- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
291 lines
7.8 KiB
Text
291 lines
7.8 KiB
Text
-- *****************************************************************
|
|
-- Dry Contacts MIB
|
|
-- *****************************************************************
|
|
|
|
SL-DRY-CON-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE,
|
|
NOTIFICATION-TYPE, Counter64,
|
|
Gauge32 FROM SNMPv2-SMI
|
|
DisplayString, TruthValue, RowStatus
|
|
FROM SNMPv2-TC
|
|
MODULE-COMPLIANCE, OBJECT-GROUP,
|
|
NOTIFICATION-GROUP FROM SNMPv2-CONF
|
|
InterfaceIndex, ifIndex FROM IF-MIB
|
|
PerfCurrentCount, PerfIntervalCount,
|
|
PerfTotalCount FROM PerfHist-TC-MIB
|
|
sitelight FROM SL-NE-MIB;
|
|
|
|
slDryConMib MODULE-IDENTITY
|
|
LAST-UPDATED "200108070000Z"
|
|
ORGANIZATION "PacketLight Networks Ltd."
|
|
CONTACT-INFO
|
|
"Omri_Viner@PacketLight.com"
|
|
DESCRIPTION
|
|
"This MIB module describes the Dry Contacts."
|
|
::= { sitelight 7 }
|
|
|
|
|
|
slDryConOut OBJECT IDENTIFIER ::= { slDryConMib 1}
|
|
slDryConIn OBJECT IDENTIFIER ::= { slDryConMib 2}
|
|
slDryConTraps OBJECT IDENTIFIER ::= { slDryConMib 3}
|
|
|
|
-- *******************************************
|
|
-- Dry Contact Outputs
|
|
-- *******************************************
|
|
|
|
|
|
slDryConAlarmCutoff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
dummy(1)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this variable cause to Alarms Cutoff."
|
|
::= {slDryConOut 1}
|
|
|
|
slDryConOutTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SlDryConOutEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Dry Contact Out table configure the dry contact outputs."
|
|
::= { slDryConOut 2 }
|
|
|
|
slDryConOutEntry OBJECT-TYPE
|
|
SYNTAX SlDryConOutEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"There is an entry for each Output Dry Contact"
|
|
INDEX { slDryConOutIndex }
|
|
::= { slDryConOutTable 1 }
|
|
|
|
SlDryConOutEntry ::=
|
|
SEQUENCE {
|
|
slDryConOutIndex INTEGER,
|
|
slDryConOutCommand INTEGER,
|
|
slDryConOutActiveStatus TruthValue
|
|
}
|
|
|
|
|
|
slDryConOutIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the output dry contact."
|
|
::= {slDryConOutEntry 1}
|
|
|
|
slDryConOutCommand OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
activate(1),
|
|
deactivate(2),
|
|
clear(3)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object controls the output dry contact state:
|
|
activate(1) - activate the output dry contact
|
|
deactivate(2) - dectivate the output dry contact
|
|
clear(3) - clears the output dry contact command
|
|
The object value can also be read by the management.
|
|
In this case the agent should return the current command
|
|
to the management. The object value should not be kept in
|
|
the NVRAM because it is used only for testing.
|
|
The intial value should be clear(3)."
|
|
::= {slDryConOutEntry 2}
|
|
|
|
slDryConOutActiveStatus OBJECT-TYPE
|
|
SYNTAX TruthValue
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current status of the output dry contact:
|
|
TRUE - means that it is currently active
|
|
FLASE - means that it is not active"
|
|
::= {slDryConOutEntry 3}
|
|
|
|
-- *******************************************
|
|
-- Dry Contact Inputs
|
|
-- *******************************************
|
|
|
|
slDryConLastChange OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
dummy(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Sys Uptime at the last input change."
|
|
::= {slDryConIn 1}
|
|
|
|
slDryConInTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF SlDryConInEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Dry Contact In table describes the dry contacts inputs."
|
|
::= { slDryConIn 2 }
|
|
|
|
slDryConInEntry OBJECT-TYPE
|
|
SYNTAX SlDryConInEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"There is an entry for each Input Dry Contact"
|
|
INDEX { slDryConInIndex }
|
|
::= { slDryConInTable 1 }
|
|
|
|
SlDryConInEntry ::=
|
|
SEQUENCE {
|
|
slDryConInIndex INTEGER,
|
|
slDryConInDescription DisplayString,
|
|
slDryConInSeverity INTEGER,
|
|
slDryConInEnable INTEGER,
|
|
slDryConInPolarity INTEGER,
|
|
slDryConInStatus INTEGER,
|
|
slDryConInAlmType INTEGER
|
|
}
|
|
|
|
|
|
slDryConInIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (1..4)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the input dry contact."
|
|
::= {slDryConInEntry 1}
|
|
|
|
slDryConInDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..40))
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A textual description of the input dry contact alarm."
|
|
REFERENCE
|
|
"GR-833-CORE Appendix L (<almmsg>)."
|
|
::= {slDryConInEntry 2}
|
|
|
|
slDryConInSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
critical(1),
|
|
major(2),
|
|
minor(3),
|
|
cleared(4),
|
|
notification(5)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A severity of the input dry contact alarm."
|
|
::= {slDryConInEntry 3}
|
|
|
|
slDryConInEnable OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
enable(1),
|
|
disable(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/Disable the input dry contact alarm report generation."
|
|
::= {slDryConInEntry 4}
|
|
|
|
slDryConInPolarity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
activeClose(1),
|
|
activeOpen(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Determines the input dry contact alarm polarity."
|
|
::= {slDryConInEntry 5}
|
|
|
|
slDryConInStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
active(1),
|
|
inactive(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describe the current input dry contact alarm status."
|
|
::= {slDryConInEntry 6}
|
|
|
|
slDryConInAlmType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
aircompr(1), -- Air compressor failure
|
|
aircond(2), -- Air conditioning failure
|
|
airdryd(3), -- Air dryer failure
|
|
batdschrg(4), -- Battery discharging
|
|
battery(5), -- Battery failure
|
|
clfan(6), -- Cooling fan failure
|
|
cpmajor(7), -- Centralized Power Major Environmental Alarm or Major Equipment Failure
|
|
cpminor(8), -- Centralized Power Minor Environmental Alarm or Minor Equipment Failure
|
|
engine(9), -- Engine failure
|
|
engoprg(10), -- Engine operating
|
|
explgs(11), -- Explosive gas
|
|
firdetr(12), -- Fire detector failure
|
|
fire(13), -- Fire
|
|
flood(14), -- Flood
|
|
fuse(15), -- Fuse failure
|
|
gen(16), -- Generator failure
|
|
hiair(17), -- High airflow
|
|
hihum(18), -- High humidity
|
|
hitemp(19), -- High temperature
|
|
hiwtr(20), -- High water
|
|
intruder(21), -- Intrusion
|
|
lwbatvg(22), -- Low battery voltage
|
|
lwfuel(23), -- Low fuel
|
|
lwhum(24), -- Low humidity
|
|
lwpres(25), -- Low cable pressure
|
|
lwtemp(26), -- Low temperature
|
|
lwwtr(27), -- Low water
|
|
misc(28), -- Miscellaneous
|
|
opendr(29), -- Open door
|
|
pump(30), -- Pump failure
|
|
power(31), -- Commercial power failure
|
|
pwrX(32), -- X Volt power supply failure (X is a positive integer)
|
|
rect(33), -- Rectifier failure
|
|
recthi(34), -- Rectifier high voltage
|
|
rectlo(35), -- Rectifier low voltage
|
|
smoke(36), -- Smoke
|
|
toxicgas(37), -- Toxic gas
|
|
ventn(38) -- Ventilation system failure
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Describe the current input dry contact alarm type."
|
|
REFERENCE
|
|
"GR-833-CORE Appendix F Table 1."
|
|
::= {slDryConInEntry 7}
|
|
|
|
|
|
-- *******************************************
|
|
-- Dry Contact Traps
|
|
-- *******************************************
|
|
|
|
slDryConStatusChangeTrap NOTIFICATION-TYPE
|
|
OBJECTS { slDryConInIndex, slDryConInStatus, slDryConInAlmType }
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An slDryConStatusChangeTrap notification is sent when
|
|
the the Status of an input dry contact is changed and the
|
|
corresponding alarm is enabled.
|
|
In order to shoten the Trap, the DisplayString that
|
|
describes the alarm is not sent. To find out this string
|
|
the NMS should use the index and get it from the table."
|
|
::= { slDryConTraps 1 }
|
|
|
|
|
|
|
|
END
|
|
|
|
|
|
|