- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
2762 lines
65 KiB
Text
2762 lines
65 KiB
Text
-- company power MIB
|
|
|
|
--
|
|
-- { iso org(3) dod(6) internet(1) private(4) enterprises(1) company(2111)
|
|
-- products(1) ups(1)
|
|
--
|
|
-- ==============================================================================================
|
|
|
|
|
|
companyMIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
MODULE-IDENTITY, OBJECT-TYPE, OBJECT-IDENTITY
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
TRAP-TYPE
|
|
FROM RFC-1215
|
|
PositiveInteger, NonNegativeInteger
|
|
FROM UPS-MIB;
|
|
|
|
|
|
companyMIB MODULE-IDENTITY
|
|
LAST-UPDATED "201005060000Z"
|
|
ORGANIZATION "company Power Technology"
|
|
CONTACT-INFO " "
|
|
|
|
DESCRIPTION
|
|
"The MIB module to describe UPS"
|
|
|
|
|
|
|
|
::= { enterprises 21111 }
|
|
|
|
|
|
|
|
products OBJECT IDENTIFIER ::= { companyMIB 1 }
|
|
ups OBJECT IDENTIFIER ::= { products 1 }
|
|
inverter OBJECT IDENTIFIER ::= { products 2 }
|
|
charger OBJECT IDENTIFIER ::= { products 3 }
|
|
ATS OBJECT IDENTIFIER ::= { products 4 }
|
|
|
|
upsIdent OBJECT IDENTIFIER ::= { ups 1 }
|
|
upsRating OBJECT IDENTIFIER ::= { ups 2 }
|
|
upsBattery OBJECT IDENTIFIER ::= { ups 3 }
|
|
upsInput OBJECT IDENTIFIER ::= { ups 4 }
|
|
upsOutput OBJECT IDENTIFIER ::= { ups 5 }
|
|
upsBypass OBJECT IDENTIFIER ::= { ups 6 }
|
|
upsTest OBJECT IDENTIFIER ::= { ups 7 }
|
|
upsControl OBJECT IDENTIFIER ::= { ups 8 }
|
|
agentConfig OBJECT IDENTIFIER ::= { ups 9 }
|
|
commConfig OBJECT IDENTIFIER ::= { ups 10 }
|
|
upsConfig OBJECT IDENTIFIER ::= { ups 11 }
|
|
upsTraps OBJECT IDENTIFIER ::= { ups 12 }
|
|
extend OBJECT IDENTIFIER ::= { ups 13 }
|
|
|
|
solarIdent OBJECT IDENTIFIER ::= { inverter 1 }
|
|
solarRating OBJECT IDENTIFIER ::= { inverter 2 }
|
|
solarBattery OBJECT IDENTIFIER ::= { inverter 3 }
|
|
solarGrid OBJECT IDENTIFIER ::= { inverter 4 }
|
|
solarACOutput OBJECT IDENTIFIER ::= { inverter 5 }
|
|
solarPV OBJECT IDENTIFIER ::= { inverter 6 }
|
|
solarEnergy OBJECT IDENTIFIER ::= { inverter 7 }
|
|
solarTest OBJECT IDENTIFIER ::= { inverter 8 }
|
|
solarDefValue OBJECT IDENTIFIER ::= { inverter 9 }
|
|
solarFaultInfo OBJECT IDENTIFIER ::= { inverter 10 }
|
|
solarControl OBJECT IDENTIFIER ::= { inverter 11 }
|
|
solarAgentConfig OBJECT IDENTIFIER ::= { inverter 12 }
|
|
solarCommConfig OBJECT IDENTIFIER ::= { inverter 13 }
|
|
solarConfig OBJECT IDENTIFIER ::= { inverter 14 }
|
|
solarTraps OBJECT IDENTIFIER ::= { inverter 15 }
|
|
solarExtend OBJECT IDENTIFIER ::= { inverter 16 }
|
|
|
|
|
|
ATSIdent OBJECT IDENTIFIER ::= { ATS 1 }
|
|
ATSRating OBJECT IDENTIFIER ::= { ATS 2 }
|
|
ATSInformation OBJECT IDENTIFIER ::= { ATS 3 }
|
|
ATSControl OBJECT IDENTIFIER ::= { ATS 4 }
|
|
ATSAgentConfig OBJECT IDENTIFIER ::= { ATS 5 }
|
|
ATSCommConfig OBJECT IDENTIFIER ::= { ATS 6 }
|
|
ATSConfig OBJECT IDENTIFIER ::= { ATS 7 }
|
|
ATSTraps OBJECT IDENTIFIER ::= { ATS 8 }
|
|
ATSExtend OBJECT IDENTIFIER ::= { ATS 9 }
|
|
|
|
---=======================================================
|
|
---upsIdent
|
|
--- prefix =upsId
|
|
---========================================================
|
|
|
|
upsIdManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The name of the UPS manufacturer."
|
|
::= { upsIdent 1 }
|
|
|
|
upsIdProtocol OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(-1),
|
|
pmv(99),
|
|
p00(0),
|
|
p01(1),
|
|
p02(2),
|
|
p03(3),
|
|
p04(4),
|
|
p05(5),
|
|
p06(6),
|
|
p07(7),
|
|
p08(8),
|
|
p09(9),
|
|
p10(10),
|
|
sec(80)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Protocol id."
|
|
::= { upsIdent 2 }
|
|
|
|
upsIdModelName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..15))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS Model designation."
|
|
::= { upsIdent 3 }
|
|
|
|
upsIdSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The UPS serial no."
|
|
::= { upsIdent 4 }
|
|
|
|
upsIdName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"A string identifying the UPS. This object should be
|
|
set by the administrator."
|
|
::= { upsIdent 5 }
|
|
|
|
upsIdFWVersion OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(0..31))
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"Main CPU firmware version."
|
|
::= { upsIdent 6 }
|
|
|
|
|
|
upsIdUPSType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
standy(0),
|
|
line-interactive(1),
|
|
on-line(2)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"UPS type."
|
|
::= { upsIdent 7 }
|
|
--===========================================================================
|
|
--upsRating
|
|
--prefix =upsRat
|
|
--the rating info of ups
|
|
--==========================================================================
|
|
upsRatinVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rating input voltage of UPS"
|
|
::= { upsRating 1 }
|
|
|
|
upsRatoutVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rating output voltage of UPS"
|
|
::= { upsRating 2 }
|
|
|
|
upsRatoutFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 HZ"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rating output frequency of UPS"
|
|
::= { upsRating 3 }
|
|
|
|
upsRatoutCurrent OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rating output current of UPS"
|
|
::= { upsRating 4 }
|
|
|
|
upsRatoutApparentPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 VA"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rating output apparent power of UPS"
|
|
::= { upsRating 5 }
|
|
|
|
upsRatoutTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Wt"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rating output true power of UPS"
|
|
::= { upsRating 6 }
|
|
|
|
upsRatBatVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 vol"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rating battery voltage of UPS"
|
|
::= { upsRating 7 }
|
|
|
|
|
|
|
|
-- ===========================================================================
|
|
-- upsBattery
|
|
-- prefix = upsBat
|
|
-- The Battery group.
|
|
-- est=estimated
|
|
-- ===========================================================================
|
|
|
|
upsBatStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
batteryNormal(2),
|
|
batteryLow(3),
|
|
batteryDepleted(4),
|
|
batteryDischarging(5),
|
|
batteryFailure(6),
|
|
batteryReplace(7),
|
|
batterysilence(8)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The indication of the status in the UPS system's batteries."
|
|
::= { upsBattery 1 }
|
|
|
|
|
|
|
|
upsBatSecondsOnBattery OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "seconds"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If the unit is on battery power, the elapsed time
|
|
since the UPS last switched to battery power, or the
|
|
time since the network management subsystem was last
|
|
restarted, whichever is less. -1 shall be returned
|
|
if the unit is not on battery power."
|
|
::= { upsBattery 2 }
|
|
|
|
upsBatEstMinutesRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "minutes"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An estimate of the time to battery charge depletion
|
|
under the present load conditions if the utility power
|
|
is off and remains off, or if it were to be lost and
|
|
remain off."
|
|
::= { upsBattery 3 }
|
|
|
|
upsBatEstChargeRemaining OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "percent"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An estimate of the battery charge remaining expressed
|
|
as a percent of full charge."
|
|
::= { upsBattery 4 }
|
|
|
|
upsBatPBatVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present Positive battery voltage."
|
|
::= { upsBattery 5 }
|
|
|
|
|
|
upsBatNBatVoltage OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Volt DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present negative battery voltage."
|
|
::= { upsBattery 6 }
|
|
|
|
upsBatPBatCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The positive battery present current."
|
|
::= { upsBattery 7 }
|
|
|
|
upsBatNBatCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present negative battery current."
|
|
::= { upsBattery 8 }
|
|
|
|
upsBatPBatChargCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Positive battery charging current."
|
|
::= { upsBattery 9 }
|
|
|
|
upsBatNBatchargCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present negative battery charging current."
|
|
::= { upsBattery 10 }
|
|
|
|
upsBatPBatDischargCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present positive battery discharging current."
|
|
::= { upsBattery 11 }
|
|
|
|
upsBatNBatDischargCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present negative battery discharging current."
|
|
::= { upsBattery 12 }
|
|
|
|
upsBatTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "degrees 0.1 Centigrade"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature at or near the UPS Battery
|
|
casing."
|
|
::= { upsBattery 13 }
|
|
|
|
upsBatNumberInSeries OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of battery in series."
|
|
::= { upsBattery 14 }
|
|
|
|
|
|
upsBatNumberInParallel OBJECT-TYPE
|
|
SYNTAX PositiveInteger
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of battery in Parallel."
|
|
::= { upsBattery 15 }
|
|
|
|
upsBatPBatDischargCurrent2 OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present positive battery pipe2 discharging current."
|
|
::= { upsBattery 16 }
|
|
|
|
-- ===========================================================================
|
|
-- upsInput
|
|
-- prefix = upsIn
|
|
-- Input group.
|
|
-- ===========================================================================
|
|
|
|
upsInLineBads OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A count of the number of times the input entered an
|
|
out-of-tolerance condition as defined by the
|
|
manufacturer. This count is incremented by one each
|
|
time the input transitions from zero out-of-tolerance
|
|
lines to one or more input lines out-of-tolerance."
|
|
::= { upsInput 1 }
|
|
|
|
|
|
upsInTtlApparentPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1VA"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total input apparent power ."
|
|
::= { upsInput 2 }
|
|
|
|
upsInTtlTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1WT"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total input active(true) power ."
|
|
::= { upsInput 3 }
|
|
|
|
|
|
|
|
upsInNumLines OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of input lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
input table."
|
|
::= { upsInput 4 }
|
|
|
|
|
|
upsInTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsInEntry
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of input table entries. The number of entries
|
|
is given by the value of upsInputNumLines."
|
|
::= { upsInput 5 }
|
|
|
|
|
|
upsInTtlVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input utility line tatol voltage ."
|
|
::= { upsInput 6 }
|
|
|
|
upsInTtlCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 A"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input utility line tatol current."
|
|
::= { upsInput 7 }
|
|
|
|
upsInEntry OBJECT-TYPE
|
|
SYNTAX UpsInEntry
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular input line."
|
|
INDEX { upsInLineIndex }
|
|
::= { upsInTable 1 }
|
|
|
|
UpsInEntry ::=
|
|
SEQUENCE {
|
|
upsInLineIndex PositiveInteger,
|
|
upsInFrequency NonNegativeInteger,
|
|
upsInVoltage NonNegativeInteger,
|
|
upsInCurrent NonNegativeInteger,
|
|
upsInApparentPower NonNegativeInteger,
|
|
upsInTruePower NonNegativeInteger,
|
|
upsInPowerFactor NonNegativeInteger,
|
|
upsInLineVoltage NonNegativeInteger
|
|
}
|
|
|
|
upsInLineIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10)
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of output lines"
|
|
::= { upsInEntry 1 }
|
|
|
|
upsInFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present input frequency."
|
|
::= { upsInEntry 2 }
|
|
|
|
upsInVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input utility line voltage ."
|
|
::= { upsInEntry 3 }
|
|
|
|
upsInCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1Amp"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input current "
|
|
::= { upsInEntry 4 }
|
|
|
|
|
|
|
|
upsInApparentPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1VA"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input Apparent power."
|
|
::= { upsInEntry 5 }
|
|
|
|
|
|
upsInTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1Watts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The magnitude of the present input true power."
|
|
::= { upsInEntry 6 }
|
|
|
|
|
|
|
|
upsInPowerFactor OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.01"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input true power/apparent power factor "
|
|
::= { upsInEntry 7 }
|
|
|
|
upsInLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input utility line voltage .
|
|
if upsInLineIndex =1, upsInLineVoltage = Line voltage of RS phase;
|
|
if upsInLineIndex =2, upsInLineVoltage = Line voltage of ST phase;
|
|
if upsInLineIndex =3, upsInLineVoltage = Line voltage of TR phase."
|
|
::= { upsInEntry 8 }
|
|
|
|
-- ===========================================================================
|
|
-- upsOutput
|
|
-- prefix= upsOut
|
|
-- Output group
|
|
-- ===========================================================================
|
|
|
|
upsOutSource OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7),
|
|
batterytest(8),
|
|
fault(9),
|
|
HE-ECOmode(10),
|
|
convertermode(11)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker.==UPS standby mode"
|
|
::= { upsOutput 1 }
|
|
|
|
upsOutFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current output frequency of the UPS system "
|
|
::= { upsOutput 2 }
|
|
|
|
|
|
upsOutTtlApparentPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1VA"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total output apparent power ."
|
|
::= { upsOutput 3 }
|
|
|
|
upsOutTtlTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1Watts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total output active(true) power ."
|
|
::= { upsOutput 4 }
|
|
|
|
|
|
upsOutTtlPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "percent"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line, i.e., the greater of
|
|
the percent load of true power capacity and the
|
|
percent load of VA."
|
|
::= { upsOutput 5 }
|
|
|
|
|
|
|
|
|
|
upsOutNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of output lines utilized in this device.
|
|
This variable indicates the number of rows in the
|
|
output table."
|
|
::= { upsOutput 6 }
|
|
|
|
upsOutTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsOutEntry
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of output table entries. The number of
|
|
entries is given by the value of upsOutputNumLines."
|
|
::= { upsOutput 7 }
|
|
|
|
|
|
upsOutTtlVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1vot"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total output voltage ."
|
|
::= { upsOutput 8 }
|
|
|
|
upsOutTtlCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1A"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total output current."
|
|
::= { upsOutput 9 }
|
|
|
|
upsOutStatus OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (4..4))
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
" For HVDC device.
|
|
char status[4];
|
|
status[0]status[1]:00, no output1; 01, line output1; 02, bat output1
|
|
status[2]status[3]:00, no output2; 01, line output2; 02, bat output2
|
|
"
|
|
::= { upsOutput 10 }
|
|
|
|
|
|
|
|
upsOutSource2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
other(1),
|
|
none(2),
|
|
normal(3),
|
|
bypass(4),
|
|
battery(5),
|
|
booster(6),
|
|
reducer(7),
|
|
batterytest(8),
|
|
fault(9),
|
|
HE-ECOmode(10),
|
|
convertermode(11)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"For HVDC(protocol:P12) machine. The present source of output power. The enumeration
|
|
none(2) indicates that there is no source of output
|
|
power (and therefore no output power), for example,
|
|
the system has opened the output breaker.==UPS standby mode"
|
|
::= { upsOutput 11 }
|
|
|
|
|
|
upsOutEntry OBJECT-TYPE
|
|
SYNTAX UpsOutEntry
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular output line."
|
|
INDEX { upsOutLineIndex }
|
|
::= { upsOutTable 1 }
|
|
|
|
UpsOutEntry ::=
|
|
SEQUENCE {
|
|
upsOutLineIndex PositiveInteger,
|
|
upsOutVoltage NonNegativeInteger,
|
|
upsOutCurrent NonNegativeInteger,
|
|
upsOutApparentPower NonNegativeInteger,
|
|
upsOutTruePower NonNegativeInteger,
|
|
upsOutPowerFactor NonNegativeInteger,
|
|
upsOutPercentLoad INTEGER,
|
|
upsOutLineVoltage NonNegativeInteger
|
|
}
|
|
|
|
upsOutLineIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..10)
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output line identifier."
|
|
::= { upsOutEntry 1 }
|
|
|
|
upsOutVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output voltage of the UPS system."
|
|
::= { upsOutEntry 2 }
|
|
|
|
upsOutCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output current of the UPS system"
|
|
::= { upsOutEntry 3 }
|
|
|
|
upsOutApparentPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1VA"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output apparent power."
|
|
::= { upsOutEntry 4 }
|
|
|
|
upsOutTruePower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1Watts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output true power."
|
|
::= { upsOutEntry 5 }
|
|
|
|
upsOutPowerFactor OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.01"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output true power/apparent power factor "
|
|
::= { upsOutEntry 6 }
|
|
|
|
upsOutPercentLoad OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "percent"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The percentage of the UPS power capacity presently
|
|
being used on this output line, i.e., the greater of
|
|
the percent load of true power capacity and the
|
|
percent load of VA."
|
|
::= { upsOutEntry 7 }
|
|
|
|
upsOutLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output line voltage of the UPS system.
|
|
if upsOutLineIndex =1, upsOutLineVoltage = Line voltage of RS phase;
|
|
if upsOutLineIndex =2, upsOutLineVoltage = Line voltage of ST phase;
|
|
if upsOutLineIndex =3, upsOutLineVoltage = Line voltage of TR phase."
|
|
::= { upsOutEntry 8 }
|
|
|
|
upsOutFrequency OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1Hertz"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present output frequency."
|
|
::= { upsOutEntry 9 }
|
|
|
|
-- ===========================================================================
|
|
-- upsBypass
|
|
-- prefix =upsBy
|
|
-- ===========================================================================
|
|
|
|
upsByFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass frequency."
|
|
::= { upsBypass 1 }
|
|
|
|
|
|
|
|
upsByNumLines OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of bypass lines utilized in this device.
|
|
This entry indicates the number of rows in the bypass
|
|
table."
|
|
::= { upsBypass 2 }
|
|
|
|
|
|
upsByTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF UpsByEntry
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of bypass table entries. The number of
|
|
entries is given by the value of upsBypassNumLines."
|
|
::= { upsBypass 3 }
|
|
|
|
upsByEntry OBJECT-TYPE
|
|
SYNTAX UpsByEntry
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An entry containing information applicable to a
|
|
particular bypass input."
|
|
INDEX { upsByLineIndex }
|
|
::= { upsByTable 1 }
|
|
|
|
UpsByEntry ::=
|
|
SEQUENCE {
|
|
upsByLineIndex PositiveInteger,
|
|
upsByVoltage NonNegativeInteger,
|
|
upsByCurrent NonNegativeInteger,
|
|
upsByPower NonNegativeInteger,
|
|
upsByLineVoltage INTEGER
|
|
}
|
|
|
|
upsByLineIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..65535)
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass line identifier."
|
|
::= { upsByEntry 1 }
|
|
|
|
upsByVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass voltage."
|
|
::= { upsByEntry 2 }
|
|
|
|
upsByCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 RMS Amp"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass current."
|
|
::= { upsByEntry 3 }
|
|
|
|
upsByPower OBJECT-TYPE
|
|
SYNTAX NonNegativeInteger
|
|
UNITS "0.1Watts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present true power conveyed by the bypass."
|
|
::= { upsByEntry 4 }
|
|
|
|
upsByLineVoltage OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present bypass line voltage.
|
|
if upsByLineIndex=1,upsByLineVoltage=Line voltage of RS phase;
|
|
if upsByLineIndex=2,upsByLineVoltage=Line voltage of ST phase;
|
|
if upsByLineIndex=3,upsByLineVoltage=Line voltage of TR phase."
|
|
::= { upsByEntry 5 }
|
|
|
|
-- ===========================================================================
|
|
-- upsTest
|
|
-- prefix=upsTst
|
|
-- ===========================================================================
|
|
|
|
|
|
upsTstBatteryTest OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
battTest10sec(2),
|
|
battTestUntilLow(3),
|
|
battTestWithTime(4),
|
|
battTestCancelTest(5),
|
|
battTestClearInfo(6)
|
|
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object specify the battery test type and initiate
|
|
battery test. If battTestWithTime selected, the test
|
|
time is refer to upsTestBatteryTestTime."
|
|
::= { upsTest 1 }
|
|
|
|
upsTstBatteryTestResult OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
donePassed(1),
|
|
doneWarning(2),
|
|
doneError(3),
|
|
aborted(4),
|
|
inProgress(5),
|
|
noTestsInitiated(6)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The results of the current or last UPS diagnostics
|
|
test performed. The values for donePassed(1),
|
|
doneWarning(2), and doneError(3) indicate that the
|
|
test completed either successfully, with a warning, or
|
|
with an error, respectively. The value aborted(4) is
|
|
returned for tests which are aborted by setting the
|
|
value of upsTestId to upsTestAbortTestInProgress.
|
|
Tests which have not yet concluded are indicated by
|
|
inProgress(5). The value noTestsInitiated(6)
|
|
indicates that no previous test results are available,
|
|
such as is the case when no tests have been run since
|
|
the last reinitialization of the network management
|
|
subsystem and the system has no provision for non-
|
|
volatile storage of test results."
|
|
::= { upsTest 2 }
|
|
|
|
|
|
|
|
upsTstBatteryTestStartTime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE(19..19))
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of the time the test in progress was initiated,
|
|
or, if no test is in progress, the time the previous test
|
|
was initiated. If the value of upsTestBatteryTestResult
|
|
is noTestsInitiated(6), upsTestStartTime has the value
|
|
01/01/1970 00:00:00. format is (MM/DD/YYYY hh:mm:ss)"
|
|
::= { upsTest 3 }
|
|
|
|
|
|
upsTstBatterySettingTime OBJECT-TYPE
|
|
SYNTAX INTEGER (12..5940)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION
|
|
"The object specify the test time for battery test, the unit is seconds"
|
|
::= { upsTest 4 }
|
|
|
|
--below 1 minute 0.2-1.0 ,larger than 1 minutes ,1,2,3..99;
|
|
|
|
-- ===========================================================================
|
|
-- upsControl
|
|
-- prefix=upsCtl
|
|
-- ===========================================================================
|
|
|
|
|
|
upsCtlShutdownDelay OBJECT-TYPE
|
|
SYNTAX INTEGER (-2..2147483648)
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delay in seconds the UPS remains on after being told
|
|
to turn off. if value=-2 cancel shutdown, if value=-1 donothing,
|
|
value=0 shutdown ups immediately"
|
|
::= { upsControl 1 }
|
|
|
|
|
|
upsCtlSleepTime OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..2147483648)
|
|
UNITS "minutes"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The time in minutes for the UPS to go to sleep when
|
|
instructed. When in sleep mode, the UPS will not provide
|
|
output power regardless of the input line state. Once the
|
|
specified time has elapsed, output power will be restored.
|
|
|
|
This is a configuration setting. The UPS will not go to
|
|
sleep until told to do so by the manager from a management
|
|
station.
|
|
|
|
Any input value is allowed, however the UPS only recognizes
|
|
0 - 9999 minutes in one minute increments.
|
|
|
|
If the provided value is higher than the highest acceptable
|
|
value, the highest acceptable value is used."
|
|
::= { upsControl 2 }
|
|
|
|
upsCtlStartupAfterDelay OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..2147483648)
|
|
UNITS "seconds"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object will start the output after the
|
|
indicated number of seconds, including starting the
|
|
UPS, if necessary. -1 mean not startup.
|
|
must set upsCtlStartupAfterDelay before upsCtlShutdownDelay ,
|
|
the value must larger than 59 if the value not equal -1 "
|
|
|
|
::= { upsControl 3 }
|
|
|
|
|
|
|
|
upsCtlbuzzer OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to 'on' or 'off' to enable or disable buzzer"
|
|
|
|
::= { upsControl 4 }
|
|
|
|
|
|
|
|
upsCtlRemoteControlUPS OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to turn 'on' or 'off' UPS "
|
|
|
|
::= { upsControl 5 }
|
|
|
|
upsCtloutletPoweron OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2)
|
|
ACCESS write-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to 1 means 1st outlet,2 means 2nd outlet , immediately process"
|
|
|
|
::= { upsControl 6 }
|
|
|
|
|
|
|
|
upsCtloutletPoweroff OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2)
|
|
ACCESS write-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to 1 means 1st outlet,
|
|
2 means 2nd outlet , immediately process"
|
|
|
|
::= { upsControl 7 }
|
|
|
|
|
|
upsCtlOutlet1Powerofftime OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..999)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"setting this object to -1 means this control not effect,
|
|
0 means immediately process,
|
|
>0 means wait times unit is minutes
|
|
use in battery mode"
|
|
::= { upsControl 8 }
|
|
|
|
upsCtlOutlet2Powerofftime OBJECT-TYPE
|
|
SYNTAX INTEGER (-1..999)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"setting this object to -1 means this control not effect,
|
|
0 means immediately process ,
|
|
>0 means wait times unit is minutes .use in battery mode"
|
|
::= { upsControl 9 }
|
|
|
|
upsCtlResetConfigure OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
reset(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
" reset all configure para to default."
|
|
::= { upsControl 10 }
|
|
|
|
|
|
--===========================================================================
|
|
--
|
|
-- agentConfig
|
|
-- prefix=agent
|
|
-- ===========================================================================
|
|
|
|
|
|
agentConfigDatetime OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (19..19))
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The datetime in agent, format is (MM/DD/YYYY hh:mm:ss)"
|
|
::= { agentConfig 1 }
|
|
|
|
|
|
|
|
|
|
---======================================================================
|
|
-- commConfig
|
|
-- prefix =comm
|
|
---======================================================================
|
|
|
|
commBaudRate OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
B1200(1),
|
|
B2400(2),
|
|
B4800(3),
|
|
B9600(4),
|
|
B19200(5)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS communicate baudrate"
|
|
::= { commConfig 1 }
|
|
|
|
|
|
|
|
commDatabits OBJECT-TYPE
|
|
SYNTAX INTEGER (8..9)
|
|
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS communicate data bits"
|
|
::= { commConfig 2 }
|
|
|
|
|
|
commStopbits OBJECT-TYPE
|
|
SYNTAX INTEGER (1..2)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS communicate stop bits "
|
|
|
|
::= { commConfig 3 }
|
|
|
|
commParity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
odd(1),
|
|
even(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS communicate Parity "
|
|
::= { commConfig 4 }
|
|
|
|
commTimeout OBJECT-TYPE
|
|
SYNTAX INTEGER (100..1000)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS communicate timeout"
|
|
::= { commConfig 5 }
|
|
|
|
|
|
--===========================================================================
|
|
--
|
|
-- upsConfig
|
|
--prefix=upsCfg
|
|
-- ===========================================================================
|
|
|
|
upsCfgAlarmbypass OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object enable /disable alarm bypass mode"
|
|
|
|
::= { upsConfig 1 }
|
|
|
|
upsCfgAlarmbattery OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object enable/disable alarm battery mode"
|
|
|
|
::= { upsConfig 2 }
|
|
|
|
upsCfgAutoReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object enable/disable auto reboot"
|
|
::= { upsConfig 3 }
|
|
|
|
|
|
upsCfgBypasswhenupsoff OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object start/stop bypass when ups off"
|
|
::= { upsConfig 4 }
|
|
|
|
|
|
upsCfgBatterDDP OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable battery deep-discharge protection"
|
|
::= { upsConfig 5 }
|
|
|
|
|
|
|
|
|
|
upsCfgConvertermode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable converter mode "
|
|
|
|
::= { upsConfig 6 }
|
|
|
|
|
|
upsCfgECOmode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable ECO mode"
|
|
::= { upsConfig 7 }
|
|
|
|
|
|
|
|
upsCfgAdvanceECOmode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable advance ECO mode"
|
|
::= { upsConfig 8 }
|
|
|
|
|
|
upsCfgGreenPowerFunction OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable green power function"
|
|
::= { upsConfig 9 }
|
|
|
|
|
|
|
|
|
|
upsCfgBatteryOSC OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable battery open status check"
|
|
::= { upsConfig 10 }
|
|
|
|
|
|
upsCfgAllowShort3times OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable short 3 times"
|
|
::= { upsConfig 11 }
|
|
|
|
|
|
|
|
upsCfgColdstart OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to cold start ups"
|
|
::= { upsConfig 12 }
|
|
|
|
|
|
upsCfgBypassNotAllowed OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable bypass mode"
|
|
::= { upsConfig 13 }
|
|
|
|
|
|
upsCfgBatterylowprotect OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable battery low protect"
|
|
::= { upsConfig 14 }
|
|
|
|
|
|
|
|
upsCfgP1progoutletcontrol OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable p1 programmable outlet control (battery mode)"
|
|
::= { upsConfig 15 }
|
|
|
|
|
|
|
|
upsCfgP2progoutletcontrol OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable p2 programmable outlet control (battery mode)"
|
|
::= { upsConfig 16 }
|
|
|
|
|
|
upsCfgInverterShortClear OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable Inverter short clear function"
|
|
::= { upsConfig 17 }
|
|
|
|
|
|
|
|
|
|
upsCfgSitefaildetection OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Setting this object to enable/disable site fail detection"
|
|
::= { upsConfig 18 }
|
|
|
|
|
|
|
|
upsCfgBatNumInParallel OBJECT-TYPE
|
|
SYNTAX INTEGER (1..99)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery numbers in parallel (battery numbers setting)"
|
|
::= { upsConfig 19 }
|
|
|
|
|
|
upsCfgBatNumInSeries OBJECT-TYPE
|
|
SYNTAX INTEGER (1..20)
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery numbers in series (battery numbers setting)"
|
|
::= { upsConfig 20 }
|
|
|
|
|
|
|
|
upsCfgBypassmaxvoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (1760..2760)
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass mode max voltage"
|
|
|
|
::= { upsConfig 21 }
|
|
|
|
|
|
upsCfgBypassminvoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (1760..2640)
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass mode min voltage"
|
|
::= { upsConfig 22 }
|
|
|
|
|
|
upsCfgBypassmaxfrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (510..700) -- ( 510..600 ,610..700)
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass mode max frequency ,for 50 HZ (510..600) for 60HZ (610..700)"
|
|
::= { upsConfig 23 }
|
|
|
|
|
|
|
|
upsCfgBypassminfrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (400..590) --(400..490,500..590)
|
|
UNITS "0.1 Hertz"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass mode min frequency, for 50HZ (400..490) for 60Hz (500..590)"
|
|
::= { upsConfig 24 }
|
|
|
|
|
|
|
|
upsCfgECOmaxvoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (10..3000)
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ECO mode max voltage"
|
|
|
|
::= { upsConfig 25 }
|
|
|
|
upsCfgECOminvoltage OBJECT-TYPE
|
|
SYNTAX INTEGER (10..3000)
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ECO mode min voltage"
|
|
::= { upsConfig 26 }
|
|
|
|
|
|
upsCfgFreeRunMaxFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (400..700)
|
|
UNITS "0.1 Hertz "
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Free run mode max frequency"
|
|
::= { upsConfig 27 }
|
|
|
|
|
|
|
|
upsCfgFreeRunMinFrequency OBJECT-TYPE
|
|
SYNTAX INTEGER (400..700)
|
|
UNITS "0.1 Hertz "
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Free run mode min frequency"
|
|
::= { upsConfig 28 }
|
|
|
|
|
|
|
|
|
|
upsCfgEPOStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get EPO status,configured by mamual"
|
|
::= { upsConfig 29 }
|
|
|
|
|
|
|
|
upsCfgQSK1Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get QSK 1 status"
|
|
::= { upsConfig 30 }
|
|
|
|
upsCfgQSK2Status OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get QSK 2 status"
|
|
::= { upsConfig 31 }
|
|
|
|
upsCfgQSKT1Delaytime OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
UNITS "minutes "
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get QSKT 1 time delay"
|
|
::= { upsConfig 32 }
|
|
|
|
upsCfgQSKT2Delaytime OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
UNITS "minutes "
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get QSKT 2 time delay"
|
|
::= { upsConfig 33 }
|
|
|
|
upsCfgConstantPhaseAngle OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"setting this object to Enable/disable Constant Phase Angle function"
|
|
::= { upsConfig 34 }
|
|
|
|
---PE/PD q
|
|
|
|
upsCfgInPhaseAngle OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
Angle000(0),
|
|
Angle120(120),
|
|
Angle180(180),
|
|
Angle240(240)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Get input phase angle"
|
|
::= { upsConfig 35 }
|
|
|
|
---QPD
|
|
|
|
upsCfgOutPhaseAngle OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
Angle000(0),
|
|
Angle120(120),
|
|
Angle180(180),
|
|
Angle240(240)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set output phase angle"
|
|
::= { upsConfig 36 }
|
|
|
|
---QPD PPD<NNN>
|
|
|
|
upsCfgLimiRunOnBatMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/disable limited runtime on battery mode"
|
|
::= { upsConfig 37 }
|
|
|
|
|
|
upsCfgChargingCurrent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Amp DC"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Set charging current to battery ."
|
|
::= { upsConfig 38 }
|
|
|
|
upsCfgBatSeftCheckVolt OBJECT-TYPE
|
|
SYNTAX INTEGER (2400..2800)
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"BatTest until battery voltage lower than <nnn>"
|
|
::= { upsConfig 39 }
|
|
|
|
upsCfgOverChargVolt OBJECT-TYPE
|
|
SYNTAX INTEGER (130..143)
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set over charging voltage to per battery"
|
|
::= { upsConfig 40 }
|
|
|
|
upsCfgBattUnderVolt OBJECT-TYPE
|
|
SYNTAX INTEGER (2000..2400)
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set battery under voltage of setting value.value is a number ranging from 200V to 240V"
|
|
::= { upsConfig 41 }
|
|
|
|
upsCfgBattLowVolt OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set battery low voltage of setting value.it is 10 to 40V high than battery under voltage.
|
|
it is 10 to 40V high than battery under voltage.default 20.
|
|
it means that the battery low point is battery under add 20.
|
|
for example, if the battery under voltage is 210V, the battry low point voltage is 230V.
|
|
"
|
|
::= { upsConfig 42 }
|
|
|
|
upsCfgIn1VoltHLoss OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set input1 voltage high loss point."
|
|
::= { upsConfig 43 }
|
|
|
|
upsCfgIn1VoltLLoss OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set input1 voltage low loss point."
|
|
::= { upsConfig 44 }
|
|
|
|
upsCfgIn2VoltHLoss OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set input2 voltage high loss point."
|
|
::= { upsConfig 45 }
|
|
|
|
upsCfgIn2VoltLLoss OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
UNITS "0.1 Volts"
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"set input2 voltage low loss point."
|
|
::= { upsConfig 46 }
|
|
|
|
upsCfgBatteryTurnOn OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disable(0),
|
|
enable(1),
|
|
notsupport(2)
|
|
}
|
|
ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Enable/disable battery turn on."
|
|
::= { upsConfig 47 }
|
|
|
|
-- ===========================================================================
|
|
-- upsTraps
|
|
-- prefix = upsTraps
|
|
-- Traps group
|
|
-- ===========================================================================
|
|
|
|
-- This section defines the well-known notifications sent by
|
|
-- UPS agents.
|
|
|
|
-- this traps use one share trap-node for send traps ,the trap-node vlaue between 1 and 127.
|
|
-- the share trap-node name is trapleafnodev1v2;
|
|
|
|
-- if failure or warning occur ,traps send immediately , if question not resolved,agent will resend every 4 seconds.
|
|
-- info only send once
|
|
|
|
trapleafnodev103 OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (16..16))
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The share trap-node for send all traps,snmpcard V1-03 and later use this trap-node
|
|
char trap[16];
|
|
trap[0]: trap[0]=1,fault trap ; trap[0]=0,warn trap"
|
|
::= { upsTraps 998 }
|
|
|
|
trapleafnodev1v2 OBJECT-TYPE
|
|
SYNTAX INTEGER (0..255)
|
|
ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The share trap-node for send all traps"
|
|
::= { upsTraps 999 }
|
|
|
|
|
|
cmpACFailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"AC failure"
|
|
::= 1
|
|
|
|
cmpFanFailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Fan failure"
|
|
::= 2
|
|
|
|
cmpUPSFailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"UPS failure"
|
|
::= 3
|
|
|
|
cmpChargerFailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Charger failure"
|
|
::= 4
|
|
|
|
cmpOverloadFailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Overload failure"
|
|
::= 5
|
|
|
|
cmpOvertempFailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Over temperature fault."
|
|
::= 6
|
|
|
|
cmpInvertershortcircuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Inverter short-circuited"
|
|
::= 7
|
|
|
|
cmpbatteryfusebeingoc TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery fuse being open-dcircuited failure"
|
|
::= 8
|
|
|
|
|
|
|
|
cmpLowbattery TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"The UPS has returned from a low battery
|
|
condition."
|
|
::= 9
|
|
|
|
cmpSysgotoshutdown TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"System is going to shutdown"
|
|
::= 10
|
|
|
|
|
|
cmpSitefault TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Site fault"
|
|
::= 11
|
|
|
|
|
|
cmpPhasesequenceincorrect TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Phase sequence incorrect"
|
|
::= 12
|
|
|
|
cmpPhasesequenceincorrectbypass TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Phase sequence incorrect in bypass"
|
|
::= 13
|
|
|
|
cmpFanalarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Fan alarm."
|
|
::= 14
|
|
|
|
|
|
cmpEPOenabled TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EPO enabled"
|
|
::= 15
|
|
|
|
cmpUnabletotrunonUPS TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Unalbe to turn on UPS"
|
|
::= 16
|
|
|
|
cmpOvertemperaturealarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Over temperature alarm"
|
|
::= 17
|
|
|
|
cmpInputfrequnstablebypass TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Input frequency unstable in bypass"
|
|
::= 18
|
|
|
|
|
|
cmpChargeralarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Charger alarm"
|
|
::= 19
|
|
|
|
|
|
cmpL1inputfusenotwork TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L1 input fuse not working"
|
|
::= 20
|
|
|
|
cmpNeutralnotConnected TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Neutral not connected"
|
|
::= 21
|
|
|
|
cmpL2inputfusenotwork TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L2 input fuse not working"
|
|
::= 22
|
|
|
|
cmpL3inputfusenotwork TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L3 input fuse not working"
|
|
::= 23
|
|
|
|
|
|
cmpPositivePFCabnormalL1 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Positive PFC abnormal in L1"
|
|
::= 24
|
|
|
|
|
|
cmpNegativePFCabnormalL1 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Negative PFC abnormal in L1"
|
|
::= 25
|
|
|
|
|
|
cmpPositivePFCabnormalL2 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Positive PFC abnormal in L2"
|
|
::= 26
|
|
|
|
cmpNegativePFCabnormalL2 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Negative PFC abnormal in L2"
|
|
::= 27
|
|
|
|
cmpPositivePFCabnormalL3 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Positive PFC abnormal in L3"
|
|
::= 28
|
|
|
|
cmpNegativePFCabnormalL3 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Negative PFC abnormal in L3"
|
|
::= 29
|
|
|
|
|
|
cmpBusvoltagenotwds TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bus voltage not within default setting"
|
|
::= 30
|
|
|
|
|
|
cmpBusvoltageovermaxvalue TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bus voltage over maxinum value"
|
|
::= 31
|
|
|
|
cmpBusvoltagebelowminvalue TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bus voltage below mininum value"
|
|
::= 32
|
|
|
|
cmpBusvoltagediffoutofrange TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bus voltage differences out fo acceptable range"
|
|
::= 33
|
|
|
|
cmpBusvoltageofsloperatetoofast TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bus voltage of slope rate drops too fast"
|
|
::= 34
|
|
|
|
cmpOvercurrentinPFCII TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"WARNING:Over current in PFC input inductor."
|
|
::= 35
|
|
|
|
cmpInvertervoloutofrange TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Inverter voltage not within default setting."
|
|
::= 36
|
|
|
|
cmpInvertervolovermaxvalue TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Inverter voltage over maximum value."
|
|
::= 37
|
|
|
|
cmpInvertervolbelowminvalue TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Inverter voltage below minimum value."
|
|
::= 38
|
|
|
|
|
|
cmpBatteryoppositelyconnected TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery oppositely connected."
|
|
::= 39
|
|
|
|
cmpL2phaseshortcicuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L2Phase inverter short-cicuited."
|
|
::= 40
|
|
|
|
cmpL3phaseshortcicuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L3Phase inverter short-cicuited."
|
|
::= 41
|
|
|
|
cmpL1L2invertershortcicuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L1L2Inverter short-cicuited."
|
|
::= 42
|
|
|
|
cmpL2L3invertershortcicuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L2L3Inverter short-cicuited."
|
|
::= 43
|
|
|
|
cmpL3L1invertershortcicuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L3L1Inverter short-cicuited."
|
|
::= 44
|
|
|
|
|
|
cmpL1negativepoweroutofrange TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L1 inverter negative powere out of acceptable range."
|
|
::= 45
|
|
|
|
cmpL2negativepoweroutofrange TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L2 inverter negative powere out of acceptable range."
|
|
::= 46
|
|
|
|
cmpL3negativepoweroutofrange TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"L3 inverter negative powere out of acceptable range."
|
|
::= 47
|
|
|
|
cmpBatterySCRshortcircuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery SCR short-circuited."
|
|
::= 48
|
|
|
|
cmpLineSCRshortcircuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Line SCR short-circuited."
|
|
::= 49
|
|
|
|
cmpInverterrelayopenfault TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Inverter relay open fault."
|
|
::= 50
|
|
|
|
cmpInverterrelayshortcircuited TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Inverter relay short-circuited."
|
|
::= 51
|
|
|
|
cmpInoutwiresoppositelyconnected TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Input and output wires oppositely connected."
|
|
::= 52
|
|
|
|
cmpabnormalcanbuscommunication TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Abnormal in CAN-bus communication."
|
|
::= 53
|
|
|
|
cmpcommfailurebcupsboard TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Communication failure between cpus in control board.Or DSP and MCU communication error"
|
|
::= 54
|
|
|
|
cmpabnormalsyncsignalcircuit TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Abnomal in synchronous signal circuit."
|
|
::= 55
|
|
|
|
cmpabnormalsyncpulsesignalcircuit TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Abnomal in synchronous pulse signal circuit."
|
|
::= 56
|
|
|
|
|
|
cmpcurrent3punbalancedetected TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Warning for a three-phase input current unbalance detected."
|
|
::= 57
|
|
|
|
cmpbatteryselftestfailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery self-test failure."
|
|
::= 58
|
|
|
|
cmpintercurrentunbalance TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Inverter inter-current unbalance."
|
|
::= 59
|
|
|
|
cmpbatterydisconnected TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery disconnected."
|
|
::= 60
|
|
|
|
cmpabnormalhostsignalcircuit TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Abnormal in host signal circuit."
|
|
::= 61
|
|
|
|
cmpbatteryovercharged TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bettery overcharged."
|
|
::= 62
|
|
|
|
cmpbatteryvoltoohigh TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bettery voltage is too high."
|
|
::= 63
|
|
|
|
cmpbatteryvoltoolow TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bettery voltage is too low."
|
|
::= 64
|
|
|
|
cmpfemaleconnectornotconnwell TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Female connector of parallel cable not connected well."
|
|
::= 65
|
|
|
|
cmpmaleconnectornotconnwell TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Male connector of parallel cable not connected well."
|
|
::= 66
|
|
|
|
|
|
cmplockingbypassA3COW30M TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Locking inbypass mode after 3 consecutive overloads within 30 minutes"
|
|
|
|
::= 67
|
|
|
|
|
|
cmpparallelcabledisconnected TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Parallel cable disconnected"
|
|
|
|
::= 68
|
|
|
|
cmpsyncpulsecircuitfault TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Synchronous pulse signal circuit fault"
|
|
|
|
::= 69
|
|
|
|
|
|
cmpsyncsignalcircuitfalt TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Synchronous signal circuit fault"
|
|
|
|
::= 70
|
|
|
|
cmphostsignalcircuitfault TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Host signal circuit fault"
|
|
|
|
::= 71
|
|
|
|
cmpcanbuscommunicationfault TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Can-bus communication fault"
|
|
|
|
::= 72
|
|
|
|
cmplowlosspointforvolinACmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Low loss point for voltage in ac mode not consistent in parallel systems"
|
|
|
|
::= 73
|
|
|
|
cmphighlosspointforvolinACmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"High loss point for voltage in ac mode not consistent in parallel systems"
|
|
|
|
::= 74
|
|
|
|
cmplowlosspointforfreqinACmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Low loss point for frequency in ac mode not consistent in parallel systems"
|
|
|
|
::= 75
|
|
|
|
cmphighlosspointforfreqinACmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"High loss point for frequency in ac mode not consistent in parallel systems"
|
|
|
|
::= 76
|
|
|
|
cmplowlosspointforvolinbypassmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Low loss point for voltage in bypass mode not consistent in parallel systems"
|
|
|
|
::= 77
|
|
|
|
|
|
cmphighlosspointforvolinbypassmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"High loss point for voltage in bypass mode not consistent in parallel systems"
|
|
|
|
::= 78
|
|
|
|
|
|
cmplowlosspointforfreqinbypassmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Low loss point for frequency in bypass mode not consistent in parallel systems"
|
|
|
|
::= 79
|
|
|
|
cmphighlosspointforfreqinbypassmode TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"High loss point for frequency in bypass mode not consistent in parallel systems"
|
|
|
|
::= 80
|
|
|
|
cmploadunbalanced TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Load unbalanced"
|
|
|
|
::= 81
|
|
|
|
|
|
cmpoverloadalarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Overload alarm"
|
|
|
|
::= 82
|
|
|
|
|
|
cmpparallelnotconnectedwell TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Parallel cable not connected well"
|
|
|
|
::= 83
|
|
|
|
cmpcommunicationlost TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Communication lost"
|
|
::= 84
|
|
|
|
|
|
cmpbatteryconnnotsonsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery connection not consistent in parallel systems"
|
|
::= 85
|
|
|
|
|
|
cmpconverternotconsisstent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Converter setting not consistent in parallel systems"
|
|
::= 86
|
|
|
|
cmpbypassnotallownotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bypass not allowed setting not consistent in parallel systems"
|
|
::= 87
|
|
|
|
|
|
cmpACconnnotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"AC connection not consistent in parallel systems"
|
|
::= 88
|
|
|
|
cmpinput3pcurrentunbalance TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Warning for three-phase ac input current unbalance"
|
|
::= 89
|
|
|
|
cmpbypassconnnotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bypass connection not consistent in parallel systems"
|
|
::= 90
|
|
|
|
cmpbatteryprotectionnotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery protection setting not consistent in parallel systems"
|
|
::= 91
|
|
|
|
cmpbatterydetectionnotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery detection setting not consistent in parallel systems"
|
|
::= 92
|
|
|
|
|
|
|
|
cmpupsmodeltypesnotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"UPS model types not consistent in parallel systems"
|
|
::= 93
|
|
|
|
cmpbypassnotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bypass setting not consistent in parallel systems"
|
|
::= 94
|
|
|
|
|
|
cmpcapacitynotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Capacity of upss not consistent in parallel systems"
|
|
::= 95
|
|
|
|
cmpautorestartnotconsistent TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Auto restart setting not consistent in parallel systems"
|
|
::= 96
|
|
|
|
|
|
cmpBatteryReplace TRAP-TYPE ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery need to be replace"
|
|
::= 97
|
|
|
|
|
|
cmpACNormal TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"AC normal"
|
|
::= 100
|
|
|
|
cmpOutputBadAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Output bad alarm"
|
|
::= 103
|
|
|
|
|
|
cmpBypassBadAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Bypass bad alarm"
|
|
::= 104
|
|
|
|
|
|
cmpOutputOffAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Output off alarm"
|
|
::= 105
|
|
|
|
|
|
cmpUPSShutAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"UPS shutdown alarm"
|
|
::= 106
|
|
|
|
cmpSystemOffAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"System off alarm"
|
|
::= 107
|
|
|
|
cmpFuseFailureAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Fuse failure alarm"
|
|
::= 108
|
|
|
|
cmpGenFailureAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"General failure alarm"
|
|
::= 109
|
|
|
|
cmpAwaitPowerAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Awaiting power alarm"
|
|
::= 110
|
|
|
|
cmpShutPendingAlarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Shutdown pending alarm"
|
|
::= 111
|
|
|
|
cmpBatDepleted TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery depleted"
|
|
::= 112
|
|
|
|
|
|
cmpUnknowStatus TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery unknow status"
|
|
::= 113
|
|
|
|
cmpOutputOn TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Output on"
|
|
::= 114
|
|
|
|
cmpTurntobypass TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Ups turn to bypass mode"
|
|
::= 115
|
|
|
|
cmpTurntobattery TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Ups turn to battery mode"
|
|
::= 116
|
|
|
|
cmpOutBooster TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Turn to booster"
|
|
::= 117
|
|
|
|
|
|
cmpOutReducer TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Turn to reducer"
|
|
::= 118
|
|
|
|
cmpOutBattest TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Turn to battery test mode"
|
|
::= 119
|
|
|
|
|
|
cmpOtherSource TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Other source"
|
|
::= 120
|
|
|
|
cmpBatfailure TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery failure"
|
|
::= 121
|
|
|
|
|
|
cmpBatTestDonePassed TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery test passed"
|
|
::= 122
|
|
|
|
cmpBatTestDoneWarning TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery test done warning "
|
|
::= 123
|
|
|
|
|
|
cmpBatTestDoneAborted TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery test done Aborted"
|
|
::= 124
|
|
|
|
cmpBatteryNormal TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery normal"
|
|
::= 125
|
|
|
|
cmpBatteryDischarging TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Battery Discharging "
|
|
::= 126
|
|
|
|
cmpP1cutoffprealarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"P1 cut off pre-alarm "
|
|
::= 127
|
|
|
|
cmpInputPhaseError TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Warning for input phase error for LV 6-10K UPS"
|
|
::= 128
|
|
cmpMaintainSwitchOpenalarm TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"Warning for maintain switch open"
|
|
::= 129
|
|
|
|
cmpEMDChAbnormal1 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 1 Abnormal"
|
|
::= 130
|
|
cmpEMDChAbnormal2 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 2 Abnormal"
|
|
::= 131
|
|
cmpEMDChAbnormal3 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 3 Abnormal"
|
|
::= 132
|
|
cmpEMDChAbnormal4 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 4 Abnormal"
|
|
::= 133
|
|
cmpEMDChAbnormal5 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 5 Abnormal: smoke alarm"
|
|
::= 134
|
|
cmpEMDChAbnormal6 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 6 Abnormal"
|
|
::= 135
|
|
cmpEMDChAbnormal7 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 7 Abnormal"
|
|
::= 136
|
|
cmpEMDChAbnormal8 TRAP-TYPE
|
|
ENTERPRISE upsTraps
|
|
DESCRIPTION
|
|
"EMD Channels 8 Abnormal"
|
|
::= 137
|
|
--===============================================================================
|
|
--extend
|
|
--===============================================================================
|
|
|
|
extendWorkTemperature OBJECT-TYPE
|
|
SYNTAX INTEGER (-2200..2200)
|
|
UNITS "degrees 0.1 Centigrade"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature of work environment"
|
|
::= { extend 1 }
|
|
|
|
extendWorkhumidity OBJECT-TYPE
|
|
SYNTAX INTEGER (0..100)
|
|
UNITS "percent"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity of work environment"
|
|
::= { extend 2 }
|
|
|
|
|
|
extendSmokeScope OBJECT-TYPE
|
|
SYNTAX INTEGER (0..1000000)
|
|
UNITS "%/FOOT"
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The smokeScope of work environment"
|
|
::= { extend 3 }
|
|
|
|
|
|
extendEMDAlarm1 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(0)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment detector alarm 1"
|
|
::= { extend 4 }
|
|
|
|
extendEMDAlarm2 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(0)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment detector alarm 2"
|
|
::= { extend 5 }
|
|
|
|
|
|
extendEMDAlarm3 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(0)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment detector alarm 3"
|
|
::= { extend 6 }
|
|
|
|
extendEMDAlarm4 OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
on(1),
|
|
off(0)
|
|
}
|
|
ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Environment detector alarm 4"
|
|
::= { extend 7 }
|
|
|
|
END
|