MBG-SNMP-FDMXPT-MIB DEFINITIONS ::= BEGIN
--
-- Top-level infrastructure of the MBG FDMXPT-SNMP project enterprise MIB tree
--
IMPORTS
MODULE-IDENTITY, OBJECT-TYPE, Integer32, NOTIFICATION-TYPE FROM SNMPv2-SMI
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
DisplayString FROM SNMPv2-TC
mbgSnmpRoot FROM MBG-SNMP-ROOT-MIB;
mbgFDM MODULE-IDENTITY
LAST-UPDATED "201201250000Z"
ORGANIZATION "www.meinberg.de"
CONTACT-INFO
"postal: Meinberg Funkuhren
Auf der Landwehr 22
31812 Bad Pyrmont
Germany
email: info@meinberg.de"
DESCRIPTION
"Top-level infrastructure of the MBG-SNMP project enterprise MIB tree"
REVISION "201201250000Z"
DESCRIPTION
"Update to new format using MBG-SNMP-ROOT-MIB"
REVISION "200601200000Z"
DESCRIPTION
"Covering FDMXPT modules from Meinberg"
::= { mbgSnmpRoot 15 }
--
-- MBG-SNMP enterprise-specific management objects
--
--
-- Copy everything from here into your MBG-SNMP-MIB.txt file, if you are using several different SNMP-supporting Meinberg systems
--
mbgFDMData OBJECT IDENTIFIER ::= {mbgFDM 2}
mbgFDMTraps OBJECT IDENTIFIER ::= {mbgFDM 3}
mbgFDMMode OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current Mode of FDM"
::= { mbgFDMData 1 }
mbgFDMModeVal OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current Mode of FDM as value"
--- " 0: Normal Operation"
--- " 1: Direct Mode (no automatic monitoring)"
--- " 2: Timeout Error (no communication with FDM)"
--- " 3: Error (check error bits)"
DEFVAL { 0 }
::= { mbgFDMData 2 }
mbgFDMFrequency OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current powerline frequency in Hz as measured by FDM"
--- Example: "49.997" represents 49.997 Hz
::= { mbgFDMData 3 }
mbgFDMFrequencyVal OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current powerline frequency in Hz*1000 as value"
--- Example: 50034 represents 50.034 Hz
DEFVAL { 0 }
::= { mbgFDMData 4 }
mbgFDMRefTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current reference time of FDM"
--- Example: "15:35:01", is provided by the reference clock (e.g. GPS)
::= { mbgFDMData 5 }
mbgFDMPLTime OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current powerline time of FDM"
--- Example: "15:35:01", is initially read from the reference clock and then
--- the powerline frequency is used as a clock frequency
::= { mbgFDMData 6 }
mbgFDMFreqDev OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Frequency Devidation in Hz"
--- Example: "-00.002" represents a difference of -0.002 Hz
--- (current powerline frequency compared to nominal powerline frequency)
::= { mbgFDMData 7 }
mbgFDMFreqDevVal OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current frequency deviation in Hz*1000 as value"
--- Example: -22 represents -0.022 Hz
DEFVAL { 0 }
::= { mbgFDMData 8 }
mbgFDMTimeDev OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Time Devidation in seconds"
--- Example: "-00.102" represents a time difference of -102 ms or -0.102 seconds"
--- (reftime compared to pltime)
::= { mbgFDMData 9 }
mbgFDMTimeDevVal OBJECT-TYPE
SYNTAX Integer32
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"current time deviation in ms"
--- Example: -22 represents -22 ms
DEFVAL { 0 }
::= { mbgFDMData 10 }
mbgFDMErrorStatus OBJECT-TYPE
SYNTAX DisplayString
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"The 8 error bits of the FDM in string format"
--- Example: "00000000" says "no error bits set"
--- and "00000101" says Error bits 1 and 3 set
::= { mbgFDMData 11 }
--
-- SNMP trap definitions
--
mbgFDMTrapInternalError NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when an internal error occurs (see error bits)"
::= { mbgFDMTraps 1 }
mbgFDMTrapNoTimeString NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when no time string can be read from reference clock"
::= { mbgFDMTraps 2 }
mbgFDMTrapNo10Mhz NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when the reference frequency is not available"
::= { mbgFDMTraps 3 }
mbgFDMTrapNoPPS NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when the reference Pulse Per Second is not available"
::= { mbgFDMTraps 4 }
mbgFDMTrapNoPowerline NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when powerline frequency could not be detected"
-- is the powerline connected?
::= { mbgFDMTraps 5 }
mbgFDMTrapTimeDeviationOverflow NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when a time deviation overflow happens"
::= { mbgFDMTraps 6 }
mbgFDMTrapA1Overflow NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when Analog1 overflows"
::= { mbgFDMTraps 7 }
mbgFDMTrapA2Overflow NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when Analog2 overflows"
::= { mbgFDMTraps 8 }
mbgFDMTrapFreqLimitExceeded NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when the current frequency exceeds the valid frequency range"
::= { mbgFDMTraps 9 }
mbgFDMXPTReboot NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when the FDMXPT module starts up"
-- happens at system startup and if the FDMXPT module reboots
::= { mbgFDMTraps 10 }
mbgFDMNormalOperation NOTIFICATION-TYPE
STATUS current
DESCRIPTION
"trap to be sent when the FDM status is OK (Normal Operation)"
-- happens at system startup and as soon as all error conditions have been cleared
::= { mbgFDMTraps 99 }
--
-- Conformance Statements
--
mbgFDMConformance OBJECT IDENTIFIER ::= { mbgFDM 90 }
mbgFDMCompliances OBJECT IDENTIFIER ::= { mbgFDMConformance 1 }
mbgFDMGroups OBJECT IDENTIFIER ::= { mbgFDMConformance 2 }
mbgFDMCompliance MODULE-COMPLIANCE
STATUS current
DESCRIPTION
"The compliance statement for SNMP entities which implement version 2
of the XPT MIB"
MODULE -- this module
MANDATORY-GROUPS {
mbgFDMObjectsGroup,
mbgFDMTrapsGroup
}
::= { mbgFDMCompliances 1 }
mbgFDMObjectsGroup OBJECT-GROUP
OBJECTS {
mbgFDMMode,
mbgFDMModeVal,
mbgFDMFrequency,
mbgFDMFrequencyVal,
mbgFDMRefTime,
mbgFDMPLTime,
mbgFDMFreqDev,
mbgFDMFreqDevVal,
mbgFDMTimeDev,
mbgFDMTimeDevVal,
mbgFDMErrorStatus
}
STATUS current
DESCRIPTION
"The collection of objects for the MBG FDMXPT MIB"
::= { mbgFDMGroups 1 }
mbgFDMTrapsGroup NOTIFICATION-GROUP
NOTIFICATIONS {
mbgFDMTrapInternalError,
mbgFDMTrapNoTimeString,
mbgFDMTrapNo10Mhz,
mbgFDMTrapNoPPS,
mbgFDMTrapNoPowerline,
mbgFDMTrapTimeDeviationOverflow,
mbgFDMTrapA1Overflow,
mbgFDMTrapA2Overflow,
mbgFDMTrapFreqLimitExceeded,
mbgFDMXPTReboot,
mbgFDMNormalOperation
}
STATUS current
DESCRIPTION
"The collection of traps for the MBG FDMXPT MIB"
::= { mbgFDMGroups 2 }