- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
292 lines
7.8 KiB
Text
Executable file
292 lines
7.8 KiB
Text
Executable file
MBG-SNMP-FDMXPT-MIB DEFINITIONS ::= BEGIN
|
|
|
|
--
|
|
-- Top-level infrastructure of the MBG FDMXPT-SNMP project enterprise MIB tree
|
|
--
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, Integer32, NOTIFICATION-TYPE FROM SNMPv2-SMI
|
|
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
|
|
DisplayString FROM SNMPv2-TC
|
|
|
|
mbgSnmpRoot FROM MBG-SNMP-ROOT-MIB;
|
|
|
|
mbgFDM MODULE-IDENTITY
|
|
LAST-UPDATED "201201250000Z"
|
|
ORGANIZATION "www.meinberg.de"
|
|
CONTACT-INFO
|
|
"postal: Meinberg Funkuhren
|
|
Auf der Landwehr 22
|
|
31812 Bad Pyrmont
|
|
Germany
|
|
|
|
email: info@meinberg.de"
|
|
DESCRIPTION
|
|
"Top-level infrastructure of the MBG-SNMP project enterprise MIB tree"
|
|
REVISION "201201250000Z"
|
|
DESCRIPTION
|
|
"Update to new format using MBG-SNMP-ROOT-MIB"
|
|
REVISION "200601200000Z"
|
|
DESCRIPTION
|
|
"Covering FDMXPT modules from Meinberg"
|
|
::= { mbgSnmpRoot 15 }
|
|
|
|
|
|
--
|
|
-- MBG-SNMP enterprise-specific management objects
|
|
--
|
|
--
|
|
-- Copy everything from here into your MBG-SNMP-MIB.txt file, if you are using several different SNMP-supporting Meinberg systems
|
|
--
|
|
|
|
mbgFDMData OBJECT IDENTIFIER ::= {mbgFDM 2}
|
|
mbgFDMTraps OBJECT IDENTIFIER ::= {mbgFDM 3}
|
|
|
|
|
|
|
|
mbgFDMMode OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current Mode of FDM"
|
|
::= { mbgFDMData 1 }
|
|
|
|
mbgFDMModeVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current Mode of FDM as value"
|
|
--- " 0: Normal Operation"
|
|
--- " 1: Direct Mode (no automatic monitoring)"
|
|
--- " 2: Timeout Error (no communication with FDM)"
|
|
--- " 3: Error (check error bits)"
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 2 }
|
|
|
|
mbgFDMFrequency OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current powerline frequency in Hz as measured by FDM"
|
|
--- Example: "49.997" represents 49.997 Hz
|
|
::= { mbgFDMData 3 }
|
|
|
|
mbgFDMFrequencyVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current powerline frequency in Hz*1000 as value"
|
|
--- Example: 50034 represents 50.034 Hz
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 4 }
|
|
|
|
|
|
mbgFDMRefTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current reference time of FDM"
|
|
--- Example: "15:35:01", is provided by the reference clock (e.g. GPS)
|
|
::= { mbgFDMData 5 }
|
|
|
|
mbgFDMPLTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current powerline time of FDM"
|
|
--- Example: "15:35:01", is initially read from the reference clock and then
|
|
--- the powerline frequency is used as a clock frequency
|
|
::= { mbgFDMData 6 }
|
|
|
|
mbgFDMFreqDev OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Frequency Devidation in Hz"
|
|
--- Example: "-00.002" represents a difference of -0.002 Hz
|
|
--- (current powerline frequency compared to nominal powerline frequency)
|
|
::= { mbgFDMData 7 }
|
|
|
|
mbgFDMFreqDevVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current frequency deviation in Hz*1000 as value"
|
|
--- Example: -22 represents -0.022 Hz
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 8 }
|
|
|
|
mbgFDMTimeDev OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time Devidation in seconds"
|
|
--- Example: "-00.102" represents a time difference of -102 ms or -0.102 seconds"
|
|
--- (reftime compared to pltime)
|
|
::= { mbgFDMData 9 }
|
|
|
|
mbgFDMTimeDevVal OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"current time deviation in ms"
|
|
--- Example: -22 represents -22 ms
|
|
DEFVAL { 0 }
|
|
::= { mbgFDMData 10 }
|
|
|
|
mbgFDMErrorStatus OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 8 error bits of the FDM in string format"
|
|
--- Example: "00000000" says "no error bits set"
|
|
--- and "00000101" says Error bits 1 and 3 set
|
|
::= { mbgFDMData 11 }
|
|
|
|
--
|
|
-- SNMP trap definitions
|
|
--
|
|
|
|
mbgFDMTrapInternalError NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when an internal error occurs (see error bits)"
|
|
::= { mbgFDMTraps 1 }
|
|
|
|
mbgFDMTrapNoTimeString NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when no time string can be read from reference clock"
|
|
::= { mbgFDMTraps 2 }
|
|
|
|
mbgFDMTrapNo10Mhz NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the reference frequency is not available"
|
|
::= { mbgFDMTraps 3 }
|
|
|
|
mbgFDMTrapNoPPS NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the reference Pulse Per Second is not available"
|
|
::= { mbgFDMTraps 4 }
|
|
|
|
mbgFDMTrapNoPowerline NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when powerline frequency could not be detected"
|
|
-- is the powerline connected?
|
|
::= { mbgFDMTraps 5 }
|
|
|
|
mbgFDMTrapTimeDeviationOverflow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when a time deviation overflow happens"
|
|
::= { mbgFDMTraps 6 }
|
|
|
|
mbgFDMTrapA1Overflow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when Analog1 overflows"
|
|
::= { mbgFDMTraps 7 }
|
|
|
|
mbgFDMTrapA2Overflow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when Analog2 overflows"
|
|
::= { mbgFDMTraps 8 }
|
|
|
|
mbgFDMTrapFreqLimitExceeded NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the current frequency exceeds the valid frequency range"
|
|
::= { mbgFDMTraps 9 }
|
|
|
|
mbgFDMXPTReboot NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the FDMXPT module starts up"
|
|
-- happens at system startup and if the FDMXPT module reboots
|
|
::= { mbgFDMTraps 10 }
|
|
|
|
mbgFDMNormalOperation NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"trap to be sent when the FDM status is OK (Normal Operation)"
|
|
-- happens at system startup and as soon as all error conditions have been cleared
|
|
::= { mbgFDMTraps 99 }
|
|
|
|
--
|
|
-- Conformance Statements
|
|
--
|
|
|
|
|
|
mbgFDMConformance OBJECT IDENTIFIER ::= { mbgFDM 90 }
|
|
mbgFDMCompliances OBJECT IDENTIFIER ::= { mbgFDMConformance 1 }
|
|
mbgFDMGroups OBJECT IDENTIFIER ::= { mbgFDMConformance 2 }
|
|
|
|
mbgFDMCompliance MODULE-COMPLIANCE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compliance statement for SNMP entities which implement version 2
|
|
of the XPT MIB"
|
|
MODULE -- this module
|
|
MANDATORY-GROUPS {
|
|
mbgFDMObjectsGroup,
|
|
mbgFDMTrapsGroup
|
|
}
|
|
::= { mbgFDMCompliances 1 }
|
|
|
|
|
|
mbgFDMObjectsGroup OBJECT-GROUP
|
|
OBJECTS {
|
|
mbgFDMMode,
|
|
mbgFDMModeVal,
|
|
mbgFDMFrequency,
|
|
mbgFDMFrequencyVal,
|
|
mbgFDMRefTime,
|
|
mbgFDMPLTime,
|
|
mbgFDMFreqDev,
|
|
mbgFDMFreqDevVal,
|
|
mbgFDMTimeDev,
|
|
mbgFDMTimeDevVal,
|
|
mbgFDMErrorStatus
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The collection of objects for the MBG FDMXPT MIB"
|
|
|
|
::= { mbgFDMGroups 1 }
|
|
|
|
mbgFDMTrapsGroup NOTIFICATION-GROUP
|
|
NOTIFICATIONS {
|
|
mbgFDMTrapInternalError,
|
|
mbgFDMTrapNoTimeString,
|
|
mbgFDMTrapNo10Mhz,
|
|
mbgFDMTrapNoPPS,
|
|
mbgFDMTrapNoPowerline,
|
|
mbgFDMTrapTimeDeviationOverflow,
|
|
mbgFDMTrapA1Overflow,
|
|
mbgFDMTrapA2Overflow,
|
|
mbgFDMTrapFreqLimitExceeded,
|
|
mbgFDMXPTReboot,
|
|
mbgFDMNormalOperation
|
|
}
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The collection of traps for the MBG FDMXPT MIB"
|
|
|
|
::= { mbgFDMGroups 2 }
|
|
|
|