- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
2976 lines
82 KiB
Text
2976 lines
82 KiB
Text
TRIPPLITE-12X DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
DisplayString,
|
|
TruthValue,
|
|
TimeStamp,
|
|
TimeInterval,
|
|
DateAndTime,
|
|
AutonomousType,
|
|
VariablePointer,
|
|
RowStatus
|
|
FROM SNMPv2-TC
|
|
OBJECT-GROUP,
|
|
NOTIFICATION-GROUP
|
|
FROM SNMPv2-CONF
|
|
MODULE-IDENTITY,
|
|
OBJECT-IDENTITY,
|
|
OBJECT-TYPE,
|
|
NOTIFICATION-TYPE,
|
|
Gauge32,
|
|
Integer32,
|
|
IpAddress
|
|
FROM SNMPv2-SMI
|
|
PositiveInteger,
|
|
NonNegativeInteger
|
|
FROM UPS-MIB
|
|
tripplite
|
|
FROM TRIPPLITE;
|
|
|
|
tlPowerAlert MODULE-IDENTITY
|
|
LAST-UPDATED "201702281600Z"
|
|
ORGANIZATION "Tripp Lite"
|
|
CONTACT-INFO
|
|
"Software Engineering
|
|
Tripp Lite
|
|
1111 W. 35th St.
|
|
Chicago, IL 60609"
|
|
DESCRIPTION
|
|
"This MIB module defines MIB objects which provide mechanisms for
|
|
remote management capabilities of Tripplite PowerAlert and related
|
|
software."
|
|
REVISION "201702281600Z"
|
|
"Corrected spelling errors"
|
|
REVISION "201507290000Z"
|
|
DESCRIPTION
|
|
"Removed obsolete legacy PowerAlert 11 sections"
|
|
REVISION "201410170930Z"
|
|
DESCRIPTION
|
|
"Added tlUpsAggregatePowerFactor"
|
|
REVISION "201409181000Z"
|
|
DESCRIPTION
|
|
"Added additional tlUpsInputSource... elements"
|
|
REVISION "201408060830Z"
|
|
DESCRIPTION
|
|
"Added additional elements to tlUpsOutputCircuitTable"
|
|
REVISION "201405080830Z"
|
|
DESCRIPTION
|
|
"Added tlUpsInputSourceSelect"
|
|
REVISION "201404091000Z"
|
|
DESCRIPTION
|
|
"Added missing well known alarms"
|
|
REVISION "201310301300Z"
|
|
DESCRIPTION
|
|
"Consolidated and Released for PAL v12.06.006x"
|
|
|
|
::= { tripplite 90 }
|
|
|
|
|
|
--------------------------------------------------------------------------
|
|
-- Enumerations
|
|
--------------------------------------------------------------------------
|
|
|
|
tlEnumerations OBJECT IDENTIFIER ::= { tripplite 2 }
|
|
|
|
tlOperatingSystems OBJECT IDENTIFIER ::= { tlEnumerations 1 }
|
|
|
|
hpux9 OBJECT IDENTIFIER ::= { tlOperatingSystems 1 }
|
|
|
|
sunos4 OBJECT IDENTIFIER ::= { tlOperatingSystems 2 }
|
|
|
|
solaris OBJECT IDENTIFIER ::= { tlOperatingSystems 3 }
|
|
|
|
osf OBJECT IDENTIFIER ::= { tlOperatingSystems 4 }
|
|
|
|
ultrix OBJECT IDENTIFIER ::= { tlOperatingSystems 5 }
|
|
|
|
hpux10 OBJECT IDENTIFIER ::= { tlOperatingSystems 6 }
|
|
|
|
netbsd1 OBJECT IDENTIFIER ::= { tlOperatingSystems 7 }
|
|
|
|
freebsd OBJECT IDENTIFIER ::= { tlOperatingSystems 8 }
|
|
|
|
irix OBJECT IDENTIFIER ::= { tlOperatingSystems 9 }
|
|
|
|
linux OBJECT IDENTIFIER ::= { tlOperatingSystems 10 }
|
|
|
|
bsdi OBJECT IDENTIFIER ::= { tlOperatingSystems 11 }
|
|
|
|
openbsd OBJECT IDENTIFIER ::= { tlOperatingSystems 12 }
|
|
|
|
win32 OBJECT IDENTIFIER ::= { tlOperatingSystems 13 }
|
|
|
|
hpux11 OBJECT IDENTIFIER ::= { tlOperatingSystems 14 }
|
|
|
|
win9x OBJECT IDENTIFIER ::= { tlOperatingSystems 50 }
|
|
|
|
winnt OBJECT IDENTIFIER ::= { tlOperatingSystems 51 }
|
|
|
|
solspark OBJECT IDENTIFIER ::= { tlOperatingSystems 52 }
|
|
|
|
solintel OBJECT IDENTIFIER ::= { tlOperatingSystems 53 }
|
|
|
|
aix OBJECT IDENTIFIER ::= { tlOperatingSystems 54 }
|
|
|
|
sco OBJECT IDENTIFIER ::= { tlOperatingSystems 55 }
|
|
|
|
osx OBJECT IDENTIFIER ::= { tlOperatingSystems 56 }
|
|
|
|
unknown OBJECT IDENTIFIER ::= { tlOperatingSystems 255 }
|
|
|
|
--------------------------------------------------------------------------
|
|
-- Power Alert System Settings
|
|
--------------------------------------------------------------------------
|
|
-- tlPowerAlert OBJECT IDENTIFIER ::= { tripplite 90 }
|
|
|
|
tlPASystem OBJECT IDENTIFIER ::= { tlPowerAlert 1 }
|
|
|
|
tlPAContacts OBJECT IDENTIFIER ::= { tlPASystem 1 }
|
|
|
|
tlPAEmailContacts OBJECT IDENTIFIER ::= { tlPAContacts 1 }
|
|
|
|
tlPANumberOfEmailContacts OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number email contacts currently defined."
|
|
::= { tlPAEmailContacts 1 }
|
|
|
|
tlPAEmailContactsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlPAEmailContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list email contact entries. The number of entries is
|
|
given by the value of tlPANumberOfEmailContacts."
|
|
::= { tlPAEmailContacts 2 }
|
|
|
|
tlPAEmailContactEntry OBJECT-TYPE
|
|
SYNTAX TlPAEmailContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing email contacts information."
|
|
INDEX { tlPAEmailContactIndex }
|
|
::= { tlPAEmailContactsTable 1 }
|
|
|
|
TlPAEmailContactEntry ::= SEQUENCE {
|
|
tlPAEmailContactIndex PositiveInteger,
|
|
tlPAEmailContactRowStatus RowStatus,
|
|
tlPAEmailContactName DisplayString,
|
|
tlPAEmailContactAddress DisplayString
|
|
}
|
|
|
|
tlPAEmailContactIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index number of the email contact."
|
|
::= { tlPAEmailContactEntry 1 }
|
|
|
|
tlPAEmailContactRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The row status for the tlPAEmailContactTable row"
|
|
::= { tlPAEmailContactEntry 2 }
|
|
|
|
tlPAEmailContactName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the email contact."
|
|
::= { tlPAEmailContactEntry 3 }
|
|
|
|
tlPAEmailContactAddress OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The address of the email contact."
|
|
::= { tlPAEmailContactEntry 4 }
|
|
|
|
tlPASnmpContacts OBJECT IDENTIFIER ::= { tlPAContacts 2 }
|
|
|
|
tlPANumberOfSnmpContacts OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number SNMP contacts currently defined."
|
|
::= { tlPASnmpContacts 1 }
|
|
|
|
tlPASnmpContactsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlPASnmpContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list SNMP contact entries. The number of entries is
|
|
given by the value of tlPANumberOfSnmpContacts."
|
|
::= { tlPASnmpContacts 2 }
|
|
|
|
tlPASnmpContactEntry OBJECT-TYPE
|
|
SYNTAX TlPASnmpContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing SNMP contacts information."
|
|
INDEX { tlPASnmpContactIndex }
|
|
::= { tlPASnmpContactsTable 1 }
|
|
|
|
TlPASnmpContactEntry ::= SEQUENCE {
|
|
tlPASnmpContactIndex PositiveInteger,
|
|
tlPASnmpContactRowStatus RowStatus,
|
|
tlPASnmpContactName DisplayString,
|
|
tlPASnmpContactIpAddress DisplayString,
|
|
tlPASnmpContactPort PositiveInteger,
|
|
tlPASnmpContactSnmpVersion INTEGER,
|
|
tlPASnmpContactSecurityName DisplayString,
|
|
tlPASnmpContactPrivPassword DisplayString,
|
|
tlPASnmpContactAuthPassword DisplayString
|
|
}
|
|
|
|
tlPASnmpContactIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index number of this SNMP contact."
|
|
::= { tlPASnmpContactEntry 1 }
|
|
|
|
tlPASnmpContactRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The row status for the tlPASnmpContactTable row"
|
|
::= { tlPASnmpContactEntry 2 }
|
|
|
|
tlPASnmpContactName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the SNMP contact."
|
|
::= { tlPASnmpContactEntry 3 }
|
|
|
|
tlPASnmpContactIpAddress OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The IP address of the SNMP contact."
|
|
::= { tlPASnmpContactEntry 4 }
|
|
|
|
tlPASnmpContactPort OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The port of the SNMP contact."
|
|
::= { tlPASnmpContactEntry 5 }
|
|
|
|
tlPASnmpContactSnmpVersion OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
snmpv1(1),
|
|
snmpv2c(2),
|
|
snmpv3(3) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SNMP contact version to use for sending traps."
|
|
::= { tlPASnmpContactEntry 6 }
|
|
|
|
tlPASnmpContactSecurityName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SNMP contact security name."
|
|
::= { tlPASnmpContactEntry 7 }
|
|
|
|
tlPASnmpContactPrivPassword OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SNMP contact priv password to use for sending V3 traps."
|
|
::= { tlPASnmpContactEntry 8 }
|
|
|
|
tlPASnmpContactAuthPassword OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SNMP contact auth password to use for sending V3 traps."
|
|
::= { tlPASnmpContactEntry 9 }
|
|
|
|
--------------------------------------------------------------------------
|
|
-- UPS Device
|
|
--------------------------------------------------------------------------
|
|
|
|
tlUPS OBJECT IDENTIFIER ::= { tripplite 100 }
|
|
|
|
tlUpsObjects OBJECT IDENTIFIER ::= { tlUPS 1 }
|
|
|
|
tlUpsIdent OBJECT IDENTIFIER ::= { tlUpsObjects 1 }
|
|
|
|
tlUpsIdentUpsSoftwareChecksum OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A checksum for the UPS software."
|
|
::= { tlUpsIdent 1 }
|
|
|
|
tlUpsIdentSerialNum OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number for the UPS."
|
|
::= { tlUpsIdent 2 }
|
|
|
|
tlUpsIdentID OBJECT-TYPE
|
|
SYNTAX Integer32 (0..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-supplied ID for the UPS."
|
|
::= { tlUpsIdent 3 }
|
|
|
|
tlUpsSnmpCardSerialNum OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial number for the UPS."
|
|
::= { tlUpsIdent 4 }
|
|
|
|
tlUpsSelectedDeviceID OBJECT-TYPE
|
|
SYNTAX Integer32 (0..65535)
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device ID selected to be used for retrieving data for this mib.
|
|
As the snmp web card has only one device, this is read only for it"
|
|
::= { tlUpsIdent 5 }
|
|
|
|
tlUpsLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device location string."
|
|
::= { tlUpsIdent 6 }
|
|
|
|
tlUpsBattery OBJECT IDENTIFIER ::= { tlUpsObjects 2 }
|
|
|
|
tlUpsBatteryAge OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The age of the battery in years. This is equal to
|
|
the current date minus tlConfigBattReplDate."
|
|
::= { tlUpsBattery 1 }
|
|
|
|
|
|
tlUpsTemperatureF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature of the battery, in Farenheight degrees. This is
|
|
calculated from upsBatteryTemperature, which is in Celsius degrees."
|
|
::= { tlUpsBattery 2 }
|
|
|
|
tlUpsExternalBatteryAge OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The age of external battery in years. This is equal to
|
|
the current date minus tlConfigExternalBattReplDate."
|
|
::= { tlUpsBattery 3 }
|
|
|
|
tlUpsInput OBJECT IDENTIFIER ::= { tlUpsObjects 3 }
|
|
|
|
tlUpsInputNumVoltages OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of input voltages. Phase to phase
|
|
or phase to neutral. This variable indicates the
|
|
number of rows in the input table."
|
|
::= { tlUpsInput 1 }
|
|
|
|
tlUpsInputVoltageTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlUpsInputVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of voltage input table entries. The number of entries
|
|
is given by the value of tlUpsInputNumVoltages."
|
|
::= { tlUpsInput 2 }
|
|
|
|
tlUpsInputVoltageEntry OBJECT-TYPE
|
|
SYNTAX TlUpsInputVoltageEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input voltage."
|
|
INDEX { tlUpsInputVoltageIndex }
|
|
::= { tlUpsInputVoltageTable 1 }
|
|
|
|
TlUpsInputVoltageEntry ::= SEQUENCE {
|
|
tlUpsInputVoltageIndex PositiveInteger,
|
|
tlUpsInputVoltageType NonNegativeInteger,
|
|
tlUpsInputVoltage NonNegativeInteger
|
|
}
|
|
|
|
tlUpsInputVoltageIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input voltage identifier."
|
|
::= { tlUpsInputVoltageEntry 1 }
|
|
|
|
tlUpsInputVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
phaseToNeutral(0),
|
|
phaseToPhase(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Whether voltage measured is phase to
|
|
phase or phase to neutral."
|
|
::= { tlUpsInputVoltageEntry 2 }
|
|
|
|
tlUpsInputVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "RMS Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input voltage.
|
|
A value of 6553 indicates Unknown."
|
|
::= { tlUpsInputVoltageEntry 3 }
|
|
|
|
tlUpsInputSourceSelect OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inputSourceA(0),
|
|
inputSourceB(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The determination as to which of two AC input
|
|
lines is designated as the primary input source.
|
|
The other is designated as the secondary input
|
|
source. This value will always return inputSourceA(0)
|
|
for devices with a single input source. Setting
|
|
this value is supported only on selected models."
|
|
::= { tlUpsInput 3 }
|
|
|
|
tlUpsPhaseImbalance OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Percentage of imbalance of the 3 phases."
|
|
::= { tlUpsInput 4 }
|
|
|
|
tlUpsInputSourceAvailability OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
inputSourceA(1),
|
|
inputSourceB(2),
|
|
inputSourceAB(3) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The determination as to which of two AC input lines
|
|
are available. The agent will return either inputSourceA(1)
|
|
or inputSourceB(2) if only one line is available, or
|
|
inputSourceAB(3) if both lines are available. The agent
|
|
will never return none(0) since the device will be powered
|
|
off if neither line is available."
|
|
::= { tlUpsInput 5 }
|
|
|
|
tlUpsInputSourceInUse OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
inputSourceA(0),
|
|
inputSourceB(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The determination as to which one of two AC input lines is
|
|
in use."
|
|
::= { tlUpsInput 6 }
|
|
|
|
tlUpsInputSourceTransitionCount OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of times the device transitions between primary and
|
|
secondary sources. Most devices are limied to 65533 transitions,
|
|
after which the value will not increment."
|
|
::= { tlUpsInput 7 }
|
|
|
|
tlUpsOutput OBJECT IDENTIFIER ::= { tlUpsObjects 4 }
|
|
|
|
tlUpsOutputPowerTotal OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power capacity of the device."
|
|
::= { tlUpsOutput 5 }
|
|
|
|
tlUpsOutputCircuits OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of output circuits. This variable
|
|
indicates the number of rows in the output circuit table."
|
|
::= { tlUpsOutput 6 }
|
|
|
|
tlUpsOutputCircuitTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlUpsOutputCircuitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of output currents table entries. The number of entries
|
|
is given by the value of tlUpsOutputNumCircuits."
|
|
::= { tlUpsOutput 7 }
|
|
|
|
tlUpsOutputCircuitEntry OBJECT-TYPE
|
|
SYNTAX TlUpsOutputCircuitEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output circuit."
|
|
INDEX { tlUpsOutputCircuitIndex }
|
|
::= { tlUpsOutputCircuitTable 1 }
|
|
|
|
TlUpsOutputCircuitEntry ::= SEQUENCE {
|
|
tlUpsOutputCircuitIndex PositiveInteger,
|
|
tlUpsOutputCircuitStatus INTEGER,
|
|
tlUpsOutputCircuitLoadCurrent NonNegativeInteger,
|
|
tlUpsOutputCircuitVoltage NonNegativeInteger,
|
|
tlUpsOutputCircuitPower NonNegativeInteger,
|
|
tlUpsOutputCircuitPowerFactor NonNegativeInteger
|
|
}
|
|
|
|
tlUpsOutputCircuitIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output circuit identifier."
|
|
::= { tlUpsOutputCircuitEntry 1 }
|
|
|
|
tlUpsOutputCircuitStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
open(0),
|
|
closed(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Whether the breaker is open or closed."
|
|
::= { tlUpsOutputCircuitEntry 2 }
|
|
|
|
tlUpsOutputCircuitLoadCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Amperes"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present output current in
|
|
tenths of an amp. A value of 65534 indicates Unknown."
|
|
::= { tlUpsOutputCircuitEntry 3 }
|
|
|
|
tlUpsOutputCircuitVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Volts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present circuit voltage in
|
|
tenths of an volt."
|
|
::= { tlUpsOutputCircuitEntry 4 }
|
|
|
|
tlUpsOutputCircuitPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present power in watts.
|
|
tenths of an amp."
|
|
::= { tlUpsOutputCircuitEntry 5 }
|
|
|
|
tlUpsOutputCircuitPowerFactor OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "Percent"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power factor of all receptacles in a given circuit as
|
|
a %."
|
|
::= { tlUpsOutputCircuitEntry 6 }
|
|
|
|
tlUpsAggregatePowerFactor OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS "0.1 Watts"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The aggregrate power factor of all phases."
|
|
::= { tlUpsOutput 8 }
|
|
|
|
-- tlUpsBypass [unused] OBJECT IDENTIFIER ::= { tlUpsObjects 5 }
|
|
|
|
tlUpsAlarm OBJECT IDENTIFIER ::= { tlUpsObjects 6 }
|
|
|
|
tlUpsAlarmsPresent OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of active alarm conditions."
|
|
::= { tlUpsAlarm 1 }
|
|
|
|
tlUpsAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlUpsAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of alarm table entries."
|
|
::= { tlUpsAlarm 2 }
|
|
|
|
tlUpsAlarmEntry OBJECT-TYPE
|
|
SYNTAX TlUpsAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a particular alarm."
|
|
INDEX { tlUpsAlarmId }
|
|
::= { tlUpsAlarmTable 1 }
|
|
|
|
TlUpsAlarmEntry ::= SEQUENCE {
|
|
tlUpsAlarmId PositiveInteger,
|
|
tlUpsAlarmDescr AutonomousType,
|
|
tlUpsAlarmTime TimeStamp,
|
|
tlUpsAlarmDetail DisplayString,
|
|
tlUpsAlarmDeviceId PositiveInteger,
|
|
tlUpsAlarmDeviceName DisplayString,
|
|
tlUpsAlarmLocation DisplayString,
|
|
tlUpsAlarmGroup INTEGER,
|
|
tlUpsAlarmIp IpAddress,
|
|
tlUpsAlarmMac DisplayString
|
|
}
|
|
|
|
tlUpsAlarmId OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique identifier for an alarm condition."
|
|
::= { tlUpsAlarmEntry 1 }
|
|
|
|
tlUpsAlarmDescr OBJECT-TYPE
|
|
SYNTAX AutonomousType
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A description of the alarm condition."
|
|
::= { tlUpsAlarmEntry 2 }
|
|
|
|
tlUpsAlarmTime OBJECT-TYPE
|
|
SYNTAX TimeStamp
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the alarm condition was detected."
|
|
::= { tlUpsAlarmEntry 3 }
|
|
|
|
tlUpsAlarmDetail OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual description of the alarm condition."
|
|
::= { tlUpsAlarmEntry 4 }
|
|
|
|
tlUpsAlarmDeviceId OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A numeric identifier for the device on which the alarm is active."
|
|
::= { tlUpsAlarmEntry 5 }
|
|
|
|
tlUpsAlarmDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifier for the device on which the alarm is active."
|
|
::= { tlUpsAlarmEntry 6 }
|
|
|
|
tlUpsAlarmLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The location of the device on which the alarm is active."
|
|
::= { tlUpsAlarmEntry 7 }
|
|
|
|
tlUpsAlarmGroup OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
critical(1),
|
|
warning(2),
|
|
info(3),
|
|
status(4),
|
|
offline(5),
|
|
custom(6) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The category/group of this alarm."
|
|
::= { tlUpsAlarmEntry 8 }
|
|
|
|
tlUpsAlarmIp OBJECT-TYPE
|
|
SYNTAX IpAddress
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The originating IP address associated with this alarm."
|
|
::= { tlUpsAlarmEntry 9 }
|
|
|
|
tlUpsAlarmMac OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The originating mac address associated with this alarm."
|
|
::= { tlUpsAlarmEntry 10 }
|
|
|
|
tlUpsWellKnownAlarms OBJECT IDENTIFIER ::= { tlUpsAlarm 3 }
|
|
|
|
tlUpsAlarmPrimaryPowerOutage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The primary power source is not present."
|
|
::= { tlUpsWellKnownAlarms 1 }
|
|
|
|
tlUpsAlarmSecondaryPowerOutage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The secondary power source is not present."
|
|
::= { tlUpsWellKnownAlarms 2 }
|
|
|
|
tlUpsAlarmLoadLevelAboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The load level is above the designated threshold."
|
|
::= { tlUpsWellKnownAlarms 3 }
|
|
|
|
tlUpsAlarmOutputCurrentChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output current changed from its last known value."
|
|
::= { tlUpsWellKnownAlarms 4 }
|
|
|
|
tlUpsAlarmBatteryAgeAboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement."
|
|
::= { tlUpsWellKnownAlarms 5 }
|
|
|
|
tlUpsAlarmLoadOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The load is off."
|
|
::= { tlUpsWellKnownAlarms 6 }
|
|
|
|
tlUpsAlarmUserDefined OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A user-defined event is in alarm."
|
|
::= { tlUpsWellKnownAlarms 7 }
|
|
|
|
tlUpsAlarmBatteryBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more batteries have been determined to require
|
|
replacement."
|
|
::= { tlUpsWellKnownAlarms 8 }
|
|
|
|
tlUpsAlarmOnBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS is drawing power from the batteries."
|
|
::= { tlUpsWellKnownAlarms 9 }
|
|
|
|
tlUpsAlarmLowBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remaining battery run-time is less than or equal
|
|
to upsConfigLowBattTime."
|
|
::= { tlUpsWellKnownAlarms 10 }
|
|
|
|
tlUpsAlarmDepletedBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will be unable to sustain the present load
|
|
when and if the utility power is lost."
|
|
::= { tlUpsWellKnownAlarms 11 }
|
|
|
|
tlUpsAlarmTempBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature is out of tolerance."
|
|
::= { tlUpsWellKnownAlarms 12 }
|
|
|
|
tlUpsAlarmInputBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An input condition is out of tolerance."
|
|
::= { tlUpsWellKnownAlarms 13 }
|
|
|
|
tlUpsAlarmOutputBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An output condition (other than OutputOverload) is
|
|
out of tolerance."
|
|
::= { tlUpsWellKnownAlarms 14 }
|
|
|
|
tlUpsAlarmOutputOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output load exceeds the UPS output capacity."
|
|
::= { tlUpsWellKnownAlarms 15 }
|
|
|
|
tlUpsAlarmOnBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is presently engaged on the UPS."
|
|
::= { tlUpsWellKnownAlarms 16 }
|
|
|
|
tlUpsAlarmBypassBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass is out of tolerance."
|
|
::= { tlUpsWellKnownAlarms 17 }
|
|
|
|
tlUpsAlarmOutputOffAsRequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has shutdown as requested, i.e., the output
|
|
is off."
|
|
::= { tlUpsWellKnownAlarms 18 }
|
|
|
|
tlUpsAlarmUpsOffAsRequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The entire UPS has shutdown as commanded."
|
|
::= { tlUpsWellKnownAlarms 19 }
|
|
|
|
tlUpsAlarmChargerFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An uncorrected problem has been detected within the
|
|
UPS charger subsystem."
|
|
::= { tlUpsWellKnownAlarms 20 }
|
|
|
|
tlUpsAlarmUpsOutputOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output of the UPS is in the off state."
|
|
::= { tlUpsWellKnownAlarms 21 }
|
|
|
|
tlUpsAlarmUpsSystemOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS system is in the off state."
|
|
::= { tlUpsWellKnownAlarms 22 }
|
|
|
|
tlUpsAlarmFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fans in the UPS has been
|
|
detected."
|
|
::= { tlUpsWellKnownAlarms 23 }
|
|
|
|
tlUpsAlarmFuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The failure of one or more fuses has been detected."
|
|
::= { tlUpsWellKnownAlarms 24 }
|
|
|
|
tlUpsAlarmGeneralFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected."
|
|
::= { tlUpsWellKnownAlarms 25 }
|
|
|
|
tlUpsAlarmDiagnosticTestFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The result of the last diagnostic test indicates a
|
|
failure."
|
|
::= { tlUpsWellKnownAlarms 26 }
|
|
|
|
tlUpsAlarmCommunicationsLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem has been encountered in the communications
|
|
between the agent and the UPS."
|
|
::= { tlUpsWellKnownAlarms 27 }
|
|
|
|
tlUpsAlarmAwaitingPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the
|
|
return of input power."
|
|
::= { tlUpsWellKnownAlarms 28 }
|
|
|
|
tlUpsAlarmShutdownPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A upsShutdownAfterDelay countdown is underway."
|
|
::= { tlUpsWellKnownAlarms 29 }
|
|
|
|
tlUpsAlarmShutdownImminent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS will turn off power to the load in less than
|
|
5 seconds; this may be either a timed shutdown or a
|
|
low battery shutdown."
|
|
::= { tlUpsWellKnownAlarms 30 }
|
|
|
|
tlUpsAlarmTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A test is in progress, as initiated and indicated by
|
|
the Test Group. Tests initiated via other
|
|
implementation-specific mechanisms can indicate the
|
|
presence of the testing in the alarm table, if
|
|
desired, via a OBJECT-IDENTITY macro in the MIB
|
|
document specific to that implementation and are
|
|
outside the scope of this OBJECT-IDENTITY."
|
|
::= { tlUpsWellKnownAlarms 31 }
|
|
|
|
tlUpsAlarmCircuitBreaker1Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #1 is open."
|
|
::= { tlUpsWellKnownAlarms 32 }
|
|
|
|
tlUpsAlarmCircuitBreaker2Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #2 is open."
|
|
::= { tlUpsWellKnownAlarms 33 }
|
|
|
|
tlUpsAlarmCircuitBreaker3Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #3 is open."
|
|
::= { tlUpsWellKnownAlarms 34 }
|
|
|
|
tlUpsAlarmCircuitBreaker4Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #4 is open."
|
|
::= { tlUpsWellKnownAlarms 35 }
|
|
|
|
tlUpsAlarmCircuitBreaker5Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #5 is open."
|
|
::= { tlUpsWellKnownAlarms 36 }
|
|
|
|
tlUpsAlarmCircuitBreaker6Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #6 is open."
|
|
::= { tlUpsWellKnownAlarms 37 }
|
|
|
|
tlUpsAlarmCircuitBreaker7Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #7 is open."
|
|
::= { tlUpsWellKnownAlarms 38 }
|
|
|
|
tlUpsAlarmCircuitBreaker8Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Circuit breakers #8 is open."
|
|
::= { tlUpsWellKnownAlarms 39 }
|
|
|
|
tlUpsAlarmCurrent1AboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output current on line 1 exceeds load limits."
|
|
::= { tlUpsWellKnownAlarms 40 }
|
|
|
|
tlUpsAlarmCurrent2AboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output current on line 2 exceeds load limits."
|
|
::= { tlUpsWellKnownAlarms 41 }
|
|
|
|
tlUpsAlarmCurrent3AboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output current on line 3 exceeds load limits."
|
|
::= { tlUpsWellKnownAlarms 42 }
|
|
|
|
tlUpsAlarmRuntimeBelowWarningLevel OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery seconds remaining is below warning level."
|
|
::= { tlUpsWellKnownAlarms 43 }
|
|
|
|
tlUpsAlarmBusStartVoltageLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter start up bus voltage is too low."
|
|
::= { tlUpsWellKnownAlarms 44 }
|
|
|
|
tlUpsAlarmBusOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter bus voltage is too high."
|
|
::= { tlUpsWellKnownAlarms 45 }
|
|
|
|
tlUpsAlarmBusUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter bus voltage is too low."
|
|
::= { tlUpsWellKnownAlarms 46 }
|
|
|
|
tlUpsAlarmBusVoltageUnbalanced OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter bus voltage is not balanced."
|
|
::= { tlUpsWellKnownAlarms 47 }
|
|
|
|
tlUpsAlarmInverterSoftStartBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter bus voltage cannot reach desired voltage within a
|
|
specified duration."
|
|
::= { tlUpsWellKnownAlarms 48 }
|
|
|
|
tlUpsAlarmInverterOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter voltage is too high."
|
|
::= { tlUpsWellKnownAlarms 49 }
|
|
|
|
tlUpsAlarmInverterUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter voltage is too low."
|
|
::= { tlUpsWellKnownAlarms 50 }
|
|
|
|
tlUpsAlarmInverterCircuitBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter output is shorted."
|
|
::= { tlUpsWellKnownAlarms 51 }
|
|
|
|
tlUpsAlarmBatteryOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery voltage is too high."
|
|
::= { tlUpsWellKnownAlarms 52 }
|
|
|
|
tlUpsAlarmBatteryUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery voltage is too low."
|
|
::= { tlUpsWellKnownAlarms 53 }
|
|
|
|
tlUpsAlarmSiteWiringFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The utility input wiring is faulty."
|
|
::= { tlUpsWellKnownAlarms 54 }
|
|
|
|
tlUpsAlarmOverTemperatureProtection OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The over temperature protection is activated."
|
|
::= { tlUpsWellKnownAlarms 55 }
|
|
|
|
tlUpsAlarmOverCharged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS is over charged."
|
|
::= { tlUpsWellKnownAlarms 56 }
|
|
|
|
tlUpsAlarmEPOActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The EPO is currently activate."
|
|
::= { tlUpsWellKnownAlarms 57 }
|
|
|
|
tlUpsAlarmBypassFrequencyBad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass frequency is out of tolerance."
|
|
::= { tlUpsWellKnownAlarms 58 }
|
|
|
|
tlUpsAlarmExternalSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more external smart batteries have been determined to require
|
|
replacement."
|
|
::= { tlUpsWellKnownAlarms 59 }
|
|
|
|
tlUpsAlarmExternalNonSmartBatteryAgeAboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more external non-smart batteries have been determined to require
|
|
replacement."
|
|
::= { tlUpsWellKnownAlarms 60 }
|
|
|
|
tlUpsAlarmSmartBatteryCommLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communications with the smart batteries was lost."
|
|
::= { tlUpsWellKnownAlarms 61 }
|
|
|
|
tlUpsAlarmSourceAOutage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input power source A is not present."
|
|
::= { tlUpsWellKnownAlarms 62 }
|
|
|
|
tlUpsAlarmSourceBOutage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input power source B is not present."
|
|
::= { tlUpsWellKnownAlarms 63 }
|
|
|
|
tlUpsAlarmWatchdogReset OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The internal watchdog triggered a reset of the device."
|
|
::= { tlUpsWellKnownAlarms 64 }
|
|
|
|
tlUpsAlarmDevName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The name of the device, tlDevName, corresponding to the device that is
|
|
associated with this alarm."
|
|
::= { tlUpsAlarm 7 }
|
|
|
|
tlUpsAlarmDevLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The location of the device, tlDevLocation, corresponding to the device
|
|
that is associated with this alarm."
|
|
::= { tlUpsAlarm 8 }
|
|
|
|
tlUpsAlarmCategory OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The category, tlDevEvtCategory, of this alarm."
|
|
::= { tlUpsAlarm 9 }
|
|
|
|
tlUpsTest OBJECT IDENTIFIER ::= { tlUpsObjects 7 }
|
|
|
|
tlUpsTestDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date of the last self-test run on the ups, in the
|
|
format YYYYMMDD."
|
|
::= { tlUpsTest 1 }
|
|
|
|
tlUpsTestResultsDetail OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Result of the last self-test run on the ups."
|
|
::= { tlUpsTest 2 }
|
|
|
|
tlUpsControl OBJECT IDENTIFIER ::= { tlUpsObjects 8 }
|
|
|
|
tlUpsWatchdogSupported OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether or not this UPS supports a watchdog reboot."
|
|
::= { tlUpsControl 1 }
|
|
|
|
|
|
tlUpsWatchdogSecsBeforeReboot OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum number of seconds that can expire between polls that
|
|
the engine makes to the UPS for data. If this time runs out, then
|
|
the UPS will cycle its outputs. Set this to zero to turns disable
|
|
this feature."
|
|
::= { tlUpsControl 2 }
|
|
|
|
tlUpsWellKnownControls OBJECT IDENTIFIER ::= { tlUpsControl 3 }
|
|
|
|
tlUpsControlSelfTest OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set to TRUE to initiate Self Test"
|
|
::= { tlUpsWellKnownControls 1 }
|
|
|
|
tlUpsControlRamp OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set to TRUE to initiate Ramp"
|
|
::= { tlUpsWellKnownControls 2 }
|
|
|
|
tlUpsControlShed OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set to TRUE to initiate Shed"
|
|
::= { tlUpsWellKnownControls 3 }
|
|
|
|
tlUpsControlUpsOn OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set to TRUE to turn UPS on"
|
|
::= { tlUpsWellKnownControls 4 }
|
|
|
|
tlUpsControlUpsOff OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set to TRUE to turn UPS off"
|
|
::= { tlUpsWellKnownControls 5 }
|
|
|
|
tlUpsConfig OBJECT IDENTIFIER ::= { tlUpsObjects 9 }
|
|
|
|
tlUpsConfigBattReplDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date on which the battery was last replaced, in the format
|
|
YYYYMMDD."
|
|
::= { tlUpsConfig 1 }
|
|
|
|
-- Deprecated, interface no longer supported.
|
|
--
|
|
-- tlUpsConfigTftpGetAddr OBJECT-TYPE
|
|
-- SYNTAX IpAddress
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The IP address of the TFTP server you wish to acquire a config ini file from, non persistent, 0.0.0.0 when empty"
|
|
-- ::= { tlUpsConfig 2 }
|
|
--
|
|
-- tlUpsConfigTftpGetAcction OBJECT-TYPE
|
|
-- SYNTAX INTEGER {
|
|
-- get(1),
|
|
-- getting(2),
|
|
-- idle(3) }
|
|
-- MAX-ACCESS read-write
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "setting this entry to get(1) will start a down load from the specified address, during the download this entry
|
|
-- will read getting(2), when finished, the card will reboot to the new ini supplied parms. At all other times this
|
|
-- entry will read idle(3)"
|
|
-- ::= { tlUpsConfig 3 }
|
|
|
|
tlUpsConfigDisplayUnits OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
english(0),
|
|
metric(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects English or Metric display for all readings. This selection may not
|
|
be available on all devices. Further, some devices may support this selection,
|
|
but not via a software selector. In this latter case, selections must be
|
|
performed on the device itself."
|
|
::= { tlUpsConfig 4 }
|
|
|
|
tlUpsConfigExternalBattReplDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The date on which the external battery was last replaced, in the format
|
|
YYYYMMDD."
|
|
::= { tlUpsConfig 5 }
|
|
|
|
tlUpsOutlet OBJECT IDENTIFIER ::= { tlUpsObjects 10 }
|
|
|
|
tlUpsOutletNumOutlets OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of available Outlets in this device."
|
|
::= { tlUpsOutlet 1 }
|
|
|
|
tlUpsOutletTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlUpsOutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of all device Outlets for all devices."
|
|
::= { tlUpsOutlet 2 }
|
|
|
|
tlUpsOutletEntry OBJECT-TYPE
|
|
SYNTAX TlUpsOutletEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing Outlet information applicable to a particular
|
|
device managed by this agent."
|
|
INDEX {
|
|
tlUpsOutletIndex }
|
|
::= { tlUpsOutletTable 1 }
|
|
|
|
TlUpsOutletEntry ::= SEQUENCE {
|
|
tlUpsOutletIndex PositiveInteger,
|
|
tlUpsOutletState INTEGER,
|
|
tlUpsOutletType Integer32,
|
|
tlUpsOutletControl INTEGER,
|
|
tlUpsOutletName DisplayString,
|
|
tlUpsOutletRampAction INTEGER,
|
|
tlUpsOutletRampDataType INTEGER,
|
|
tlUpsOutletRampData Integer32,
|
|
tlUpsOutletShedAction INTEGER,
|
|
tlUpsOutletShedDataType INTEGER,
|
|
tlUpsOutletShedData Integer32,
|
|
tlUpsOutletGroupNdx Integer32,
|
|
tlUpsOutletCurrent PositiveInteger,
|
|
tlUpsOutletPower PositiveInteger }
|
|
|
|
tlUpsOutletIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index number of this Outlet for the device
|
|
indicated by tlDeviceIndex."
|
|
::= { tlUpsOutletEntry 1 }
|
|
|
|
tlUpsOutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
off(1),
|
|
on(2) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the Outlet."
|
|
::= { tlUpsOutletEntry 2 }
|
|
|
|
tlUpsOutletType OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a bit field that indicates the type of this Outlet.
|
|
When 0, the outlet is not controllable and has none of the
|
|
other features indicated in the bit map. When non-zero,
|
|
the features present for this outlet can be interpreted with the
|
|
definition.
|
|
|
|
Bit Display
|
|
0 Reserved, may be 1 or 0
|
|
1 Controllable
|
|
2
|
|
3
|
|
4
|
|
5
|
|
6
|
|
7
|
|
8
|
|
9
|
|
10
|
|
11
|
|
12
|
|
13
|
|
14
|
|
15
|
|
"
|
|
::= { tlUpsOutletEntry 3 }
|
|
|
|
tlUpsOutletControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOff(1),
|
|
turnOn(2),
|
|
cycle(3) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Controls the state of the Outlet."
|
|
::= { tlUpsOutletEntry 4 }
|
|
|
|
tlUpsOutletName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A string identifying the devices attached to the
|
|
output(s) of the device."
|
|
::= { tlUpsOutletEntry 5 }
|
|
|
|
|
|
tlUpsOutletRampAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
remainOff(0),
|
|
turnOnAfterDelay(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ramp action to take on the Outlet."
|
|
::= { tlUpsOutletEntry 6 }
|
|
|
|
tlUpsOutletRampDataType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
delayInSeconds(0)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of data associated with ramp action."
|
|
::= { tlUpsOutletEntry 7 }
|
|
|
|
tlUpsOutletRampData OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The data value associated with type of ramp data."
|
|
::= { tlUpsOutletEntry 8 }
|
|
|
|
tlUpsOutletShedAction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
remainOn(0),
|
|
turnOffAfterDelay(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The shed action to take on the Outlet."
|
|
::= { tlUpsOutletEntry 9 }
|
|
|
|
tlUpsOutletShedDataType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
delayInSeconds(0)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of data associated with shed action."
|
|
::= { tlUpsOutletEntry 10 }
|
|
|
|
tlUpsOutletShedData OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The data value associated with type of shed data."
|
|
::= { tlUpsOutletEntry 11 }
|
|
|
|
tlUpsOutletGroupNdx OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"tlUpsOutletGroupIndex of corresponding outlet group, or 0 if ungrouped."
|
|
::= { tlUpsOutletEntry 12 }
|
|
|
|
tlUpsOutletCurrent OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
UNITS "0.1 RMS Amp"
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of this outlet's current, represented as 0.1A."
|
|
::= { tlUpsOutletEntry 13 }
|
|
|
|
tlUpsOutletPower OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of this outlet's power in watts."
|
|
::= { tlUpsOutletEntry 14 }
|
|
|
|
|
|
tlUpsOutletGroup OBJECT IDENTIFIER ::= { tlUpsObjects 11 }
|
|
|
|
tlUpsOutletNumOutletGroups OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of available Outlet Groups in this device."
|
|
::= { tlUpsOutletGroup 1 }
|
|
|
|
tlUpsOutletGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlUpsOutletGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of device outlet group entries. The number of entries is
|
|
given by the value of tlUpsOutletNumOutletGroups."
|
|
::= { tlUpsOutletGroup 2 }
|
|
|
|
tlUpsOutletGroupEntry OBJECT-TYPE
|
|
SYNTAX TlUpsOutletGroupEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing outlet group information applicable
|
|
to a particular device managed by this agent"
|
|
INDEX { tlUpsOutletGroupIndex }
|
|
::= { tlUpsOutletGroupTable 1 }
|
|
|
|
TlUpsOutletGroupEntry ::= SEQUENCE {
|
|
tlUpsOutletGroupIndex PositiveInteger,
|
|
tlUpsOutletGroupRowStatus RowStatus,
|
|
tlUpsOutletGroupName DisplayString,
|
|
tlUpsOutletGroupDesc DisplayString,
|
|
tlUpsOutletGroupState INTEGER,
|
|
tlUpsOutletGroupControl INTEGER }
|
|
|
|
tlUpsOutletGroupIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index number of this load group for the device."
|
|
::= { tlUpsOutletGroupEntry 1 }
|
|
|
|
tlUpsOutletGroupRowStatus OBJECT-TYPE
|
|
SYNTAX RowStatus
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Row status for the tlUpsOutletGroupTable"
|
|
::= { tlUpsOutletGroupEntry 2 }
|
|
|
|
tlUpsOutletGroupName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of this outlet group."
|
|
::= { tlUpsOutletGroupEntry 3 }
|
|
|
|
tlUpsOutletGroupDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A description for this outlet group."
|
|
::= { tlUpsOutletGroupEntry 4 }
|
|
|
|
tlUpsOutletGroupState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
off(1),
|
|
on(2),
|
|
mixed(3) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the outlet group."
|
|
::= { tlUpsOutletGroupEntry 5 }
|
|
|
|
tlUpsOutletGroupControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOff(1),
|
|
turnOn(2),
|
|
cycle(3) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Controls the state of every outlet associated with the group."
|
|
::= { tlUpsOutletGroupEntry 6 }
|
|
|
|
tlUpsMainOutlet OBJECT IDENTIFIER ::= { tlUpsObjects 12 }
|
|
|
|
tlUpsMainOutletState OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(0),
|
|
off(1),
|
|
on(2),
|
|
mixed(3) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current state of the main output of the device."
|
|
::= { tlUpsMainOutlet 1 }
|
|
|
|
|
|
tlUpsMainOutletControllable OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if this device has controllable outlets"
|
|
::= { tlUpsMainOutlet 2 }
|
|
|
|
tlUpsMainOutletControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
idle(0),
|
|
turnOff(1),
|
|
turnOn(2),
|
|
cycle(3) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Controls the state of the main outlet of the device."
|
|
::= { tlUpsMainOutlet 3 }
|
|
|
|
tlUpsEnvironment OBJECT IDENTIFIER ::= { tlUpsObjects 13 }
|
|
|
|
tlUpsTemperature OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature. The measurement returned will either be in
|
|
units of Celsius (C) or Fahrenheit (F) depending upon whether Metric
|
|
or English was selected for the reading by tlUpsConfigDisplayUnits."
|
|
::= { tlUpsEnvironment 1 }
|
|
|
|
|
|
---------------------------------------------------------------
|
|
-- UPS traps
|
|
---------------------------------------------------------------
|
|
|
|
tlUpsTraps OBJECT IDENTIFIER ::= { tlUPS 2 }
|
|
|
|
tlUpsTrapAlarmEntryAddedV1 TRAP-TYPE
|
|
ENTERPRISE tlUpsTraps
|
|
VARIABLES { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
|
|
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is inserted into
|
|
to the alarm table."
|
|
--#SUMMARY "UPS Alarm: %s - %s."
|
|
--#ARGUMENTS {6, 2}
|
|
--#SEVERITY WARNING
|
|
::= 3
|
|
|
|
tlUpsTrapAlarmEntryAdded NOTIFICATION-TYPE
|
|
OBJECTS { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
|
|
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is inserted into
|
|
to the alarm table."
|
|
--#SUMMARY "UPS Alarm: %s - %s."
|
|
--#ARGUMENTS {6, 2}
|
|
--#SEVERITY WARNING
|
|
::= { tlUpsTraps 3 }
|
|
|
|
tlUpsTrapAlarmEntryRemovedV1 TRAP-TYPE
|
|
ENTERPRISE tlUpsTraps
|
|
VARIABLES { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
|
|
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is removed from
|
|
the alarm table."
|
|
--#SUMMARY "UPS Alarm: %s - %s."
|
|
--#ARGUMENTS {6, 2}
|
|
--#SEVERITY WARNING
|
|
::= 4
|
|
|
|
tlUpsTrapAlarmEntryRemoved NOTIFICATION-TYPE
|
|
OBJECTS { tlUpsAlarmId, tlUpsAlarmDescr, tlUpsAlarmDetail, tlUpsAlarmDeviceId,
|
|
tlUpsAlarmDeviceName, tlUpsAlarmLocation, tlUpsAlarmGroup }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This trap is sent each time an alarm is removed from
|
|
the alarm table."
|
|
--#SUMMARY "UPS Alarm: %s - %s."
|
|
--#ARGUMENTS {6, 2}
|
|
--#SEVERITY WARNING
|
|
::= { tlUpsTraps 4 }
|
|
|
|
--------------------------------------------------------------------------
|
|
--------------------------------------------------------------------------
|
|
-- begin new traps
|
|
--------------------------------------------------------------------------
|
|
--------------------------------------------------------------------------
|
|
|
|
tlUpsTrapSystemStartup NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Used to inform another entity of an engine's startup. The varbinds that follow are:
|
|
|
|
OBJ1 = tlEngineType
|
|
Obj1Value = The type of engine providing this data
|
|
OBJ2 = tlEngineSoftwareVersion
|
|
Obj2Value = The current version of the engine
|
|
OBJ3 = tlEngineMACAddr
|
|
Obj3Value = The MAC address of the engine
|
|
OBJ4 = tlUpsSnmpCardSerialNum
|
|
Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC]
|
|
|
|
--- if this trap is extended, place all static OIDs above this mark. all objects below
|
|
--- the number of devices (tlNumDevices) is explicit as per device for enumeration by
|
|
--- the target receiver
|
|
|
|
OBJ5 = tlNumDevices
|
|
Obj5Value = The number of devices attached
|
|
|
|
--- The following objects will be replicated per each device:
|
|
|
|
OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device
|
|
Obj6Value = The device's manufacturer
|
|
OBJ7 = The OID for an entry of tlDevModel, indexed by device
|
|
Obj7Value = The device's model name
|
|
OBJ8 = The OID for an entry of tlDevName, indexed by device
|
|
Obj8Value = The device's display name
|
|
OBJ9 = The OID for an entry of tlDevLocation, indexed by device
|
|
Obj9Value = The device's location
|
|
OBJ10 = The OID for an entry of tlDevRegion, indexed by device
|
|
Obj10Value= The device's region
|
|
OBJ11 = The OID for an entry of tlDevProtocol, indexed by device
|
|
Obj11Value= The device's protocol (display string format)
|
|
"
|
|
::= { tlUpsTraps 5 }
|
|
|
|
tlUpsTrapSystemShutdown NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Used to inform another entity of an engine's startup. The varbinds that follow are:
|
|
|
|
OBJ1 = tlEngineType
|
|
Obj1Value = The type of engine providing this data
|
|
OBJ2 = tlEngineSoftwareVersion
|
|
Obj2Value = The current version of the engine
|
|
OBJ3 = tlEngineMACAddr
|
|
Obj3Value = The MAC address of the engine
|
|
OBJ4 = tlUpsSnmpCardSerialNum
|
|
Obj4Value = The serial number of the SNMPWEBCARD [should be 0 on PC]
|
|
|
|
--- if this trap is extended, place all static OIDs above this mark. all objects below
|
|
--- the number of devices (tlNumDevices) is explicit as per device for enumeration by
|
|
--- the target receiver
|
|
|
|
OBJ5 = tlNumDevices
|
|
Obj5Value = The number of devices attached
|
|
|
|
--- The following objects will be replicated per each device:
|
|
|
|
OBJ6 = The OID for an entry of tlDevManufacturer, indexed by device
|
|
Obj6Value = The device's manufacturer
|
|
OBJ7 = The OID for an entry of tlDevModel, indexed by device
|
|
Obj7Value = The device's model name
|
|
OBJ8 = The OID for an entry of tlDevName, indexed by device
|
|
Obj8Value = The device's display name
|
|
OBJ9 = The OID for an entry of tlDevLocation, indexed by device
|
|
Obj9Value = The device's location
|
|
OBJ10 = The OID for an entry of tlDevRegion, indexed by device
|
|
Obj10Value= The device's region
|
|
OBJ11 = The OID for an entry of tlDevProtocol, indexed by device
|
|
Obj11Value= The device's protocol (display string format)
|
|
"
|
|
::= { tlUpsTraps 6 }
|
|
|
|
--------------------------------------------------------------------------
|
|
--------------------------------------------------------------------------
|
|
--- end new traps
|
|
--------------------------------------------------------------------------
|
|
--------------------------------------------------------------------------
|
|
--------------------------------------------------------------------------
|
|
-- EnviroSense Device
|
|
--------------------------------------------------------------------------
|
|
|
|
tlEnviroSense OBJECT IDENTIFIER ::= { tripplite 101 }
|
|
|
|
tlEnvEnvironment OBJECT IDENTIFIER ::= { tlEnviroSense 1 }
|
|
|
|
tlEnvTemperatureData OBJECT IDENTIFIER ::= { tlEnvEnvironment 1 }
|
|
|
|
tlEnvTemperatureC OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature (C)."
|
|
::= { tlEnvTemperatureData 1 }
|
|
|
|
tlEnvTemperatureF OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature (F)."
|
|
::= { tlEnvTemperatureData 2 }
|
|
|
|
tlEnvTemperatureLowLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The lower alarm limit for ambient temperature (F)."
|
|
::= { tlEnvTemperatureData 3 }
|
|
|
|
tlEnvTemperatureHighLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upper alarm limit for ambient temperature (F)."
|
|
::= { tlEnvTemperatureData 4 }
|
|
|
|
tlEnvTemperatureInAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether or not temperature is in alarm."
|
|
::= { tlEnvTemperatureData 5 }
|
|
|
|
tlEnvHumidityData OBJECT IDENTIFIER ::= { tlEnvEnvironment 2 }
|
|
|
|
tlEnvHumidity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient humidity (%)."
|
|
::= { tlEnvHumidityData 1 }
|
|
|
|
tlEnvHumidityLowLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The lower alarm limit for ambient humidity (%)."
|
|
::= { tlEnvHumidityData 2 }
|
|
|
|
tlEnvHumidityHighLimit OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The upper alarm limit for ambient humidity (%)."
|
|
::= { tlEnvHumidityData 3 }
|
|
|
|
tlEnvHumidityInAlarm OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates whether or not humidity is in alarm."
|
|
::= { tlEnvHumidityData 4 }
|
|
|
|
tlEnvContacts OBJECT IDENTIFIER ::= { tlEnviroSense 2 }
|
|
|
|
tlEnvContactTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TlEnvContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A table of contacts."
|
|
::= { tlEnvContacts 1 }
|
|
|
|
tlEnvContactEntry OBJECT-TYPE
|
|
SYNTAX TlEnvContactEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a particular contact."
|
|
INDEX {
|
|
tlEnvContactIndex }
|
|
::= { tlEnvContactTable 1 }
|
|
|
|
TlEnvContactEntry ::= SEQUENCE {
|
|
tlEnvContactIndex PositiveInteger,
|
|
tlEnvContactName DisplayString,
|
|
tlEnvContactStatus INTEGER,
|
|
tlEnvContactConfig INTEGER }
|
|
|
|
tlEnvContactIndex OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The table row index for the contact."
|
|
::= { tlEnvContactEntry 1 }
|
|
|
|
tlEnvContactName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name or description of the contact."
|
|
::= { tlEnvContactEntry 2 }
|
|
|
|
tlEnvContactStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
alarm(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current status of the contact."
|
|
::= { tlEnvContactEntry 3 }
|
|
|
|
tlEnvContactConfig OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normallyOpen(0),
|
|
normallyClosed(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The configuration of the contact."
|
|
::= { tlEnvContactEntry 4 }
|
|
|
|
|
|
--------------------------------------------------------------------------
|
|
-- KVM over IP Device
|
|
--------------------------------------------------------------------------
|
|
|
|
-- this is a 3rd party MIB structure located at { tripplite 102 }
|
|
|
|
--------------------------------------------------------------------------
|
|
-- SR Cooling Device
|
|
--------------------------------------------------------------------------
|
|
|
|
tlCooling OBJECT IDENTIFIER ::= { tripplite 103 }
|
|
|
|
tlCoolingEnvironment OBJECT IDENTIFIER ::= { tlCooling 1 }
|
|
|
|
tlCoolingIdent OBJECT IDENTIFIER ::= { tlCoolingEnvironment 1 }
|
|
|
|
tlCoolingModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The model name for the AC Unit."
|
|
::= { tlCoolingIdent 1}
|
|
|
|
tlCoolingManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The manufacturer of the AC Unit."
|
|
::= { tlCoolingIdent 2 }
|
|
|
|
tlCoolingSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number of the AC unit."
|
|
::= { tlCoolingIdent 3 }
|
|
|
|
tlCoolingFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The firmware version of the AC Unit."
|
|
::= { tlCoolingIdent 4 }
|
|
|
|
tlCoolingHostSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The hardware version of the AC unit."
|
|
::= { tlCoolingIdent 5 }
|
|
|
|
tlCoolingName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user defined name for the AC Unit."
|
|
::= { tlCoolingIdent 6 }
|
|
|
|
tlCoolingLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user defined location of the AC Unit."
|
|
::= { tlCoolingIdent 7 }
|
|
|
|
tlCoolingStatus OBJECT IDENTIFIER ::= { tlCoolingEnvironment 2 }
|
|
|
|
tlCoolingCondOutletTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser outlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 1 }
|
|
|
|
tlCoolingCondInletTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser inlet air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 2 }
|
|
|
|
tlCoolingRefrigerantTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature of the refrigerant in the suction line. This is displayed in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 3 }
|
|
|
|
tlCoolingEvapSurfaceTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The surface temperature of the evaporator in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 4}
|
|
|
|
tlCoolingSuctionPressure OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure of the compressor suction line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 5}
|
|
|
|
tlCoolingDischargePressure OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure of the compressor discharge line in tenths of (Mpa/psi) depending on the value of tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 6}
|
|
|
|
tlCoolingEvapFanSpeed OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
low(1),
|
|
medLow(2),
|
|
med (3),
|
|
medHi (4),
|
|
hi (5) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current speed of the evaporator fan."
|
|
::= { tlCoolingStatus 7}
|
|
|
|
tlCoolingCondFanSpeed OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(0),
|
|
low(1),
|
|
hi (2) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current speed of the condenser fan."
|
|
::= { tlCoolingStatus 8}
|
|
|
|
tlCoolingCompFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The operating frequency of the compressor in tenths of Arms."
|
|
::= { tlCoolingStatus 9}
|
|
|
|
tlCoolingEEVPercentage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The opening percentage of the EEV."
|
|
::= { tlCoolingStatus 10}
|
|
|
|
tlCoolingUnitCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The the total current draw of the unit in tenths of Arms."
|
|
::= { tlCoolingStatus 11}
|
|
|
|
tlCoolingFanCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Thethe current draw of the Evaporator and Condenser fans in tents of Arms."
|
|
::= { tlCoolingStatus 12 }
|
|
|
|
tlCoolingCompCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The operating current of the compressor in Arms."
|
|
::= { tlCoolingStatus 13}
|
|
|
|
tlCoolingReturnAirTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 14 }
|
|
|
|
tlCoolingSuctionTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature of the compressor suction line in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 15 }
|
|
|
|
tlCoolingSupplyAirTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply air temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlCoolingDisplayUnits."
|
|
::= { tlCoolingStatus 16 }
|
|
|
|
tlCoolingRunTimes OBJECT IDENTIFIER ::= { tlCoolingEnvironment 3 }
|
|
|
|
tlCoolingAirFilterRunHours OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total hours the air filter has been under operation."
|
|
::= { tlCoolingRunTimes 1 }
|
|
|
|
tlCoolingEvapFanRunDays OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total days the evaporator fan has been under operation."
|
|
::= { tlCoolingRunTimes 2 }
|
|
|
|
tlCoolingCondFanRunDays OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total days the condenser fan has been under operation."
|
|
::= { tlCoolingRunTimes 3 }
|
|
|
|
tlCoolingCompressorRunDays OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total days the compressor has been under operation."
|
|
::= { tlCoolingRunTimes 4 }
|
|
|
|
tlCoolingCondPumpRunDays OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total days the condensate pump has been under operation."
|
|
::= { tlCoolingRunTimes 5 }
|
|
|
|
tlCoolingAtomizerRunDays OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total days the atomizer has been under operation."
|
|
::= { tlCoolingRunTimes 6 }
|
|
|
|
tlCoolingConfig OBJECT IDENTIFIER ::= { tlCoolingEnvironment 4 }
|
|
|
|
tlCoolingOnOff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOffUnit(0),
|
|
turnOnUnit(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Turn the unit off or on."
|
|
::= { tlCoolingConfig 1 }
|
|
|
|
tlCoolingSetPointTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The set point temperature the unit will control the temperature to in tenths of degrees in Celsius or Fahrenheit based upon tleCoolDisplayUnits."
|
|
::= { tlCoolingConfig 2 }
|
|
|
|
tlCoolingAutoStart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Specified if the unit should start automatically on power up."
|
|
::= { tlCoolingConfig 3 }
|
|
|
|
tlCoolingFanSpeedOverride OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
autoFanSpeed(0),
|
|
low(1),
|
|
medLow(2),
|
|
med(3),
|
|
medHi(4),
|
|
hi(5) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Speed of evaporator fan set by the user."
|
|
::= { tlCoolingConfig 4 }
|
|
|
|
tlCoolingControlType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
returnAirTemp(0),
|
|
remoteTemperature(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Which temperature to be used as a control point."
|
|
::= { tlCoolingConfig 5 }
|
|
|
|
tlCoolingCurrentRemoteTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external remote temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlCoolingDisplayUnits"
|
|
::= { tlCoolingConfig 6 }
|
|
|
|
tlCoolingDisplayUnits OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
metric(0),
|
|
english(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects English or Metric display for all readings."
|
|
::= { tlCoolingConfig 7 }
|
|
|
|
tlCoolingBeepOnKey OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noBeep(0),
|
|
beepOn(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if the display sounds a beep when a key is pressed."
|
|
::= { tlCoolingConfig 8 }
|
|
|
|
tlCoolingOutputRelaySource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
allAlarmsAndWarnings(1),
|
|
criticalAlarmsOnly(2) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The alarm level that causes the ouput relay to activate."
|
|
::= { tlCoolingConfig 9 }
|
|
|
|
tlCoolingOffOnLeak OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOff(0),
|
|
alarmOnly(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if the unit should stop cooling when leak input is activated."
|
|
::= { tlCoolingConfig 10 }
|
|
|
|
tlCoolingOffOnInputContact OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOff(0),
|
|
alarmOnly(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates if the unit should stop cooling when input contact is activated."
|
|
::= { tlCoolingConfig 11 }
|
|
|
|
tlCoolingInputContactType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
ncRelay(0),
|
|
noRelay(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input contact type."
|
|
::= { tlCoolingConfig 12 }
|
|
|
|
tlCoolingOutputRelayDefault OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
nc(0),
|
|
no(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Type of contact to make when output relay is activated."
|
|
::= { tlCoolingConfig 13 }
|
|
|
|
tlCoolingAirFilterInterval OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of weeks before the air filter needs to be changed."
|
|
::= { tlCoolingConfig 14 }
|
|
|
|
tlCoolingWaterLeakContactType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noRelay(0),
|
|
ncRelay(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input contact type."
|
|
::= { tlCoolingConfig 15 }
|
|
|
|
tlCoolingThresholds OBJECT IDENTIFIER ::= { tlCoolingEnvironment 5 }
|
|
|
|
tlCoolingMaxAirFilterRunHours OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maximum interval for air filter run hours before warning is annunciated."
|
|
::= { tlCoolingThresholds 1 }
|
|
|
|
tlCoolingEnableAirFilterAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(0),
|
|
enabled(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded."
|
|
::= { tlCoolingThresholds 2 }
|
|
|
|
tlCoolingMaxSupplyTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum allowed supply air temperature before firing an alarm."
|
|
::= { tlCoolingThresholds 3 }
|
|
|
|
tlCoolingMinSupplyTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Minimum allowed supply air temperature allowed before firing an alarm."
|
|
::= { tlCoolingThresholds 4 }
|
|
|
|
tlCoolingTempDiffAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum allowed air temperature deviation from set allowed before firing an alarm."
|
|
::= { tlCoolingThresholds 5 }
|
|
|
|
tlCoolingMaxReturnAirTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When enabled indicated that an alarm should occur when the maximum number of air filter run hours has been exceeded."
|
|
::= { tlCoolingThresholds 6 }
|
|
|
|
tlCoolingAlarm OBJECT IDENTIFIER ::= { tlCooling 6 }
|
|
|
|
tlCoolingWellKnownAlarms OBJECT IDENTIFIER ::= { tlCoolingAlarm 3 }
|
|
|
|
tlCoolingSupplyAirSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply air sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 1 }
|
|
|
|
tlCoolingReturnAirSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return air sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 2 }
|
|
|
|
tlCoolingCondenserInletAirSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser inlet air sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 3 }
|
|
|
|
tlCoolingCondenserOutletAirSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser outlet air sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 4 }
|
|
|
|
tlCoolingSuctionTemperatureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The suction temperature sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 5 }
|
|
|
|
tlCoolingEvaporatorTemperatureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator temperature sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 6 }
|
|
|
|
tlCoolingAirFilterClogged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air filter is clogged."
|
|
::= { tlCoolingWellKnownAlarms 7 }
|
|
|
|
tlCoolingAirFilterRunHoursViolation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air filter run hours was violated."
|
|
::= { tlCoolingWellKnownAlarms 8 }
|
|
|
|
tlCoolingSuctionPressureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The suction pressure sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 9 }
|
|
|
|
tlCoolingInverterCommunicationsFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter communications is in fault."
|
|
::= { tlCoolingWellKnownAlarms 10 }
|
|
|
|
tlCoolingRemoteShutdownViaInputContact OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A remote shutdown was triggerd by an input contact."
|
|
::= { tlCoolingWellKnownAlarms 11 }
|
|
|
|
tlCoolingCondensatePumpFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condensate pump is in fault."
|
|
::= { tlCoolingWellKnownAlarms 12 }
|
|
|
|
tlCoolingLowRefrigerantStartupFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The low refrigerant startup is in fault."
|
|
::= { tlCoolingWellKnownAlarms 13 }
|
|
|
|
tlCoolingCondenserFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser fan is in fault."
|
|
::= { tlCoolingWellKnownAlarms 14 }
|
|
|
|
tlCoolingCondenserFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser has failed."
|
|
::= { tlCoolingWellKnownAlarms 15 }
|
|
|
|
tlCoolingEvaporatorCoolingFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator cooling is in fault."
|
|
::= { tlCoolingWellKnownAlarms 16 }
|
|
|
|
tlCoolingReturnAirTempHigh OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return air temperature is high."
|
|
::= { tlCoolingWellKnownAlarms 17 }
|
|
|
|
tlCoolingSupplyAirTempHigh OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply air temperature is high."
|
|
::= { tlCoolingWellKnownAlarms 18 }
|
|
|
|
tlCoolingEvaporatorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator has failed."
|
|
::= { tlCoolingWellKnownAlarms 19 }
|
|
|
|
tlCoolingEvaporatorFreezeUp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator is frozen."
|
|
::= { tlCoolingWellKnownAlarms 20 }
|
|
|
|
tlCoolingDischargePressureHigh OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The discharge pressure is high."
|
|
::= { tlCoolingWellKnownAlarms 21 }
|
|
|
|
tlCoolingPressureGaugeFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure gauge has failed."
|
|
::= { tlCoolingWellKnownAlarms 22 }
|
|
|
|
tlCoolingDischargePressurePersistentHigh OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The discharge pressure is persistently high."
|
|
::= { tlCoolingWellKnownAlarms 23 }
|
|
|
|
tlCoolingSuctionPressureLowStartFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cannot start due to low suction pressure."
|
|
::= { tlCoolingWellKnownAlarms 24 }
|
|
|
|
tlCoolingSuctionPressureLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The suction pressure is low."
|
|
::= { tlCoolingWellKnownAlarms 25 }
|
|
|
|
tlCoolingSuctionPressurePersistentLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The suction pressure is persistently low."
|
|
::= { tlCoolingWellKnownAlarms 26 }
|
|
|
|
tlCoolingStartupLinePressureImbalance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The startup line pressure is in imbalance."
|
|
::= { tlCoolingWellKnownAlarms 27 }
|
|
|
|
tlCoolingCompressorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compressor has failed."
|
|
::= { tlCoolingWellKnownAlarms 28 }
|
|
|
|
tlCoolingCurrentLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current is out of range."
|
|
::= { tlCoolingWellKnownAlarms 29 }
|
|
|
|
tlCoolingWaterLeak OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water is leaking."
|
|
::= { tlCoolingWellKnownAlarms 30 }
|
|
|
|
tlCoolingFanUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan is under current."
|
|
::= { tlCoolingWellKnownAlarms 31 }
|
|
|
|
tlCoolingFanOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan is over current."
|
|
::= { tlCoolingWellKnownAlarms 32 }
|
|
|
|
tlCoolingDischargePressureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The discharge pressure sensor is in fault."
|
|
::= { tlCoolingWellKnownAlarms 33 }
|
|
|
|
tlCoolingWaterFull OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water is Full."
|
|
::= { tlCoolingWellKnownAlarms 34 }
|
|
|
|
tlCoolingAutoCoolingOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic cooling was activated to lower the temperature below the
|
|
remote set point."
|
|
::= { tlCoolingWellKnownAlarms 35 }
|
|
|
|
tlCoolingPowerButtonPressed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power button was pressed on the front panel."
|
|
::= { tlCoolingWellKnownAlarms 36 }
|
|
|
|
tlCoolingDisconnectedFromDevice OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device communications is disconnected."
|
|
::= { tlCoolingWellKnownAlarms 37 }
|
|
|
|
|
|
--------------------------------------------------------------------------
|
|
-- SRCOOLNET Device
|
|
--------------------------------------------------------------------------
|
|
|
|
tlSrCoolNet OBJECT IDENTIFIER ::= { tripplite 104}
|
|
|
|
tlSrCoolNetData OBJECT IDENTIFIER ::= { tlSrCoolNet 1 }
|
|
|
|
tlSrCoolNetIdent OBJECT IDENTIFIER ::= { tlSrCoolNetData 1 }
|
|
|
|
tlSrCoolNetModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The model name for the device attached to the SRCOOLNET."
|
|
::= { tlSrCoolNetIdent 1}
|
|
|
|
tlSrCoolNetManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The manufacturer of the AC Unit."
|
|
::= { tlSrCoolNetIdent 2 }
|
|
|
|
tlSrCoolNetSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number of the SRCOOLNET device."
|
|
::= { tlSrCoolNetIdent 3 }
|
|
|
|
tlSrCoolNetHostSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The software version of the SRCOOLNET device."
|
|
::= { tlSrCoolNetIdent 4 }
|
|
|
|
tlSrCoolNetName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user defined name for the AC Unit."
|
|
::= { tlSrCoolNetIdent 5 }
|
|
|
|
tlSrCoolNetLocation OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user defined location of the AC Unit."
|
|
::= { tlSrCoolNetIdent 6 }
|
|
|
|
tlSrCoolNetStatus OBJECT IDENTIFIER ::= { tlSrCoolNetData 2 }
|
|
|
|
tlSrCoolNetMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
idle (1),
|
|
cooling (2),
|
|
unknown (3),
|
|
dehumidifying (4),
|
|
defrost (5),
|
|
notconnected(6) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current mode of SRCOOLNET."
|
|
::= { tlSrCoolNetStatus 1}
|
|
|
|
tlSrCoolNetFanSpeed OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off (0),
|
|
low (1),
|
|
med (2),
|
|
hi (3) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current speed of the fan."
|
|
::= { tlSrCoolNetStatus 2}
|
|
|
|
tlSrCoolNetReturnAirTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return air stream temperature in tenths of degrees in the units Celsius/Fahrenheit as specified in tlSrCoolNetDisplayUnits."
|
|
::= { tlSrCoolNetStatus 3 }
|
|
|
|
tlSrCoolNetWaterFull OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
waterNotFull(0),
|
|
waterFull(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the water reservoir is full or not full."
|
|
::= { tlSrCoolNetStatus 4 }
|
|
|
|
tlSrCoolNetCurrentRemoteTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The EnviroSense temperature in tenths of degrees in Celsius or Fahrenheit depending upon value of tlSrCoolNetDisplayUnits.
|
|
Only available if EnviroSense is connected to SRCOOLNET."
|
|
::= { tlSrCoolNetStatus 5 }
|
|
|
|
tlSrCoolNetDisplayUnits OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
metric(0),
|
|
english(1) }
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Selects English or Metric display for all readings. AC unit must be manually configured to match this setting."
|
|
::= { tlSrCoolNetStatus 6 }
|
|
|
|
|
|
tlSrCoolNetConfig OBJECT IDENTIFIER ::= { tlSrCoolNetData 3 }
|
|
|
|
tlSrCoolNetOnOff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
turnOffUnit(0),
|
|
turnOnUnit (1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Turn the unit off or on."
|
|
::= { tlSrCoolNetConfig 1 }
|
|
|
|
tlSrCoolSetMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
cooling(0),
|
|
dehumidifying (1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set the operating mode of cooling unit. Unit must be ON to set mode."
|
|
::= { tlSrCoolNetConfig 2 }
|
|
|
|
tlSrCoolNetSetPointTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The local set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits."
|
|
::= { tlSrCoolNetConfig 3 }
|
|
|
|
tlSrCoolNetRemoteSetPointTemp OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remote set point temperature in tenths of degrees in Celsius or Fahrenheit based upon tlSrCoolNetDisplayUnits.
|
|
Only available when EnviroSense is connected to SRCOOLNET."
|
|
::= { tlSrCoolNetConfig 4 }
|
|
|
|
tlSrCoolNetFanSpeedSetting OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
auto(0),
|
|
low(1),
|
|
med(2),
|
|
high(3) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set the fan speed of the AC unit."
|
|
::= { tlSrCoolNetConfig 5 }
|
|
|
|
tlSrCoolNetRemoteSetpointEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Use remote temperature setpoint for control point versus return air temp. Only available when EnviroSense is connected
|
|
to SRCOOLNET."
|
|
::= { tlSrCoolNetConfig 6 }
|
|
|
|
tlSrCoolNetFanAlwaysOn OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1) }
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Leave fans on when not cooling. Only available when EnviroSense is connected to SRCOOLNET."
|
|
::= { tlSrCoolNetConfig 7 }
|
|
|
|
|
|
|
|
tlSrCoolNetAlarm OBJECT IDENTIFIER ::= { tlSrCoolNet 2 }
|
|
|
|
tlSrCoolNetWellKnownAlarms OBJECT IDENTIFIER ::= { tlSrCoolNetAlarm 1 }
|
|
|
|
tlSrCoolNetWaterFullAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water reservoir full."
|
|
::= { tlSrCoolNetWellKnownAlarms 1 }
|
|
|
|
--------------------------------------------------------------------------
|
|
-- Conformance definitions
|
|
--------------------------------------------------------------------------
|
|
|
|
tlConformance OBJECT IDENTIFIER ::= { tripplite 20 }
|
|
|
|
tlCompliances OBJECT IDENTIFIER ::= { tlConformance 1 }
|
|
|
|
tlGroups OBJECT IDENTIFIER ::= { tlConformance 2 }
|
|
|
|
tlSubsetGroups OBJECT IDENTIFIER ::= { tlGroups 1 }
|
|
|
|
tlBasicGroups OBJECT IDENTIFIER ::= { tlGroups 2 }
|
|
|
|
tlFullGroups OBJECT IDENTIFIER ::= { tlGroups 3 }
|
|
|
|
tlUpsFullGroups OBJECT IDENTIFIER ::= { tlFullGroups 100 }
|
|
|
|
tlUpsFullIdentGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
tlUpsIdentUpsSoftwareChecksum,
|
|
tlUpsIdentSerialNum,
|
|
tlUpsIdentID,
|
|
tlUpsSelectedDeviceID }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The tlUpsFullIdentGroup defines objects which are common to the Ident
|
|
group of fully compliant Tripplite UPS's"
|
|
::= { tlUpsFullGroups 1 }
|
|
|
|
tlUpsFullBatteryGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
tlUpsBatteryAge,
|
|
tlUpsTemperatureF }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The tlUpsFullBatteryGroup defines objects which are common to the Battery
|
|
group of fully compliant Tripplite UPS's"
|
|
::= { tlUpsFullGroups 2 }
|
|
|
|
tlUpsFullAlarmGroup OBJECT IDENTIFIER ::= { tlUpsFullGroups 6 }
|
|
|
|
tlUpsFullAlarmObjsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
tlUpsAlarmDevName,
|
|
tlUpsAlarmDevLocation,
|
|
tlUpsAlarmCategory }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The tlUpsFullAlarmObjsGroup defines objects which are common to
|
|
the Alarm group of fully compliant Tripplite UPS's"
|
|
::= { tlUpsFullAlarmGroup 1 }
|
|
|
|
--tlUpsFullAlarmsGroup NOTIFICATION-GROUP
|
|
-- NOTIFICATIONS { }
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "The tlUpsFullAlarmGroup defines notifications which are
|
|
-- common to the Alarm group of fully compliant Tripplite UPS's"
|
|
-- ::= { tlUpsFullAlarmGroup 2 }
|
|
|
|
tlUpsFullTestGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
tlUpsTestDate,
|
|
tlUpsTestResultsDetail }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The tlUpsFullTestGroup defines objects which are common to the Test
|
|
group of fully compliant Tripplite UPS's"
|
|
::= { tlUpsFullGroups 7 }
|
|
|
|
tlUpsFullControlGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
tlUpsWatchdogSupported,
|
|
tlUpsWatchdogSecsBeforeReboot }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The tlUpsFullControlGroup defines objects which are common to the Control
|
|
group of fully compliant Tripplite UPS's"
|
|
::= { tlUpsFullGroups 8 }
|
|
|
|
tlUpsFullConfigGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
tlUpsConfigBattReplDate }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The tlUpsFullConfigGroup defines objects which are common to the Config
|
|
group of fully compliant Tripplite UPS's"
|
|
::= { tlUpsFullGroups 9 }
|
|
|
|
tlUpsFullOutletGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
tlUpsOutletNumOutlets }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The tlUpsFullOutletGroup defines objects which are common to the Outlet
|
|
group of fully compliant Tripplite UPS's"
|
|
::= { tlUpsFullGroups 10 }
|
|
|
|
|
|