no commercial use and was deprecated in agent
version 20."
::= { tlpPduOutletEntry 15 }
tlpPduOutletCircuit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which circuit the given outlet is wired."
::= { tlpPduOutletEntry 16 }
tlpPduOutletPhase OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
phase1(1),
phase2(2),
phase3(3),
phase1-2(4),
phase2-3(5),
phase3-1(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which phase or phases the given outlet is
associated. For single phase devices, this object will
always return phase1(1). For 3-phase devices with outlets
wired to a single phase, this object will return phase1(1),
phase2(2) or phase3(3). For 3-phase devices with outlets
wired to two phases, this object will return phase1-2(4)
for phases 1 and 2, phase2-3(5) for phases 2 and 3, and
phase3-1(6) for phases 3 and 1. Devices that do not report
phase connections will return unknown(0)."
::= { tlpPduOutletEntry 17 }
tlpPduOutletReceptacleType OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
nema-515R(1),
nema-520R(2),
nema-530R(3),
nema-L515R(4),
nema-L520R(5),
nema-L530R(6),
nema-L615R(7),
nema-L620R(8),
nema-L630R(9),
nema-L1430R(10),
nema-L1520R(11),
nema-L1530R(12),
nema-L2120R(13),
nema-L2130R(14),
nema-L2230R(15),
iec-309-1620(16),
iec-309-3032(17),
iec-309-6063(18),
iec-320-C13(19),
iec-320-C14(20),
iec-320-C15(21),
iec-320-C17(22),
iec-320-C19(23),
iec-320-C20(24) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of receptacle for this outlet. Not all devices report
receptacle types. The value will return unknown(0) when not supported."
::= { tlpPduOutletEntry 18 }
tlpPduOutletPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor ratio for this outlet."
::= { tlpPduOutletEntry 19 }
tlpPduOutletApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The apparent power of this outlet."
::= { tlpPduOutletEntry 20 }
tlpPduOutletReactivePower OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reactive power of this outlet."
::= { tlpPduOutletEntry 21 }
tlpPduOutletFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The frequency of this outlet."
::= { tlpPduOutletEntry 22 }
tlpPduOutletUtilization OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of utilization of this outlet."
::= { tlpPduOutletEntry 23 }
tlpPduOutlet24hrEnergy OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption of this outlet."
::= { tlpPduOutletEntry 24 }
tlpPduOutletOvercurrent OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether this outlet is in an overcurrent condition."
::= { tlpPduOutletEntry 25 }
tlpPduOutletGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The receptacle grouping details of each pdu in device table.
This is a sparse dependent table, and will contain the number
of entries based upon the value of tlpPduIdentNumOutletGroups per
each device."
::= { tlpPduOutlet 2 }
tlpPduOutletGroupEntry OBJECT-TYPE
SYNTAX TlpPduOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular outlet
group managed by this agent."
INDEX { tlpDeviceIndex, tlpPduOutletGroupIndex }
::= { tlpPduOutletGroupTable 1 }
TlpPduOutletGroupEntry ::= SEQUENCE {
tlpPduOutletGroupIndex Unsigned32,
tlpPduOutletGroupRowStatus RowStatus,
tlpPduOutletGroupName DisplayString,
tlpPduOutletGroupDescription DisplayString,
tlpPduOutletGroupState INTEGER,
tlpPduOutletGroupCommand INTEGER }
tlpPduOutletGroupIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the pdu outlet group."
::= { tlpPduOutletGroupEntry 1 }
tlpPduOutletGroupRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Row status for the tlpPduOutletGroupTable"
::= { tlpPduOutletGroupEntry 2 }
tlpPduOutletGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of this outlet group."
::= { tlpPduOutletGroupEntry 3 }
tlpPduOutletGroupDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A description for this outlet group."
::= { tlpPduOutletGroupEntry 4 }
tlpPduOutletGroupState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2),
mixed(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the outlet group. This value will report
off(1) if all outlets in the group are off, on(2) if all outlets
in the group are on, mixed(3) if some outlets in the group are
off and others are on, or unknown(0) if the state of the outlets
cannot be determined."
::= { tlpPduOutletGroupEntry 5 }
tlpPduOutletGroupCommand OBJECT-TYPE
SYNTAX INTEGER {
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value to
turnOff(1) will turn off every outlet associated with the group.
Setting this value to turnOn(2) will turn on every outlet associated
with the group. Setting this value to cycle(3) will turn off every
outlet associated with the group, then turn each outlet back on."
::= { tlpPduOutletGroupEntry 6 }
tlpPduCircuitTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of pdu circuit table entries. The number of entries
is given by the value of tlpPduIdentNumCircuits."
::= { tlpPduCircuit 1 }
tlpPduCircuitEntry OBJECT-TYPE
SYNTAX TlpPduCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular circuit
managed by this agent."
INDEX { tlpDeviceIndex, tlpPduCircuitIndex }
::= { tlpPduCircuitTable 1 }
TlpPduCircuitEntry ::= SEQUENCE {
tlpPduCircuitIndex Unsigned32,
tlpPduCircuitPhase INTEGER,
tlpPduCircuitInputVoltage Integer32,
tlpPduCircuitTotalCurrent Integer32,
tlpPduCircuitCurrentLimit Integer32,
tlpPduCircuitCurrentMin Integer32,
tlpPduCircuitCurrentMax Integer32,
tlpPduCircuitTotalPower Integer32,
tlpPduCircuitPowerFactor INTEGER,
tlpPduCircuitUtilization Unsigned32,
tlpPduCircuitApparentPower Unsigned32,
tlpPduCircuitReactivePower Integer32,
tlpPduCircuitFrequency Unsigned32,
tlpPduCircuitWattHours Unsigned32,
tlpPduCircuitPeakPower Unsigned32 }
tlpPduCircuitIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the pdu circuit."
::= { tlpPduCircuitEntry 1 }
tlpPduCircuitPhase OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
phase1(1),
phase2(2),
phase3(3),
phase1-2(4),
phase2-3(5),
phase3-1(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which phase or phases the given circuit is
wired. For single phase devices, this object will always
return phase1(1). For 3-phase devices with outlets wired
to a single phase, this object will return phase1(1),
phase2(2) or phase3(3). For 3-phase devices with outlets
wired to two phases, this object will return phase1-2(4)
for phases 1 and 2, phase2-3(5) for phases 2 and 3, and
phase3-1(6) for phases 3 and 1. Devices that do not report
phase connections will return unknown(0)."
::= { tlpPduCircuitEntry 2 }
tlpPduCircuitInputVoltage OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input voltage for a circuit."
::= { tlpPduCircuitEntry 3 }
tlpPduCircuitTotalCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total current, in hundredths of amps, for all receptacles
in a given circuit."
::= { tlpPduCircuitEntry 4 }
tlpPduCircuitCurrentLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current capacity, in hundredths of amps, of a circuit in
the pdu limited by the circuit breaker or wiring used in a
given unit."
::= { tlpPduCircuitEntry 5 }
tlpPduCircuitCurrentMin OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum total current, in hundredths of amps, for
all receptacles in a given circuit since last reset."
::= { tlpPduCircuitEntry 6 }
tlpPduCircuitCurrentMax OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum total current, in hundredths of amps, for
all receptacles in a given circuit since last reset."
::= { tlpPduCircuitEntry 7 }
tlpPduCircuitTotalPower OBJECT-TYPE
SYNTAX Integer32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total power for all receptacles in a given circuit."
::= { tlpPduCircuitEntry 8 }
tlpPduCircuitPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor ratio for all receptacles in a given circuit."
::= { tlpPduCircuitEntry 9 }
tlpPduCircuitUtilization OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of utilization of a given circuit. This is typically
a calculation of tlpPduCircuitTotalCurrent / tlpPduCircuitCurrentLimit."
::= { tlpPduCircuitEntry 10 }
tlpPduCircuitApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The apparent power of a given circuit."
::= { tlpPduCircuitEntry 11 }
tlpPduCircuitReactivePower OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reactive power of a given circuit."
::= { tlpPduCircuitEntry 12 }
tlpPduCircuitFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The frequency of a given circuit."
::= { tlpPduCircuitEntry 13 }
tlpPduCircuitWattHours OBJECT-TYPE
SYNTAX Unsigned32
UNITS "WH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of watt hours of energy utilized in the past 24 hours. Use
tlpPduControlResetWattHours to reset the watt hours calculation algorithm."
::= { tlpPduCircuitEntry 14 }
tlpPduCircuitPeakPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum 1 second average power value since the last reset. Use
tlpPduControlResetPeakPower to reset the peak power calculations."
::= { tlpPduCircuitEntry 15 }
tlpPduBreakerTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduBreakerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of pdu circuit breaker table entries. The number of entries
is given by the value of tlpPduIdentNumBreakers."
::= { tlpPduBreaker 1 }
tlpPduBreakerEntry OBJECT-TYPE
SYNTAX TlpPduBreakerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular circuit
breaker managed by this agent."
INDEX { tlpDeviceIndex, tlpPduBreakerIndex }
::= { tlpPduBreakerTable 1 }
TlpPduBreakerEntry ::= SEQUENCE {
tlpPduBreakerIndex Unsigned32,
tlpPduBreakerStatus INTEGER }
tlpPduBreakerIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the pdu circuit breaker."
::= { tlpPduBreakerEntry 1 }
tlpPduBreakerStatus OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1),
notInstalled(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the circuit breaker is open(0), closed(1) or not
installed(2)."
::= { tlpPduBreakerEntry 2 }
tlpPduHeatsinkTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduHeatsinkEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of pdu heatsink thermistor table entries. The number of entries
is given by the value of tlpPduIdentNumHeatsinks."
::= { tlpPduHeatsink 1 }
tlpPduHeatsinkEntry OBJECT-TYPE
SYNTAX TlpPduHeatsinkEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular heatsink
thermistor managed by this agent."
INDEX { tlpDeviceIndex, tlpPduHeatsinkIndex }
::= { tlpPduHeatsinkTable 1 }
TlpPduHeatsinkEntry ::= SEQUENCE {
tlpPduHeatsinkIndex Unsigned32,
tlpPduHeatsinkStatus INTEGER,
tlpPduHeatsinkTemperatureC Integer32,
tlpPduHeatsinkTemperatureF Integer32 }
tlpPduHeatsinkIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the pdu heatsink thermistor."
::= { tlpPduHeatsinkEntry 1 }
tlpPduHeatsinkStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvailable(0),
available(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the heatsink thermistor is available. The entry
will return notAvailable(0) if a thermistor is either non-existent or
disconnected, or available(1) when connected."
::= { tlpPduHeatsinkEntry 2 }
tlpPduHeatsinkTemperatureC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at the heatsink thermistor in tenths degrees Celsius.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduHeatsinkEntry 3 }
tlpPduHeatsinkTemperatureF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at the heatsink thermistor in tenths degrees Fahrenheit.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpPduHeatsinkEntry 4 }
tlpPduControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable controls for each pdu in device table. This is a
sparse dependent table, and will contain some subset of devices
that are pdus."
::= { tlpPduControl 1 }
tlpPduControlEntry OBJECT-TYPE
SYNTAX TlpPduControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing controls for a particular pdu."
INDEX { tlpDeviceIndex }
::= { tlpPduControlTable 1 }
TlpPduControlEntry ::= SEQUENCE {
tlpPduControlRamp TruthValue,
tlpPduControlShed TruthValue,
tlpPduControlPduOn TruthValue,
tlpPduControlPduOff TruthValue,
tlpPduControlPduRestart TruthValue,
tlpPduControlResetGeneralFault TruthValue,
tlpPduControlResetWattHours TruthValue,
tlpPduControlResetPeakPower TruthValue,
tlpPduControlClearEventLog TruthValue }
tlpPduControlRamp OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate the pre-designated ramp
sequence on the pdu."
::= { tlpPduControlEntry 1 }
tlpPduControlShed OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate the pre-designated shed
sequence on the pdu."
::= { tlpPduControlEntry 2 }
tlpPduControlPduOn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the pdu on."
::= { tlpPduControlEntry 3 }
tlpPduControlPduOff OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the pdu off."
::= { tlpPduControlEntry 4 }
tlpPduControlPduRestart OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to restart the pdu."
::= { tlpPduControlEntry 5 }
tlpPduControlResetGeneralFault OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the general fault alarm indicated by
tlpPduDeviceGeneralFault."
::= { tlpPduControlEntry 6 }
tlpPduControlResetWattHours OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the tlpPduDeviceWattHoursTotal, tlpPduOutputWattHours
and tlpPduCircuitWattHours calculation algorithms."
::= { tlpPduControlEntry 7 }
tlpPduControlResetPeakPower OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the tlpPduCircuitPeakPower and tlpPduOutputPeakPower
calculation algorithms."
::= { tlpPduControlEntry 8 }
tlpPduControlClearEventLog OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to clear the event log retained by the pdu."
::= { tlpPduControlEntry 9 }
tlpPduControlOutputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduControlOutputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable output phase-specific controls for each pdu in device
table. This is a sparse dependent table, and will contain some subset of
devices that are pdus."
::= { tlpPduControl 2 }
tlpPduControlOutputPhaseEntry OBJECT-TYPE
SYNTAX TlpPduControlOutputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular output
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpPduOutputIndex }
::= { tlpPduControlOutputPhaseTable 1 }
TlpPduControlOutputPhaseEntry ::= SEQUENCE {
tlpPduControlResetOutputCurrentMinMax TruthValue }
tlpPduControlResetOutputCurrentMinMax OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset tlpPduOutputCurrentMin and tlpPduOutputCurrentMax
to their appropriate minimum and maximum values. This value will return
ERROR_NO_SUCH_NAME if not supported."
::= { tlpPduControlOutputPhaseEntry 1 }
tlpPduControlInputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduControlInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable input phase-specific controls for each pdu in device
table. This is a sparse dependent table, and will contain some subset of
devices that are pdus."
::= { tlpPduControl 3 }
tlpPduControlInputPhaseEntry OBJECT-TYPE
SYNTAX TlpPduControlInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular input
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpPduInputPhaseIndex }
::= { tlpPduControlInputPhaseTable 1 }
TlpPduControlInputPhaseEntry ::= SEQUENCE {
tlpPduControlResetInputVoltageMinMax TruthValue }
tlpPduControlResetInputVoltageMinMax OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset tlpPduInputPhaseVoltageMin and tlpPduInputPhaseVoltageMax
to their appropriate minimum and maximum values. Resetting the minimum and maximum
values for one phase on some devices will reset the values for all phases. This
value will return ERROR_NO_SUCH_NAME if not supported."
::= { tlpPduControlInputPhaseEntry 1 }
tlpPduConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each pdu in device table. This
is a sparse dependent table, and will contain some subset of
devices that are pdus. Not all options are available on all
pdus."
::= { tlpPduConfig 1 }
tlpPduConfigEntry OBJECT-TYPE
SYNTAX TlpPduConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing configuration options for a particular pdu."
INDEX { tlpDeviceIndex }
::= { tlpPduConfigTable 1 }
TlpPduConfigEntry ::= SEQUENCE {
tlpPduConfigInputVoltage Unsigned32,
tlpPduConfigIsoBreakerSetting INTEGER,
tlpPduConfigRelayCalibrationSetting INTEGER,
tlpPduConfigThdSetting INTEGER,
tlpPduConfigWaveformCaptureSetting INTEGER,
tlpPduConfigRemoteResetSetting INTEGER }
tlpPduConfigInputVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the value will be rejected and an appropriate error
message will be returned."
::= { tlpPduConfigEntry 1 }
tlpPduConfigIsoBreakerSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The IsoBreaker feature uses software to eliminate the cause
of an overcurrent before the circuit break trips. If a specific outlet
has an overcurrent, this outlet is probably the cause, and this outlet
should be turned off. This setting specifies whether the pdu turns off
outlets to correct overcurrent."
::= { tlpPduConfigEntry 2 }
tlpPduConfigRelayCalibrationSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether to automatically self-calibrate the relays on the
device."
::= { tlpPduConfigEntry 3 }
tlpPduConfigThdSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether the total harmonic distortion features on the device are
enabled."
::= { tlpPduConfigEntry 4 }
tlpPduConfigWaveformCaptureSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether the device will capture waveforms to associate with
logged events."
::= { tlpPduConfigEntry 5 }
tlpPduConfigRemoteResetSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether the LX Card can be remotely reset via a Wake-On-LAN (WOL)
packet."
::= { tlpPduConfigEntry 6 }
tlpPduConfigOutputPhaseThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduConfigOutputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each pdu in device table. This
is a sparse dependent table, and will contain some subset of
devices that are pdus. Not all options are available on all
pdus."
::= { tlpPduConfig 2 }
tlpPduConfigOutputPhaseThresholdEntry OBJECT-TYPE
SYNTAX TlpPduConfigOutputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing threshold configuration options for a particular pdu."
INDEX { tlpDeviceIndex, tlpPduOutputIndex }
::= { tlpPduConfigOutputPhaseThresholdTable 1 }
TlpPduConfigOutputPhaseThresholdEntry ::= SEQUENCE {
tlpPduConfigOutputCurrentThresholdTolerance Unsigned32,
tlpPduConfigOutputCurrentHighThreshold Unsigned32,
tlpPduConfigOutputCurrentLowThreshold Unsigned32,
tlpPduConfigOutputVoltageThresholdTolerance Unsigned32,
tlpPduConfigOutputVoltageHighCriticalThreshold Unsigned32,
tlpPduConfigOutputVoltageHighWarningThreshold Unsigned32,
tlpPduConfigOutputVoltageLowWarningThreshold Unsigned32,
tlpPduConfigOutputVoltageLowCriticalThreshold Unsigned32 }
tlpPduConfigOutputCurrentThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value, in hundredths of amps, used
together with output current high/low threshold to evaluate
output current high/low condition. The actual precision of this
value, whether a whole number, tenths or hundredths, is returned
by tlpPduDeviceOutputCurrentPrecision."
::= { tlpPduConfigOutputPhaseThresholdEntry 1 }
tlpPduConfigOutputCurrentHighThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value, in hundredths of amps, at which an output current
high condition is declared. The actual precision of this value,
whether a whole number, tenths or hundredths, is returned by
tlpPduDeviceOutputCurrentPrecision."
::= { tlpPduConfigOutputPhaseThresholdEntry 2 }
tlpPduConfigOutputCurrentLowThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value, in hundredths of amps, at which an output current
low condition is declared. The actual precision of this value,
whether a whole number, tenths or hundredths, is returned by
tlpPduDeviceOutputCurrentPrecision."
::= { tlpPduConfigOutputPhaseThresholdEntry 3 }
tlpPduConfigOutputVoltageThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output voltage high/low
threshold to evaluate output voltage high/low condition."
::= { tlpPduConfigOutputPhaseThresholdEntry 4 }
tlpPduConfigOutputVoltageHighCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage high critical condition is declared."
::= { tlpPduConfigOutputPhaseThresholdEntry 5 }
tlpPduConfigOutputVoltageHighWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage high warning condition is declared."
::= { tlpPduConfigOutputPhaseThresholdEntry 6 }
tlpPduConfigOutputVoltageLowWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage low warning condition is declared."
::= { tlpPduConfigOutputPhaseThresholdEntry 7 }
tlpPduConfigOutputVoltageLowCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage low critical condition is declared."
::= { tlpPduConfigOutputPhaseThresholdEntry 8 }
tlpPduConfigInputPhaseThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduConfigInputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input phase configuration details for each pdu in device table.
This is a sparse dependent table, and will contain the number of
entries based on the number of pdus managed by the agent as reported
by tlpPduIdentNumPdu and tlpPduIdentNumPhases. Not all options are
available on all pdus."
::= { tlpPduConfig 3 }
tlpPduConfigInputPhaseThresholdEntry OBJECT-TYPE
SYNTAX TlpPduConfigInputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular input
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpPduInputPhaseIndex }
::= { tlpPduConfigInputPhaseThresholdTable 1 }
TlpPduConfigInputPhaseThresholdEntry ::= SEQUENCE {
tlpPduConfigInputVoltageThresholdTolerance Unsigned32,
tlpPduConfigInputVoltageHighCriticalThreshold Unsigned32,
tlpPduConfigInputVoltageHighWarningThreshold Unsigned32,
tlpPduConfigInputVoltageLowWarningThreshold Unsigned32,
tlpPduConfigInputVoltageLowCriticalThreshold Unsigned32 }
tlpPduConfigInputVoltageThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output voltage high/low
threshold to evaluate output voltage high/low condition."
::= { tlpPduConfigInputPhaseThresholdEntry 1 }
tlpPduConfigInputVoltageHighCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage high critical condition is declared."
::= { tlpPduConfigInputPhaseThresholdEntry 2 }
tlpPduConfigInputVoltageHighWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage high warning condition is declared."
::= { tlpPduConfigInputPhaseThresholdEntry 3 }
tlpPduConfigInputVoltageLowWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage low warning condition is declared."
::= { tlpPduConfigInputPhaseThresholdEntry 4 }
tlpPduConfigInputVoltageLowCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage low critical condition is declared."
::= { tlpPduConfigInputPhaseThresholdEntry 5 }
tlpPduConfigThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpPduConfigThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configurable threshold options of each pdu in device table. This
is a sparse dependent table, and will contain some subset of devices that
are pdus. Not all options are available on all pdus."
::= { tlpPduConfig 4 }
tlpPduConfigThresholdEntry OBJECT-TYPE
SYNTAX TlpPduConfigThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing configurable threshold options for a particular pdu."
INDEX { tlpDeviceIndex }
::= { tlpPduConfigThresholdTable 1 }
TlpPduConfigThresholdEntry ::= SEQUENCE {
tlpPduConfigThdOutOfRangeThreshold Unsigned32 }
tlpPduConfigThdOutOfRangeThreshold OBJECT-TYPE
SYNTAX Unsigned32 (1..9999)
UNITS "0.01 percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Denotes the percentage of THD voltage in hundredths of a percent at which
the THD voltage out of range condition occurs. The out of range condition,
tlpPduAlarmThdOutOfRange, is triggered when the THD voltage exceeds this
value."
::= { tlpPduConfigThresholdEntry 1 }
-- envirosense
tlpEnvIdentNumEnvirosense OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of envirosense devices that this agent is currently managing."
::= { tlpEnvIdent 1 }
tlpEnvIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpEnvIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The identity details of each envirosense in device table. This is a
sparse dependent table, and will contain some subset of devices
that are envirosenses."
::= { tlpEnvIdent 2 }
tlpEnvIdentEntry OBJECT-TYPE
SYNTAX TlpEnvIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing details for a particular envirosense."
INDEX { tlpDeviceIndex }
::= { tlpEnvIdentTable 1 }
TlpEnvIdentEntry ::= SEQUENCE {
tlpEnvIdentTempSupported TruthValue,
tlpEnvIdentHumiditySupported TruthValue,
tlpEnvNumInputContacts Unsigned32,
tlpEnvNumOutputContacts Unsigned32 }
tlpEnvIdentTempSupported OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not temperature is supported."
::= { tlpEnvIdentEntry 1 }
tlpEnvIdentHumiditySupported OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not humidity is supported."
::= { tlpEnvIdentEntry 2 }
tlpEnvNumInputContacts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of input contacts supported by the envirosense."
::= { tlpEnvIdentEntry 3 }
tlpEnvNumOutputContacts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of output contacts supported by the envirosense."
::= { tlpEnvIdentEntry 4 }
tlpEnvTemperatureTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpEnvTemperatureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The temperature details of each envirosense in device table. The
number of entries is given by the value of tlpDevicesNumDevices."
::= { tlpEnvDetail 1 }
tlpEnvTemperatureEntry OBJECT-TYPE
SYNTAX TlpEnvTemperatureEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing temperature details for a particular
envirosense."
INDEX { tlpDeviceIndex }
::= { tlpEnvTemperatureTable 1 }
TlpEnvTemperatureEntry ::= SEQUENCE {
tlpEnvTemperatureC Integer32,
tlpEnvTemperatureF Integer32,
tlpEnvTemperatureInAlarm TruthValue }
tlpEnvTemperatureC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature."
::= { tlpEnvTemperatureEntry 1 }
tlpEnvTemperatureF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature."
::= { tlpEnvTemperatureEntry 2 }
tlpEnvTemperatureInAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not temperature is in alarm."
::= { tlpEnvTemperatureEntry 3 }
tlpEnvHumidityTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpEnvHumidityEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The humidity details of each envirosense in device table. The
number of entries is given by the value of tlpDevicesNumDevices."
::= { tlpEnvDetail 2 }
tlpEnvHumidityEntry OBJECT-TYPE
SYNTAX TlpEnvHumidityEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing humidity details for a particular
envirosense."
INDEX { tlpDeviceIndex }
::= { tlpEnvHumidityTable 1 }
TlpEnvHumidityEntry ::= SEQUENCE {
tlpEnvHumidityHumidity INTEGER,
tlpEnvHumidityInAlarm TruthValue }
tlpEnvHumidityHumidity OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient humidity."
::= { tlpEnvHumidityEntry 1 }
tlpEnvHumidityInAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not humidity is in alarm."
::= { tlpEnvHumidityEntry 2 }
tlpEnvInputContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpEnvInputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input contact details of each envirosense in device table.
The number of entries is given by the value of tlpDevicesNumDevices."
::= { tlpEnvDetail 3 }
tlpEnvInputContactEntry OBJECT-TYPE
SYNTAX TlpEnvInputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing input contact details for a particular
envirosense."
INDEX { tlpDeviceIndex, tlpEnvInputContactIndex }
::= { tlpEnvInputContactTable 1 }
TlpEnvInputContactEntry ::= SEQUENCE {
tlpEnvInputContactIndex Unsigned32,
tlpEnvInputContactName DisplayString,
tlpEnvInputContactNormalState INTEGER,
tlpEnvInputContactCurrentState INTEGER,
tlpEnvInputContactInAlarm TruthValue }
tlpEnvInputContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the envirosense input contact details."
::= { tlpEnvInputContactEntry 1 }
tlpEnvInputContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name or description of the contact."
::= { tlpEnvInputContactEntry 2 }
tlpEnvInputContactNormalState OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The normal operating position of the contact."
::= { tlpEnvInputContactEntry 3 }
tlpEnvInputContactCurrentState OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the contact."
::= { tlpEnvInputContactEntry 4 }
tlpEnvInputContactInAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the contact is in alarm."
::= { tlpEnvInputContactEntry 5 }
tlpEnvOutputContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpEnvOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output contact details of each envirosense in device table.
The number of entries is given by the value of tlpDevicesNumDevices."
::= { tlpEnvDetail 4 }
tlpEnvOutputContactEntry OBJECT-TYPE
SYNTAX TlpEnvOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing output contact details for a particular
envirosense."
INDEX { tlpDeviceIndex, tlpEnvOutputContactIndex }
::= { tlpEnvOutputContactTable 1 }
TlpEnvOutputContactEntry ::= SEQUENCE {
tlpEnvOutputContactIndex Unsigned32,
tlpEnvOutputContactName DisplayString,
tlpEnvOutputContactNormalState INTEGER,
tlpEnvOutputContactCurrentState INTEGER,
tlpEnvOutputContactInAlarm TruthValue }
tlpEnvOutputContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the envirosense output contact details."
::= { tlpEnvOutputContactEntry 1 }
tlpEnvOutputContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name or description of the contact."
::= { tlpEnvOutputContactEntry 2 }
tlpEnvOutputContactNormalState OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The normal operating position of the contact."
::= { tlpEnvOutputContactEntry 3 }
tlpEnvOutputContactCurrentState OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the contact. Use tlpEnvControlOutputContactOpen
and tlpEnvControlOutputContactClose to change the state of the output
contact."
::= { tlpEnvOutputContactEntry 4 }
tlpEnvOutputContactInAlarm OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the contact is in alarm."
::= { tlpEnvOutputContactEntry 5 }
tlpEnvControlOutputContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpEnvControlOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable controls for each sensor in device table. This is a
sparse dependent table, and will contain some subset of devices
that are sensors."
::= { tlpEnvControl 1 }
tlpEnvControlOutputContactEntry OBJECT-TYPE
SYNTAX TlpEnvControlOutputContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing controls for a particular pdu."
INDEX { tlpDeviceIndex, tlpEnvOutputContactIndex }
::= { tlpEnvControlOutputContactTable 1 }
TlpEnvControlOutputContactEntry ::= SEQUENCE {
tlpEnvControlOutputContactOpen TruthValue,
tlpEnvControlOutputContactClose TruthValue }
tlpEnvControlOutputContactOpen OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to open this output contact."
::= { tlpEnvControlOutputContactEntry 1 }
tlpEnvControlOutputContactClose OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to close this output contact."
::= { tlpEnvControlOutputContactEntry 2 }
tlpEnvConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpEnvConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each envirosense in device table.
This is a sparse dependent table, and will contain some subset of
devices that are envirosenses. Not all options are available on
all envirosenses."
::= { tlpEnvConfig 1 }
tlpEnvConfigEntry OBJECT-TYPE
SYNTAX TlpEnvConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing configuration options for a particular
envirosenses."
INDEX { tlpDeviceIndex }
::= { tlpEnvConfigTable 1 }
TlpEnvConfigEntry ::= SEQUENCE {
tlpEnvTemperatureLowLimit Integer32,
tlpEnvTemperatureHighLimit Integer32,
tlpEnvHumidityLowLimit INTEGER,
tlpEnvHumidityHighLimit INTEGER }
tlpEnvTemperatureLowLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower alarm limit for ambient temperature."
::= { tlpEnvConfigEntry 1 }
tlpEnvTemperatureHighLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper alarm limit for ambient temperature."
::= { tlpEnvConfigEntry 2 }
tlpEnvHumidityLowLimit OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The lower alarm limit for ambient humidity."
::= { tlpEnvConfigEntry 3 }
tlpEnvHumidityHighLimit OBJECT-TYPE
SYNTAX INTEGER (0..100)
UNITS "percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The upper alarm limit for ambient humidity."
::= { tlpEnvConfigEntry 4 }
-- ats
tlpAtsIdentNumAts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of ats devices that this agent is currently managing."
::= { tlpAtsIdent 1 }
tlpAtsIdentTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The identity details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss."
::= { tlpAtsIdent 2 }
tlpAtsIdentEntry OBJECT-TYPE
SYNTAX TlpAtsIdentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing details for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsIdentTable 1 }
TlpAtsIdentEntry ::= SEQUENCE {
tlpAtsIdentNumInputs Unsigned32,
tlpAtsIdentNumOutputs Unsigned32,
tlpAtsIdentNumPhases Unsigned32,
tlpAtsIdentNumOutlets Unsigned32,
tlpAtsIdentNumOutletGroups Unsigned32,
tlpAtsIdentNumCircuits Unsigned32,
tlpAtsIdentNumBreakers Unsigned32,
tlpAtsIdentNumHeatsinks Unsigned32 }
tlpAtsIdentNumInputs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of inputs supported by the ats."
::= { tlpAtsIdentEntry 1 }
tlpAtsIdentNumOutputs OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of outputs supported by the ats."
::= { tlpAtsIdentEntry 2 }
tlpAtsIdentNumPhases OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of phases per input supported by the ats."
::= { tlpAtsIdentEntry 3 }
tlpAtsIdentNumOutlets OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of receptacles supported by the ats."
::= { tlpAtsIdentEntry 4 }
tlpAtsIdentNumOutletGroups OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of user-defined receptacle groups created for the
ats."
::= { tlpAtsIdentEntry 5 }
tlpAtsIdentNumCircuits OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of circuits supported by the ats."
::= { tlpAtsIdentEntry 6 }
tlpAtsIdentNumBreakers OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of monitored circuit breakers supported by the ats.
If the ats has breakers that are not monitored by the device,
the value of zero(0) will be returned."
::= { tlpAtsIdentEntry 7 }
tlpAtsIdentNumHeatsinks OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of heatsink thermistors supported by the ats."
::= { tlpAtsIdentEntry 8 }
tlpAtsSupportsTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsSupportsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The supported details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss."
::= { tlpAtsIdent 3 }
tlpAtsSupportsEntry OBJECT-TYPE
SYNTAX TlpAtsSupportsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing supported details for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsSupportsTable 1 }
TlpAtsSupportsEntry ::= SEQUENCE {
tlpAtsSupportsEnergywise TruthValue,
tlpAtsSupportsRampShed TruthValue,
tlpAtsSupportsOutletGroup TruthValue,
tlpAtsSupportsOutletCurrent TruthValue,
tlpAtsSupportsOutletVoltage TruthValue,
tlpAtsSupportsOutletActivePower TruthValue }
tlpAtsSupportsEnergywise OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Indicates whether the ats supports Cisco EnergyWise."
::= { tlpAtsSupportsEntry 1 }
tlpAtsSupportsRampShed OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ats supports ramping and shedding."
::= { tlpAtsSupportsEntry 2 }
tlpAtsSupportsOutletGroup OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ats supports outlet groups."
::= { tlpAtsSupportsEntry 3 }
tlpAtsSupportsOutletCurrent OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ats reports individual receptacle
current measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpAtsOutletCurrent."
::= { tlpAtsSupportsEntry 4 }
tlpAtsSupportsOutletVoltage OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ats reports individual receptacle voltage
measurements. Devices that do not support individual receptacle
measurements will always return ERROR_NO_SUCH_NAME for
tlpAtsOutletVoltage."
::= { tlpAtsSupportsEntry 5 }
tlpAtsSupportsOutletActivePower OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the ats reports individual receptacle
power measurements. Devices that do not support individual
receptacle measurements will always return ERROR_NO_SUCH_NAME for
tlpAtsOutletActivePower."
::= { tlpAtsSupportsEntry 6 }
tlpAtsDisplayTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsDisplayEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"The display details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss."
::= { tlpAtsIdent 4 }
tlpAtsDisplayEntry OBJECT-TYPE
SYNTAX TlpAtsDisplayEntry
MAX-ACCESS not-accessible
STATUS deprecated
DESCRIPTION
"An entry containing display details for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsDisplayTable 1 }
TlpAtsDisplayEntry ::= SEQUENCE {
tlpAtsDisplayScheme INTEGER,
tlpAtsDisplayOrientation INTEGER,
tlpAtsDisplayAutoScroll INTEGER,
tlpAtsDisplayIntensity INTEGER,
tlpAtsDisplayUnits INTEGER }
tlpAtsDisplayScheme OBJECT-TYPE
SYNTAX INTEGER {
schemeReverse(0),
schemeNormal(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the display scheme of the LED display. The value
schemeReverse(0) indicates the tricolor LED indicator uses an
alternate pattern. The value schemeNormal(1) indicates the
LED indicator uses the standard pattern. This value may not
be supported on all models. If not supported, the value will
always return schemeNormal(1)."
::= { tlpAtsDisplayEntry 1 }
tlpAtsDisplayOrientation OBJECT-TYPE
SYNTAX INTEGER {
displayNormal(0),
displayReverse(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the physical orientation of the LED display. The value
displayNormal(0) indicates the display is right-side-up (normal).
The value displayReverse(1) indicates the display is upside-down.
This value may not be supported on all models. If not supported,
the value will always return displayNormal(0)."
::= { tlpAtsDisplayEntry 2 }
tlpAtsDisplayAutoScroll OBJECT-TYPE
SYNTAX INTEGER {
scrollDisabled(0),
scrollEnabled(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates whether the LED display automatically scrolls through
displaying status values."
::= { tlpAtsDisplayEntry 3 }
tlpAtsDisplayIntensity OBJECT-TYPE
SYNTAX INTEGER {
intensity25(1),
intensity50(2),
intensity75(3),
intensity100(4) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the intensity, as a percentage, of the LED display. The
value intensity100(4) indicates the display is at 100% intensity.
The other values indicate the display is at a lesser intensity based
upon the respective percentage denoted."
::= { tlpAtsDisplayEntry 4 }
tlpAtsDisplayUnits OBJECT-TYPE
SYNTAX INTEGER {
normal(0),
metric(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates the units of measurement displayed on the LED display.
The value normal(0) indicates that a temperature value, for example,
is displayed in degrees Fahrenheit. The value metric(1) indicates a
temperature value is displayed in degrees Celsius."
::= { tlpAtsDisplayEntry 5 }
tlpAtsDeviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The device details of each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss."
::= { tlpAtsDevice 1 }
tlpAtsDeviceEntry OBJECT-TYPE
SYNTAX TlpAtsDeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing device details for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsDeviceTable 1 }
TlpAtsDeviceEntry ::= SEQUENCE {
tlpAtsDeviceMainLoadState INTEGER,
tlpAtsDeviceMainLoadControllable TruthValue,
tlpAtsDeviceMainLoadCommand INTEGER,
tlpAtsDevicePowerOnDelay Integer32,
tlpAtsDeviceTotalInputPowerRating Integer32,
tlpAtsDeviceTemperatureC Integer32,
tlpAtsDeviceTemperatureF Integer32,
tlpAtsDevicePhaseImbalance INTEGER,
tlpAtsDeviceOutputActivePowerTotal Unsigned32,
tlpAtsDeviceAggregatePowerFactor Unsigned32,
tlpAtsDeviceOutputCurrentPrecision INTEGER,
tlpAtsDeviceGeneralFault TruthValue,
tlpAtsDeviceTotalOutputUtilization INTEGER,
tlpAtsDeviceOutputApparentPowerTotal Unsigned32,
tlpAtsDeviceOutputReactivePowerTotal Integer32,
tlpAtsDeviceOutputCurrentTotal Unsigned32,
tlpAtsDeviceWattHoursTotal Unsigned32,
tlpAtsDevicePeakPowerTotal Unsigned32,
tlpAtsDevice24hrEnergyTotal Unsigned32 }
tlpAtsDeviceMainLoadState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the main output of the device."
::= { tlpAtsDeviceEntry 1 }
tlpAtsDeviceMainLoadControllable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the main output is controllable, and whether
the ups can be turned off and on."
::= { tlpAtsDeviceEntry 2 }
tlpAtsDeviceMainLoadCommand OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value to
turnOff(1) will turn off the main output of the ups. Setting this
value to turnOn(2) will turn on the main output of the ups. Setting
this value to cycle(3) will turn off the main output, then turn it
back on."
::= { tlpAtsDeviceEntry 3 }
tlpAtsDevicePowerOnDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "Seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The configurable delay value, which sets the amount of additional
time a given device will wait before it connects to a valid AC
source. By default the delay value is set to 0. For devices with
multiple AC input sources, this delay only applies to the primary
input source."
::= { tlpAtsDeviceEntry 4 }
tlpAtsDeviceTotalInputPowerRating OBJECT-TYPE
SYNTAX Integer32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total input power rating of all phases on the device. This
value may not be supported on all models. If not supported, this
value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsDeviceEntry 5 }
tlpAtsDeviceTemperatureC OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the ats casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsDeviceEntry 6 }
tlpAtsDeviceTemperatureF OBJECT-TYPE
SYNTAX Integer32
UNITS "degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature at or near the ats casing. Temperature
measurements are not supported on all models. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsDeviceEntry 7 }
tlpAtsDevicePhaseImbalance OBJECT-TYPE
SYNTAX INTEGER (0..200)
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of imbalance of the three phases. This value is in
the range from 0% imbalance to 100% imbalance. The lower the value,
the better balanced the phases are. If all load is on a single phase,
the imbalance is defined as 100%."
::= { tlpAtsDeviceEntry 8 }
tlpAtsDeviceOutputActivePowerTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC output total true power for all circuits."
::= { tlpAtsDeviceEntry 9 }
tlpAtsDeviceAggregatePowerFactor OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The aggregate power factor of all phases."
::= { tlpAtsDeviceEntry 10 }
tlpAtsDeviceOutputCurrentPrecision OBJECT-TYPE
SYNTAX INTEGER {
none(0),
tenths(1),
hundredths(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Output current is reported by tlpAtsOutputCurrent, tlpAtsOutputCurrentMin
and tlpAtsOutputCurrentMax. These values are all reported in hundredths
(0.01A), which accommodates all models; however, on any given device the
actual precision may vary. This value describes the actual precision, which
can be used as a divisor against the output current values to obtain the
true output current measurement. For example, if tlpAtsOutputCurrent reports
530 and tlpAtsDeviceOutputCurrentPrecision is tenths(1), then the actual
output current is 5.3."
::= { tlpAtsDeviceEntry 11 }
tlpAtsDeviceGeneralFault OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether or not the ats is in a fault condition. When the ats is in such
a fault condition, the condition can be cleared with tlpAtsControlResetGeneralFault."
::= { tlpAtsDeviceEntry 12 }
tlpAtsDeviceTotalOutputUtilization OBJECT-TYPE
SYNTAX INTEGER
UNITS "percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total percentage of the ats power capacity presently being
used on the ats."
::= { tlpAtsDeviceEntry 13 }
tlpAtsDeviceOutputApparentPowerTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC output total apparent power for all circuits. If not supported, this
value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsDeviceEntry 14 }
tlpAtsDeviceOutputReactivePowerTotal OBJECT-TYPE
SYNTAX Integer32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The AC output total reactive power for all circuits. If not supported, this
value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsDeviceEntry 15 }
tlpAtsDeviceOutputCurrentTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total output current, in hundredths of amps.The actual precision of
this value, whether a whole number, tenths or hundredths, is returned
by tlpAtsDeviceOutputCurrentPrecision."
::= { tlpAtsDeviceEntry 16 }
tlpAtsDeviceWattHoursTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "WH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of watt hours of energy utilized in the past 24 hours. Use
tlpAtsControlResetWattHours to reset the watt hours calculation algorithm."
::= { tlpAtsDeviceEntry 17 }
tlpAtsDevicePeakPowerTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum 1 second average power value since the last reset. Use
tlpAtsControlResetPeakPower to reset the peak power calculations."
::= { tlpAtsDeviceEntry 18 }
tlpAtsDevice24hrEnergyTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption using present value
of tlpAtsOutputPowerKW."
::= { tlpAtsDeviceEntry 19 }
tlpAtsInputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input details of each ats in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the number of atss managed by the agent as reported by tlpAtsIdentNumAts."
::= { tlpAtsInput 1 }
tlpAtsInputEntry OBJECT-TYPE
SYNTAX TlpAtsInputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular primary
input phase managed by this agent."
INDEX { tlpDeviceIndex }
::= { tlpAtsInputTable 1 }
TlpAtsInputEntry ::= SEQUENCE {
tlpAtsInputNominalVoltage Unsigned32,
tlpAtsInputNominalVoltagePhaseToPhase Unsigned32,
tlpAtsInputNominalVoltagePhaseToNeutral Unsigned32,
tlpAtsInputLowTransferVoltage Unsigned32,
tlpAtsInputLowTransferVoltageLowerBound Unsigned32,
tlpAtsInputLowTransferVoltageUpperBound Unsigned32,
tlpAtsInputHighTransferVoltage Unsigned32,
tlpAtsInputHighTransferVoltageLowerBound Unsigned32,
tlpAtsInputHighTransferVoltageUpperBound Unsigned32,
tlpAtsInputFairVoltageThreshold Unsigned32,
tlpAtsInputBadVoltageThreshold Unsigned32,
tlpAtsInputSourceAvailability INTEGER,
tlpAtsInputSourceInUse INTEGER,
tlpAtsInputSourceTransitionCount Unsigned32,
tlpAtsInputCurrentLimit Unsigned32,
tlpAtsInputCurrentTotal Unsigned32 }
tlpAtsInputNominalVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsInputEntry 1 }
tlpAtsInputNominalVoltagePhaseToPhase OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line voltage as measured from
phase to phase. This value may not be supported on all models.
If not supported, this value will always return zero."
::= { tlpAtsInputEntry 2 }
tlpAtsInputNominalVoltagePhaseToNeutral OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The nominal value of the input line voltage as measured from
phase to neutral. This value may not be supported on all models.
If not supported, this value will always return zero."
::= { tlpAtsInputEntry 3 }
tlpAtsInputLowTransferVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum line voltage allowed before the unit disconnects the
AC input connection."
::= { tlpAtsInputEntry 4 }
tlpAtsInputLowTransferVoltageLowerBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lower boundary value of tlpAtsInputLowTransferVoltage as dictated
by the hardware of the unit."
::= { tlpAtsInputEntry 5 }
tlpAtsInputLowTransferVoltageUpperBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The upper boundary value of tlpAtsInputLowTransferVoltage as dictated
by the hardware of the unit."
::= { tlpAtsInputEntry 6 }
tlpAtsInputHighTransferVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum line voltage allowed before the unit disconnects the
AC input connection."
::= { tlpAtsInputEntry 7 }
tlpAtsInputHighTransferVoltageLowerBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The lower boundary value of tlpAtsInputHighTransferVoltage as dictated
by the hardware of the unit."
::= { tlpAtsInputEntry 8 }
tlpAtsInputHighTransferVoltageUpperBound OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The upper boundary value of tlpAtsInputHighTransferVoltage as dictated
by the hardware of the unit."
::= { tlpAtsInputEntry 9 }
tlpAtsInputFairVoltageThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The voltage level at which the device will transition between sources."
::= { tlpAtsInputEntry 10 }
tlpAtsInputBadVoltageThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum line voltage allowed before the device disconnects the AC input
connection."
::= { tlpAtsInputEntry 11 }
tlpAtsInputSourceAvailability OBJECT-TYPE
SYNTAX INTEGER {
none(0),
inputSourceA(1),
inputSourceB(2),
inputSourceAB(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The determination as to which of two AC input lines are available.
The agent will return either inputSourceA(1) or inputSourceB(2) if
only one line is available, or inputSourceAB(3) if both lines are
available. The agent will never return none(0) since the device will
be powered off if neither line is available."
::= { tlpAtsInputEntry 12 }
tlpAtsInputSourceInUse OBJECT-TYPE
SYNTAX INTEGER {
inputSourceA(0),
inputSourceB(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The determination as to which one of two AC input lines is in use. Not all
devices support the reporting of which source is currently in use. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsInputEntry 13 }
tlpAtsInputSourceTransitionCount OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of times the device transitions between primary and secondary
sources. Most devices are limited to 65533 transitions, after which the
value will not increment. If not supported, this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpAtsInputEntry 14 }
tlpAtsInputCurrentLimit OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The capacity of each phase conductor in the ats limited by the AC input
cord or any other potential limiting factors unique to a given unit. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsInputEntry 15 }
tlpAtsInputCurrentTotal OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The aggregate total of conductor currents. If the ats does not support this value,
then the agent will report ERROR_NO_SUCH_NAME."
::= { tlpAtsInputEntry 16 }
tlpAtsInputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input phase details of each ats in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpAtsIdentNumInputs and tlpAtsIdentNumPhases per each
device."
::= { tlpAtsInput 2 }
tlpAtsInputPhaseEntry OBJECT-TYPE
SYNTAX TlpAtsInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular primary
input phase managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsInputLineIndex, tlpAtsInputPhaseIndex }
::= { tlpAtsInputPhaseTable 1 }
TlpAtsInputPhaseEntry ::= SEQUENCE {
tlpAtsInputLineIndex Unsigned32,
tlpAtsInputPhaseIndex Unsigned32,
tlpAtsInputPhaseType INTEGER,
tlpAtsInputPhaseFrequency Unsigned32,
tlpAtsInputPhaseVoltage Unsigned32,
tlpAtsInputPhaseVoltageMin Unsigned32,
tlpAtsInputPhaseVoltageMax Unsigned32,
tlpAtsInputPhaseCurrent Unsigned32,
tlpAtsInputPhasePower Unsigned32,
tlpAtsInputPhaseThdVoltage Unsigned32 }
tlpAtsInputLineIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the input line on the ats."
::= { tlpAtsInputPhaseEntry 1 }
tlpAtsInputPhaseIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the input phase for the input line."
::= { tlpAtsInputPhaseEntry 2 }
tlpAtsInputPhaseType OBJECT-TYPE
SYNTAX INTEGER {
phaseToNeutral(0),
phaseToPhase(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether measurements are phase to neutral(0) or phase
to phase(1)."
::= { tlpAtsInputPhaseEntry 3 }
tlpAtsInputPhaseFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present input frequency for a given phase."
::= { tlpAtsInputPhaseEntry 4 }
tlpAtsInputPhaseVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input voltage for a given phase."
::= { tlpAtsInputPhaseEntry 5 }
tlpAtsInputPhaseVoltageMin OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpAtsInputPhaseVoltageMin or tlpAtsInputPhaseVoltageMax using
agent version below 20, both will be reset to their appropriate
minimum and maximum values. Writes are deprecated as of agent
version 20. Use tlpAtsControlResetInputVoltageMinMax to reset
this value."
::= { tlpAtsInputPhaseEntry 6 }
tlpAtsInputPhaseVoltageMax OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum input voltage value since the last reset of this
value for a given input line. If any value is written to either
tlpAtsInputPhaseVoltageMin or tlpAtsInputPhaseVoltageMax using
agent version below 20, both will be reset to their appropriate
minimum and maximum values. Writes are deprecated as of agent
version 20. Use tlpAtsControlResetInputVoltageMinMax to reset
this value."
::= { tlpAtsInputPhaseEntry 7 }
tlpAtsInputPhaseCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input current for a given phase."
::= { tlpAtsInputPhaseEntry 8 }
tlpAtsInputPhasePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present input true power."
::= { tlpAtsInputPhaseEntry 9 }
tlpAtsInputPhaseThdVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The voltage thd (total harmonic distortion) for this phase in hundredths
of a percent."
::= { tlpAtsInputPhaseEntry 10 }
tlpAtsOutputTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The output details of each ats in device table. This is a sparse
dependent table, and will contain the number of entries based upon
the value of tlpAtsIdentNumOutputs per each device."
::= { tlpAtsOutput 1 }
tlpAtsOutputEntry OBJECT-TYPE
SYNTAX TlpAtsOutputEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing output information applicable to a particular
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsOutputIndex }
::= { tlpAtsOutputTable 1 }
TlpAtsOutputEntry ::= SEQUENCE {
tlpAtsOutputIndex Unsigned32,
tlpAtsOutputPhase INTEGER,
tlpAtsOutputPhaseType INTEGER,
tlpAtsOutputVoltage Unsigned32,
tlpAtsOutputCurrent Unsigned32,
tlpAtsOutputCurrentMin Unsigned32,
tlpAtsOutputCurrentMax Unsigned32,
tlpAtsOutputActivePower Unsigned32,
tlpAtsOutputPowerFactor INTEGER,
tlpAtsOutputSource INTEGER,
tlpAtsOutputFrequency Unsigned32,
tlpAtsOutputPowerKVA Unsigned32,
tlpAtsOutputPowerKW Unsigned32,
tlpAtsOutput24hrEnergy Unsigned32,
tlpAtsOutputApparentPower Unsigned32,
tlpAtsOutputReactivePower Integer32,
tlpAtsOutputUtilization Unsigned32,
tlpAtsOutputWattHours Unsigned32,
tlpAtsOutputPeakPower Unsigned32 }
tlpAtsOutputIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ats phase."
::= { tlpAtsOutputEntry 1 }
tlpAtsOutputPhase OBJECT-TYPE
SYNTAX INTEGER {
phase1(1),
phase2(2),
phase3(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates the phase associated with the output line."
::= { tlpAtsOutputEntry 2 }
tlpAtsOutputPhaseType OBJECT-TYPE
SYNTAX INTEGER {
phaseToNeutral(0),
phaseToPhase(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether measurements are phase to neutral(0) or phase
to phase(1)."
::= { tlpAtsOutputEntry 3 }
tlpAtsOutputVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present output voltage for a given output line."
::= { tlpAtsOutputEntry 4 }
tlpAtsOutputCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output current, in hundredths of amps, for a given phase.
The actual precision of this value, whether a whole number, tenths
or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecision."
::= { tlpAtsOutputEntry 5 }
tlpAtsOutputCurrentMin OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecision. Use
tlpAtsControlResetOutputCurrentMinMax to reset this value."
::= { tlpAtsOutputEntry 6 }
tlpAtsOutputCurrentMax OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum current, in hundredths of amps, observed for a given phase
since last reset. The actual precision of this value, whether a whole number,
tenths or hundredths, is returned by tlpAtsDeviceOutputCurrentPrecision. Use
tlpAtsControlResetOutputCurrentMinMax to reset this value."
::= { tlpAtsOutputEntry 7 }
tlpAtsOutputActivePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output true power for a given phase."
::= { tlpAtsOutputEntry 8 }
tlpAtsOutputPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output power factor ratio for a given phase."
::= { tlpAtsOutputEntry 9 }
tlpAtsOutputSource OBJECT-TYPE
SYNTAX INTEGER {
none(0),
normal(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present source of output power. The enumeration none(0)
indicates that there is no source of output power (and
therefore no output power), for example, the ats has an open
circuit breaker."
::= { tlpAtsOutputEntry 10 }
tlpAtsOutputFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output frequency. If not supported, the agent reports ERROR_NO_SUCH_NAME."
::= { tlpAtsOutputEntry 11 }
tlpAtsOutputPowerKVA OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KVA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of apparent power being used."
::= { tlpAtsOutputEntry 12 }
tlpAtsOutputPowerKW OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KW"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of active power being used."
::= { tlpAtsOutputEntry 13 }
tlpAtsOutput24hrEnergy OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption using present value
of tlpAtsOutputPowerKW."
::= { tlpAtsOutputEntry 14 }
tlpAtsOutputApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of apparent power being used."
::= { tlpAtsOutputEntry 15 }
tlpAtsOutputReactivePower OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The amount of reactive power being used."
::= { tlpAtsOutputEntry 16 }
tlpAtsOutputUtilization OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of the ats power capacity presently being used on
this output line."
::= { tlpAtsOutputEntry 17 }
tlpAtsOutputWattHours OBJECT-TYPE
SYNTAX Unsigned32
UNITS "WH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of watt hours of energy utilized in the past 24 hours. Use
tlpAtsControlResetWattHours to reset the watt hours calculation algorithm."
::= { tlpAtsOutputEntry 18 }
tlpAtsOutputPeakPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum 1 second average power value since the last reset. Use
tlpAtsControlResetPeakPower to reset the peak power calculations."
::= { tlpAtsOutputEntry 19 }
tlpAtsOutletTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The receptacle status details of each ats in device table. This
is a sparse dependent table, and will contain the number of entries
based upon the value of tlpAtsIdentNumOutlets per each device."
::= { tlpAtsOutlet 1 }
tlpAtsOutletEntry OBJECT-TYPE
SYNTAX TlpAtsOutletEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular outlet
managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsOutletIndex }
::= { tlpAtsOutletTable 1 }
TlpAtsOutletEntry ::= SEQUENCE {
tlpAtsOutletIndex Unsigned32,
tlpAtsOutletName DisplayString,
tlpAtsOutletDescription DisplayString,
tlpAtsOutletState INTEGER,
tlpAtsOutletControllable TruthValue,
tlpAtsOutletCommand INTEGER,
tlpAtsOutletVoltage Unsigned32,
tlpAtsOutletCurrent Unsigned32,
tlpAtsOutletActivePower Unsigned32,
tlpAtsOutletRampAction INTEGER,
tlpAtsOutletRampDelay Integer32,
tlpAtsOutletShedAction INTEGER,
tlpAtsOutletShedDelay Integer32,
tlpAtsOutletGroup Integer32,
tlpAtsOutletBank Integer32,
tlpAtsOutletCircuit Integer32,
tlpAtsOutletPhase INTEGER,
tlpAtsOutletReceptacleType INTEGER,
tlpAtsOutletPowerFactor INTEGER,
tlpAtsOutletApparentPower Unsigned32,
tlpAtsOutletReactivePower Integer32,
tlpAtsOutletFrequency Unsigned32,
tlpAtsOutletUtilization Unsigned32,
tlpAtsOutlet24hrEnergy Unsigned32,
tlpAtsOutletOvercurrent TruthValue }
tlpAtsOutletIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ats outlet."
::= { tlpAtsOutletEntry 1 }
tlpAtsOutletName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-definable string identifying the name of the outlet."
::= { tlpAtsOutletEntry 2 }
tlpAtsOutletDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A user-definable string identifying the device(s) connected to
the given outlet."
::= { tlpAtsOutletEntry 3 }
tlpAtsOutletState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the outlet."
::= { tlpAtsOutletEntry 4 }
tlpAtsOutletControllable OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether this outlet is controllable."
::= { tlpAtsOutletEntry 5 }
tlpAtsOutletCommand OBJECT-TYPE
SYNTAX INTEGER {
idle(0),
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value
to turnOff(1) will turn off the outlet. Setting this value
to turnOn(2) will turn on the outlet. Setting this value to
cycle(3) will turn the outlet off, then turn it back on."
::= { tlpAtsOutletEntry 6 }
tlpAtsOutletVoltage OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The magnitude of the present output voltage for a given outlet.
If the voltage measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will always return ERROR_NO_SUCH_NAME.
Device-wide support for receptacle voltage measurements is denoted
by tlpAtsSupportsOutletVoltage."
::= { tlpAtsOutletEntry 7 }
tlpAtsOutletCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present output current, in hundredths of amps, of a given outlet.
If the current measurement is not supported for an individual
receptacle regardless whether device-wide or just for this
receptacle, then this value will always return ERROR_NO_SUCH_NAME.
Device-wide support for receptacle current measurements is denoted
by tlpAtsSupportsOutletCurrent."
::= { tlpAtsOutletEntry 8 }
tlpAtsOutletActivePower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The output power of a given outlet. If the power measurement is
not supported for an individual receptacle regardless whether
device-wide or just for this receptacle, then this value will
always return ERROR_NO_SUCH_NAME. Device-wide support for receptacle
power measurements is denoted by tlpAtsSupportsOutletActivePower."
::= { tlpAtsOutletEntry 9 }
tlpAtsOutletRampAction OBJECT-TYPE
SYNTAX INTEGER {
remainOff(0),
turnOnAfterDelay(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The ramp action to take on a given outlet when powering on the
device. If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpAtsOutletEntry 10 }
tlpAtsOutletRampDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of seconds to delay before powering on the given outlet.
If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpAtsOutletEntry 11 }
tlpAtsOutletShedAction OBJECT-TYPE
SYNTAX INTEGER {
remainOn(0),
turnOffAfterDelay(1)
}
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The shed action to take on a given outlet when powering off the
device. If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpAtsOutletEntry 12 }
tlpAtsOutletShedDelay OBJECT-TYPE
SYNTAX Integer32
UNITS "seconds"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The number of seconds to delay before powering off the given outlet.
If this receptacle is not controllable, as denoted by
tlpAtsOutletControllable, then this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpAtsOutletEntry 13 }
tlpAtsOutletGroup OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The tlpAtsOutletGroupIndex group index of the respective group to
which the given outlet is assigned, or zero (0) if the given
outlet is not grouped."
::= { tlpAtsOutletEntry 14 }
tlpAtsOutletBank OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"This is reported as a bank number, but it is rather an internal
number unrelated to a bank as silk-screened on many devices and is
unrelated to and often confused with tlpAtsOutletCircuit. The value
reported is of no commercial use and was deprecated in agent
version 20."
::= { tlpAtsOutletEntry 15 }
tlpAtsOutletCircuit OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which circuit the given outlet is wired."
::= { tlpAtsOutletEntry 16 }
tlpAtsOutletPhase OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
phase1(1),
phase2(2),
phase3(3),
phase1-2(4),
phase2-3(5),
phase3-1(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which phase or phases the given outlet is
associated. For single phase devices, this object will
always return phase1(1). For 3-phase devices with outlets
wired to a single phase, this object will return phase1(1),
phase2(2) or phase3(3). For 3-phase devices with outlets
wired to two phases, this object will return phase1-2(4)
for phases 1 and 2, phase2-3(5) for phases 2 and 3, and
phase3-1(6) for phases 3 and 1. Devices that do not report
phase connections will return unknown(0)."
::= { tlpAtsOutletEntry 17 }
tlpAtsOutletReceptacleType OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
nema-515R(1),
nema-520R(2),
nema-530R(3),
nema-L515R(4),
nema-L520R(5),
nema-L530R(6),
nema-L615R(7),
nema-L620R(8),
nema-L630R(9),
nema-L1430R(10),
nema-L1520R(11),
nema-L1530R(12),
nema-L2120R(13),
nema-L2130R(14),
nema-L2230R(15),
iec-309-1620(16),
iec-309-3032(17),
iec-309-6063(18),
iec-320-C13(19),
iec-320-C14(20),
iec-320-C15(21),
iec-320-C17(22),
iec-320-C19(23),
iec-320-C20(24) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of receptacle for this outlet. Not all devices report
receptacle types. The value will return unknown(0) when not supported."
::= { tlpAtsOutletEntry 18 }
tlpAtsOutletPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor ratio for this outlet."
::= { tlpAtsOutletEntry 19 }
tlpAtsOutletApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The apparent power of this outlet."
::= { tlpAtsOutletEntry 20 }
tlpAtsOutletReactivePower OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reactive power of this outlet."
::= { tlpAtsOutletEntry 21 }
tlpAtsOutletFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The frequency of this outlet."
::= { tlpAtsOutletEntry 22 }
tlpAtsOutletUtilization OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of utilization of this outlet."
::= { tlpAtsOutletEntry 23 }
tlpAtsOutlet24hrEnergy OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 KWH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Estimated 24 hour power consumption of this outlet."
::= { tlpAtsOutletEntry 24 }
tlpAtsOutletOvercurrent OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Denotes whether this outlet is in an overcurrent condition."
::= { tlpAtsOutletEntry 25 }
tlpAtsOutletGroupTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The receptacle grouping details of each ats in device table.
This is a sparse dependent table, and will contain the number
of entries based upon the value of tlpAtsIdentNumOutletGroups per
each device."
::= { tlpAtsOutlet 2 }
tlpAtsOutletGroupEntry OBJECT-TYPE
SYNTAX TlpAtsOutletGroupEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular outlet
group managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsOutletGroupIndex }
::= { tlpAtsOutletGroupTable 1 }
TlpAtsOutletGroupEntry ::= SEQUENCE {
tlpAtsOutletGroupIndex Unsigned32,
tlpAtsOutletGroupRowStatus RowStatus,
tlpAtsOutletGroupName DisplayString,
tlpAtsOutletGroupDescription DisplayString,
tlpAtsOutletGroupState INTEGER,
tlpAtsOutletGroupCommand INTEGER }
tlpAtsOutletGroupIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ats outlet group."
::= { tlpAtsOutletGroupEntry 1 }
tlpAtsOutletGroupRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Row status for the tlpAtsOutletGroupTable"
::= { tlpAtsOutletGroupEntry 2 }
tlpAtsOutletGroupName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of this outlet group."
::= { tlpAtsOutletGroupEntry 3 }
tlpAtsOutletGroupDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"A description for this outlet group."
::= { tlpAtsOutletGroupEntry 4 }
tlpAtsOutletGroupState OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
off(1),
on(2),
mixed(3) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of the outlet group. This value will report
off(1) if all outlets in the group are off, on(2) if all outlets
in the group are on, mixed(3) if some outlets in the group are
off and others are on, or unknown(0) if the state of the outlets
cannot be determined."
::= { tlpAtsOutletGroupEntry 5 }
tlpAtsOutletGroupCommand OBJECT-TYPE
SYNTAX INTEGER {
turnOff(1),
turnOn(2),
cycle(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Reading this value will always return 0. Setting this value to
turnOff(1) will turn off every outlet associated with the group.
Setting this value to turnOn(2) will turn on every outlet associated
with the group. Setting this value to cycle(3) will turn off every
outlet associated with the group, then turn each outlet back on."
::= { tlpAtsOutletGroupEntry 6 }
tlpAtsCircuitTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of ats circuit table entries. The number of entries
is given by the value of tlpAtsIdentNumCircuits."
::= { tlpAtsCircuit 1 }
tlpAtsCircuitEntry OBJECT-TYPE
SYNTAX TlpAtsCircuitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular circuit
managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsCircuitIndex }
::= { tlpAtsCircuitTable 1 }
TlpAtsCircuitEntry ::= SEQUENCE {
tlpAtsCircuitIndex Unsigned32,
tlpAtsCircuitPhase INTEGER,
tlpAtsCircuitInputVoltage Integer32,
tlpAtsCircuitTotalCurrent Integer32,
tlpAtsCircuitCurrentLimit Integer32,
tlpAtsCircuitCurrentMin Integer32,
tlpAtsCircuitCurrentMax Integer32,
tlpAtsCircuitTotalPower Integer32,
tlpAtsCircuitPowerFactor INTEGER,
tlpAtsCircuitUtilization Unsigned32,
tlpAtsCircuitApparentPower Unsigned32,
tlpAtsCircuitReactivePower Integer32,
tlpAtsCircuitFrequency Unsigned32,
tlpAtsCircuitWattHours Unsigned32,
tlpAtsCircuitPeakPower Unsigned32 }
tlpAtsCircuitIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ats circuit."
::= { tlpAtsCircuitEntry 1 }
tlpAtsCircuitPhase OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
phase1(1),
phase2(2),
phase3(3),
phase1-2(4),
phase2-3(5),
phase3-1(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates on which phase or phases the given circuit is
wired. For single phase devices, this object will always
return phase1(1). For 3-phase devices with outlets wired
to a single phase, this object will return phase1(1),
phase2(2) or phase3(3). For 3-phase devices with outlets
wired to two phases, this object will return phase1-2(4)
for phases 1 and 2, phase2-3(5) for phases 2 and 3, and
phase3-1(6) for phases 3 and 1. Devices that do not report
phase connections will return unknown(0)."
::= { tlpAtsCircuitEntry 2 }
tlpAtsCircuitInputVoltage OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 Volts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The input voltage for a circuit."
::= { tlpAtsCircuitEntry 3 }
tlpAtsCircuitTotalCurrent OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total current for all receptacles in a given circuit."
::= { tlpAtsCircuitEntry 4 }
tlpAtsCircuitCurrentLimit OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current capacity of a circuit in the ats limited by
the circuit breaker or wiring used in a given unit."
::= { tlpAtsCircuitEntry 5 }
tlpAtsCircuitCurrentMin OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The minimum total current for all receptacles in a given
circuit since last reset."
::= { tlpAtsCircuitEntry 6 }
tlpAtsCircuitCurrentMax OBJECT-TYPE
SYNTAX Integer32
UNITS "0.01 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum total current for all receptacles in a given
circuit since last reset."
::= { tlpAtsCircuitEntry 7 }
tlpAtsCircuitTotalPower OBJECT-TYPE
SYNTAX Integer32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total power for all receptacles in a given circuit."
::= { tlpAtsCircuitEntry 8 }
tlpAtsCircuitPowerFactor OBJECT-TYPE
SYNTAX INTEGER
UNITS "0.01"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The power factor ratio for all receptacles in a given circuit."
::= { tlpAtsCircuitEntry 9 }
tlpAtsCircuitUtilization OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.01 percent"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The percentage of utilization of a given circuit. This is typically
a calculation of tlpAtsCircuitTotalCurrent / tlpAtsCircuitCurrentLimit."
::= { tlpAtsCircuitEntry 10 }
tlpAtsCircuitApparentPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "VA"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The apparent power of a given circuit."
::= { tlpAtsCircuitEntry 11 }
tlpAtsCircuitReactivePower OBJECT-TYPE
SYNTAX Integer32
UNITS "VAR"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The reactive power of a given circuit."
::= { tlpAtsCircuitEntry 12 }
tlpAtsCircuitFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The frequency of a given circuit."
::= { tlpAtsCircuitEntry 13 }
tlpAtsCircuitWattHours OBJECT-TYPE
SYNTAX Unsigned32
UNITS "WH"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of watt hours of energy utilized in the past 24 hours. Use
tlpAtsControlResetWattHours to reset the watt hours calculation algorithm."
::= { tlpAtsCircuitEntry 14 }
tlpAtsCircuitPeakPower OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Watts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The maximum 1 second average power value since the last reset. Use
tlpAtsControlResetPeakPower to reset the peak power calculations."
::= { tlpAtsCircuitEntry 15 }
tlpAtsBreakerTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsBreakerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of ats circuit breaker table entries. The number of entries
is given by the value of tlpAtsIdentNumBreakers."
::= { tlpAtsBreaker 1 }
tlpAtsBreakerEntry OBJECT-TYPE
SYNTAX TlpAtsBreakerEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular circuit
breaker managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsBreakerIndex }
::= { tlpAtsBreakerTable 1 }
TlpAtsBreakerEntry ::= SEQUENCE {
tlpAtsBreakerIndex Unsigned32,
tlpAtsBreakerStatus INTEGER }
tlpAtsBreakerIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ats circuit breaker."
::= { tlpAtsBreakerEntry 1 }
tlpAtsBreakerStatus OBJECT-TYPE
SYNTAX INTEGER {
open(0),
closed(1),
notInstalled(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the circuit breaker is open(0), closed(1) or not
installed(2)."
::= { tlpAtsBreakerEntry 2 }
tlpAtsHeatsinkTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsHeatsinkEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of ats heatsink thermistor table entries. The number of entries
is given by the value of tlpAtsIdentNumHeatsinks."
::= { tlpAtsHeatsink 1 }
tlpAtsHeatsinkEntry OBJECT-TYPE
SYNTAX TlpAtsHeatsinkEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular heatsink
thermistor managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsHeatsinkIndex }
::= { tlpAtsHeatsinkTable 1 }
TlpAtsHeatsinkEntry ::= SEQUENCE {
tlpAtsHeatsinkIndex Unsigned32,
tlpAtsHeatsinkStatus INTEGER,
tlpAtsHeatsinkTemperatureC Integer32,
tlpAtsHeatsinkTemperatureF Integer32 }
tlpAtsHeatsinkIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the ats heatsink thermistor."
::= { tlpAtsHeatsinkEntry 1 }
tlpAtsHeatsinkStatus OBJECT-TYPE
SYNTAX INTEGER {
notAvailable(0),
available(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the heatsink thermistor is available. The entry
will return notAvailable(0) if a thermistor is either non-existent or
disconnected, or available(1) when connected."
::= { tlpAtsHeatsinkEntry 2 }
tlpAtsHeatsinkTemperatureC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at the heatsink thermistor in tenths degrees Celsius.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsHeatsinkEntry 3 }
tlpAtsHeatsinkTemperatureF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature at the heatsink thermistor in tenths degrees Fahrenheit.
Heatsink temperature measurements are not supported on all models. If
not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsHeatsinkEntry 4 }
tlpAtsControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable controls for each ats in device table. This is a
sparse dependent table, and will contain some subset of devices
that are atss."
::= { tlpAtsControl 1 }
tlpAtsControlEntry OBJECT-TYPE
SYNTAX TlpAtsControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing controls for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsControlTable 1 }
TlpAtsControlEntry ::= SEQUENCE {
tlpAtsControlRamp TruthValue,
tlpAtsControlShed TruthValue,
tlpAtsControlOn TruthValue,
tlpAtsControlOff TruthValue,
tlpAtsControlRestart TruthValue,
tlpAtsControlResetGeneralFault TruthValue,
tlpAtsControlResetWattHours TruthValue,
tlpAtsControlResetPeakPower TruthValue,
tlpAtsControlClearEventLog TruthValue }
tlpAtsControlRamp OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate the pre-designated ramp
sequence on the ats."
::= { tlpAtsControlEntry 1 }
tlpAtsControlShed OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to initiate the pre-designated shed
sequence on the ats."
::= { tlpAtsControlEntry 2 }
tlpAtsControlOn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the ats on."
::= { tlpAtsControlEntry 3 }
tlpAtsControlOff OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the ats off."
::= { tlpAtsControlEntry 4 }
tlpAtsControlRestart OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to restart the ats."
::= { tlpAtsControlEntry 5 }
tlpAtsControlResetGeneralFault OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the general fault alarm indicated by
tlpAtsDeviceGeneralFault."
::= { tlpAtsControlEntry 6 }
tlpAtsControlResetWattHours OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the tlpAtsDeviceWattHoursTotal, tlpAtsOutputWattHours
and tlpAtsCircuitWattHours calculation algorithms."
::= { tlpAtsControlEntry 7 }
tlpAtsControlResetPeakPower OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset the tlpAtsCircuitPeakPower and tlpAtsOutputPeakPower
calculation algorithms."
::= { tlpAtsControlEntry 8 }
tlpAtsControlClearEventLog OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to clear the event log retained by the ats."
::= { tlpAtsControlEntry 9 }
tlpAtsControlOutputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsControlOutputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable output phase-specific controls for each ats in device
table. This is a sparse dependent table, and will contain some subset of
devices that are atss."
::= { tlpAtsControl 2 }
tlpAtsControlOutputPhaseEntry OBJECT-TYPE
SYNTAX TlpAtsControlOutputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular output
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsOutputIndex }
::= { tlpAtsControlOutputPhaseTable 1 }
TlpAtsControlOutputPhaseEntry ::= SEQUENCE {
tlpAtsControlResetOutputCurrentMinMax TruthValue }
tlpAtsControlResetOutputCurrentMinMax OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset tlpAtsOutputCurrentMin and tlpAtsOutputCurrentMax
to their appropriate minimum and maximum values. This value will return
ERROR_NO_SUCH_NAME if not supported."
::= { tlpAtsControlOutputPhaseEntry 1 }
tlpAtsControlInputPhaseTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsControlInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable input phase-specific controls for each ups in device
table. This is a sparse dependent table, and will contain some subset of
devices that are upss."
::= { tlpAtsControl 3 }
tlpAtsControlInputPhaseEntry OBJECT-TYPE
SYNTAX TlpAtsControlInputPhaseEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular input
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsInputPhaseIndex }
::= { tlpAtsControlInputPhaseTable 1 }
TlpAtsControlInputPhaseEntry ::= SEQUENCE {
tlpAtsControlResetInputVoltageMinMax TruthValue }
tlpAtsControlResetInputVoltageMinMax OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to reset tlpAtsInputPhaseVoltageMin and tlpAtsInputPhaseVoltageMax
to their appropriate minimum and maximum values. Resetting the minimum and maximum
values for one phase on some devices will reset the values for all phases. Resetting
values for a phase will reset that value or values for both input sources. This
value will return ERROR_NO_SUCH_NAME if not supported."
::= { tlpAtsControlInputPhaseEntry 1 }
tlpAtsConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each ats in device table. This
is a sparse dependent table, and will contain some subset of
devices that are atss. Not all options are available on all
atss."
::= { tlpAtsConfig 1 }
tlpAtsConfigEntry OBJECT-TYPE
SYNTAX TlpAtsConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing configuration options for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsConfigTable 1 }
TlpAtsConfigEntry ::= SEQUENCE {
tlpAtsConfigInputVoltage Unsigned32,
tlpAtsConfigSourceSelect INTEGER,
tlpAtsConfigSource1ReturnTime Unsigned32,
tlpAtsConfigSource2ReturnTime Unsigned32,
tlpAtsConfigAutoRampOnTransition INTEGER,
tlpAtsConfigAutoShedOnTransition INTEGER,
tlpAtsConfigIsoBreakerSetting INTEGER,
tlpAtsConfigRelayCalibrationSetting INTEGER,
tlpAtsConfigThdSetting INTEGER,
tlpAtsConfigWaveformCaptureSetting INTEGER,
tlpAtsConfigRemoteResetSetting INTEGER }
tlpAtsConfigInputVoltage OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal value of the input line voltage. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME. This value may not be writable on all models. If
not writable, the value will be rejected and an appropriate error
message will be returned."
::= { tlpAtsConfigEntry 1 }
tlpAtsConfigSourceSelect OBJECT-TYPE
SYNTAX INTEGER {
inputSourceA(1),
inputSourceB(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The determination as to which of two AC input lines is designated
as the primary input source. The other is designated as the
secondary input source. This value will always return inputSourceA(1)
for devices with a single input source. Setting this value is
supported only on selected models."
::= { tlpAtsConfigEntry 2 }
tlpAtsConfigSource1ReturnTime OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal time to delay a transition to Source 1, if it is the
preferred source."
::= { tlpAtsConfigEntry 3 }
tlpAtsConfigSource2ReturnTime OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The nominal time to delay a transition to Source 2, if it is the
preferred source."
::= { tlpAtsConfigEntry 4 }
tlpAtsConfigAutoRampOnTransition OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When enabled(1), the ats should perform its preconfigured ramp sequence when
the input source transfers from its designated secondary source to its
designated primary source. This value not supported on all ats devices. If not
supported, then this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigEntry 5 }
tlpAtsConfigAutoShedOnTransition OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"When enabled(1), the ats should perform its preconfigured shed sequence when
the input source transfers from its designated primary source to its designated
secondary source. This value not supported on all ats devices. If not supported,
then this value will always return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigEntry 6 }
tlpAtsConfigIsoBreakerSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(4) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The IsoBreaker feature uses software to eliminate the cause
of an overcurrent before the circuit break trips. If a specific outlet
has an overcurrent, this outlet is probably the cause, and this outlet
should be turned off. This setting specifies the method by which the
ats turns off outlets to correct overcurrent."
::= { tlpAtsConfigEntry 7 }
tlpAtsConfigRelayCalibrationSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether to automatically self-calibrate the relays on the
device."
::= { tlpAtsConfigEntry 8 }
tlpAtsConfigThdSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether the total harmonic distortion features on the device are
enabled."
::= { tlpAtsConfigEntry 9 }
tlpAtsConfigWaveformCaptureSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether the device will capture waveforms to associate with
logged events."
::= { tlpAtsConfigEntry 10 }
tlpAtsConfigRemoteResetSetting OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Determines whether the LX Card can be remotely reset via a Wake-On-LAN (WOL)
packet."
::= { tlpAtsConfigEntry 11 }
tlpAtsConfigVoltageRangeOldTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsConfigVoltageRangeOldEntry
MAX-ACCESS not-accessible
STATUS obsolete
DESCRIPTION
"The voltage range options in this table is intended to configure the
operating voltages of an ats. This is a sparse dependent table, and will
contain some subset of devices that are atss. All voltage points defined
in this table are listed in a specific order from high to low. All voltage
points must satisfy the conditions and ranges defined for each point. Any
point violating any of the relative limits will be rejected.
For optimal operation, it is recommended that tlpAtsConfigHighVoltageReset
be set lower than tlpAtsConfigHighVoltageTransfer by a margin no less than 1%
of tlpAtsConfigHighVoltageTransfer; and that tlpAtsConfigSource1TransferReset
(tlpAtsConfigSource2TransferReset) be set higher than
tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet) by a margin no
less than 1% of tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet).
*The upper limit of line voltage is tlpAtsInputHighTransferVoltageUpperBound.
The lower limit of line voltage is tlpAtsInputLowTransferVoltageLowerBound. All
minimum and maximum limits for each voltage point are all exclusive unless
indicated otherwise.
This table in its entirety is obsolete and replaced by tlpAtsConfigVoltageRangeTable."
::= { tlpAtsConfig 2 }
tlpAtsConfigVoltageRangeOldEntry OBJECT-TYPE
SYNTAX TlpAtsConfigVoltageRangeOldEntry
MAX-ACCESS not-accessible
STATUS obsolete
DESCRIPTION
"An entry containing voltage range configuration options for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsConfigVoltageRangeOldTable 1 }
TlpAtsConfigVoltageRangeOldEntry ::= SEQUENCE {
tlpAtsConfigHighVoltageTransferOld Unsigned32,
tlpAtsConfigHighVoltageResetOld Unsigned32,
tlpAtsConfigSource1TransferResetOld Unsigned32,
tlpAtsConfigSource1BrownoutSetOld Unsigned32,
tlpAtsConfigSource1TransferSetOld Unsigned32,
tlpAtsConfigSource2TransferResetOld Unsigned32,
tlpAtsConfigSource2BrownoutSetOld Unsigned32,
tlpAtsConfigSource2TransferSetOld Unsigned32,
tlpAtsConfigLowVoltageResetOld Unsigned32,
tlpAtsConfigLowVoltageTransferOld Unsigned32 }
tlpAtsConfigHighVoltageTransferOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"The maximum line voltage allowed before the unit disconnects the
AC input connection. The maximum value allowed is dictated by
tlpAtsInputHighTransferVoltageUpperBound (inclusively). The minimum
value allowed is dictated by tlpAtsConfigHighVoltageResetOld. This value
may not be configurable on all models. If not supported, this value will
return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 1 }
tlpAtsConfigHighVoltageResetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"If a unit is disconnected due to over-voltage, the line voltage has to
fall below this value before the unit re-connects the AC input connection.
The maximum value allowed is dictated by tlpAtsConfigHighVoltageTransferOld.
The minimum value allowed is dictated by the greater of
tlpAtsConfigSource1TransferResetOld and tlpAtsConfigSource2TransferResetOld. If
not supported, this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 2 }
tlpAtsConfigSource1TransferResetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"If input source 1 voltage level is above this value, a unit connected to
source 2 will transition to source 1 (if it is the preferred source). The
maximum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. The
minimum value allowed is dictated by tlpAtsConfigSource1BrownoutSetOld. If not
supported, this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 3 }
tlpAtsConfigSource1BrownoutSetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"This value dictates the voltage level below which source 1 goes into a
brown out condition. The maximum value allowed is dictated by
tlpAtsConfigSource1TransferResetOld. The minimum value allowed is dictated by
tlpAtsConfigSource1TransferSetOld. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 4 }
tlpAtsConfigSource1TransferSetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"If input source 1 voltage level falls below this value, a unit connected to
source 1 will transition to source 2 (if it is in fair condition as denoted
by tlpAtsConfigSource2TransferSetOld). The maximum value allowed is dictated by
tlpAtsConfigSource1BrownoutSetOld. The minimum value allowed is dictated by
tlpAtsConfigLowVoltageResetOld. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 5 }
tlpAtsConfigSource2TransferResetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"If input source 2 voltage level is above this value, a unit connected to
source 1 will transition to source 2 (if it is the preferred source). The
maximum value allowed is dictated by tlpAtsConfigHighVoltageResetOld. The
minimum value allowed is dictated by tlpAtsConfigSource2BrownoutSetOld. If not
supported, this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 6 }
tlpAtsConfigSource2BrownoutSetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"This value dictates the voltage level below which source 2 goes into a
brown out condition. The maximum value allowed is dictated by
tlpAtsConfigSource2TransferResetOld. The minimum value allowed is dictated by
tlpAtsConfigSource2TransferSetOld. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 7 }
tlpAtsConfigSource2TransferSetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"If input source 2 voltage level falls below this value, a unit connected to
source 2 will transition to source 1 (if it is in fair condition as denoted
by tlpAtsConfigSource1TransferSetOld). The maximum value allowed is dictated by
tlpAtsConfigSource2BrownoutSetOld. The minimum value allowed is dictated by
tlpAtsConfigLowVoltageResetOld. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 8 }
tlpAtsConfigLowVoltageResetOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"If a unit is disconnected due to under-voltage or is not powered up yet, the
line voltage has to rise above this value before the unit gets connected to
the AC input connection. The maximum value allowed is dictated by the lesser
value of tlpAtsConfigSource1TransferSetOld and tlpAtsConfigSource2TransferSetOld.
The minimum value allowed is dictated by tlpAtsConfigLowVoltageTransferOld. If
not supported, this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 9 }
tlpAtsConfigLowVoltageTransferOld OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"The minimum line voltage allowed before the unit disconnects the
AC input connection. The maximum value allowed is dictated by
tlpAtsConfigLowVoltageResetOld. The minimum value allowed is dictated by
tlpAtsInputLowTransferVoltageLowerBound (inclusively). If not supported, this
value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeOldEntry 10 }
tlpAtsConfigVoltageRangeLimitsTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsConfigVoltageRangeLimitsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The voltage range table, as documented by tlpAtsConfigVoltageRangeTable requires
that all changes adhere with stack order, from high transfer voltage down to low
transfer voltage. In addition to stack order, certain voltage range values have
limits defining the absolute minimum and absolute maximum for such values. Any
voltage value violating any respective limit defined herein will be rejected."
::= { tlpAtsConfig 3 }
tlpAtsConfigVoltageRangeLimitsEntry OBJECT-TYPE
SYNTAX TlpAtsConfigVoltageRangeLimitsEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing voltage range limits configuration options for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsConfigVoltageRangeLimitsTable 1 }
TlpAtsConfigVoltageRangeLimitsEntry ::= SEQUENCE {
tlpAtsConfigSourceBrownoutSetMinimum Unsigned32,
tlpAtsConfigSourceBrownoutSetMaximum Unsigned32,
tlpAtsConfigSourceTransferSetMinimum Unsigned32,
tlpAtsConfigSourceTransferSetMaximum Unsigned32 }
tlpAtsConfigSourceBrownoutSetMinimum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value dictates the absolute lower limit by which tlpAtsConfigSource1BrownoutSet
and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1TransferSet and
tlpAtsConfigSource2TransferSet, respectively, are also used when determining the
lowest value a brownout value can be set at any given time. If not supported, this
value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeLimitsEntry 1 }
tlpAtsConfigSourceBrownoutSetMaximum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value dictates the absolute upper limit by which tlpAtsConfigSource1BrownoutSet
and tlpAtsConfigSource2BrownoutSet can be set. tlpAtsConfigSource1TransferReset and
tlpAtsConfigSource2TransferReset, respectively, are also used when determining the
greatest value a brownout value can be set at any given time. If not supported, this
value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeLimitsEntry 2 }
tlpAtsConfigSourceTransferSetMinimum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value dictates the absolute lower limit by which tlpAtsConfigSource1TransferSet
and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigLowVoltageReset is also
used when determining the lowest value a transferset value can be set at any given
time. If not supported, this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeLimitsEntry 3 }
tlpAtsConfigSourceTransferSetMaximum OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value dictates the absolute upper limit by which tlpAtsConfigSource1TransferSet
and tlpAtsConfigSource2TransferSet can be set. tlpAtsConfigSource1BrownoutSet and
tlpAtsConfigSource2BrownoutSet, respectively, are also used when determining the
greatest value a transferset value can be set at any given time. If not supported,
this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeLimitsEntry 4 }
tlpAtsConfigThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsConfigThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configurable threshold options of each ats in device table. This
is a sparse dependent table, and will contain some subset of devices that
are atss. Not all options are available on all atss."
::= { tlpAtsConfig 4 }
tlpAtsConfigThresholdEntry OBJECT-TYPE
SYNTAX TlpAtsConfigThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing configurable threshold options for a particular ats."
INDEX { tlpDeviceIndex }
::= { tlpAtsConfigThresholdTable 1 }
TlpAtsConfigThresholdEntry ::= SEQUENCE {
tlpAtsConfigOutputCurrentThreshold Unsigned32,
tlpAtsConfigOverTemperatureThreshold Unsigned32,
tlpAtsConfigOverVoltageThreshold Unsigned32,
tlpAtsConfigOverLoadThreshold Unsigned32,
tlpAtsConfigThdOutOfRangeThreshold Unsigned32 }
tlpAtsConfigOutputCurrentThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The output current measurement at which an over current condition is reported.
This value may not be supported on all models. If not supported, this value
will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigThresholdEntry 1 }
tlpAtsConfigOverTemperatureThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The device temperature at which an over temperature condition is reported.
This value may not be supported on all models. If not supported, this value
will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigThresholdEntry 2 }
tlpAtsConfigOverVoltageThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The input voltage measurement at which an over voltage condition is reported.
This value may not be supported on all models. If not supported, this value
will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigThresholdEntry 3 }
tlpAtsConfigOverLoadThreshold OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The device load at which an overload condition is reported. This value may not
be supported on all models. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigThresholdEntry 4 }
tlpAtsConfigThdOutOfRangeThreshold OBJECT-TYPE
SYNTAX Unsigned32 (1..9999)
UNITS "0.01 percent"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Denotes the percentage of THD voltage in hundredths of a percent at which
the THD voltage out of range condition occurs. The out of range condition,
tlpAtsAlarmThdOutOfRange, is triggered when the THD voltage exceeds this
value."
::= { tlpAtsConfigThresholdEntry 5 }
tlpAtsConfigVoltageRangeTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsConfigVoltageRangeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The voltage range options in this table is intended to configure the
operating voltages of an ats. This is a sparse dependent table, and will
contain some subset of devices that are atss. All voltage points defined
in this table are listed in a specific order from high to low. All voltage
points must satisfy the conditions and ranges defined for each point. Any
point violating any of the relative limits will be rejected.
For optimal operation, it is recommended that tlpAtsConfigHighVoltageReset
be set lower than tlpAtsConfigHighVoltageTransfer by a margin no less than 1%
of tlpAtsConfigHighVoltageTransfer; and that tlpAtsConfigSource1TransferReset
(tlpAtsConfigSource2TransferReset) be set higher than
tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet) by a margin no
less than 1% of tlpAtsConfigSource1BrownoutSet (tlpAtsConfigSource2BrownoutSet).
*The upper limit of line voltage is tlpAtsInputHighTransferVoltageUpperBound.
The lower limit of line voltage is tlpAtsInputLowTransferVoltageLowerBound. All
minimum and maximum limits for each voltage point are all exclusive unless
indicated otherwise."
::= { tlpAtsConfig 5 }
tlpAtsConfigVoltageRangeEntry OBJECT-TYPE
SYNTAX TlpAtsConfigVoltageRangeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing voltage range configuration options for a particular ats."
INDEX { tlpDeviceIndex, tlpAtsInputLineIndex }
::= { tlpAtsConfigVoltageRangeTable 1 }
TlpAtsConfigVoltageRangeEntry ::= SEQUENCE {
tlpAtsConfigHighVoltageTransfer Unsigned32,
tlpAtsConfigHighVoltageReset Unsigned32,
tlpAtsConfigTransferReset Unsigned32,
tlpAtsConfigBrownoutSet Unsigned32,
tlpAtsConfigTransferSet Unsigned32,
tlpAtsConfigLowVoltageReset Unsigned32,
tlpAtsConfigLowVoltageTransfer Unsigned32 }
tlpAtsConfigHighVoltageTransfer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The maximum line voltage allowed on the input source before the unit
disconnects the AC input connection. tlpAtsConfigHighVoltageTransfer is the
same value for both input sources on some units. On such units, changing
this value on one source will change the value on the other source. The
maximum value allowed is dictated by tlpAtsInputHighTransferVoltageUpperBound
(inclusively). The minimum value allowed is dictated by tlpAtsConfigHighVoltageReset.
This value may not be configurable on all models. If not supported, this value will
return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeEntry 1 }
tlpAtsConfigHighVoltageReset OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If an input connection is disconnected due to over-voltage, the line voltage
on the input source has to fall below this value before the unit re-connects
the AC input connection for the input source. tlpAtsConfigHighVoltageReset is the
same value for both input sources on some units. On such units, changing this
value on one source will change the value on the other source. The maximum value
allowed is dictated by tlpAtsConfigHighVoltageTransfer. On units where this is
the same value for both sources, the minimum value allowed is dictated by the
greater of tlpAtsConfigTransferReset.1 and tlpAtsConfigTransferReset.2. On units
where the value is distinct for each source, the minimum value allowed is
dictated solely by this source's tlpAtsConfigTransferReset. If not supported,
this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeEntry 2 }
tlpAtsConfigTransferReset OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If input source voltage level is above this value, a unit connected to
this other input source will transition to this input source (if it is the
preferred source). The maximum value allowed is dictated by
tlpAtsConfigHighVoltageReset. The minimum value allowed is dictated by
tlpAtsConfigBrownoutSet. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeEntry 3 }
tlpAtsConfigBrownoutSet OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This value dictates the voltage level below which the input source goes
into a brown out condition. The maximum value allowed is dictated by
tlpAtsConfigTransferReset. The minimum value allowed is dictated by
tlpAtsConfigTransferSet. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeEntry 4 }
tlpAtsConfigTransferSet OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If input source voltage level falls below this value, a unit connected to
this input source will transition to other input source (if it is in fair
condition as denoted by tlpAtsConfigTransferSet). The maximum value allowed
is dictated by tlpAtsConfigBrownoutSet. The minimum value allowed is dictated
by tlpAtsConfigLowVoltageReset. If not supported, this value will return
ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeEntry 5 }
tlpAtsConfigLowVoltageReset OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"If a unit is disconnected due to under-voltage or is not powered up yet, the
line voltage has to rise above this value before the unit gets connected to
the AC input connection. tlpAtsConfigLowVoltageReset is the same value for both
input sources. As such, changing this value on one source will change the value
on the other source. The maximum value allowed is dictated by the lesser value
of tlpAtsConfigTransferSet.1 and tlpAtsConfigTransferSet.2. The minimum value
allowed is dictated by tlpAtsConfigLowVoltageTransfer. If not supported, this
value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeEntry 6 }
tlpAtsConfigLowVoltageTransfer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The minimum line voltage allowed before the unit disconnects the AC input
connection. tlpAtsConfigLowVoltageTransfer is the same value for both input
sources. As such, changing this value on one source will change the value on the
other source. The maximum value allowed is dictated by tlpAtsConfigLowVoltageReset.
The minimum value allowed is dictated by tlpAtsInputLowTransferVoltageLowerBound
(inclusively). If not supported, this value will return ERROR_NO_SUCH_NAME."
::= { tlpAtsConfigVoltageRangeEntry 7 }
tlpAtsConfigOutputPhaseThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsConfigOutputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration options of each ats in device table. This
is a sparse dependent table, and will contain some subset of
devices that are atss. Not all options are available on all
atss."
::= { tlpAtsConfig 6 }
tlpAtsConfigOutputPhaseThresholdEntry OBJECT-TYPE
SYNTAX TlpAtsConfigOutputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing threshold configuration options for a particular ats."
INDEX { tlpDeviceIndex, tlpAtsOutputIndex }
::= { tlpAtsConfigOutputPhaseThresholdTable 1 }
TlpAtsConfigOutputPhaseThresholdEntry ::= SEQUENCE {
tlpAtsConfigOutputCurrentThresholdTolerance Unsigned32,
tlpAtsConfigOutputCurrentHighThreshold Unsigned32,
tlpAtsConfigOutputCurrentLowThreshold Unsigned32,
tlpAtsConfigOutputVoltageThresholdTolerance Unsigned32,
tlpAtsConfigOutputVoltageHighCriticalThreshold Unsigned32,
tlpAtsConfigOutputVoltageHighWarningThreshold Unsigned32,
tlpAtsConfigOutputVoltageLowWarningThreshold Unsigned32,
tlpAtsConfigOutputVoltageLowCriticalThreshold Unsigned32 }
tlpAtsConfigOutputCurrentThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output current high/low
threshold to evaluate output current high/low condition."
::= { tlpAtsConfigOutputPhaseThresholdEntry 1 }
tlpAtsConfigOutputCurrentHighThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which an output current high condition is declared."
::= { tlpAtsConfigOutputPhaseThresholdEntry 2 }
tlpAtsConfigOutputCurrentLowThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which an output current low condition is declared."
::= { tlpAtsConfigOutputPhaseThresholdEntry 3 }
tlpAtsConfigOutputVoltageThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output voltage high/low
threshold to evaluate output voltage high/low condition."
::= { tlpAtsConfigOutputPhaseThresholdEntry 4 }
tlpAtsConfigOutputVoltageHighCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage high critical condition is declared."
::= { tlpAtsConfigOutputPhaseThresholdEntry 5 }
tlpAtsConfigOutputVoltageHighWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage high warning condition is declared."
::= { tlpAtsConfigOutputPhaseThresholdEntry 6 }
tlpAtsConfigOutputVoltageLowWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage low warning condition is declared."
::= { tlpAtsConfigOutputPhaseThresholdEntry 7 }
tlpAtsConfigOutputVoltageLowCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the output voltage low critical condition is declared."
::= { tlpAtsConfigOutputPhaseThresholdEntry 8 }
tlpAtsConfigInputPhaseThresholdTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAtsConfigInputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input phase configuration details for each ats in device table.
This is a sparse dependent table, and will contain the number of
entries based on the number of atss managed by the agent as reported
by tlpAtsIdentNumAts and tlpAtsIdentNumPhases. Not all options are
available on all atss."
::= { tlpAtsConfig 7 }
tlpAtsConfigInputPhaseThresholdEntry OBJECT-TYPE
SYNTAX TlpAtsConfigInputPhaseThresholdEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information applicable to a particular input
phase managed by this agent."
INDEX { tlpDeviceIndex, tlpAtsInputLineIndex, tlpAtsInputPhaseIndex }
::= { tlpAtsConfigInputPhaseThresholdTable 1 }
TlpAtsConfigInputPhaseThresholdEntry ::= SEQUENCE {
tlpAtsConfigInputVoltageThresholdTolerance Unsigned32,
tlpAtsConfigInputVoltageHighCriticalThreshold Unsigned32,
tlpAtsConfigInputVoltageHighWarningThreshold Unsigned32,
tlpAtsConfigInputVoltageLowWarningThreshold Unsigned32,
tlpAtsConfigInputVoltageLowCriticalThreshold Unsigned32 }
tlpAtsConfigInputVoltageThresholdTolerance OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The threshold tolerance value used together with output voltage high/low
threshold to evaluate output voltage high/low condition."
::= { tlpAtsConfigInputPhaseThresholdEntry 1 }
tlpAtsConfigInputVoltageHighCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage high critical condition is declared."
::= { tlpAtsConfigInputPhaseThresholdEntry 2 }
tlpAtsConfigInputVoltageHighWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage high warning condition is declared."
::= { tlpAtsConfigInputPhaseThresholdEntry 3 }
tlpAtsConfigInputVoltageLowWarningThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage low warning condition is declared."
::= { tlpAtsConfigInputPhaseThresholdEntry 4 }
tlpAtsConfigInputVoltageLowCriticalThreshold OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Volts"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The value at which the input voltage low critical condition is declared."
::= { tlpAtsConfigInputPhaseThresholdEntry 5 }
-- cooling
tlpCoolingIdentNumCooling OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of cooling devices that this agent is currently managing."
::= { tlpCoolingIdent 1 }
tlpCoolingCurrentTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingCurrentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The input current for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingDetail 3 }
tlpCoolingCurrentEntry OBJECT-TYPE
SYNTAX TlpCoolingCurrentEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing input current for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingCurrentTable 1 }
TlpCoolingCurrentEntry ::= SEQUENCE {
tlpCoolingUnitCurrent Unsigned32,
tlpCoolingCompressorCurrent Unsigned32,
tlpCoolingEvaporatorFanCurrent Unsigned32,
tlpCoolingCondenserFanCurrent Unsigned32 }
tlpCoolingUnitCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The total current draw of the unit in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingCurrentEntry 1 }
tlpCoolingCompressorCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The compressor current draw of the unit in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingCurrentEntry 2 }
tlpCoolingEvaporatorFanCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current draw of the evaporator fan in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingCurrentEntry 3 }
tlpCoolingCondenserFanCurrent OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Amps"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current draw of the condenser fan in tenths of Amps. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingCurrentEntry 4 }
tlpCoolingTemperatureFahrenheitTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingTemperatureFahrenheitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The temperature details for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingTemperature 1 }
tlpCoolingTemperatureFahrenheitEntry OBJECT-TYPE
SYNTAX TlpCoolingTemperatureFahrenheitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing temperature details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingTemperatureFahrenheitTable 1 }
TlpCoolingTemperatureFahrenheitEntry ::= SEQUENCE {
tlpCoolingAmbientDegF Integer32,
tlpCoolingSupplyAirDegF Integer32,
tlpCoolingReturnAirDegF Integer32,
tlpCoolingCondenserInletDegF Integer32,
tlpCoolingEvaporatorDegF Integer32,
tlpCoolingSuctionDegF Integer32,
tlpCoolingRemoteDegF Integer32,
tlpCoolingCondenserOutletDegF Integer32}
tlpCoolingAmbientDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The ambient temperature in tenths degrees Fahrenheit. If not supported,
this value will always return ERROR_NO_SUCH_NAME. Support was deprecated
in agent versions 20 and later and superseded by tlpCoolingReturnAirDegF."
::= { tlpCoolingTemperatureFahrenheitEntry 1 }
tlpCoolingSupplyAirDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air supplied to the room in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureFahrenheitEntry 2 }
tlpCoolingReturnAirDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air entering the cooling unit in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureFahrenheitEntry 3 }
tlpCoolingCondenserInletDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air entering the condenser in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureFahrenheitEntry 4 }
tlpCoolingEvaporatorDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the evaporator surface in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureFahrenheitEntry 5 }
tlpCoolingSuctionDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the low pressure refrigerant line in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureFahrenheitEntry 6 }
tlpCoolingRemoteDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The external remote temperature in tenths degrees Fahrenheit. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureFahrenheitEntry 7 }
tlpCoolingCondenserOutletDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air leaving the condenser in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureFahrenheitEntry 8 }
tlpCoolingTemperatureCelsiusTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingTemperatureCelsiusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The temperature details for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingTemperature 2 }
tlpCoolingTemperatureCelsiusEntry OBJECT-TYPE
SYNTAX TlpCoolingTemperatureCelsiusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing temperature details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingTemperatureCelsiusTable 1 }
TlpCoolingTemperatureCelsiusEntry ::= SEQUENCE {
tlpCoolingAmbientDegC Integer32,
tlpCoolingSupplyAirDegC Integer32,
tlpCoolingReturnAirDegC Integer32,
tlpCoolingCondenserInletDegC Integer32,
tlpCoolingEvaporatorDegC Integer32,
tlpCoolingSuctionDegC Integer32,
tlpCoolingRemoteDegC Integer32,
tlpCoolingCondenserOutletDegC Integer32 }
tlpCoolingAmbientDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The ambient temperature in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME. Support was deprecated
in agent versions 20 and later and superseded by tlpCoolingReturnAirDegC."
::= { tlpCoolingTemperatureCelsiusEntry 1 }
tlpCoolingSupplyAirDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air supplied to the room in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureCelsiusEntry 2 }
tlpCoolingReturnAirDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air entering the cooling unit in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureCelsiusEntry 3 }
tlpCoolingCondenserInletDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air entering the condenser in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureCelsiusEntry 4 }
tlpCoolingEvaporatorDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the evaporator surface in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureCelsiusEntry 5 }
tlpCoolingSuctionDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the low pressure refrigerant line in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureCelsiusEntry 6 }
tlpCoolingRemoteDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The external remote temperature in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureCelsiusEntry 7 }
tlpCoolingCondenserOutletDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The temperature of the air leaving the condenser in tenths degrees Celsius. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingTemperatureCelsiusEntry 8 }
tlpCoolingPressureMpaTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingPressureMpaEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The pressure detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingPressure 1 }
tlpCoolingPressureMpaEntry OBJECT-TYPE
SYNTAX TlpCoolingPressureMpaEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing pressure details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingPressureMpaTable 1 }
TlpCoolingPressureMpaEntry ::= SEQUENCE {
tlpCoolingSuctionPressureMpa Unsigned32,
tlpCoolingDischargePressureMpa Unsigned32 }
tlpCoolingSuctionPressureMpa OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Mpa"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pressure of the compressor discharge line in tenths of Mpa. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingPressureMpaEntry 1 }
tlpCoolingDischargePressureMpa OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Mpa"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pressure of the compressor discharge line in tenths of Mpa. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingPressureMpaEntry 2 }
tlpCoolingPressurePsiTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingPressurePsiEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The pressure detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingPressure 2 }
tlpCoolingPressurePsiEntry OBJECT-TYPE
SYNTAX TlpCoolingPressurePsiEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing pressure details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingPressurePsiTable 1 }
TlpCoolingPressurePsiEntry ::= SEQUENCE {
tlpCoolingSuctionPressurePsi Unsigned32,
tlpCoolingDischargePressurePsi Unsigned32 }
tlpCoolingSuctionPressurePsi OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Psi"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pressure of the compressor discharge line in tenths of Psi. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingPressurePsiEntry 1 }
tlpCoolingDischargePressurePsi OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 Psi"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The pressure of the compressor discharge line in tenths of Psi. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingPressurePsiEntry 2 }
tlpCoolingDynamicTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingDynamicEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The dynamic detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingDetail 4 }
tlpCoolingDynamicEntry OBJECT-TYPE
SYNTAX TlpCoolingDynamicEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry dynamic details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingDynamicTable 1 }
TlpCoolingDynamicEntry ::= SEQUENCE {
tlpCoolingEvaporatorFanSpeed INTEGER,
tlpCoolingCondenserFanSpeed INTEGER,
tlpCoolingCompressorFrequency Unsigned32,
tlpCoolingEEVSteps INTEGER }
tlpCoolingEvaporatorFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
off(0),
low(1),
mediumLow(2),
medium(3),
mediumHigh(4),
high(5),
auto(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current speed of the evaporator fan. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingDynamicEntry 1 }
tlpCoolingCondenserFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
off(0),
low(1),
mediumLow(2),
medium(3),
mediumHigh(4),
high(5),
auto(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current speed of the condenser fan. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingDynamicEntry 2 }
tlpCoolingCompressorFrequency OBJECT-TYPE
SYNTAX Unsigned32
UNITS "Hertz"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The operating mechanical frequency(Hz) of the compressor. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingDynamicEntry 3 }
tlpCoolingEEVSteps OBJECT-TYPE
SYNTAX INTEGER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current EEV steps. If not supported, this value will always
return ERROR_NO_SUCH_NAME."
::= { tlpCoolingDynamicEntry 4 }
tlpCoolingRuntimeTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingRuntimeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The runtime detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingDetail 5 }
tlpCoolingRuntimeEntry OBJECT-TYPE
SYNTAX TlpCoolingRuntimeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing runtime for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingRuntimeTable 1 }
TlpCoolingRuntimeEntry ::= SEQUENCE {
tlpCoolingCompressorRunDays Unsigned32,
tlpCoolingCondensatePumpRunDays Unsigned32,
tlpCoolingAirFilterRunHours Unsigned32,
tlpCoolingEvaporatorFanRunDays Unsigned32,
tlpCoolingCondenserFanRunDays Unsigned32,
tlpCoolingAtomizerRunDays Unsigned32 }
tlpCoolingCompressorRunDays OBJECT-TYPE
SYNTAX Unsigned32
UNITS "days"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the compressor has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingRuntimeEntry 1 }
tlpCoolingCondensatePumpRunDays OBJECT-TYPE
SYNTAX Unsigned32
UNITS "days"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the condensate pump has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingRuntimeEntry 2}
tlpCoolingAirFilterRunHours OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total hours the air filter has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingRuntimeEntry 3 }
tlpCoolingEvaporatorFanRunDays OBJECT-TYPE
SYNTAX Unsigned32
UNITS "days"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the evaporator fan has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingRuntimeEntry 4 }
tlpCoolingCondenserFanRunDays OBJECT-TYPE
SYNTAX Unsigned32
UNITS "days"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the condenser fan has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingRuntimeEntry 5 }
tlpCoolingAtomizerRunDays OBJECT-TYPE
SYNTAX Unsigned32
UNITS "days"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Total days the atomizer has been under operation. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingRuntimeEntry 6 }
tlpCoolingStatusTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The status detail for each cooling device in device table. This is a
sparse dependent table, and will contain the number of entries based upon the
number of cooling device managed by the agent as reported by tlpCoolingIdentNumCooling."
::= { tlpCoolingDetail 6 }
tlpCoolingStatusEntry OBJECT-TYPE
SYNTAX TlpCoolingStatusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing status for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingStatusTable 1 }
TlpCoolingStatusEntry ::= SEQUENCE {
tlpCoolingOperatingMode INTEGER,
tlpCoolingCoolOutput Unsigned32,
tlpCoolingAlarmStatus INTEGER,
tlpCoolingCompressorStatus INTEGER,
tlpCoolingWaterStatus INTEGER,
tlpCoolingDefrostMode INTEGER,
tlpCoolingQuietMode INTEGER,
tlpCoolingHotGasBypass INTEGER,
tlpCoolingAutoFanSpeed INTEGER }
tlpCoolingOperatingMode OBJECT-TYPE
SYNTAX INTEGER {
off(0),
idle(1),
cooling(2),
shuttingDown(3),
dehumidifying(4),
defrosting(5),
notConnected(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current operating mode. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 1 }
tlpCoolingCoolOutput OBJECT-TYPE
SYNTAX Unsigned32
UNITS "0.1 kilowatts"
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current cooling output of the cooling device in tenth of kilowatt. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 2 }
tlpCoolingAlarmStatus OBJECT-TYPE
SYNTAX INTEGER {
noAlarm(0),
warning(1),
critical(2)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current alarm status of the cooling device. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 3 }
tlpCoolingCompressorStatus OBJECT-TYPE
SYNTAX INTEGER {
off(0),
on(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current operating status of compressor. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 4 }
tlpCoolingWaterStatus OBJECT-TYPE
SYNTAX INTEGER {
notFull(0),
full(1)}
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current water status of cooling unit. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 5 }
tlpCoolingDefrostMode OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the defrost mode is presently enabled or disabled.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 6 }
tlpCoolingQuietMode OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the quiet mode is presently enabled or disabled.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 7 }
tlpCoolingHotGasBypass OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the hot gas bypass mode is presently enabled or disabled.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 8 }
tlpCoolingAutoFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the auto fan speed is presently enabled or disabled.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingStatusEntry 9 }
tlpCoolingControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The actionable controls for each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device."
::= { tlpCoolingControl 1 }
tlpCoolingControlEntry OBJECT-TYPE
SYNTAX TlpCoolingControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing controls for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingControlTable 1 }
TlpCoolingControlEntry ::= SEQUENCE {
tlpCoolingMode INTEGER,
tlpCoolingControlOn TruthValue,
tlpCoolingControlOff TruthValue }
tlpCoolingMode OBJECT-TYPE
SYNTAX INTEGER {
turnOffUnit(0),
turnOnUnit(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Turn the unit on or off."
::= { tlpCoolingControlEntry 1 }
tlpCoolingControlOn OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the cooling device on."
::= { tlpCoolingControlEntry 2 }
tlpCoolingControlOff OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to turn the cooling device off."
::= { tlpCoolingControlEntry 3 }
tlpCoolingConfigTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration details for each each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device. Not all options are available on all
cooling devices."
::= { tlpCoolingConfig 1 }
tlpCoolingConfigEntry OBJECT-TYPE
SYNTAX TlpCoolingConfigEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry configuration details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingConfigTable 1 }
TlpCoolingConfigEntry ::= SEQUENCE {
tlpCoolingConfigAutoStart INTEGER,
tlpCoolingConfigFanSpeed INTEGER,
tlpCoolingConfigControlType INTEGER,
tlpCoolingConfigDisplayUnits INTEGER,
tlpCoolingConfigBeepOnKey INTEGER,
tlpCoolingConfigInputContactType INTEGER,
tlpCoolingConfigOutputContactType INTEGER,
tlpCoolingConfigOutputRelaySource INTEGER,
tlpCoolingConfigOutputRelayDefault INTEGER,
tlpCoolingConfigOffOnInputContact INTEGER,
tlpCoolingConfigOffOnLeak INTEGER,
tlpCoolingConfigWaterLeakContactType INTEGER,
tlpCoolingConfigAirFilterInterval Unsigned32,
tlpCoolingConfigAirFilterAlarm INTEGER,
tlpCoolingConfigMaxAirFilterRunHours Unsigned32,
tlpCoolingConfigStartTimer Unsigned32,
tlpCoolingConfigStopTimer Unsigned32,
tlpCoolingConfigEnergyMode INTEGER,
tlpCoolingConfigDefrostMode INTEGER,
tlpCoolingConfigRemoteTemperatureSensor INTEGER,
tlpCoolingConfigDehumidifyingMode INTEGER,
tlpCoolingConfigFanAlwaysOn INTEGER,
tlpCoolingConfigQuietMode INTEGER,
tlpCoolingConfigHotGasBypass INTEGER,
tlpCoolingConfigAutoFanSpeed INTEGER }
tlpCoolingConfigAutoStart OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Specifies if the unit should start automatically on power up. This value is
deprecated as of agent version 20. If not supported, this value will always
return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 1 }
tlpCoolingConfigFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
off(0),
low(1),
mediumLow(2),
medium(3),
mediumHigh(4),
high(5),
auto(6) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Specifies the actual speed of the evaporator fan. Setting the fan speed
to auto(6) will enable tlpCoolingAutoFanSpeed; however, on most units getting
the fan speed will return the actual fan speed regardless whether auto fan
speed is enabled or disabled. The value auto(6) is returned only on units that
do not report the actual fan speed when auto fan speed is enabled. Not all
values are supported on all cooling units. Invalid values will return an appropriate
error when accessed. If not supported, this value will always return ERROR_NO_SUCH_NAME"
::= { tlpCoolingConfigEntry 2 }
tlpCoolingConfigControlType OBJECT-TYPE
SYNTAX INTEGER {
returnAirTemperature(0),
remoteTemperature(1) }
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Specifies which temperature is used as a control point. This value is obsolete as of
agent version 15. It is superseded by tlpCoolingConfigRemoteTemperatureSensor. This value
will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 3 }
tlpCoolingConfigDisplayUnits OBJECT-TYPE
SYNTAX INTEGER {
metric(0),
english(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Specifies whether displays output values in Metric or English formats. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 4 }
tlpCoolingConfigBeepOnKey OBJECT-TYPE
SYNTAX INTEGER {
noBeep(0),
beepOn(1) }
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"Specifies whether a beep is emitted when a key is pressed on the unit's display panel.
This value is obsolete as of agent version 15 and will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 5 }
tlpCoolingConfigInputContactType OBJECT-TYPE
SYNTAX INTEGER {
normallyClosed(0),
normallyOpen(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The input contact type. This value is deprecated as of agent version 20. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 6 }
tlpCoolingConfigOutputContactType OBJECT-TYPE
SYNTAX INTEGER {
normallyClosed(0),
normallyOpen(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The output contact type. This value is deprecated as of agent version 20. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 7 }
tlpCoolingConfigOutputRelaySource OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
allAlarmsAndWarnings(1),
criticalAlarmsOnly(2) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The alarm level that causes the output relay to activate. This value is deprecated
as of agent version 20. If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 8 }
tlpCoolingConfigOutputRelayDefault OBJECT-TYPE
SYNTAX INTEGER {
normallyClosed(0),
normallyOpen(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Type of contact to make when output relay is activated. This value is deprecated
as of agent version 20. If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 9 }
tlpCoolingConfigOffOnInputContact OBJECT-TYPE
SYNTAX INTEGER {
turnOff(0),
alarmOnly(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates if the unit should stop cooling when input contact is activated. This value
is deprecated as of agent version 20. If not supported, this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 10 }
tlpCoolingConfigOffOnLeak OBJECT-TYPE
SYNTAX INTEGER {
turnOff(0),
alarmOnly(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"Indicates if the unit should stop cooling when leak input is activated. This value
is deprecated as of agent version 20. If not supported, this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 11 }
tlpCoolingConfigWaterLeakContactType OBJECT-TYPE
SYNTAX INTEGER {
normallyClosed(0),
normallyOpen(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The water leak contact type. This value is deprecated as of agent version 20. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 12 }
tlpCoolingConfigAirFilterInterval OBJECT-TYPE
SYNTAX Unsigned32
UNITS "weeks"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The number of weeks before the air filter needs to be changed. This value is
deprecated as of agent version 20. If not supported, this value will always
return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 13 }
tlpCoolingConfigAirFilterAlarm OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
UNITS "hours"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"When enabled, an alarm should occur when the maximum number of air filter run hours
has been exceeded. This value is deprecated as of agent version 20. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 14 }
tlpCoolingConfigMaxAirFilterRunHours OBJECT-TYPE
SYNTAX Unsigned32
UNITS "hours"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The maximum interval for air filter run hours before warning is annunciated. This
value is deprecated as of agent version 20. If not supported, this value will always
return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 15 }
tlpCoolingConfigStartTimer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "minutes"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The unit will start operate after the specified timer elapsed. This value is
deprecated as of agent version 20. If not supported, this value will always return
ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 16 }
tlpCoolingConfigStopTimer OBJECT-TYPE
SYNTAX Unsigned32
UNITS "minutes"
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The unit will switch to standby mode after the specified timer elapsed. This value
is deprecated as of agent version 20. If not supported, this value will always
return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 17 }
tlpCoolingConfigEnergyMode OBJECT-TYPE
SYNTAX INTEGER {
normalCooling(0),
energySaving(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option enables or disables the energy saving mode.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 18 }
tlpCoolingConfigDefrostMode OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"This option enables or disables the defrost mode. This value is
deprecated as of agent version 20 and not remotely configurable
on any device. It is superseded by tlpCoolingDefrostMode."
::= { tlpCoolingConfigEntry 19 }
tlpCoolingConfigRemoteTemperatureSensor OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option enables or disables the remote temperature sensor. If not
supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 20 }
tlpCoolingConfigDehumidifyingMode OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option enables or disables the dehumidifying mode. If not supported,
this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 21 }
tlpCoolingConfigFanAlwaysOn OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"This option enables or disables the fan always on. If not supported, this
value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigEntry 22 }
tlpCoolingConfigQuietMode OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"This option enables or disables the quiet mode. This value is
deprecated as of agent version 20 and not remotely configurable on any
device. It is superseded by tlpCoolingQuietMode."
::= { tlpCoolingConfigEntry 23 }
tlpCoolingConfigHotGasBypass OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"This option enables or disables the hot gas bypass. This value is
deprecated as of agent version 20 and not remotely configurable on any
device. It is superseded by tlpCoolingHotGasBypass."
::= { tlpCoolingConfigEntry 24 }
tlpCoolingConfigAutoFanSpeed OBJECT-TYPE
SYNTAX INTEGER {
disabled(0),
enabled(1) }
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"This option enables or disables the auto fan speed. This value is deprecated
as of agent version 20 and superseded by tlpCoolingFanSpeed and
tlpCoolingAutoFanSpeed."
::= { tlpCoolingConfigEntry 25 }
tlpCoolingConfigTemperatureFahrenheitTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingConfigTemperatureFahrenheitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration details for each each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device. Not all options are available on all
cooling devices."
::= { tlpCoolingConfig 2 }
tlpCoolingConfigTemperatureFahrenheitEntry OBJECT-TYPE
SYNTAX TlpCoolingConfigTemperatureFahrenheitEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry configuration details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingConfigTemperatureFahrenheitTable 1 }
TlpCoolingConfigTemperatureFahrenheitEntry ::= SEQUENCE {
tlpCoolingSetPointDegF Integer32,
tlpCoolingSupplyAirHighLimitDegF Integer32,
tlpCoolingSupplyAirLowLimitDegF Integer32,
tlpCoolingMaxDeviationLimitDegF Integer32,
tlpCoolingReturnAirHighLimitDegF Integer32,
tlpCoolingReturnAirLowLimitDegF Integer32,
tlpCoolingRemoteSetPointDegF Integer32 }
tlpCoolingSetPointDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The set point temperature the unit will control the temperature in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureFahrenheitEntry 1 }
tlpCoolingSupplyAirHighLimitDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureFahrenheitEntry 2 }
tlpCoolingSupplyAirLowLimitDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureFahrenheitEntry 3 }
tlpCoolingMaxDeviationLimitDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed air temperature deviation from set temperature before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureFahrenheitEntry 4 }
tlpCoolingReturnAirHighLimitDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureFahrenheitEntry 5 }
tlpCoolingReturnAirLowLimitDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimum allowed supply air temperature in tenths degrees Fahrenheit before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureFahrenheitEntry 6 }
tlpCoolingRemoteSetPointDegF OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Fahrenheit"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The remote set point temperature the unit will control the temperature in tenths degrees Fahrenheit.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureFahrenheitEntry 7 }
tlpCoolingConfigTemperatureCelsiusTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpCoolingConfigTemperatureCelsiusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"The configuration details for each cooling device in device table. This
is a sparse dependent table, and will contain some subset of
devices that are cooling device. Not all options are available on all
cooling devices."
::= { tlpCoolingConfig 3 }
tlpCoolingConfigTemperatureCelsiusEntry OBJECT-TYPE
SYNTAX TlpCoolingConfigTemperatureCelsiusEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry configuration details for a particular cooling device."
INDEX { tlpDeviceIndex }
::= { tlpCoolingConfigTemperatureCelsiusTable 1 }
TlpCoolingConfigTemperatureCelsiusEntry ::= SEQUENCE {
tlpCoolingSetPointDegC Integer32,
tlpCoolingSupplyAirHighLimitDegC Integer32,
tlpCoolingSupplyAirLowLimitDegC Integer32,
tlpCoolingMaxDeviationLimitDegC Integer32,
tlpCoolingReturnAirHighLimitDegC Integer32,
tlpCoolingReturnAirLowLimitDegC Integer32,
tlpCoolingRemoteSetPointDegC Integer32 }
tlpCoolingSetPointDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The set point temperature the unit will control the temperature in tenths degrees Celsius.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureCelsiusEntry 1 }
tlpCoolingSupplyAirHighLimitDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed supply air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureCelsiusEntry 2 }
tlpCoolingSupplyAirLowLimitDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimum allowed supply air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureCelsiusEntry 3 }
tlpCoolingMaxDeviationLimitDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed air temperature deviation from set temperature before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureCelsiusEntry 4 }
tlpCoolingReturnAirHighLimitDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Maximum allowed return air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureCelsiusEntry 5 }
tlpCoolingReturnAirLowLimitDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Minimum allowed return air temperature in tenths degrees Celsius before firing an alarm.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureCelsiusEntry 6 }
tlpCoolingRemoteSetPointDegC OBJECT-TYPE
SYNTAX Integer32
UNITS "0.1 degrees Celsius"
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The remote set point temperature the unit will control the temperature in tenths degrees Celsius.
If not supported, this value will always return ERROR_NO_SUCH_NAME."
::= { tlpCoolingConfigTemperatureCelsiusEntry 7 }
-- kvm
tlpKvmIdentNumKvm OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of kvm devices that this agent is currently managing."
::= { tlpKvmIdent 1 }
-- rackTrack
tlpRackTrackIdentNumRackTrack OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of rack track devices that this agent is currently managing."
::= { tlpRackTrackIdent 1 }
-- switch
tlpSwitchIdentNumSwitch OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of switch devices that this agent is currently managing."
::= { tlpSwitchIdent 1 }
-- software
tlpAgentType OBJECT-TYPE
SYNTAX INTEGER {
unknown(0),
pal(1),
pansa(2),
delta(3),
sinetica(4),
netos6(5),
netos7(6),
panms(7),
nmc5(8) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of PowerAlert engine providing this data."
::= { tlpAgentIdent 1 }
tlpAgentVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The version of the agent software."
::= { tlpAgentIdent 2 }
tlpAgentDriverVersion OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The driver version of the agent software. This value is not supported
in PowerAlert agents v20 and above and will return ERROR_NO_SUCH_NAME."
::= { tlpAgentIdent 3 }
tlpAgentMAC OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The MAC Address of the agent."
::= { tlpAgentIdent 4 }
tlpAgentSerialNum OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Serial number of the web card providing the agent data. This value is
only supported by a web card agent. PowerAlert for PC (PAL) agents do
not support this value and will return ERROR_NO_SUCH_NAME."
::= { tlpAgentIdent 5 }
tlpAgentUuid OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Universally unique identifier for this host in the form 8-4-4-4-12 for a
total of 36 characters (32 alphanumeric characters and four hyphens). For
example: 550e8400-e29b-41d4-a716-446655440000."
::= { tlpAgentIdent 6 }
tlpAgentAttributesSupports OBJECT IDENTIFIER
::= { tlpAgentAttributes 1 }
tlpAgentAttributesSupportsHTTP OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent supports HTTP connections."
::= { tlpAgentAttributesSupports 1 }
tlpAgentAttributesSupportsHTTPS OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent supports HTTPS connections."
::= { tlpAgentAttributesSupports 2 }
tlpAgentAttributesSupportsFTP OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent supports FTP connections."
::= { tlpAgentAttributesSupports 3 }
tlpAgentAttributesSupportsTelnet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent supports Telnet connections."
::= { tlpAgentAttributesSupports 4 }
tlpAgentAttributesSupportsObsolete1 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unused."
::= { tlpAgentAttributesSupports 5 }
tlpAgentAttributesSupportsSSH OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent supports SSH connections."
::= { tlpAgentAttributesSupports 6 }
tlpAgentAttributesSupportsObsolete2 OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unused."
::= { tlpAgentAttributesSupports 7 }
tlpAgentAttributesSupportsSNMP OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent supports SNMP connections."
::= { tlpAgentAttributesSupports 8 }
tlpAgentAttributesSupportsSNMPTrap OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent supports listening for SNMP traps. This
is only applicable for network monitoring applications, PowerAlert
Shutdown Agent for an example, that connect to a web card or PowerAlert
Local and listen for outbound traps. As such, this value is not supported
and will always return 2(false) for a web card or PowerAlert Local."
::= { tlpAgentAttributesSupports 9 }
tlpAgentAttributesEnabled OBJECT IDENTIFIER
::= { tlpAgentAttributes 2 }
tlpAgentAttributesHTTPEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent will allow HTTP connections."
::= { tlpAgentAttributesEnabled 1 }
tlpAgentAttributesHTTPSEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent will allow HTTPS connections."
::= { tlpAgentAttributesEnabled 2 }
tlpAgentAttributesFTPEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Indicates whether the agent will allow FTP connections."
::= { tlpAgentAttributesEnabled 3 }
tlpAgentAttributesTelnetEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent will allow Telnet connections."
::= { tlpAgentAttributesEnabled 4 }
tlpAgentAttributesObsolete1Enabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unused."
::= { tlpAgentAttributesEnabled 5 }
tlpAgentAttributesSSHEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent will allow SSH connections."
::= { tlpAgentAttributesEnabled 6 }
tlpAgentAttributesSFTPEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Indicates whether the agent will allow SFTP and SCP connections."
::= { tlpAgentAttributesEnabled 7 }
tlpAgentAttributesObsolete2Enabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unknown."
::= { tlpAgentAttributesEnabled 8 }
tlpAgentAttributesSnmp OBJECT IDENTIFIER
::= { tlpAgentAttributes 3 }
tlpAgentAttributesSNMPv1Enabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent will allow SNMPv1 connections."
::= { tlpAgentAttributesSnmp 1 }
tlpAgentAttributesSNMPv2cEnabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent will allow SNMPv2c connections."
::= { tlpAgentAttributesSnmp 2 }
tlpAgentAttributesSNMPv3Enabled OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether the agent will allow SNMPv3 connections."
::= { tlpAgentAttributesSnmp 3 }
tlpAgentAttributesPorts OBJECT IDENTIFIER
::= { tlpAgentAttributes 4 }
tlpAgentAttributesHTTPPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The port used for HTTP communications."
::= { tlpAgentAttributesPorts 1 }
tlpAgentAttributesHTTPSPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The port used for HTTPS communications."
::= { tlpAgentAttributesPorts 2 }
tlpAgentAttributesFTPPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The port used for FTP communications."
::= { tlpAgentAttributesPorts 3 }
tlpAgentAttributesTelnetPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The port used for Telnet communications."
::= { tlpAgentAttributesPorts 4 }
tlpAgentAttributesObsolete1Port OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unused."
::= { tlpAgentAttributesPorts 5 }
tlpAgentAttributesSSHPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The port used for SSH communications."
::= { tlpAgentAttributesPorts 6 }
tlpAgentAttributesObsolete2Port OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"Unused."
::= { tlpAgentAttributesPorts 7 }
tlpAgentAttributesSNMPPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The port used for SNMP communications."
::= { tlpAgentAttributesPorts 8 }
tlpAgentAttributesSNMPTrapPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The port used for SNMP trap and notifications."
::= { tlpAgentAttributesPorts 9 }
tlpAgentAttributesOptions OBJECT IDENTIFIER
::= { tlpAgentAttributes 5 }
tlpAgentAttributesHTTPRedirected OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Indicates whether HTTP traffic is redirected to HTTPS."
::= { tlpAgentAttributesOptions 1 }
tlpAgentAddressIPv4 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IPv4 address of the agent."
::= { tlpAgentAddresses 1 }
tlpAgentAddressIPv6 OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The IPv6 address of the agent."
::= { tlpAgentAddresses 2 }
tlpAgentConfigRemoteRegistration OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Registers an SNMP contact's IP address and the port on which
the contact is listening for SNMP traps. Setting this
value is used to CREATE a table entry in a non-standard way.
Getting this value will return a string INADDR_ANY and any
port number.
The port number should always be included. When unregistering
an SNMP contact, the requester's IP address should be provided
with a port number of 0. When setting or unsetting this OID,
the IP address string should never be 0 nor should it be empty.
The registration uses its default community string to register
each contact. To use a community other than the default, then
it must be appended to the end of the string delimited with a
comma.
The address should be of the format 0.0.0.0:00000 for IPv4.
If IPv6 is supported, use the bracket-enclosed format given
in IETF RFC 2732 Section 2, with the following examples:
[FEDC:BA98:7654:3210:FEDC:BA98:7654:3210]:80
[1080:0:0:0:8:800:200C:417A]:162
[3ffe:2a00:100:7031::1]:162
[1080::8:800:200C:417A]:162,myCommunity
[::192.9.5.5]:162,myCommunity
[::FFFF:129.144.52.38]:80
[2010:836B:4179::836B:4179]:162"
::= { tlpAgentConfig 1 }
tlpAgentConfigCurrentTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"PowerAlert's current date and time in UTC. Setting this value must
follow the RFC3339 time format (e.g. '2030-07-04 00:00:00+05:00').
Regardless of any time offset used when setting this value, the
agent will always return a value with an offset of +00:00."
::= { tlpAgentConfig 2 }
tlpAgentNumEmailContacts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of email contacts currently defined in the agent."
::= { tlpAgentEmailContacts 1 }
tlpAgentEmailContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAgentEmailContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of email contact entries. The number of entries is given by
the value of tlpAgentNumEmailContacts."
::= { tlpAgentEmailContacts 2 }
tlpAgentEmailContactEntry OBJECT-TYPE
SYNTAX TlpAgentEmailContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing the details of an email contact."
INDEX { tlpAgentEmailContactIndex }
::= { tlpAgentEmailContactTable 1 }
TlpAgentEmailContactEntry ::= SEQUENCE {
tlpAgentEmailContactIndex Unsigned32,
tlpAgentEmailContactRowStatus RowStatus,
tlpAgentEmailContactName DisplayString,
tlpAgentEmailContactAddress DisplayString,
tlpAgentEmailContactTest TruthValue }
tlpAgentEmailContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the email contact."
::= { tlpAgentEmailContactEntry 1 }
tlpAgentEmailContactRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Row status for the tlpAgentEmailContactTable."
::= { tlpAgentEmailContactEntry 2 }
tlpAgentEmailContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the email contact."
::= { tlpAgentEmailContactEntry 3 }
tlpAgentEmailContactAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The address of the email contact."
::= { tlpAgentEmailContactEntry 4 }
tlpAgentEmailContactTest OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to send a test email to the contact."
::= { tlpAgentEmailContactEntry 5 }
tlpAgentNumSnmpContacts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SNMP contacts currently defined in the agent."
::= { tlpAgentSnmpContacts 1 }
tlpAgentSnmpContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAgentSnmpContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of SNMP contact entries. The number of entries is given by
the value of tlpAgentNumSnmpContacts."
::= { tlpAgentSnmpContacts 2 }
tlpAgentSnmpContactEntry OBJECT-TYPE
SYNTAX TlpAgentSnmpContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing the details of an SNMP contact."
INDEX { tlpAgentSnmpContactIndex }
::= { tlpAgentSnmpContactTable 1 }
TlpAgentSnmpContactEntry ::= SEQUENCE {
tlpAgentSnmpContactIndex Unsigned32,
tlpAgentSnmpContactRowStatus RowStatus,
tlpAgentSnmpContactName DisplayString,
tlpAgentSnmpContactIpAddress DisplayString,
tlpAgentSnmpContactTrapPort Unsigned32,
tlpAgentSnmpContactSnmpVersion INTEGER,
tlpAgentSnmpContactSecurityName DisplayString,
tlpAgentSnmpContactPrivPassword DisplayString,
tlpAgentSnmpContactAuthPassword DisplayString,
tlpAgentSnmpContactTrapType INTEGER,
tlpAgentSnmpContactSetPort Unsigned32,
tlpAgentSnmpContactSupportsTrap TruthValue,
tlpAgentSnmpContactSupportsSet TruthValue,
tlpAgentSnmpContactTestTrap TruthValue }
tlpAgentSnmpContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the SNMP contact."
::= { tlpAgentSnmpContactEntry 1 }
tlpAgentSnmpContactRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Row status for the tlpAgentSnmpContactTable."
::= { tlpAgentSnmpContactEntry 2 }
tlpAgentSnmpContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the SNMP contact."
::= { tlpAgentSnmpContactEntry 3 }
tlpAgentSnmpContactIpAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The IP address of the SNMP contact."
::= { tlpAgentSnmpContactEntry 4 }
tlpAgentSnmpContactTrapPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The trap port used for the SNMP contact."
::= { tlpAgentSnmpContactEntry 5 }
tlpAgentSnmpContactSnmpVersion OBJECT-TYPE
SYNTAX INTEGER {
snmpv1(1),
snmpv2c(2),
snmpv3(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The SNMP contact version to use for sending traps."
::= { tlpAgentSnmpContactEntry 6 }
tlpAgentSnmpContactSecurityName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS deprecated
DESCRIPTION
"The security name for the SNMP contact."
::= { tlpAgentSnmpContactEntry 7 }
tlpAgentSnmpContactPrivPassword OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"The privacy password to use for sending V3 traps to the SNMP
contact."
::= { tlpAgentSnmpContactEntry 8 }
tlpAgentSnmpContactAuthPassword OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS obsolete
DESCRIPTION
"The authentication password to use for sending V3 traps to the
SNMP contact."
::= { tlpAgentSnmpContactEntry 9 }
tlpAgentSnmpContactTrapType OBJECT-TYPE
SYNTAX INTEGER {
trap(0),
inform(1) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The type of notification to use for the SNMP contact. SNMPv1 does not support inform(1)."
::= { tlpAgentSnmpContactEntry 10 }
tlpAgentSnmpContactSetPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The set port used by the SNMP contact."
::= { tlpAgentSnmpContactEntry 11 }
tlpAgentSnmpContactSupportsTrap OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates whether the SNMP contact supports notifications."
::= { tlpAgentSnmpContactEntry 12 }
tlpAgentSnmpContactSupportsSet OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Indicates whether the SNMP contact supports sets."
::= { tlpAgentSnmpContactEntry 13 }
tlpAgentSnmpContactTestTrap OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to send a test trap to the contact."
::= { tlpAgentSnmpContactEntry 14 }
-- Reserved for future use
-- tlpAgentSnmpContactTestSet
-- ::= { tlpAgentSnmpContactEntry 15 }
tlpAgentSmsNumSmsContacts OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of SMS contacts currently defined in the agent."
::= { tlpAgentSmsContacts 1 }
tlpAgentSmsContactTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAgentSmsContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of SMS contact entries. The number of entries is given by
the value of tlpAgentSmsContacts."
::= { tlpAgentSmsContacts 2 }
tlpAgentSmsContactEntry OBJECT-TYPE
SYNTAX TlpAgentSmsContactEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing the details of an SMS contact."
INDEX { tlpAgentSmsContactIndex }
::= { tlpAgentSmsContactTable 1 }
TlpAgentSmsContactEntry ::= SEQUENCE {
tlpAgentSmsContactIndex Unsigned32,
tlpAgentSmsContactRowStatus RowStatus,
tlpAgentSmsContactName DisplayString,
tlpAgentSmsContactNumber DisplayString,
tlpAgentSmsContactTest TruthValue }
tlpAgentSmsContactIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the SMS contact."
::= { tlpAgentSmsContactEntry 1 }
tlpAgentSmsContactRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Row status for the tlpAgentSmsContactTable."
::= { tlpAgentSmsContactEntry 2 }
tlpAgentSmsContactName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The name of the SMS contact."
::= { tlpAgentSmsContactEntry 3 }
tlpAgentSmsContactNumber OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The Phone number of the SMS contact."
::= { tlpAgentSmsContactEntry 4 }
tlpAgentSmsContactTest OBJECT-TYPE
SYNTAX TruthValue
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Set to TRUE to send a test text message to the contact."
::= { tlpAgentSmsContactEntry 5 }
tlpAgentAutoProbeNumProbes OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of probes currently defined in the agent."
::= { tlpAgentAutoProbe 1 }
tlpAgentAutoProbeTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAgentAutoProbeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of probe entries. The number of entries is given by
the value of tlpAgentAutoProbeNumProbes."
::= { tlpAgentAutoProbe 2 }
tlpAgentAutoProbeEntry OBJECT-TYPE
SYNTAX TlpAgentAutoProbeEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing the details of a probe."
INDEX { tlpAgentAutoProbeIndex }
::= { tlpAgentAutoProbeTable 1 }
TlpAgentAutoProbeEntry ::= SEQUENCE {
tlpAgentAutoProbeIndex Unsigned32,
tlpAgentAutoProbeRowStatus RowStatus,
tlpAgentAutoProbeName DisplayString,
tlpAgentAutoProbeDescription DisplayString,
tlpAgentAutoProbeType INTEGER,
tlpAgentAutoProbeStatus INTEGER,
tlpAgentAutoProbeInterval Unsigned32,
tlpAgentAutoProbeRetryCount Unsigned32,
tlpAgentAutoProbePrimaryAddress DisplayString,
tlpAgentAutoProbePrimaryPort Unsigned32,
tlpAgentAutoProbeSecondaryAddress DisplayString,
tlpAgentAutoProbeSecondaryPort Unsigned32 }
tlpAgentAutoProbeIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for the probe."
::= { tlpAgentAutoProbeEntry 1 }
tlpAgentAutoProbeRowStatus OBJECT-TYPE
SYNTAX RowStatus
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Row status for the tlpAgentAutoProbeTable."
::= { tlpAgentAutoProbeEntry 2 }
tlpAgentAutoProbeName OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The name of the probe."
::= { tlpAgentAutoProbeEntry 3 }
tlpAgentAutoProbeDescription OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The description of the probe."
::= { tlpAgentAutoProbeEntry 4 }
tlpAgentAutoProbeType OBJECT-TYPE
SYNTAX INTEGER {
ntp(1),
ping(2),
snmp(3),
http(4),
https(5) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The type of probe."
::= { tlpAgentAutoProbeEntry 5 }
tlpAgentAutoProbeStatus OBJECT-TYPE
SYNTAX INTEGER {
unspecified(0),
unknown(1),
ok(2),
failed(3),
initFailed(4) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current status of the probe."
::= { tlpAgentAutoProbeEntry 6 }
tlpAgentAutoProbeInterval OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of minutes to wait between each probe attempt."
::= { tlpAgentAutoProbeEntry 7 }
tlpAgentAutoProbeRetryCount OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The number of failed probe attempts before a failure alert
is triggered."
::= { tlpAgentAutoProbeEntry 8 }
tlpAgentAutoProbePrimaryAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The primary ip address or host name to probe."
::= { tlpAgentAutoProbeEntry 9 }
tlpAgentAutoProbePrimaryPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The primary port on tlpAgentAutoProbePrimaryAddress to probe. Not all
probe types (tlpAgentAutoProbeType) support ports. If not supported, this
agent will return ERROR_NO_SUCH_NAME."
::= { tlpAgentAutoProbeEntry 10 }
tlpAgentAutoProbeSecondaryAddress OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The optional secondary ip address or host name to probe."
::= { tlpAgentAutoProbeEntry 11 }
tlpAgentAutoProbeSecondaryPort OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The secondary port on tlpAgentAutoProbeSecondaryAddress to probe. Not all
probe types (tlpAgentAutoProbeType) support ports. If not supported, this
agent will return ERROR_NO_SUCH_NAME."
::= { tlpAgentAutoProbeEntry 12 }
-- alarms
tlpAlarmsPresent OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The present number of active alarm conditions."
::= { tlpAlarms 1 }
tlpAlarmTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpDeviceAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of alarm conditions for all devices managed by this agent. This
table contains zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect or conditions not acknowledged.
The agent creates a row in the table each time a condition is detected
and deletes that row when that condition no longer pertains (becomes
inactive and is acknowledged). The agent creates the first row with
tlpAlarmId equal to 1, and increments the value of tlpAlarmId each time
a new row is created, wrapping to the first free value greater than or
equal to 1 when the maximum value of tlpAlarmId would otherwise be
exceeded. Consequently, after multiple operations, the table may become
sparse (e.g., containing entries for rows 95, 100, 101, and 203) and the
entries should not be assumed to be in chronological order because
tlpAlarmId might have wrapped.
The number of rows in the table at any given time is reflected by
the value of tlpAlarmsPresent."
::= { tlpAlarms 2 }
tlpAlarmEntry OBJECT-TYPE
SYNTAX TlpDeviceAlarmEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing information application to a particular
alarm."
INDEX { tlpAlarmId }
::= { tlpAlarmTable 1 }
TlpDeviceAlarmEntry ::= SEQUENCE {
tlpAlarmId Unsigned32,
tlpAlarmDescr OBJECT IDENTIFIER,
tlpAlarmTime TimeStamp,
tlpAlarmTableRef OBJECT IDENTIFIER,
tlpAlarmTableRowRef OBJECT IDENTIFIER,
tlpAlarmDetail DisplayString,
tlpAlarmType INTEGER,
tlpAlarmState INTEGER,
tlpAlarmAcknowledged INTEGER,
tlpAlarmSeverity INTEGER }
tlpAlarmId OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A unique identifier for an alarm condition. This value will remain
constant for the duration of the alarm condition."
::= { tlpAlarmEntry 1 }
tlpAlarmDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference of the alarm description object. The object referenced
should not be accessible, but rather be used to provide a unique
description for the alarm condition. The object referenced will be a
well known alarm object associated with the device on which the alarm
condition is active."
::= { tlpAlarmEntry 2 }
tlpAlarmTime OBJECT-TYPE
SYNTAX TimeStamp
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The value of sysUpTime when the alarm condition was detected. If the
alarm condition was detected at the time of agent startup and presumably
existed before agent startup, the value of tlpAlarmsTime shall equal
0."
::= { tlpAlarmEntry 3 }
tlpAlarmTableRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value references the OID of a table object applicable to the alarm
condition. This, in conjunction with the table row as defined by
tlpAlarmTableRowRef, specifies the object/row within this table to which
the alarm condition applies.
Example 1 -- The following sample values will be returned for a ups on
battery:
tlpAlarmId 28
tlpAlarmDescr tlpUpsAlarmOnBattery
tlpAlarmTime 12345678
tlpAlarmTableRef tlpDeviceTable
tlpAlarmTableRowRef tlpDeviceIndex.2
tlpAlarmDetail On Battery
tlpAlarmType warning
tlpAlarmState active
tlpAlarmAcknowledged notAcknowledged
tlpAlarmSeverity warning
In the above example, tlpAlarmTableRef references the device table and
tlpAlarmTableRowRef references the 2nd managed device in that table.
Example 2 -- The following sample values will be returned for a pdu with
a load turned off:
tlpAlarmId 46
tlpAlarmDescr tlpPduAlarmLoadOff
tlpAlarmTime 12345678
tlpAlarmTableRef tlpPduOutletTable
tlpAlarmTableRowRef tlpOutletIndex.1.4
tlpAlarmDetail Load Off
tlpAlarmType warning
tlpAlarmState active
tlpAlarmAcknowledged acknowledged
tlpAlarmSeverity warning
In the above example, tlpAlarmTableRef references the pdu outlet table and
tlpAlarmTableRowRef references the 4th outlet on the 1st managed device."
::= { tlpAlarmEntry 4 }
tlpAlarmTableRowRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value is used in conjunction with tlpAlarmTableRef to define the
object associated with this alarm condition. See the description of
tlpAlarmTableRef for more information."
::= { tlpAlarmEntry 5 }
tlpAlarmDetail OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A textual description of the alarm condition."
::= { tlpAlarmEntry 6 }
tlpAlarmType OBJECT-TYPE
SYNTAX INTEGER {
critical(1),
warning(2),
info(3),
status(4),
offline(5),
custom(6) }
MAX-ACCESS read-only
STATUS deprecated
DESCRIPTION
"The category/group of this alarm."
::= { tlpAlarmEntry 7 }
tlpAlarmState OBJECT-TYPE
SYNTAX INTEGER {
active(1),
inactive(2) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The current state of this alarm condition. An active(1) alarm is a condition
that currently exists. An inactive(2) alarm is a condition that no longer exists
because the alarm either cleared or was resolved. Each alarm condition must be
cleared and acknowledged before it is removed from this table (see
tlpAlarmAcknowledged)."
::= { tlpAlarmEntry 8 }
tlpAlarmAcknowledged OBJECT-TYPE
SYNTAX INTEGER {
notAcknowledged(1),
acknowledged(2) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"Denotes whether the alarm condition has been acknowledged. The agent will
return notAcknowledged(1) if the condition has not been acknowledged, or
acknowledged(2) when acknowledged. Writing the value acknowledged(2) for an
alarm acknowledges the alarm condition. Each alarm condition must be cleared
and acknowledged before it is removed from this table; therefore, even if
acknowledged, the alarm will remain in this table until the alarm becomes
inactive as denoted by tlpAlarmState."
::= { tlpAlarmEntry 9 }
tlpAlarmSeverity OBJECT-TYPE
SYNTAX INTEGER {
emergency(0),
alert(1),
critical(2),
error(3),
warning(4),
notice(5),
information(6) }
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The severity of this alarm."
::= { tlpAlarmEntry 10 }
tlpAutoProbeAlarms OBJECT IDENTIFIER
::= { tlpAgentAlarms 1 }
tlpAutoProbeAlarm01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 1 failed."
::= { tlpAutoProbeAlarms 1 }
tlpAutoProbeAlarm02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 2 failed."
::= { tlpAutoProbeAlarms 2 }
tlpAutoProbeAlarm03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 3 failed."
::= { tlpAutoProbeAlarms 3 }
tlpAutoProbeAlarm04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 4 failed."
::= { tlpAutoProbeAlarms 4 }
tlpAutoProbeAlarm05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 5 failed."
::= { tlpAutoProbeAlarms 5 }
tlpAutoProbeAlarm06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 6 failed."
::= { tlpAutoProbeAlarms 6 }
tlpAutoProbeAlarm07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 7 failed."
::= { tlpAutoProbeAlarms 7 }
tlpAutoProbeAlarm08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 8 failed."
::= { tlpAutoProbeAlarms 8 }
tlpAutoProbeAlarm09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 9 failed."
::= { tlpAutoProbeAlarms 9 }
tlpAutoProbeAlarm10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 10 failed."
::= { tlpAutoProbeAlarms 10 }
tlpAutoProbeAlarm11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 11 failed."
::= { tlpAutoProbeAlarms 11 }
tlpAutoProbeAlarm12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 12 failed."
::= { tlpAutoProbeAlarms 12 }
tlpAutoProbeAlarm13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 13 failed."
::= { tlpAutoProbeAlarms 13 }
tlpAutoProbeAlarm14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 14 failed."
::= { tlpAutoProbeAlarms 14 }
tlpAutoProbeAlarm15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 15 failed."
::= { tlpAutoProbeAlarms 15 }
tlpAutoProbeAlarm16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 16 failed."
::= { tlpAutoProbeAlarms 16 }
tlpAutoProbeAlarm17 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 17 failed."
::= { tlpAutoProbeAlarms 17 }
tlpAutoProbeAlarm18 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 18 failed."
::= { tlpAutoProbeAlarms 18 }
tlpAutoProbeAlarm19 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 19 failed."
::= { tlpAutoProbeAlarms 19 }
tlpAutoProbeAlarm20 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 20 failed."
::= { tlpAutoProbeAlarms 20 }
tlpAutoProbeAlarm21 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 21 failed."
::= { tlpAutoProbeAlarms 21 }
tlpAutoProbeAlarm22 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 22 failed."
::= { tlpAutoProbeAlarms 22 }
tlpAutoProbeAlarm23 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 23 failed."
::= { tlpAutoProbeAlarms 23 }
tlpAutoProbeAlarm24 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 24 failed."
::= { tlpAutoProbeAlarms 24 }
tlpAutoProbeAlarm25 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 25 failed."
::= { tlpAutoProbeAlarms 25 }
tlpAutoProbeAlarm26 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 26 failed."
::= { tlpAutoProbeAlarms 26 }
tlpAutoProbeAlarm27 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 27 failed."
::= { tlpAutoProbeAlarms 27 }
tlpAutoProbeAlarm28 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 28 failed."
::= { tlpAutoProbeAlarms 28 }
tlpAutoProbeAlarm29 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 29 failed."
::= { tlpAutoProbeAlarms 29 }
tlpAutoProbeAlarm30 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 30 failed."
::= { tlpAutoProbeAlarms 30 }
tlpAutoProbeAlarm31 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 31 failed."
::= { tlpAutoProbeAlarms 31 }
tlpAutoProbeAlarm32 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 32 failed."
::= { tlpAutoProbeAlarms 32 }
tlpAutoProbeAlarm33 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 33 failed."
::= { tlpAutoProbeAlarms 33 }
tlpAutoProbeAlarm34 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 34 failed."
::= { tlpAutoProbeAlarms 34 }
tlpAutoProbeAlarm35 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 35 failed."
::= { tlpAutoProbeAlarms 35 }
tlpAutoProbeAlarm36 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 36 failed."
::= { tlpAutoProbeAlarms 36 }
tlpAutoProbeAlarm37 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 37 failed."
::= { tlpAutoProbeAlarms 37 }
tlpAutoProbeAlarm38 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 38 failed."
::= { tlpAutoProbeAlarms 38 }
tlpAutoProbeAlarm39 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 39 failed."
::= { tlpAutoProbeAlarms 39 }
tlpAutoProbeAlarm40 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 40 failed."
::= { tlpAutoProbeAlarms 40 }
tlpAutoProbeAlarm41 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 41 failed."
::= { tlpAutoProbeAlarms 41 }
tlpAutoProbeAlarm42 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 42 failed."
::= { tlpAutoProbeAlarms 42 }
tlpAutoProbeAlarm43 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 43 failed."
::= { tlpAutoProbeAlarms 43 }
tlpAutoProbeAlarm44 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 44 failed."
::= { tlpAutoProbeAlarms 44 }
tlpAutoProbeAlarm45 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 45 failed."
::= { tlpAutoProbeAlarms 45 }
tlpAutoProbeAlarm46 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 46 failed."
::= { tlpAutoProbeAlarms 46 }
tlpAutoProbeAlarm47 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 47 failed."
::= { tlpAutoProbeAlarms 47 }
tlpAutoProbeAlarm48 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 48 failed."
::= { tlpAutoProbeAlarms 48 }
tlpAutoProbeAlarm49 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 49 failed."
::= { tlpAutoProbeAlarms 49 }
tlpAutoProbeAlarm50 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 50 failed."
::= { tlpAutoProbeAlarms 50 }
tlpAutoProbeAlarm51 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 51 failed."
::= { tlpAutoProbeAlarms 51 }
tlpAutoProbeAlarm52 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 52 failed."
::= { tlpAutoProbeAlarms 52 }
tlpAutoProbeAlarm53 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 53 failed."
::= { tlpAutoProbeAlarms 53 }
tlpAutoProbeAlarm54 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 54 failed."
::= { tlpAutoProbeAlarms 54 }
tlpAutoProbeAlarm55 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 55 failed."
::= { tlpAutoProbeAlarms 55 }
tlpAutoProbeAlarm56 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 56 failed."
::= { tlpAutoProbeAlarms 56 }
tlpAutoProbeAlarm57 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 57 failed."
::= { tlpAutoProbeAlarms 57 }
tlpAutoProbeAlarm58 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 58 failed."
::= { tlpAutoProbeAlarms 58 }
tlpAutoProbeAlarm59 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 59 failed."
::= { tlpAutoProbeAlarms 59 }
tlpAutoProbeAlarm60 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 60 failed."
::= { tlpAutoProbeAlarms 60 }
tlpAutoProbeAlarm61 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 61 failed."
::= { tlpAutoProbeAlarms 61 }
tlpAutoProbeAlarm62 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 62 failed."
::= { tlpAutoProbeAlarms 62 }
tlpAutoProbeAlarm63 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 63 failed."
::= { tlpAutoProbeAlarms 63 }
tlpAutoProbeAlarm64 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"AutoProbe 64 failed."
::= { tlpAutoProbeAlarms 64 }
tlpAutoProbeUserDefinedAlarms OBJECT IDENTIFIER
::= { tlpAgentAlarms 2 }
tlpAutoProbeUserDefinedAlarm01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 1 failed."
::= { tlpAutoProbeUserDefinedAlarms 1 }
tlpAutoProbeUserDefinedAlarm02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 2 failed."
::= { tlpAutoProbeUserDefinedAlarms 2 }
tlpAutoProbeUserDefinedAlarm03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 3 failed."
::= { tlpAutoProbeUserDefinedAlarms 3 }
tlpAutoProbeUserDefinedAlarm04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 4 failed."
::= { tlpAutoProbeUserDefinedAlarms 4 }
tlpAutoProbeUserDefinedAlarm05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 5 failed."
::= { tlpAutoProbeUserDefinedAlarms 5 }
tlpAutoProbeUserDefinedAlarm06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 6 failed."
::= { tlpAutoProbeUserDefinedAlarms 6 }
tlpAutoProbeUserDefinedAlarm07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 7 failed."
::= { tlpAutoProbeUserDefinedAlarms 7 }
tlpAutoProbeUserDefinedAlarm08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 8 failed."
::= { tlpAutoProbeUserDefinedAlarms 8 }
tlpAutoProbeUserDefinedAlarm09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 9 failed."
::= { tlpAutoProbeUserDefinedAlarms 9 }
tlpAutoProbeUserDefinedAlarm10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 10 failed."
::= { tlpAutoProbeUserDefinedAlarms 10 }
tlpAutoProbeUserDefinedAlarm11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 11 failed."
::= { tlpAutoProbeUserDefinedAlarms 11 }
tlpAutoProbeUserDefinedAlarm12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 12 failed."
::= { tlpAutoProbeUserDefinedAlarms 12 }
tlpAutoProbeUserDefinedAlarm13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 13 failed."
::= { tlpAutoProbeUserDefinedAlarms 13 }
tlpAutoProbeUserDefinedAlarm14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 14 failed."
::= { tlpAutoProbeUserDefinedAlarms 14 }
tlpAutoProbeUserDefinedAlarm15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 15 failed."
::= { tlpAutoProbeUserDefinedAlarms 15 }
tlpAutoProbeUserDefinedAlarm16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 16 failed."
::= { tlpAutoProbeUserDefinedAlarms 16 }
tlpAutoProbeUserDefinedAlarm17 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 17 failed."
::= { tlpAutoProbeUserDefinedAlarms 17 }
tlpAutoProbeUserDefinedAlarm18 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 18 failed."
::= { tlpAutoProbeUserDefinedAlarms 18 }
tlpAutoProbeUserDefinedAlarm19 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 19 failed."
::= { tlpAutoProbeUserDefinedAlarms 19 }
tlpAutoProbeUserDefinedAlarm20 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 20 failed."
::= { tlpAutoProbeUserDefinedAlarms 20 }
tlpAutoProbeUserDefinedAlarm21 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 21 failed."
::= { tlpAutoProbeUserDefinedAlarms 21 }
tlpAutoProbeUserDefinedAlarm22 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 22 failed."
::= { tlpAutoProbeUserDefinedAlarms 22 }
tlpAutoProbeUserDefinedAlarm23 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 23 failed."
::= { tlpAutoProbeUserDefinedAlarms 23 }
tlpAutoProbeUserDefinedAlarm24 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 24 failed."
::= { tlpAutoProbeUserDefinedAlarms 24 }
tlpAutoProbeUserDefinedAlarm25 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 25 failed."
::= { tlpAutoProbeUserDefinedAlarms 25 }
tlpAutoProbeUserDefinedAlarm26 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 26 failed."
::= { tlpAutoProbeUserDefinedAlarms 26 }
tlpAutoProbeUserDefinedAlarm27 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 27 failed."
::= { tlpAutoProbeUserDefinedAlarms 27 }
tlpAutoProbeUserDefinedAlarm28 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 28 failed."
::= { tlpAutoProbeUserDefinedAlarms 28 }
tlpAutoProbeUserDefinedAlarm29 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 29 failed."
::= { tlpAutoProbeUserDefinedAlarms 29 }
tlpAutoProbeUserDefinedAlarm30 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 30 failed."
::= { tlpAutoProbeUserDefinedAlarms 30 }
tlpAutoProbeUserDefinedAlarm31 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 31 failed."
::= { tlpAutoProbeUserDefinedAlarms 31 }
tlpAutoProbeUserDefinedAlarm32 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 32 failed."
::= { tlpAutoProbeUserDefinedAlarms 32 }
tlpAutoProbeUserDefinedAlarm33 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 33 failed."
::= { tlpAutoProbeUserDefinedAlarms 33 }
tlpAutoProbeUserDefinedAlarm34 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 34 failed."
::= { tlpAutoProbeUserDefinedAlarms 34 }
tlpAutoProbeUserDefinedAlarm35 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 35 failed."
::= { tlpAutoProbeUserDefinedAlarms 35 }
tlpAutoProbeUserDefinedAlarm36 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 36 failed."
::= { tlpAutoProbeUserDefinedAlarms 36 }
tlpAutoProbeUserDefinedAlarm37 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 37 failed."
::= { tlpAutoProbeUserDefinedAlarms 37 }
tlpAutoProbeUserDefinedAlarm38 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 38 failed."
::= { tlpAutoProbeUserDefinedAlarms 38 }
tlpAutoProbeUserDefinedAlarm39 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 39 failed."
::= { tlpAutoProbeUserDefinedAlarms 39 }
tlpAutoProbeUserDefinedAlarm40 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 40 failed."
::= { tlpAutoProbeUserDefinedAlarms 40 }
tlpAutoProbeUserDefinedAlarm41 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 41 failed."
::= { tlpAutoProbeUserDefinedAlarms 41 }
tlpAutoProbeUserDefinedAlarm42 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 42 failed."
::= { tlpAutoProbeUserDefinedAlarms 42 }
tlpAutoProbeUserDefinedAlarm43 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 43 failed."
::= { tlpAutoProbeUserDefinedAlarms 43 }
tlpAutoProbeUserDefinedAlarm44 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 44 failed."
::= { tlpAutoProbeUserDefinedAlarms 44 }
tlpAutoProbeUserDefinedAlarm45 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 45 failed."
::= { tlpAutoProbeUserDefinedAlarms 45 }
tlpAutoProbeUserDefinedAlarm46 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 46 failed."
::= { tlpAutoProbeUserDefinedAlarms 46 }
tlpAutoProbeUserDefinedAlarm47 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 47 failed."
::= { tlpAutoProbeUserDefinedAlarms 47 }
tlpAutoProbeUserDefinedAlarm48 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 48 failed."
::= { tlpAutoProbeUserDefinedAlarms 48 }
tlpAutoProbeUserDefinedAlarm49 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 49 failed."
::= { tlpAutoProbeUserDefinedAlarms 49 }
tlpAutoProbeUserDefinedAlarm50 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 50 failed."
::= { tlpAutoProbeUserDefinedAlarms 50 }
tlpAutoProbeUserDefinedAlarm51 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 51 failed."
::= { tlpAutoProbeUserDefinedAlarms 51 }
tlpAutoProbeUserDefinedAlarm52 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 52 failed."
::= { tlpAutoProbeUserDefinedAlarms 52 }
tlpAutoProbeUserDefinedAlarm53 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 53 failed."
::= { tlpAutoProbeUserDefinedAlarms 53 }
tlpAutoProbeUserDefinedAlarm54 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 54 failed."
::= { tlpAutoProbeUserDefinedAlarms 54 }
tlpAutoProbeUserDefinedAlarm55 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 55 failed."
::= { tlpAutoProbeUserDefinedAlarms 55 }
tlpAutoProbeUserDefinedAlarm56 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 56 failed."
::= { tlpAutoProbeUserDefinedAlarms 56 }
tlpAutoProbeUserDefinedAlarm57 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 57 failed."
::= { tlpAutoProbeUserDefinedAlarms 57 }
tlpAutoProbeUserDefinedAlarm58 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 58 failed."
::= { tlpAutoProbeUserDefinedAlarms 58 }
tlpAutoProbeUserDefinedAlarm59 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 59 failed."
::= { tlpAutoProbeUserDefinedAlarms 59 }
tlpAutoProbeUserDefinedAlarm60 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 60 failed."
::= { tlpAutoProbeUserDefinedAlarms 60 }
tlpAutoProbeUserDefinedAlarm61 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 61 failed."
::= { tlpAutoProbeUserDefinedAlarms 61 }
tlpAutoProbeUserDefinedAlarm62 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 62 failed."
::= { tlpAutoProbeUserDefinedAlarms 62 }
tlpAutoProbeUserDefinedAlarm63 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 63 failed."
::= { tlpAutoProbeUserDefinedAlarms 63 }
tlpAutoProbeUserDefinedAlarm64 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined AutoProbe condition 64 failed."
::= { tlpAutoProbeUserDefinedAlarms 64 }
tlpAgentDiagnosticAlarms OBJECT IDENTIFIER
::= { tlpAgentAlarms 3 }
tlpAgentDiagnosticCPUUsageHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The CPU usage of the PowerAlert is high."
::= { tlpAgentDiagnosticAlarms 1 }
tlpAgentDiagnosticMemoryUsageHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The memory usage of PowerAlert is high."
::= { tlpAgentDiagnosticAlarms 2 }
tlpAgentDiagnosticServiceFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more PowerAlert services failed."
::= { tlpAgentDiagnosticAlarms 3 }
tlpAgentConfigurationAlarms OBJECT IDENTIFIER
::= { tlpAgentAlarms 4 }
tlpAgentConfigurationBackedUp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert configuration was backed up."
::= { tlpAgentConfigurationAlarms 1 }
tlpAgentConfigurationImported OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert configuration was imported."
::= { tlpAgentConfigurationAlarms 2 }
tlpAgentConfigurationRestored OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert configuration was restored."
::= { tlpAgentConfigurationAlarms 3 }
tlpAgentMaintenanceAlarms OBJECT IDENTIFIER
::= { tlpAgentAlarms 5 }
tlpAgentStarted OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert started."
::= { tlpAgentMaintenanceAlarms 1 }
tlpAgentStopped OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert stopped."
::= { tlpAgentMaintenanceAlarms 2 }
tlpAgentRebootInitiated OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert reboot was initiated."
::= { tlpAgentMaintenanceAlarms 3 }
tlpAgentFirmwareUpdated OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert firmware was updated."
::= { tlpAgentMaintenanceAlarms 4 }
tlpAgentRestoreFactoryDefaults OBJECT-IDENTITY
STATUS current
DESCRIPTION
"PowerAlert restoration to factory defaults was initiated."
::= { tlpAgentMaintenanceAlarms 5 }
tlpAgentUserManagementAlarms OBJECT IDENTIFIER
::= { tlpAgentAlarms 6 }
tlpAgentUserPasswordChanged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A user password was changed."
::= { tlpAgentUserManagementAlarms 1 }
tlpAgentUserAdded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A user was added."
::= { tlpAgentUserManagementAlarms 2 }
tlpAgentUserModified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A user was modified."
::= { tlpAgentUserManagementAlarms 3 }
tlpAgentUserDeleted OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A user was deleted."
::= { tlpAgentUserManagementAlarms 4 }
tlpAgentUserConditionOccurred OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A generic user management condition occurred."
::= { tlpAgentUserManagementAlarms 5 }
tlpAgentRoleAdded OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A role was added."
::= { tlpAgentUserManagementAlarms 6 }
tlpAgentRoleModified OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A role was modified."
::= { tlpAgentUserManagementAlarms 7 }
tlpAgentRoleDeleted OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A role was deleted."
::= { tlpAgentUserManagementAlarms 8 }
tlpAlarmCommunicationsLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem has been encountered in the communications between the agent
and the device."
::= { tlpDeviceAlarms 1 }
tlpAlarmUserDefined OBJECT IDENTIFIER
::= { tlpDeviceAlarms 2 }
tlpAlarmUserDefined01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 1 is in alarm."
::= { tlpAlarmUserDefined 1 }
tlpAlarmUserDefined02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 2 is in alarm."
::= { tlpAlarmUserDefined 2 }
tlpAlarmUserDefined03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 3 is in alarm."
::= { tlpAlarmUserDefined 3 }
tlpAlarmUserDefined04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 4 is in alarm."
::= { tlpAlarmUserDefined 4 }
tlpAlarmUserDefined05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 5 is in alarm."
::= { tlpAlarmUserDefined 5 }
tlpAlarmUserDefined06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 6 is in alarm."
::= { tlpAlarmUserDefined 6 }
tlpAlarmUserDefined07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 7 is in alarm."
::= { tlpAlarmUserDefined 7 }
tlpAlarmUserDefined08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 8 is in alarm."
::= { tlpAlarmUserDefined 8 }
tlpAlarmUserDefined09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 9 is in alarm."
::= { tlpAlarmUserDefined 9 }
tlpAlarmUserDefined10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 10 is in alarm."
::= { tlpAlarmUserDefined 10 }
tlpAlarmUserDefined11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 11 is in alarm."
::= { tlpAlarmUserDefined 11 }
tlpAlarmUserDefined12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 12 is in alarm."
::= { tlpAlarmUserDefined 12 }
tlpAlarmUserDefined13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 13 is in alarm."
::= { tlpAlarmUserDefined 13 }
tlpAlarmUserDefined14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 14 is in alarm."
::= { tlpAlarmUserDefined 14 }
tlpAlarmUserDefined15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 15 is in alarm."
::= { tlpAlarmUserDefined 15 }
tlpAlarmUserDefined16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 16 is in alarm."
::= { tlpAlarmUserDefined 16 }
tlpAlarmUserDefined17 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 17 is in alarm."
::= { tlpAlarmUserDefined 17 }
tlpAlarmUserDefined18 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 18 is in alarm."
::= { tlpAlarmUserDefined 18 }
tlpAlarmUserDefined19 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 19 is in alarm."
::= { tlpAlarmUserDefined 19 }
tlpAlarmUserDefined20 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 20 is in alarm."
::= { tlpAlarmUserDefined 20 }
tlpAlarmUserDefined21 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 21 is in alarm."
::= { tlpAlarmUserDefined 21 }
tlpAlarmUserDefined22 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 22 is in alarm."
::= { tlpAlarmUserDefined 22 }
tlpAlarmUserDefined23 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 23 is in alarm."
::= { tlpAlarmUserDefined 23 }
tlpAlarmUserDefined24 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 24 is in alarm."
::= { tlpAlarmUserDefined 24 }
tlpAlarmUserDefined25 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 25 is in alarm."
::= { tlpAlarmUserDefined 25 }
tlpAlarmUserDefined26 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 26 is in alarm."
::= { tlpAlarmUserDefined 26 }
tlpAlarmUserDefined27 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 27 is in alarm."
::= { tlpAlarmUserDefined 27 }
tlpAlarmUserDefined28 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 28 is in alarm."
::= { tlpAlarmUserDefined 28 }
tlpAlarmUserDefined29 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 29 is in alarm."
::= { tlpAlarmUserDefined 29 }
tlpAlarmUserDefined30 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 30 is in alarm."
::= { tlpAlarmUserDefined 30 }
tlpAlarmUserDefined31 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 31 is in alarm."
::= { tlpAlarmUserDefined 31 }
tlpAlarmUserDefined32 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 32 is in alarm."
::= { tlpAlarmUserDefined 32 }
tlpAlarmUserDefined33 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 33 is in alarm."
::= { tlpAlarmUserDefined 33 }
tlpAlarmUserDefined34 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 34 is in alarm."
::= { tlpAlarmUserDefined 34 }
tlpAlarmUserDefined35 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 35 is in alarm."
::= { tlpAlarmUserDefined 35 }
tlpAlarmUserDefined36 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 36 is in alarm."
::= { tlpAlarmUserDefined 36 }
tlpAlarmUserDefined37 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 37 is in alarm."
::= { tlpAlarmUserDefined 37 }
tlpAlarmUserDefined38 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 38 is in alarm."
::= { tlpAlarmUserDefined 38 }
tlpAlarmUserDefined39 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 39 is in alarm."
::= { tlpAlarmUserDefined 39 }
tlpAlarmUserDefined40 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 40 is in alarm."
::= { tlpAlarmUserDefined 40 }
tlpAlarmUserDefined41 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 41 is in alarm."
::= { tlpAlarmUserDefined 41 }
tlpAlarmUserDefined42 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 42 is in alarm."
::= { tlpAlarmUserDefined 42 }
tlpAlarmUserDefined43 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 43 is in alarm."
::= { tlpAlarmUserDefined 43 }
tlpAlarmUserDefined44 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 44 is in alarm."
::= { tlpAlarmUserDefined 44 }
tlpAlarmUserDefined45 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 45 is in alarm."
::= { tlpAlarmUserDefined 45 }
tlpAlarmUserDefined46 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 46 is in alarm."
::= { tlpAlarmUserDefined 46 }
tlpAlarmUserDefined47 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 47 is in alarm."
::= { tlpAlarmUserDefined 47 }
tlpAlarmUserDefined48 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 48 is in alarm."
::= { tlpAlarmUserDefined 48 }
tlpAlarmUserDefined49 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 49 is in alarm."
::= { tlpAlarmUserDefined 49 }
tlpAlarmUserDefined50 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 50 is in alarm."
::= { tlpAlarmUserDefined 50 }
tlpAlarmUserDefined51 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 51 is in alarm."
::= { tlpAlarmUserDefined 51 }
tlpAlarmUserDefined52 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 52 is in alarm."
::= { tlpAlarmUserDefined 52 }
tlpAlarmUserDefined53 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 53 is in alarm."
::= { tlpAlarmUserDefined 53 }
tlpAlarmUserDefined54 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 54 is in alarm."
::= { tlpAlarmUserDefined 54 }
tlpAlarmUserDefined55 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 55 is in alarm."
::= { tlpAlarmUserDefined 55 }
tlpAlarmUserDefined56 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 56 is in alarm."
::= { tlpAlarmUserDefined 56 }
tlpAlarmUserDefined57 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 57 is in alarm."
::= { tlpAlarmUserDefined 57 }
tlpAlarmUserDefined58 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 58 is in alarm."
::= { tlpAlarmUserDefined 58 }
tlpAlarmUserDefined59 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 59 is in alarm."
::= { tlpAlarmUserDefined 59 }
tlpAlarmUserDefined60 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 60 is in alarm."
::= { tlpAlarmUserDefined 60 }
tlpAlarmUserDefined61 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 61 is in alarm."
::= { tlpAlarmUserDefined 61 }
tlpAlarmUserDefined62 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 62 is in alarm."
::= { tlpAlarmUserDefined 62 }
tlpAlarmUserDefined63 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 63 is in alarm."
::= { tlpAlarmUserDefined 63 }
tlpAlarmUserDefined64 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"User-defined event 64 is in alarm."
::= { tlpAlarmUserDefined 64 }
tlpAlarmInternalFirmwareError OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem has been encountered with the device firmware."
::= { tlpDeviceAlarms 3 }
tlpAlarmDeviceEEPROMFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A problem has been encountered with the device EEPROM."
::= { tlpDeviceAlarms 4 }
tlpUpsAlarmBatteryBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more batteries have been determined to require replacement."
::= { tlpUpsAlarms 1 }
tlpUpsAlarmOnBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ups is drawing power from the batteries."
::= { tlpUpsAlarms 2 }
tlpUpsAlarmLowBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The remaining battery charge is less than or equal to the percentage of
capacity warning specified by tlpUpsConfigBatteryCapacityThreshold."
::= { tlpUpsAlarms 3 }
tlpUpsAlarmDepletedBattery OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ups will be unable to sustain the present load when and if
the utility power is lost."
::= { tlpUpsAlarms 4 }
tlpUpsAlarmTempBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A temperature is out of tolerance."
::= { tlpUpsAlarms 5 }
tlpUpsAlarmInputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An input condition is out of tolerance."
::= { tlpUpsAlarms 6 }
tlpUpsAlarmOutputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An output condition (other than OutputOverload) is out of
tolerance."
::= { tlpUpsAlarms 7 }
tlpUpsAlarmOutputOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output load exceeds the ups output capacity."
::= { tlpUpsAlarms 8 }
tlpUpsAlarmOnBypass OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass is presently engaged on the ups."
::= { tlpUpsAlarms 9 }
tlpUpsAlarmBypassBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The Bypass is out of tolerance."
::= { tlpUpsAlarms 10 }
tlpUpsAlarmOutputOffAsRequested OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ups has shutdown as requested, i.e., the output is off."
::= { tlpUpsAlarms 11 }
tlpUpsAlarmUpsOffAsRequested OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The entire ups has shutdown as commanded."
::= { tlpUpsAlarms 12 }
tlpUpsAlarmChargerFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An uncorrected problem has been detected within the ups
charger subsystem."
::= { tlpUpsAlarms 13 }
tlpUpsAlarmOutputOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output of the ups is in the off state."
::= { tlpUpsAlarms 14 }
tlpUpsAlarmUpsOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ups is in the off state."
::= { tlpUpsAlarms 15 }
tlpUpsAlarmFanFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The failure of one or more fans in the ups has been detected."
::= { tlpUpsAlarms 16 }
tlpUpsAlarmFuseFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The failure of one or more fuses has been detected."
::= { tlpUpsAlarms 17 }
tlpUpsAlarmGeneralFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A general fault in the ups has been detected."
::= { tlpUpsAlarms 18 }
tlpUpsAlarmDiagnosticTestFailed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The result of the last diagnostic test indicates a failure."
::= { tlpUpsAlarms 19 }
tlpUpsAlarmAwaitingPower OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ups output is off and the ups is awaiting the return of
input power."
::= { tlpUpsAlarms 20 }
tlpUpsAlarmShutdownPending OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A tlpUpsShutdownAfterDelay countdown is underway."
::= { tlpUpsAlarms 21 }
tlpUpsAlarmShutdownImminent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ups will turn off power to the load in less than 5 seconds;
this may be either a timed shutdown or a low battery shutdown."
::= { tlpUpsAlarms 22 }
tlpUpsAlarmLoadLevelAboveThreshold OBJECT IDENTIFIER
::= { tlpUpsAlarms 23 }
tlpUpsAlarmLoadLevelAboveThresholdTotal OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The total load (output utilization) level is above the designated threshold."
::= { tlpUpsAlarmLoadLevelAboveThreshold 1 }
tlpUpsAlarmLoadLevelAboveThresholdPhase1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load (output utilization) level on phase 1 exceeds load limits."
::= { tlpUpsAlarmLoadLevelAboveThreshold 2 }
tlpUpsAlarmLoadLevelAboveThresholdPhase2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load (output utilization) level on phase 2 exceeds load limits."
::= { tlpUpsAlarmLoadLevelAboveThreshold 3 }
tlpUpsAlarmLoadLevelAboveThresholdPhase3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load (output utilization) level on phase 3 exceeds load limits."
::= { tlpUpsAlarmLoadLevelAboveThreshold 4 }
tlpUpsAlarmOutputCurrentChanged OBJECT-IDENTITY
STATUS deprecated
DESCRIPTION
"The output current changed from its last known value."
::= { tlpUpsAlarms 24 }
tlpUpsAlarmBatteryAgeAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more batteries have been determined to require replacement."
::= { tlpUpsAlarms 25 }
tlpUpsAlarmLoadOff OBJECT IDENTIFIER
::= { tlpUpsAlarms 26 }
tlpUpsAlarmLoadOff01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 1 is off."
::= { tlpUpsAlarmLoadOff 1 }
tlpUpsAlarmLoadOff02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 2 is off."
::= { tlpUpsAlarmLoadOff 2 }
tlpUpsAlarmLoadOff03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 3 is off."
::= { tlpUpsAlarmLoadOff 3 }
tlpUpsAlarmLoadOff04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 4 is off."
::= { tlpUpsAlarmLoadOff 4 }
tlpUpsAlarmLoadOff05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 5 is off."
::= { tlpUpsAlarmLoadOff 5 }
tlpUpsAlarmLoadOff06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 6 is off."
::= { tlpUpsAlarmLoadOff 6 }
tlpUpsAlarmLoadOff07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 7 is off."
::= { tlpUpsAlarmLoadOff 7 }
tlpUpsAlarmLoadOff08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 8 is off."
::= { tlpUpsAlarmLoadOff 8 }
tlpUpsAlarmLoadOff09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 9 is off."
::= { tlpUpsAlarmLoadOff 9 }
tlpUpsAlarmLoadOff10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 10 is off."
::= { tlpUpsAlarmLoadOff 10 }
tlpUpsAlarmLoadOff11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 11 is off."
::= { tlpUpsAlarmLoadOff 11 }
tlpUpsAlarmLoadOff12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 12 is off."
::= { tlpUpsAlarmLoadOff 12 }
tlpUpsAlarmLoadOff13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 13 is off."
::= { tlpUpsAlarmLoadOff 13 }
tlpUpsAlarmLoadOff14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 14 is off."
::= { tlpUpsAlarmLoadOff 14 }
tlpUpsAlarmLoadOff15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 15 is off."
::= { tlpUpsAlarmLoadOff 15 }
tlpUpsAlarmLoadOff16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 16 is off."
::= { tlpUpsAlarmLoadOff 16 }
tlpUpsAlarmLoadOff17 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 17 is off."
::= { tlpUpsAlarmLoadOff 17 }
tlpUpsAlarmLoadOff18 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 18 is off."
::= { tlpUpsAlarmLoadOff 18 }
tlpUpsAlarmLoadOff19 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 19 is off."
::= { tlpUpsAlarmLoadOff 19 }
tlpUpsAlarmLoadOff20 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 20 is off."
::= { tlpUpsAlarmLoadOff 20 }
tlpUpsAlarmLoadOff21 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 21 is off."
::= { tlpUpsAlarmLoadOff 21 }
tlpUpsAlarmLoadOff22 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 22 is off."
::= { tlpUpsAlarmLoadOff 22 }
tlpUpsAlarmLoadOff23 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 23 is off."
::= { tlpUpsAlarmLoadOff 23 }
tlpUpsAlarmLoadOff24 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 24 is off."
::= { tlpUpsAlarmLoadOff 24 }
tlpUpsAlarmLoadOff25 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 25 is off."
::= { tlpUpsAlarmLoadOff 25 }
tlpUpsAlarmLoadOff26 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 26 is off."
::= { tlpUpsAlarmLoadOff 26 }
tlpUpsAlarmLoadOff27 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 27 is off."
::= { tlpUpsAlarmLoadOff 27 }
tlpUpsAlarmLoadOff28 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 28 is off."
::= { tlpUpsAlarmLoadOff 28 }
tlpUpsAlarmLoadOff29 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 29 is off."
::= { tlpUpsAlarmLoadOff 29 }
tlpUpsAlarmLoadOff30 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 30 is off."
::= { tlpUpsAlarmLoadOff 30 }
tlpUpsAlarmLoadOff31 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 31 is off."
::= { tlpUpsAlarmLoadOff 31 }
tlpUpsAlarmLoadOff32 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 32 is off."
::= { tlpUpsAlarmLoadOff 32 }
tlpUpsAlarmLoadOff33 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 33 is off."
::= { tlpUpsAlarmLoadOff 33 }
tlpUpsAlarmLoadOff34 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 34 is off."
::= { tlpUpsAlarmLoadOff 34 }
tlpUpsAlarmLoadOff35 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 35 is off."
::= { tlpUpsAlarmLoadOff 35 }
tlpUpsAlarmLoadOff36 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 36 is off."
::= { tlpUpsAlarmLoadOff 36 }
tlpUpsAlarmLoadOff37 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 37 is off."
::= { tlpUpsAlarmLoadOff 37 }
tlpUpsAlarmLoadOff38 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 38 is off."
::= { tlpUpsAlarmLoadOff 38 }
tlpUpsAlarmLoadOff39 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 39 is off."
::= { tlpUpsAlarmLoadOff 39 }
tlpUpsAlarmLoadOff40 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 40 is off."
::= { tlpUpsAlarmLoadOff 40 }
tlpUpsAlarmLoadOff41 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 41 is off."
::= { tlpUpsAlarmLoadOff 41 }
tlpUpsAlarmLoadOff42 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 42 is off."
::= { tlpUpsAlarmLoadOff 42 }
tlpUpsAlarmLoadOff43 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 43 is off."
::= { tlpUpsAlarmLoadOff 43 }
tlpUpsAlarmLoadOff44 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 44 is off."
::= { tlpUpsAlarmLoadOff 44 }
tlpUpsAlarmLoadOff45 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 45 is off."
::= { tlpUpsAlarmLoadOff 45 }
tlpUpsAlarmLoadOff46 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 46 is off."
::= { tlpUpsAlarmLoadOff 46 }
tlpUpsAlarmLoadOff47 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 47 is off."
::= { tlpUpsAlarmLoadOff 47 }
tlpUpsAlarmLoadOff48 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 48 is off."
::= { tlpUpsAlarmLoadOff 48 }
tlpUpsAlarmCurrentAboveThreshold OBJECT IDENTIFIER
::= { tlpUpsAlarms 27 }
tlpUpsAlarmCurrentAboveThreshold1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 1 or l1-l2 exceeds load limits."
::= { tlpUpsAlarmCurrentAboveThreshold 1 }
tlpUpsAlarmCurrentAboveThreshold2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 2 or l2-l3 exceeds load limits."
::= { tlpUpsAlarmCurrentAboveThreshold 2 }
tlpUpsAlarmCurrentAboveThreshold3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 3 or l3-l1 exceeds load limits."
::= { tlpUpsAlarmCurrentAboveThreshold 3 }
tlpUpsAlarmCurrentAboveThreshold4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l1-n exceeds load limits."
::= { tlpUpsAlarmCurrentAboveThreshold 4 }
tlpUpsAlarmCurrentAboveThreshold5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l2-n exceeds load limits."
::= { tlpUpsAlarmCurrentAboveThreshold 5 }
tlpUpsAlarmCurrentAboveThreshold6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l3-n exceeds load limits."
::= { tlpUpsAlarmCurrentAboveThreshold 6 }
tlpUpsAlarmRuntimeBelowWarningLevel OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery seconds remaining is below warning level."
::= { tlpUpsAlarms 28 }
tlpUpsAlarmBusStartVoltageLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter start up bus voltage is too low."
::= { tlpUpsAlarms 29 }
tlpUpsAlarmBusOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage is too high."
::= { tlpUpsAlarms 30 }
tlpUpsAlarmBusUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage is too low."
::= { tlpUpsAlarms 31 }
tlpUpsAlarmBusVoltageUnbalanced OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage is not balanced."
::= { tlpUpsAlarms 32 }
tlpUpsAlarmInverterSoftStartBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter bus voltage cannot reach desired voltage within a
specified duration."
::= { tlpUpsAlarms 33 }
tlpUpsAlarmInverterOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter voltage is too high."
::= { tlpUpsAlarms 34 }
tlpUpsAlarmInverterUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter voltage is too low."
::= { tlpUpsAlarms 35 }
tlpUpsAlarmInverterCircuitBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter output is shorted."
::= { tlpUpsAlarms 36 }
tlpUpsAlarmBatteryOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery voltage is too high."
::= { tlpUpsAlarms 37 }
tlpUpsAlarmBatteryUnderVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery voltage is too low."
::= { tlpUpsAlarms 38 }
tlpUpsAlarmSiteWiringFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The utility input wiring is faulty."
::= { tlpUpsAlarms 39 }
tlpUpsAlarmOverTemperatureProtection OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The over temperature protection is activated."
::= { tlpUpsAlarms 40 }
tlpUpsAlarmOverCharged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The ups is over charged."
::= { tlpUpsAlarms 41 }
tlpUpsAlarmEPOActive OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The EPO is currently activated."
::= { tlpUpsAlarms 42 }
tlpUpsAlarmBypassFrequencyBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The bypass frequency is out of tolerance."
::= { tlpUpsAlarms 43 }
tlpUpsAlarmExternalSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more external smart batteries have been determined to require
replacement."
::= { tlpUpsAlarms 44 }
tlpUpsAlarmExternalNonSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more external non-smart batteries have been determined to require
replacement."
::= { tlpUpsAlarms 45 }
tlpUpsAlarmInternalSmartBatteryCommLost OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Communications with the internal smart batteries was lost."
::= { tlpUpsAlarms 46 }
tlpUpsAlarmLoadsNotAllOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One of more loads are not on."
::= { tlpUpsAlarms 47 }
tlpUpsAlarmBatteryTemperatureHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery temperature is high."
::= { tlpUpsAlarms 48 }
tlpUpsAlarmBatteryTemperatureLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery temperature is low."
::= { tlpUpsAlarms 49 }
tlpUpsAlarmBatteryDisconnected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery disconnected."
::= { tlpUpsAlarms 50 }
tlpUpsAlarmBatteryTemperatureSensorDisconnected OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The battery temperature sensor disconnected."
::= { tlpUpsAlarms 51 }
tlpUpsAlarmTemperatureDerating OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Power derating due to high environment temperature."
::= { tlpUpsAlarms 52 }
tlpUpsAlarmInputContact OBJECT IDENTIFIER
::= { tlpUpsAlarms 53 }
tlpUpsAlarmInputContact1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input contact 1 in alarm."
::= { tlpUpsAlarmInputContact 1 }
tlpUpsAlarmOutputContact OBJECT IDENTIFIER
::= { tlpUpsAlarms 54 }
tlpUpsAlarmOutputContact1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 1 in alarm."
::= { tlpUpsAlarmOutputContact 1 }
tlpUpsAlarmOutputContact2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 2 in alarm."
::= { tlpUpsAlarmOutputContact 2 }
tlpUpsAlarmOutputContact3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 3 in alarm."
::= { tlpUpsAlarmOutputContact 3 }
tlpUpsAlarmOutputContact4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 4 in alarm."
::= { tlpUpsAlarmOutputContact 4 }
tlpUpsAlarmOutputContact5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 5 in alarm."
::= { tlpUpsAlarmOutputContact 5 }
tlpUpsAlarmOutputContact6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 6 in alarm."
::= { tlpUpsAlarmOutputContact 6 }
tlpUpsAlarmCurrentBelowThreshold OBJECT IDENTIFIER
::= { tlpUpsAlarms 55 }
tlpUpsAlarmCurrentBelowThreshold1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 1 or l1-l2 is below load limits."
::= { tlpUpsAlarmCurrentBelowThreshold 1 }
tlpUpsAlarmCurrentBelowThreshold2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 2 or l2-l3 is below load limits."
::= { tlpUpsAlarmCurrentBelowThreshold 2 }
tlpUpsAlarmCurrentBelowThreshold3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 3 or l3-l1 is below load limits."
::= { tlpUpsAlarmCurrentBelowThreshold 3 }
tlpUpsAlarmCurrentBelowThreshold4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l1-n is below load limits."
::= { tlpUpsAlarmCurrentBelowThreshold 4 }
tlpUpsAlarmCurrentBelowThreshold5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l2-n is below load limits."
::= { tlpUpsAlarmCurrentBelowThreshold 5 }
tlpUpsAlarmCurrentBelowThreshold6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l3-n is below load limits."
::= { tlpUpsAlarmCurrentBelowThreshold 6 }
tlpPduAlarmLoadLevelAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load level is above the designated threshold."
::= { tlpPduAlarms 1 }
tlpPduAlarmInputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An input condition is out of tolerance."
::= { tlpPduAlarms 2 }
tlpPduAlarmOutputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An output condition (other than OutputOverload) is out of
tolerance."
::= { tlpPduAlarms 3 }
tlpPduAlarmOutputOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output load exceeds the pdu output capacity."
::= { tlpPduAlarms 4 }
tlpPduAlarmOutputOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output of the pdu is in the off state."
::= { tlpPduAlarms 5 }
tlpPduAlarmLoadOff OBJECT IDENTIFIER
::= { tlpPduAlarms 6 }
tlpPduAlarmLoadOff01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 1 is off."
::= { tlpPduAlarmLoadOff 1 }
tlpPduAlarmLoadOff02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 2 is off."
::= { tlpPduAlarmLoadOff 2 }
tlpPduAlarmLoadOff03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 3 is off."
::= { tlpPduAlarmLoadOff 3 }
tlpPduAlarmLoadOff04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 4 is off."
::= { tlpPduAlarmLoadOff 4 }
tlpPduAlarmLoadOff05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 5 is off."
::= { tlpPduAlarmLoadOff 5 }
tlpPduAlarmLoadOff06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 6 is off."
::= { tlpPduAlarmLoadOff 6 }
tlpPduAlarmLoadOff07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 7 is off."
::= { tlpPduAlarmLoadOff 7 }
tlpPduAlarmLoadOff08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 8 is off."
::= { tlpPduAlarmLoadOff 8 }
tlpPduAlarmLoadOff09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 9 is off."
::= { tlpPduAlarmLoadOff 9 }
tlpPduAlarmLoadOff10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 10 is off."
::= { tlpPduAlarmLoadOff 10 }
tlpPduAlarmLoadOff11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 11 is off."
::= { tlpPduAlarmLoadOff 11 }
tlpPduAlarmLoadOff12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 12 is off."
::= { tlpPduAlarmLoadOff 12 }
tlpPduAlarmLoadOff13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 13 is off."
::= { tlpPduAlarmLoadOff 13 }
tlpPduAlarmLoadOff14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 14 is off."
::= { tlpPduAlarmLoadOff 14 }
tlpPduAlarmLoadOff15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 15 is off."
::= { tlpPduAlarmLoadOff 15 }
tlpPduAlarmLoadOff16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 16 is off."
::= { tlpPduAlarmLoadOff 16 }
tlpPduAlarmLoadOff17 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 17 is off."
::= { tlpPduAlarmLoadOff 17 }
tlpPduAlarmLoadOff18 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 18 is off."
::= { tlpPduAlarmLoadOff 18 }
tlpPduAlarmLoadOff19 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 19 is off."
::= { tlpPduAlarmLoadOff 19 }
tlpPduAlarmLoadOff20 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 20 is off."
::= { tlpPduAlarmLoadOff 20 }
tlpPduAlarmLoadOff21 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 21 is off."
::= { tlpPduAlarmLoadOff 21 }
tlpPduAlarmLoadOff22 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 22 is off."
::= { tlpPduAlarmLoadOff 22 }
tlpPduAlarmLoadOff23 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 23 is off."
::= { tlpPduAlarmLoadOff 23 }
tlpPduAlarmLoadOff24 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 24 is off."
::= { tlpPduAlarmLoadOff 24 }
tlpPduAlarmLoadOff25 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 25 is off."
::= { tlpPduAlarmLoadOff 25 }
tlpPduAlarmLoadOff26 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 26 is off."
::= { tlpPduAlarmLoadOff 26 }
tlpPduAlarmLoadOff27 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 27 is off."
::= { tlpPduAlarmLoadOff 27 }
tlpPduAlarmLoadOff28 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 28 is off."
::= { tlpPduAlarmLoadOff 28 }
tlpPduAlarmLoadOff29 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 29 is off."
::= { tlpPduAlarmLoadOff 29 }
tlpPduAlarmLoadOff30 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 30 is off."
::= { tlpPduAlarmLoadOff 30 }
tlpPduAlarmLoadOff31 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 31 is off."
::= { tlpPduAlarmLoadOff 31 }
tlpPduAlarmLoadOff32 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 32 is off."
::= { tlpPduAlarmLoadOff 32 }
tlpPduAlarmLoadOff33 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 33 is off."
::= { tlpPduAlarmLoadOff 33 }
tlpPduAlarmLoadOff34 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 34 is off."
::= { tlpPduAlarmLoadOff 34 }
tlpPduAlarmLoadOff35 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 35 is off."
::= { tlpPduAlarmLoadOff 35 }
tlpPduAlarmLoadOff36 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 36 is off."
::= { tlpPduAlarmLoadOff 36 }
tlpPduAlarmLoadOff37 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 37 is off."
::= { tlpPduAlarmLoadOff 37 }
tlpPduAlarmLoadOff38 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 38 is off."
::= { tlpPduAlarmLoadOff 38 }
tlpPduAlarmLoadOff39 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 39 is off."
::= { tlpPduAlarmLoadOff 39 }
tlpPduAlarmLoadOff40 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 40 is off."
::= { tlpPduAlarmLoadOff 40 }
tlpPduAlarmLoadOff41 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 41 is off."
::= { tlpPduAlarmLoadOff 41 }
tlpPduAlarmLoadOff42 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 42 is off."
::= { tlpPduAlarmLoadOff 42 }
tlpPduAlarmLoadOff43 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 43 is off."
::= { tlpPduAlarmLoadOff 43 }
tlpPduAlarmLoadOff44 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 44 is off."
::= { tlpPduAlarmLoadOff 44 }
tlpPduAlarmLoadOff45 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 45 is off."
::= { tlpPduAlarmLoadOff 45 }
tlpPduAlarmLoadOff46 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 46 is off."
::= { tlpPduAlarmLoadOff 46 }
tlpPduAlarmLoadOff47 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 47 is off."
::= { tlpPduAlarmLoadOff 47 }
tlpPduAlarmLoadOff48 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 48 is off."
::= { tlpPduAlarmLoadOff 48 }
tlpPduAlarmCircuitBreakerOpen OBJECT IDENTIFIER
::= { tlpPduAlarms 7 }
tlpPduAlarmCircuitBreakerOpen01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 1 is open."
::= { tlpPduAlarmCircuitBreakerOpen 1 }
tlpPduAlarmCircuitBreakerOpen02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 2 is open."
::= { tlpPduAlarmCircuitBreakerOpen 2 }
tlpPduAlarmCircuitBreakerOpen03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 3 is open."
::= { tlpPduAlarmCircuitBreakerOpen 3 }
tlpPduAlarmCircuitBreakerOpen04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 4 is open."
::= { tlpPduAlarmCircuitBreakerOpen 4 }
tlpPduAlarmCircuitBreakerOpen05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 5 is open."
::= { tlpPduAlarmCircuitBreakerOpen 5 }
tlpPduAlarmCircuitBreakerOpen06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 6 is open."
::= { tlpPduAlarmCircuitBreakerOpen 6 }
tlpPduAlarmCurrentAboveThreshold OBJECT IDENTIFIER
::= { tlpPduAlarms 8 }
tlpPduAlarmCurrentAboveThreshold1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 1 or l1-l2 exceeds load limits."
::= { tlpPduAlarmCurrentAboveThreshold 1 }
tlpPduAlarmCurrentAboveThreshold2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 2 or l2-l3 exceeds load limits."
::= { tlpPduAlarmCurrentAboveThreshold 2 }
tlpPduAlarmCurrentAboveThreshold3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 3 or l3-l1 exceeds load limits."
::= { tlpPduAlarmCurrentAboveThreshold 3 }
tlpPduAlarmCurrentAboveThreshold4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l1-n exceeds load limits."
::= { tlpPduAlarmCurrentAboveThreshold 4 }
tlpPduAlarmCurrentAboveThreshold5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l2-n exceeds load limits."
::= { tlpPduAlarmCurrentAboveThreshold 5 }
tlpPduAlarmCurrentAboveThreshold6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l3-n exceeds load limits."
::= { tlpPduAlarmCurrentAboveThreshold 6 }
tlpPduAlarmLoadsNotAllOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One of more loads are not on."
::= { tlpPduAlarms 9 }
tlpPduAlarmLoadLevelBelowThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load level is below the designated threshold."
::= { tlpPduAlarms 10 }
tlpPduAlarmCurrentBelowThreshold OBJECT IDENTIFIER
::= { tlpPduAlarms 11 }
tlpPduAlarmCurrentBelowThreshold1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 1 or l1-l2 is below load limits."
::= { tlpPduAlarmCurrentBelowThreshold 1 }
tlpPduAlarmCurrentBelowThreshold2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 2 or l2-l3 is below load limits."
::= { tlpPduAlarmCurrentBelowThreshold 2 }
tlpPduAlarmCurrentBelowThreshold3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 3 or l3-l1 is below load limits."
::= { tlpPduAlarmCurrentBelowThreshold 3 }
tlpPduAlarmCurrentBelowThreshold4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l1-n is below load limits."
::= { tlpPduAlarmCurrentBelowThreshold 4 }
tlpPduAlarmCurrentBelowThreshold5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l2-n is below load limits."
::= { tlpPduAlarmCurrentBelowThreshold 5 }
tlpPduAlarmCurrentBelowThreshold6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l3-n is below load limits."
::= { tlpPduAlarmCurrentBelowThreshold 6 }
tlpPduAlarmThdOutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The thd value is out of range."
::= { tlpPduAlarms 12 }
tlpPduAlarmGeneralFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A general fault in the pdu has been detected."
::= { tlpPduAlarms 13 }
tlpPduAlarmOutletOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more outlets is above load limits."
::= { tlpPduAlarms 14 }
tlpEnvAlarmTemperatureBeyondLimits OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The temperature exceeds limits."
::= { tlpEnvAlarms 1 }
tlpEnvAlarmHumidityBeyondLimits OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The humidity exceeds limits."
::= { tlpEnvAlarms 2 }
tlpEnvAlarmInputContact OBJECT IDENTIFIER
::= { tlpEnvAlarms 3 }
tlpEnvAlarmInputContact01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input contact 1 is in alarm."
::= { tlpEnvAlarmInputContact 1 }
tlpEnvAlarmInputContact02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input contact 2 is in alarm."
::= { tlpEnvAlarmInputContact 2 }
tlpEnvAlarmInputContact03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input contact 3 is in alarm."
::= { tlpEnvAlarmInputContact 3 }
tlpEnvAlarmInputContact04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input contact 4 is in alarm."
::= { tlpEnvAlarmInputContact 4 }
tlpEnvAlarmOutputContact OBJECT IDENTIFIER
::= { tlpEnvAlarms 4 }
tlpEnvAlarmOutputContact01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 1 is in alarm."
::= { tlpEnvAlarmOutputContact 1 }
tlpEnvAlarmOutputContact02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 2 is in alarm."
::= { tlpEnvAlarmOutputContact 2 }
tlpEnvAlarmOutputContact03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 3 is in alarm."
::= { tlpEnvAlarmOutputContact 3 }
tlpEnvAlarmOutputContact04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Output contact 4 is in alarm."
::= { tlpEnvAlarmOutputContact 4 }
tlpAtsAlarmOutage OBJECT IDENTIFIER
::= { tlpAtsAlarms 1 }
tlpAtsAlarmSource1Outage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input on source 1 is not present. For atss with the designation
of primary and secondary, this alarm denotes input on the primary
source is not present."
::= { tlpAtsAlarmOutage 1 }
tlpAtsAlarmSource2Outage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Input on source 2 is not present. For atss with the designation
of primary and secondary, this alarm denotes input on the secondary
source is not present."
::= { tlpAtsAlarmOutage 2 }
tlpAtsAlarmTemperature OBJECT IDENTIFIER
::= { tlpAtsAlarms 2 }
tlpAtsAlarmDeviceTemperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The device temperature is out of tolerance."
::= { tlpAtsAlarmTemperature 1 }
tlpAtsAlarmSource1Temperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The source 1 temperature is out of tolerance."
::= { tlpAtsAlarmTemperature 2 }
tlpAtsAlarmSource2Temperature OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The source 2 temperature is out of tolerance."
::= { tlpAtsAlarmTemperature 3 }
tlpAtsAlarmLoadLevelAboveThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load level is above the designated threshold."
::= { tlpAtsAlarms 3 }
tlpAtsAlarmInputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An input condition is out of tolerance."
::= { tlpAtsAlarms 4 }
tlpAtsAlarmOutputBad OBJECT-IDENTITY
STATUS current
DESCRIPTION
"An output condition (other than OutputOverload) is out of
tolerance."
::= { tlpAtsAlarms 5 }
tlpAtsAlarmOutputOverload OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output load exceeds the ats output capacity."
::= { tlpAtsAlarms 6 }
tlpAtsAlarmOutputOff OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output of the ats is in the off state."
::= { tlpAtsAlarms 7 }
tlpAtsAlarmLoadOff OBJECT IDENTIFIER
::= { tlpAtsAlarms 8 }
tlpAtsAlarmLoadOff01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 1 is off."
::= { tlpAtsAlarmLoadOff 1 }
tlpAtsAlarmLoadOff02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 2 is off."
::= { tlpAtsAlarmLoadOff 2 }
tlpAtsAlarmLoadOff03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 3 is off."
::= { tlpAtsAlarmLoadOff 3 }
tlpAtsAlarmLoadOff04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 4 is off."
::= { tlpAtsAlarmLoadOff 4 }
tlpAtsAlarmLoadOff05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 5 is off."
::= { tlpAtsAlarmLoadOff 5 }
tlpAtsAlarmLoadOff06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 6 is off."
::= { tlpAtsAlarmLoadOff 6 }
tlpAtsAlarmLoadOff07 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 7 is off."
::= { tlpAtsAlarmLoadOff 7 }
tlpAtsAlarmLoadOff08 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 8 is off."
::= { tlpAtsAlarmLoadOff 8 }
tlpAtsAlarmLoadOff09 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 9 is off."
::= { tlpAtsAlarmLoadOff 9 }
tlpAtsAlarmLoadOff10 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 10 is off."
::= { tlpAtsAlarmLoadOff 10 }
tlpAtsAlarmLoadOff11 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 11 is off."
::= { tlpAtsAlarmLoadOff 11 }
tlpAtsAlarmLoadOff12 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 12 is off."
::= { tlpAtsAlarmLoadOff 12 }
tlpAtsAlarmLoadOff13 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 13 is off."
::= { tlpAtsAlarmLoadOff 13 }
tlpAtsAlarmLoadOff14 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 14 is off."
::= { tlpAtsAlarmLoadOff 14 }
tlpAtsAlarmLoadOff15 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 15 is off."
::= { tlpAtsAlarmLoadOff 15 }
tlpAtsAlarmLoadOff16 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 16 is off."
::= { tlpAtsAlarmLoadOff 16 }
tlpAtsAlarmLoadOff17 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 17 is off."
::= { tlpAtsAlarmLoadOff 17 }
tlpAtsAlarmLoadOff18 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 18 is off."
::= { tlpAtsAlarmLoadOff 18 }
tlpAtsAlarmLoadOff19 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 19 is off."
::= { tlpAtsAlarmLoadOff 19 }
tlpAtsAlarmLoadOff20 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 20 is off."
::= { tlpAtsAlarmLoadOff 20 }
tlpAtsAlarmLoadOff21 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 21 is off."
::= { tlpAtsAlarmLoadOff 21 }
tlpAtsAlarmLoadOff22 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 22 is off."
::= { tlpAtsAlarmLoadOff 22 }
tlpAtsAlarmLoadOff23 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 23 is off."
::= { tlpAtsAlarmLoadOff 23 }
tlpAtsAlarmLoadOff24 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 24 is off."
::= { tlpAtsAlarmLoadOff 24 }
tlpAtsAlarmLoadOff25 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 25 is off."
::= { tlpAtsAlarmLoadOff 25 }
tlpAtsAlarmLoadOff26 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 26 is off."
::= { tlpAtsAlarmLoadOff 26 }
tlpAtsAlarmLoadOff27 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 27 is off."
::= { tlpAtsAlarmLoadOff 27 }
tlpAtsAlarmLoadOff28 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 28 is off."
::= { tlpAtsAlarmLoadOff 28 }
tlpAtsAlarmLoadOff29 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 29 is off."
::= { tlpAtsAlarmLoadOff 29 }
tlpAtsAlarmLoadOff30 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 30 is off."
::= { tlpAtsAlarmLoadOff 30 }
tlpAtsAlarmLoadOff31 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 31 is off."
::= { tlpAtsAlarmLoadOff 31 }
tlpAtsAlarmLoadOff32 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 32 is off."
::= { tlpAtsAlarmLoadOff 32 }
tlpAtsAlarmLoadOff33 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 33 is off."
::= { tlpAtsAlarmLoadOff 33 }
tlpAtsAlarmLoadOff34 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 34 is off."
::= { tlpAtsAlarmLoadOff 34 }
tlpAtsAlarmLoadOff35 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 35 is off."
::= { tlpAtsAlarmLoadOff 35 }
tlpAtsAlarmLoadOff36 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 36 is off."
::= { tlpAtsAlarmLoadOff 36 }
tlpAtsAlarmLoadOff37 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 37 is off."
::= { tlpAtsAlarmLoadOff 37 }
tlpAtsAlarmLoadOff38 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 38 is off."
::= { tlpAtsAlarmLoadOff 38 }
tlpAtsAlarmLoadOff39 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 39 is off."
::= { tlpAtsAlarmLoadOff 39 }
tlpAtsAlarmLoadOff40 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 40 is off."
::= { tlpAtsAlarmLoadOff 40 }
tlpAtsAlarmLoadOff41 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 41 is off."
::= { tlpAtsAlarmLoadOff 41 }
tlpAtsAlarmLoadOff42 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 42 is off."
::= { tlpAtsAlarmLoadOff 42 }
tlpAtsAlarmLoadOff43 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 43 is off."
::= { tlpAtsAlarmLoadOff 43 }
tlpAtsAlarmLoadOff44 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 44 is off."
::= { tlpAtsAlarmLoadOff 44 }
tlpAtsAlarmLoadOff45 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 45 is off."
::= { tlpAtsAlarmLoadOff 45 }
tlpAtsAlarmLoadOff46 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 46 is off."
::= { tlpAtsAlarmLoadOff 46 }
tlpAtsAlarmLoadOff47 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 47 is off."
::= { tlpAtsAlarmLoadOff 47 }
tlpAtsAlarmLoadOff48 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Load 48 is off."
::= { tlpAtsAlarmLoadOff 48 }
tlpAtsAlarmCircuitBreakerOpen OBJECT IDENTIFIER
::= { tlpAtsAlarms 9 }
tlpAtsAlarmCircuitBreakerOpen01 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 1 is open."
::= { tlpAtsAlarmCircuitBreakerOpen 1 }
tlpAtsAlarmCircuitBreakerOpen02 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 2 is open."
::= { tlpAtsAlarmCircuitBreakerOpen 2 }
tlpAtsAlarmCircuitBreakerOpen03 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 3 is open."
::= { tlpAtsAlarmCircuitBreakerOpen 3 }
tlpAtsAlarmCircuitBreakerOpen04 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 4 is open."
::= { tlpAtsAlarmCircuitBreakerOpen 4 }
tlpAtsAlarmCircuitBreakerOpen05 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 5 is open."
::= { tlpAtsAlarmCircuitBreakerOpen 5 }
tlpAtsAlarmCircuitBreakerOpen06 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Circuit breaker 6 is open."
::= { tlpAtsAlarmCircuitBreakerOpen 6 }
tlpAtsAlarmCurrentAboveThreshold OBJECT IDENTIFIER
::= { tlpAtsAlarms 10 }
tlpAtsAlarmCurrentAboveThreshold1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 1 or l1-l2 exceeds load limits."
::= { tlpAtsAlarmCurrentAboveThreshold 1 }
tlpAtsAlarmCurrentAboveThreshold2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 2 or l2-l3 exceeds load limits."
::= { tlpAtsAlarmCurrentAboveThreshold 2 }
tlpAtsAlarmCurrentAboveThreshold3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 3 or l3-l1 exceeds load limits."
::= { tlpAtsAlarmCurrentAboveThreshold 3 }
tlpAtsAlarmCurrentAboveThreshold4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l1-n exceeds load limits."
::= { tlpAtsAlarmCurrentAboveThreshold 4 }
tlpAtsAlarmCurrentAboveThreshold5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l2-n exceeds load limits."
::= { tlpAtsAlarmCurrentAboveThreshold 5 }
tlpAtsAlarmCurrentAboveThreshold6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l3-n exceeds load limits."
::= { tlpAtsAlarmCurrentAboveThreshold 6 }
tlpAtsAlarmLoadsNotAllOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One of more loads are not on."
::= { tlpAtsAlarms 11 }
tlpAtsAlarmGeneralFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A general fault in the ats has been detected."
::= { tlpAtsAlarms 12 }
tlpAtsAlarmVoltage OBJECT IDENTIFIER
::= { tlpAtsAlarms 13 }
tlpAtsAlarmOverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The input voltage is out of tolerance."
::= { tlpAtsAlarmVoltage 1 }
tlpAtsAlarmSource1OverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The voltage on source 1 is out of tolerance."
::= { tlpAtsAlarmVoltage 2 }
tlpAtsAlarmSource2OverVoltage OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The voltage on source 2 is out of tolerance."
::= { tlpAtsAlarmVoltage 3 }
tlpAtsAlarmFrequency OBJECT IDENTIFIER
::= { tlpAtsAlarms 14 }
tlpAtsAlarmSource1InvalidFrequency OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The voltage on source 1 is out of tolerance."
::= { tlpAtsAlarmFrequency 1 }
tlpAtsAlarmSource2InvalidFrequency OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The voltage on source 2 is out of tolerance."
::= { tlpAtsAlarmFrequency 2 }
tlpAtsAlarmLoadLevelBelowThreshold OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The load level is below the designated threshold."
::= { tlpAtsAlarms 15 }
tlpAtsAlarmCurrentBelowThreshold OBJECT IDENTIFIER
::= { tlpAtsAlarms 16 }
tlpAtsAlarmCurrentBelowThreshold1 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 1 or l1-l2 is below load limits."
::= { tlpAtsAlarmCurrentBelowThreshold 1 }
tlpAtsAlarmCurrentBelowThreshold2 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 2 or l2-l3 is below load limits."
::= { tlpAtsAlarmCurrentBelowThreshold 2 }
tlpAtsAlarmCurrentBelowThreshold3 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on phase 3 or l3-l1 is below load limits."
::= { tlpAtsAlarmCurrentBelowThreshold 3 }
tlpAtsAlarmCurrentBelowThreshold4 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l1-n is below load limits."
::= { tlpAtsAlarmCurrentBelowThreshold 4 }
tlpAtsAlarmCurrentBelowThreshold5 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l2-n is below load limits."
::= { tlpAtsAlarmCurrentBelowThreshold 5 }
tlpAtsAlarmCurrentBelowThreshold6 OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The output current on l3-n is below load limits."
::= { tlpAtsAlarmCurrentBelowThreshold 6 }
tlpAtsAlarmThdOutOfRange OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The thd value is out of range."
::= { tlpAtsAlarms 17 }
tlpAtsAlarmOutletOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"One or more outlets is above load limits."
::= { tlpAtsAlarms 18 }
tlpCoolingAlarmSupplyAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply air sensor is in fault."
::= { tlpCoolingAlarms 1 }
tlpCoolingAlarmReturnAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The return air sensor is in fault."
::= { tlpCoolingAlarms 2 }
tlpCoolingAlarmCondenserInletAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser inlet air sensor is in fault."
::= { tlpCoolingAlarms 3 }
tlpCoolingAlarmCondenserOutletAirSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser outlet air sensor is in fault."
::= { tlpCoolingAlarms 4 }
tlpCoolingAlarmSuctionTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction temperature sensor is in fault."
::= { tlpCoolingAlarms 5 }
tlpCoolingAlarmEvaporatorTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator temperature sensor is in fault."
::= { tlpCoolingAlarms 6 }
tlpCoolingAlarmAirFilterClogged OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air filter is clogged."
::= { tlpCoolingAlarms 7 }
tlpCoolingAlarmAirFilterRunHoursViolation OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The air filter run hours was violated."
::= { tlpCoolingAlarms 8 }
tlpCoolingAlarmSuctionPressureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction pressure sensor is in fault."
::= { tlpCoolingAlarms 9 }
tlpCoolingAlarmInverterCommunicationsFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The inverter communications is in fault."
::= { tlpCoolingAlarms 10 }
tlpCoolingAlarmRemoteShutdownViaInputContact OBJECT-IDENTITY
STATUS current
DESCRIPTION
"A remote shutdown was triggered by an input contact."
::= { tlpCoolingAlarms 11 }
tlpCoolingAlarmCondensatePumpFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condensate pump is in fault."
::= { tlpCoolingAlarms 12 }
tlpCoolingAlarmLowRefrigerantStartupFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The low refrigerant startup is in fault."
::= { tlpCoolingAlarms 13 }
tlpCoolingAlarmCondenserFanFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser fan is in fault."
::= { tlpCoolingAlarms 14 }
tlpCoolingAlarmCondenserFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The condenser has failed."
::= { tlpCoolingAlarms 15 }
tlpCoolingAlarmEvaporatorCoolingFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator cooling is in fault."
::= { tlpCoolingAlarms 16 }
tlpCoolingAlarmReturnAirTempHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The return air temperature is high."
::= { tlpCoolingAlarms 17 }
tlpCoolingAlarmSupplyAirTempHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The supply air temperature is high."
::= { tlpCoolingAlarms 18 }
tlpCoolingAlarmEvaporatorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator has failed."
::= { tlpCoolingAlarms 19 }
tlpCoolingAlarmEvaporatorFreezeUp OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The evaporator is frozen."
::= { tlpCoolingAlarms 20 }
tlpCoolingAlarmDischargePressureHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The discharge pressure is high."
::= { tlpCoolingAlarms 21 }
tlpCoolingAlarmPressureGaugeFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The pressure gauge has failed."
::= { tlpCoolingAlarms 22 }
tlpCoolingAlarmDischargePressurePersistentHigh OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The discharge pressure is persistently high."
::= { tlpCoolingAlarms 23 }
tlpCoolingAlarmSuctionPressureLowStartFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Cannot start due to low suction pressure."
::= { tlpCoolingAlarms 24 }
tlpCoolingAlarmSuctionPressureLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction pressure is low."
::= { tlpCoolingAlarms 25 }
tlpCoolingAlarmSuctionPressurePersistentLow OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The suction pressure is persistently low."
::= { tlpCoolingAlarms 26 }
tlpCoolingAlarmStartupLinePressureImbalance OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The startup line pressure is in imbalance."
::= { tlpCoolingAlarms 27 }
tlpCoolingAlarmCompressorFailure OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The compressor has failed."
::= { tlpCoolingAlarms 28 }
tlpCoolingAlarmCurrentLimit OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The current is out of range."
::= { tlpCoolingAlarms 29 }
tlpCoolingAlarmWaterLeak OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Water is leaking."
::= { tlpCoolingAlarms 30 }
tlpCoolingAlarmFanUnderCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fan is under current."
::= { tlpCoolingAlarms 31 }
tlpCoolingAlarmFanOverCurrent OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The fan is over current."
::= { tlpCoolingAlarms 32 }
tlpCoolingAlarmDischargePressureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The discharge pressure sensor is in fault."
::= { tlpCoolingAlarms 33 }
tlpCoolingAlarmWaterFull OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Water is Full."
::= { tlpCoolingAlarms 34 }
tlpCoolingAlarmAutoCoolingOn OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Automatic cooling was activated to lower the temperature below the
remote set point."
::= { tlpCoolingAlarms 35 }
tlpCoolingAlarmPowerButtonPressed OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Power button was pressed on the front panel."
::= { tlpCoolingAlarms 36 }
tlpCoolingAlarmDisconnectedFromDevice OBJECT-IDENTITY
STATUS current
DESCRIPTION
"The device communications is disconnected."
::= { tlpCoolingAlarms 37 }
tlpCoolingAlarmReturnAirTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Ambient (return air) temperature sensor is in fault."
::= { tlpCoolingAlarms 38 }
tlpCoolingAlarmRemoteTemperatureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Remote temperature sensor is in fault."
::= { tlpCoolingAlarms 39 }
tlpCoolingAlarmLowPressureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Low pressure sensor is in fault."
::= { tlpCoolingAlarms 40 }
tlpCoolingAlarmHighPressureSensorFault OBJECT-IDENTITY
STATUS current
DESCRIPTION
"High pressure sensor is in fault."
::= { tlpCoolingAlarms 41 }
tlpCoolingAlarmSentrytimerTimeout OBJECT-IDENTITY
STATUS current
DESCRIPTION
"Sentry timer time out."
::= { tlpCoolingAlarms 42 }
tlpAlarmControlTable OBJECT-TYPE
SYNTAX SEQUENCE OF TlpAlarmControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"A list of alarm conditions supported for each device managed by this
agent. This table contains zero, one, or many rows depending upon the
number of available alarms managed by each device."
::= { tlpAlarmControl 1 }
tlpAlarmControlEntry OBJECT-TYPE
SYNTAX TlpAlarmControlEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"An entry containing details for a particular alarm condition."
INDEX { tlpDeviceIndex, tlpAlarmControlIndex }
::= { tlpAlarmControlTable 1 }
TlpAlarmControlEntry ::= SEQUENCE {
tlpAlarmControlIndex Unsigned32,
tlpAlarmControlDescr OBJECT IDENTIFIER,
tlpAlarmControlDetail DisplayString,
tlpAlarmControlSeverity INTEGER }
tlpAlarmControlIndex OBJECT-TYPE
SYNTAX Unsigned32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The table row index for this alarm control entry for this device. The
index of any one row represents the index of the alarm entry within the
agent system. As such, the index values for any one device is not
guaranteed to start with 1 or be numerically sequential."
::= { tlpAlarmControlEntry 1 }
tlpAlarmControlDescr OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A reference of the alarm description object. The object referenced
should not be accessible, but rather be used to provide a unique
description for the alarm condition. The object referenced will be a
well known alarm object associated with the device on which the alarm
condition is active. This will be the same object description of an
alarm when in alarm as referenced by tlpAlarmDescr."
::= { tlpAlarmControlEntry 2 }
tlpAlarmControlDetail OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"A textual description of the alarm condition. This will be the same
textual description of an alarm when in alarm as referenced by
tlpAlarmDetail."
::= { tlpAlarmControlEntry 3 }
tlpAlarmControlSeverity OBJECT-TYPE
SYNTAX INTEGER {
critical(1),
warning(2),
info(3) }
MAX-ACCESS read-write
STATUS current
DESCRIPTION
"The severity of this alarm, which can be configured as desired for
each alarm condition. This will be the same severity used when in alarm
as referenced by tlpAlarmType."
::= { tlpAlarmControlEntry 4 }
-- notifications
tlpNotificationsAlarmEntryAdded NOTIFICATION-TYPE
OBJECTS { tlpAlarmId, tlpAlarmDescr, tlpAlarmTime,
tlpAlarmTableRef, tlpAlarmTableRowRef, tlpAlarmDetail,
tlpAlarmType }
STATUS current
DESCRIPTION
"This notification is sent each time an alarm condition is inserted into
the device alarm table, tlpAlarmTable."
::= { tlpNotifications 1 }
tlpNotificationsAlarmEntryRemoved NOTIFICATION-TYPE
OBJECTS { tlpAlarmId, tlpAlarmDescr, tlpAlarmTime,
tlpAlarmTableRef, tlpAlarmTableRowRef, tlpAlarmDetail,
tlpAlarmType }
STATUS current
DESCRIPTION
"This notification is sent each time an alarm condition is removed from
the device alarm table, tlpAlarmTable."
::= { tlpNotifications 2 }
tlpNotifySystemStartup NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Used to inform another entity of an agent's startup. The varbinds that follow are:
OBJ1 = tlpAgentType
Obj1Value = The type of engine providing this data
OBJ2 = tlpAgentVersion
Obj2Value = The current version of the engine
OBJ3 = tlpAgentMAC
Obj3Value = The MAC address of the engine
OBJ4 = tlpAgentSerialNum
Obj4Value = The serial number of the web card [should be 0 on PC]
--- if this trap is extended, place all static OIDs above this mark. all objects below
--- the number of devices (tlpDeviceNumDevices) is explicit as per device for enumeration by
--- the target receiver
OBJ5 = tlpDeviceNumDevices
Obj5Value = The number of devices attached
--- The following objects will be replicated per each device:
OBJ6 = The OID for an entry of tlpDeviceManufacturer, indexed by device
Obj6Value = The device's manufacturer
OBJ7 = The OID for an entry of tlpDeviceModel, indexed by device
Obj7Value = The device's model name
OBJ8 = The OID for an entry of tlpDeviceName, indexed by device
Obj8Value = The device's display name
OBJ9 = The OID for an entry of tlpDeviceLocation, indexed by device
Obj9Value = The device's location
OBJ10 = The OID for an entry of tlpDeviceRegion, indexed by device
Obj10Value= The device's region
OBJ11 = The OID for an entry of tlpDeviceIdentProtocol, indexed by device
Obj11Value= The device's protocol (display string format)
"
::= { tlpNotifications 3 }
tlpNotifySystemShutdown NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Used to inform another entity of an agent's shutdown. The varbinds that follow are:
OBJ1 = tlpAgentType
Obj1Value = The type of engine providing this data
OBJ2 = tlpAgentVersion
Obj2Value = The current version of the engine
OBJ3 = tlpAgentMAC
Obj3Value = The MAC address of the engine
OBJ4 = tlpAgentSerialNum
Obj4Value = The serial number of the web card [should be 0 on PC]
--- if this trap is extended, place all static OIDs above this mark. all objects below
--- the number of devices (tlpDeviceNumDevices) is explicit as per device for enumeration by
--- the target receiver
OBJ5 = tlpDeviceNumDevices
Obj5Value = The number of devices attached
--- The following objects will be replicated per each device:
OBJ6 = The OID for an entry of tlpDeviceManufacturer, indexed by device
Obj6Value = The device's manufacturer
OBJ7 = The OID for an entry of tlpDeviceModel, indexed by device
Obj7Value = The device's model name
OBJ8 = The OID for an entry of tlpDeviceName, indexed by device
Obj8Value = The device's display name
OBJ9 = The OID for an entry of tlpDeviceLocation, indexed by device
Obj9Value = The device's location
OBJ10 = The OID for an entry of tlpDeviceRegion, indexed by device
Obj10Value= The device's region
OBJ11 = The OID for an entry of tlpDeviceIdentProtocol, indexed by device
Obj11Value= The device's protocol (display string format)
"
::= { tlpNotifications 4 }
tlpNotifySystemUpdate NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Used to inform another entity of an engine's startup. The varbinds that follow are:
OBJ1 = tlpAgentType
Obj1Value = The type of engine providing this data
OBJ2 = tlpAgentVersion
Obj2Value = The current version of the engine
OBJ3 = tlpAgentMAC
Obj3Value = The MAC address of the engine
OBJ4 = tlpAgentSerialNum
Obj4Value = The serial number of the web card [should be 0 on PC]
--- if this trap is extended, place all static OIDs above this mark. all objects below
--- the number of devices (tlpDeviceNumDevices) is explicit as per device for enumeration by
--- the target receiver
OBJ5 = tlpDeviceNumDevices
Obj5Value = The number of devices attached
--- The following objects will be replicated per each device:
OBJ6 = The OID for an entry of tlpDeviceManufacturer, indexed by device
Obj6Value = The device's manufacturer
OBJ7 = The OID for an entry of tlpDeviceModel, indexed by device
Obj7Value = The device's model name
OBJ8 = The OID for an entry of tlpDeviceName, indexed by device
Obj8Value = The device's display name
OBJ9 = The OID for an entry of tlpDeviceLocation, indexed by device
Obj9Value = The device's location
OBJ10 = The OID for an entry of tlpDeviceRegion, indexed by device
Obj10Value= The device's region
OBJ11 = The OID for an entry of tlpDeviceIdentProtocol, indexed by device
Obj11Value= The device's protocol (display string format)
"
::= { tlpNotifications 5 }
tlpNotifyTest NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"Used when performing a test of the system or an alert notification contact. The varbinds
that follow are:
OBJ1 = tlpAgentType
Obj1Value = The type of engine providing this data
OBJ2 = tlpAgentVersion
Obj2Value = The current version of the engine
OBJ3 = tlpAgentMAC
Obj3Value = The MAC address of the engine
OBJ4 = tlpAgentSerialNum
Obj4Value = The serial number of the web card [should be 0 on PC]
"
::= { tlpNotifications 6 }
tlpNotificationsAgent OBJECT IDENTIFIER ::= { tlpNotificationsEvent 1 }
tlpNotificationsDevice OBJECT IDENTIFIER ::= { tlpNotificationsEvent 2 }
tlpNotificationsDeviceInternalFirmwareFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device experiences an internal
firmware failure."
::= { tlpNotificationsDevice 1 }
tlpNotificationsDeviceInternalHardwareFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device experiences an internal
hardware failure."
::= { tlpNotificationsDevice 2 }
tlpNotificationsDeviceConfigurationChange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device configuration changes."
::= { tlpNotificationsDevice 3 }
tlpNotificationsDeviceFirmwareUpdate NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device firmware is updated."
::= { tlpNotificationsDevice 4 }
tlpNotificationsDeviceMicrocontrollerReset NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device microcontroller resets."
::= { tlpNotificationsDevice 5 }
tlpNotificationsDeviceSystemInformation NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device system information changes."
::= { tlpNotificationsDevice 6 }
tlpNotificationsDeviceNvrChecksumMismatch NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the NVR is corrupted."
::= { tlpNotificationsDevice 7 }
tlpNotificationsDeviceUsbCommunicationsEstablished NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device USB communications is
established."
::= { tlpNotificationsDevice 8 }
tlpNotificationsDeviceUsbCommunicationsLost NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device USB communications is lost."
::= { tlpNotificationsDevice 9 }
tlpNotificationsDevicePowerSupplyShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to a power supply fault."
::= { tlpNotificationsDevice 10 }
tlpNotificationsDeviceOverLoadShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to an over load fault."
::= { tlpNotificationsDevice 11 }
tlpNotificationsDeviceCurrentLimitShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to a current limit fault."
::= { tlpNotificationsDevice 12 }
tlpNotificationsDeviceOverTemperatureShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to an over temperature fault."
::= { tlpNotificationsDevice 13 }
tlpNotificationsDeviceModeTransitionTimeout NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device timed out transitioning to
a mode."
::= { tlpNotificationsDevice 14 }
tlpNotificationsDeviceFailedModeTransitionToIdle NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device failed a transition to idle
mode."
::= { tlpNotificationsDevice 15 }
tlpNotificationsDeviceInternalCommunicationsLost NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device lost internal communications."
::= { tlpNotificationsDevice 16 }
tlpNotificationsDeviceAcknowledgeFaults NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when device faults are acknowledged."
::= { tlpNotificationsDevice 17 }
tlpNotificationsDeviceTransferToRestart NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a device restart occurred."
::= { tlpNotificationsDevice 18 }
tlpNotificationsDeviceTransferToWatchdogRestart NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a device restart occurred due to a
watchdog fault."
::= { tlpNotificationsDevice 19 }
tlpNotificationsDeviceTransferToLatchedIdle NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to latched idle
mode."
::= { tlpNotificationsDevice 20 }
tlpNotificationsDeviceTransferToLatchedStandby NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to latched
standby mode."
::= {tlpNotificationsDevice 21 }
tlpNotificationsDeviceTransferToLatchedLine NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to latched
line mode."
::= { tlpNotificationsDevice 22 }
tlpNotificationsDeviceFailSafeClockMonitorEngaged NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the fail safe clock monitor is engaged."
::= { tlpNotificationsDevice 23 }
tlpNotificationsDeviceTransferToIdle NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to idle mode."
::= { tlpNotificationsDevice 24 }
tlpNotificationsDeviceVoutUnderVoltageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to an under voltage fault."
::= { tlpNotificationsDevice 25 }
tlpNotificationsDeviceVoutOverVoltageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to an over voltage fault."
::= { tlpNotificationsDevice 26 }
tlpNotificationsDeviceRtosFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when an RTOS fault occurs."
::= { tlpNotificationsDevice 27 }
tlpNotificationsDeviceCriticalNvrValuesBlank NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a blank critical
nvr value."
::= { tlpNotificationsDevice 28 }
tlpNotificationsDeviceOutputOff NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device output is off."
::= { tlpNotificationsDevice 29 }
tlpNotificationsDeviceStartup NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device starts powering up."
::= { tlpNotificationsDevice 30 }
tlpNotificationsDeviceEpo NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when an emergency power off occurs on the
device."
::= { tlpNotificationsDevice 31 }
tlpNotificationsDeviceFirmwareMismatch NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a firmware mismatch."
::= { tlpNotificationsDevice 32 }
tlpNotificationsDeviceOverloadRelease NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when an overload condition is released."
::= { tlpNotificationsDevice 33 }
tlpNotificationsDeviceTransferToLine NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to line mode."
::= { tlpNotificationsDevice 34 }
tlpNotificationsDeviceAcFailure NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when power to the device failed."
::= { tlpNotificationsDevice 35 }
tlpNotificationsDeviceSiteWiringFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the utility input wiring is faulty."
::= { tlpNotificationsDevice 36 }
tlpNotificationsDeviceEmergencyShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports an emergency
shutdown."
::= { tlpNotificationsDevice 37 }
tlpNotificationsDeviceCircuitBreakerOpen NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a circuit breaker is open."
::= { tlpNotificationsDevice 38 }
tlpNotificationsDeviceSupplyMonitorInterrupt NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a supply monitor interrupt fault is
reported."
::= { tlpNotificationsDevice 39 }
tlpNotificationsDeviceSystemTickTimeout NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a system tick timeout occurs."
::= { tlpNotificationsDevice 40 }
tlpNotificationsDeviceRelayInUnexpectedState NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a relay is in an unexpected state."
::= { tlpNotificationsDevice 41 }
tlpNotificationsDeviceEepromQueueOverflow NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when an EEPROM queue overflow fault occurs."
::= { tlpNotificationsDevice 42 }
tlpNotificationsDeviceEepromWriteFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when an EEPROM write fault occurs."
::= { tlpNotificationsDevice 43 }
tlpNotificationsDeviceEepromOperationTimeout NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when an EEPROM operation timeout occurs."
::= { tlpNotificationsDevice 44 }
tlpNotificationsDeviceI2cWriteDelayed NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a delay occurred writing to the I2C."
::= { tlpNotificationsDevice 45 }
tlpNotificationsDeviceRampShedNvrWriteFailed NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when ramp/shed nvr write failed."
::= { tlpNotificationsDevice 46 }
tlpNotificationsDeviceFactoryRestoreFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a fault occurred during a factory restore."
::= { tlpNotificationsDevice 47 }
tlpNotificationsDeviceRelaySetTimeOutOfRange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a relay set time is out of range."
::= { tlpNotificationsDevice 48 }
tlpNotificationsDeviceRelayResetTimeOutOfRange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a relay reset time is out of range."
::= { tlpNotificationsDevice 49 }
tlpNotificationsUps OBJECT IDENTIFIER ::= { tlpNotificationsEvent 3 }
tlpNotificationsUpsBatteryLowVoltageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups reports a shutdown occurred
due to a low battery voltage fault."
::= { tlpNotificationsUps 1 }
tlpNotificationsUpsBatteryLowPercentageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups reports a shutdown occurred
due to a low battery percentage fault."
::= { tlpNotificationsUps 2 }
tlpNotificationsUpsBatteryOverVoltageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups reports a shutdown occurred
due to a battery over voltage fault."
::= { tlpNotificationsUps 3 }
tlpNotificationsUpsBatteryOverCurrentShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups reports a shutdown occurred
due to a battery over current fault."
::= { tlpNotificationsUps 4 }
tlpNotificationsUpsBatteryUnknownTypeShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups reports a shutdown occurred
due to an unknown battery type fault."
::= { tlpNotificationsUps 5 }
tlpNotificationsUpsBatteryConfigurationMismatch NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups battery configuration is
mismatched."
::= { tlpNotificationsUps 6 }
tlpNotificationsUpsBatteryUnderVoltageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups reports a shutdown occurred
due to a battery under voltage fault."
::= { tlpNotificationsUps 7 }
tlpNotificationsUpsSlaBatteryOverTemperatureShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the ups reports a shutdown occurred
due to an SLA battery over temperature fault."
::= { tlpNotificationsUps 8 }
tlpNotificationsUpsBatteryInstallation NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a battery installation occurs."
::= { tlpNotificationsUps 9 }
tlpNotificationsUpsChargerBulkToAcceptance NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when ups battery charging."
::= { tlpNotificationsUps 10 }
tlpNotificationsUpsChargerAcceptanceToFloat NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when ups battery fully charged."
::= { tlpNotificationsUps 11 }
tlpNotificationsUpsChargerFloatToBulk NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when ups battery not fully charged."
::= { tlpNotificationsUps 12 }
tlpNotificationsUpsTransferToSelftest NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a self test is initiated."
::= { tlpNotificationsUps 13 }
tlpNotificationsUpsTransferToEconomy NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to economy mode."
::= { tlpNotificationsUps 14 }
tlpNotificationsUpsLineConnectRelayFaultShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to line connect relay fault."
::= { tlpNotificationsUps 15 }
tlpNotificationsUpsTransferToFaultBypass NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to fault bypass
mode."
::= { tlpNotificationsUps 16 }
tlpNotificationsUpsBypassPowerDistributionModuleDisconnected NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when bypass power distribution module is
disconnected."
::= { tlpNotificationsUps 17 }
tlpNotificationsUpsManualBypassActivatedFromUnsupportedMode NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when manual bypass activated from an
unsupported ups mode."
::= { tlpNotificationsUps 18 }
tlpNotificationsUpsOnBatteryTimeoutShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to on battery timeout."
::= { tlpNotificationsUps 19 }
tlpNotificationsUpsLowBatteryPercentageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to low battery percentage."
::= { tlpNotificationsUps 20 }
tlpNotificationsUpsBatteryCommunicationsLost NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when communications with the battery pack
is lost."
::= { tlpNotificationsUps 21 }
tlpNotificationsUpsBatteryCommunicationsEstablished NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when communications with the battery pack
is established."
::= { tlpNotificationsUps 22 }
tlpNotificationsUpsBatteryOtaShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to the battery ota flag."
::= { tlpNotificationsUps 23 }
tlpNotificationsUpsCartInstallation NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports the occurrence of
a cart installation."
::= { tlpNotificationsUps 24 }
tlpNotificationsUpsDeadBatteryRecoveryShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to a dead battery."
::= { tlpNotificationsUps 25 }
tlpNotificationsUpsFullBridgeNotSteadyShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to the full bridge not steady."
::= { tlpNotificationsUps 26 }
tlpNotificationsUpsFullBridgeCurrentLimitShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to a current limit on the full bridge."
::= { tlpNotificationsUps 27 }
tlpNotificationsUpsTransitionFailed NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a failure to
transition."
::= { tlpNotificationsUps 28 }
tlpNotificationsUpsInverterOcp NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports an inverter ocp
fault."
::= { tlpNotificationsUps 29 }
tlpNotificationsUpsInverterVbusShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to the inverter vbus."
::= { tlpNotificationsUps 30}
tlpNotificationsUpsTransferToFaultStandby NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to a fault
standby mode."
::= { tlpNotificationsUps 31 }
tlpNotificationsUpsModbusBatteryStatusShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to the modbus battery status."
::= { tlpNotificationsUps 32}
tlpNotificationsUpsBatteryPackCountChange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the number of battery packs changed."
::= { tlpNotificationsUps 33}
tlpNotificationsUpsTransferToBattery NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to battery mode."
::= { tlpNotificationsUps 34 }
tlpNotificationsUpsTransferToBypass NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to bypass mode."
::= { tlpNotificationsUps 35 }
tlpNotificationsUpsTransferToDbrLine NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to dbr line mode."
::= { tlpNotificationsUps 36 }
tlpNotificationsUpsTransferToDbrStandby NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to dbr standby
mode."
::= { tlpNotificationsUps 37 }
tlpNotificationsUpsTransferToStandby NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to standby mode."
::= { tlpNotificationsUps 38 }
tlpNotificationsUpsTransferToOnline NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device transferred to online mode."
::= { tlpNotificationsUps 39 }
tlpNotificationsUpsV20BusNotSteadyShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to the v20 bus not steady."
::= { tlpNotificationsUps 40 }
tlpNotificationsUpsV20BusOverVoltageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to the v20 bus over voltage."
::= { tlpNotificationsUps 41 }
tlpNotificationsUpsV20BusUnderVoltageShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to the v20 bus under voltage."
::= { tlpNotificationsUps 42 }
tlpNotificationsUpsBypassOutOfRange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the bypass voltage is out of tolerance."
::= { tlpNotificationsUps 43 }
tlpNotificationsUpsEnergySavingShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to energy saving."
::= { tlpNotificationsUps 44 }
tlpNotificationsUpsDryContactShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to a dry contact."
::= { tlpNotificationsUps 45 }
tlpNotificationsUpsInverterOverCurrentShutdown NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a shutdown occurred
due to an inverter over current fault."
::= { tlpNotificationsUps 46 }
tlpNotificationsUpsPfcPrechargeFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a PFC precharge
fault."
::= { tlpNotificationsUps 47 }
tlpNotificationsUpsPfcOverVoltageFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a PFC over voltage
fault."
::= { tlpNotificationsUps 48 }
tlpNotificationsUpsPfcUnderVoltageFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a PFC under voltage
fault."
::= { tlpNotificationsUps 49 }
tlpNotificationsUpsPfcOverCurrentFault NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a PFC over current
fault."
::= { tlpNotificationsUps 50 }
tlpNotificationsPdu OBJECT IDENTIFIER ::= { tlpNotificationsEvent 4 }
tlpNotificationsPduCrestFactorOutOfRange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the crest factor is beyond normal
operating limits."
::= { tlpNotificationsPdu 1 }
tlpNotificationsPduTransferToForceLineMode NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device is forced into line mode."
::= { tlpNotificationsPdu 2 }
tlpNotificationsPduLineInRange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the line enters into normal operating
range."
::= { tlpNotificationsPdu 3 }
tlpNotificationsPduLineOutOfRange NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the line falls outside its normal
operating range."
::= { tlpNotificationsPdu 4 }
tlpNotificationsPduNotableRelayResponseTimes NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a notable relay
response time."
::= { tlpNotificationsPdu 5 }
tlpNotificationsPduOutletNearMaxRating NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports an outlet is near
its maximum rating."
::= { tlpNotificationsPdu 6 }
tlpNotificationsPduLineModeTransferToLinePartialPowerup NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports a partial powerup in
line mode."
::= { tlpNotificationsPdu 7 }
tlpNotificationsPduSinglePhasing NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the device reports it is operating with
only a single phase."
::= { tlpNotificationsPdu 8 }
tlpNotificationsEnvirosense OBJECT IDENTIFIER ::= { tlpNotificationsEvent 5 }
tlpNotificationsAts OBJECT IDENTIFIER ::= { tlpNotificationsEvent 6 }
tlpNotificationsAtsSource1NotAvailable NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when input on source one is not available.
For atss with the designation of primary and secondary, this
notification denotes input on the primary source is not available."
::= { tlpNotificationsAts 1 }
tlpNotificationsAtsSource2NotAvailable NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when input on source two is not available.
For atss with the designation of primary and secondary, this
notification denotes input on the secondary source is not available."
::= { tlpNotificationsAts 2 }
tlpNotificationsAtsLockdownToSource1 NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent upon a transfer circuit fault causing the
device to be locked on source 1."
::= { tlpNotificationsAts 3 }
tlpNotificationsAtsLockdownToSource2 NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent upon a transfer circuit fault causing the
device to be locked on source 2."
::= { tlpNotificationsAts 4 }
tlpNotificationsAtsSource1Available NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when source 1 is available and ready for
use."
::= { tlpNotificationsAts 5 }
tlpNotificationsAtsSource2Available NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when source 2 is available and ready for
use."
::= { tlpNotificationsAts 6 }
tlpNotificationsAtsSource1Brownout NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a brownout condition occurred on
source 1."
::= { tlpNotificationsAts 7 }
tlpNotificationsAtsSource2Brownout NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when a brownout condition occurred on
source 2."
::= { tlpNotificationsAts 8 }
tlpNotificationsAtsSource1VoltageDrop NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the voltage on source 1 drops below a
usable state."
::= { tlpNotificationsAts 9 }
tlpNotificationsAtsSource2VoltageDrop NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the voltage on source 2 drops below a
usable state."
::= { tlpNotificationsAts 10 }
tlpNotificationsAtsTimedReturnToSource1 NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the active input source returns to
source 1 from source 2 after a delay time expires."
::= { tlpNotificationsAts 11 }
tlpNotificationsAtsTimedReturnToSource2 NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the active input source returns to
source 2 from source 1 after a delay time expires."
::= { tlpNotificationsAts 12 }
tlpNotificationsAtsTransferToSource1 NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the active input source transfers
from source 2 to source 1."
::= { tlpNotificationsAts 13 }
tlpNotificationsAtsTransferToSource2 NOTIFICATION-TYPE
OBJECTS { sysUpTime, tlpNotifyEventTableRef, tlpNotifyEventTableRowRef }
STATUS current
DESCRIPTION
"This notification is sent when the active input source transfers
from source 1 to source 2."
::= { tlpNotificationsAts 14 }
tlpNotificationsCooling OBJECT IDENTIFIER ::= { tlpNotificationsEvent 7 }
tlpNotificationsKvm OBJECT IDENTIFIER ::= { tlpNotificationsEvent 8 }
tlpNotificationsRackTrack OBJECT IDENTIFIER ::= { tlpNotificationsEvent 9 }
tlpNotificationsSwitch OBJECT IDENTIFIER ::= { tlpNotificationsEvent 10 }
tlpNotifyEventTableRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value references the OID of a table object applicable to the event
condition. This, in conjunction with the table row as defined by
tlpAlarmTableRowRef, specifies the object/row within this table to which
the event condition applies. Refer to tlpAlarmTableRef for more information."
::= { tlpNotificationsEventParameters 1 }
tlpNotifyEventTableRowRef OBJECT-TYPE
SYNTAX OBJECT IDENTIFIER
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"This value is used in conjunction with tlpNotifyEventTableRef to define the
object associated with this event condition. See the description of
tlpNotifyEventTableRef for more information."
::= { tlpNotificationsEventParameters 2 }