- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
5534 lines
183 KiB
Text
5534 lines
183 KiB
Text
LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-IDENTITY
|
|
FROM SNMPv2-SMI
|
|
liebertFlexibleConditionsModuleReg
|
|
FROM LIEBERT-GP-REGISTRATION-MIB
|
|
lgpFlexConditions
|
|
FROM LIEBERT-GP-CONDITIONS-MIB
|
|
;
|
|
|
|
-- =============================================================================
|
|
-- Module Identification and Registration
|
|
-- =============================================================================
|
|
|
|
liebertGlobalProductsFlexibleConditionsModule MODULE-IDENTITY
|
|
LAST-UPDATED "201810020000Z"
|
|
ORGANIZATION "Liebert Corporation"
|
|
CONTACT-INFO
|
|
"Contact: Technical Support
|
|
|
|
Postal:
|
|
Liebert Corporation
|
|
1050 Dearborn Drive
|
|
P.O. Box 29186
|
|
Columbus OH, 43229
|
|
US
|
|
|
|
Tel: +1 (800) 222-5877
|
|
|
|
E-mail: liebert.monitoring@vertivco.com
|
|
Web: www.vertivco.com"
|
|
|
|
DESCRIPTION
|
|
"The MIB module used to register Liebert SNMP OIDs.
|
|
|
|
Copyright 2000-2018 Liebert Corporation. All rights reserved.
|
|
Reproduction of this document is authorized on the condition
|
|
that the forgoing copyright notice is included.
|
|
|
|
This Specification is supplied 'AS IS' and Liebert Corporation
|
|
makes no warranty, either express or implied, as to the use,
|
|
operation, condition, or performance of the Specification."
|
|
|
|
REVISION "201810020000Z"
|
|
DESCRIPTION
|
|
"Compiled From GDD Version: 6825.1"
|
|
|
|
|
|
::= { liebertFlexibleConditionsModuleReg 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpFlexConditions - Liebert Conditions Registrations
|
|
-- =============================================================================
|
|
|
|
lgpFlexConditionsWellKnown OBJECT IDENTIFIER
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Liebert well known conditions are defined by OIDs that
|
|
-- reside in this sub-tree."
|
|
::= { lgpFlexConditions 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpFlexConditionsWellKnown - Liebert "well-known" Conditions
|
|
-- =============================================================================
|
|
|
|
lgpCondId4122SystemInputPowerProblem OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input is not qualified to provide power to the system."
|
|
::= { lgpFlexConditionsWellKnown 4122 }
|
|
|
|
lgpCondId4132BypassOverloadPhaseA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on output phase A while operating on the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4132 }
|
|
|
|
lgpCondId4133BypassOverloadPhaseB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on output phase B while operating on the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4133 }
|
|
|
|
lgpCondId4134BypassOverloadPhaseC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on output phase C while operating on the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4134 }
|
|
|
|
lgpCondId4135BypassNotAvailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A problem associated with the bypass has been detected."
|
|
::= { lgpFlexConditionsWellKnown 4135 }
|
|
|
|
lgpCondId4137BypassAutoRetransferPrimed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic retransfer from bypass to inverter is possible."
|
|
::= { lgpFlexConditionsWellKnown 4137 }
|
|
|
|
lgpCondId4138BypassAutoRetransferFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"After performing a recoverable transfer to bypass, an attempt to
|
|
auto retransfer from bypass to inverter failed."
|
|
::= { lgpFlexConditionsWellKnown 4138 }
|
|
|
|
lgpCondId4139BypassExcessAutoRetransfers OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of auto retransfers, from bypass to inverter, has
|
|
exceeded the maximum for a specified time interval."
|
|
::= { lgpFlexConditionsWellKnown 4139 }
|
|
|
|
lgpCondId4140BypassRestartInhibitExternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Restart of the bypass is inhibited by the state of an external
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 4140 }
|
|
|
|
lgpCondId4141BypassBreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass breaker is closed."
|
|
::= { lgpFlexConditionsWellKnown 4141 }
|
|
|
|
lgpCondId4142BypassStaticSwitchOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass off due to static switch overload."
|
|
::= { lgpFlexConditionsWellKnown 4142 }
|
|
|
|
lgpCondId4143BypassStaticSwitchUnavailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The static bypass is unavailable to support the critical load."
|
|
::= { lgpFlexConditionsWellKnown 4143 }
|
|
|
|
lgpCondId4144BypassExcessivePulseParallel OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has performed too many pulse parallel operations within
|
|
a specified time interval."
|
|
::= { lgpFlexConditionsWellKnown 4144 }
|
|
|
|
lgpCondId4145BypassAutoTransferFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An automatic transfer to static bypass failed."
|
|
::= { lgpFlexConditionsWellKnown 4145 }
|
|
|
|
lgpCondId4146SystemInputPhsRotationError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power conductors on the input line are not wired to the UPS in
|
|
the sequence preferred for the rectifier (A-B-C)."
|
|
::= { lgpFlexConditionsWellKnown 4146 }
|
|
|
|
lgpCondId4147SystemInputCurrentLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The RMS input current has reached the input current limit
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4147 }
|
|
|
|
lgpCondId4162BatteryLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The calculated battery time remaining has reached the low battery
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4162 }
|
|
|
|
lgpCondId4163OutputOffEndofDischarge OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output turned off due to battery reaching end-of-discharge."
|
|
::= { lgpFlexConditionsWellKnown 4163 }
|
|
|
|
lgpCondId4164BatteryChargingError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is not charging properly."
|
|
::= { lgpFlexConditionsWellKnown 4164 }
|
|
|
|
lgpCondId4165BatteryChargingReducedExtrnl OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Using a reduced battery charging algorithm due to an external
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 4165 }
|
|
|
|
lgpCondId4166BatteryCapacityLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery capacity is low."
|
|
::= { lgpFlexConditionsWellKnown 4166 }
|
|
|
|
lgpCondId4167OutputOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output is off."
|
|
::= { lgpFlexConditionsWellKnown 4167 }
|
|
|
|
lgpCondId4168BatteryDischarging OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is discharging."
|
|
::= { lgpFlexConditionsWellKnown 4168 }
|
|
|
|
lgpCondId4169BatteryTemperatureImbalance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Excessive temperature differences between battery sensors detected."
|
|
::= { lgpFlexConditionsWellKnown 4169 }
|
|
|
|
lgpCondId4170BatteryEqualize OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rectifier output voltage is increased to equalize the battery
|
|
voltage level."
|
|
::= { lgpFlexConditionsWellKnown 4170 }
|
|
|
|
lgpCondId4171BatteryManualTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual battery test is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4171 }
|
|
|
|
lgpCondId4172BatteryAutoTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic battery test is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4172 }
|
|
|
|
lgpCondId4173MainBatteryDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Main battery disconnect is open."
|
|
::= { lgpFlexConditionsWellKnown 4173 }
|
|
|
|
lgpCondId4174BatteryTemperatureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor fault has been detected."
|
|
::= { lgpFlexConditionsWellKnown 4174 }
|
|
|
|
lgpCondId4175BypassFrequencyError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass frequency is outside the inverter synchronization
|
|
limits."
|
|
::= { lgpFlexConditionsWellKnown 4175 }
|
|
|
|
lgpCondId4176BatteryCircuitBreaker1Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 1 is open."
|
|
::= { lgpFlexConditionsWellKnown 4176 }
|
|
|
|
lgpCondId4177BatteryBreaker1OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 1 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4177 }
|
|
|
|
lgpCondId4178BatteryBreaker1CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 1 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4178 }
|
|
|
|
lgpCondId4179BatteryCircuitBreaker2Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 2 is open."
|
|
::= { lgpFlexConditionsWellKnown 4179 }
|
|
|
|
lgpCondId4180BatteryBreaker2OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 2 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4180 }
|
|
|
|
lgpCondId4181BatteryBreaker2CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 2 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4181 }
|
|
|
|
lgpCondId4182BatteryCircuitBreaker3Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 3 is open."
|
|
::= { lgpFlexConditionsWellKnown 4182 }
|
|
|
|
lgpCondId4183BatteryBreaker3OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 3 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4183 }
|
|
|
|
lgpCondId4184BatteryBreaker3CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 3 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4184 }
|
|
|
|
lgpCondId4185BatteryCircuitBreaker4Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 4 is open."
|
|
::= { lgpFlexConditionsWellKnown 4185 }
|
|
|
|
lgpCondId4186BatteryBreaker4OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 4 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4186 }
|
|
|
|
lgpCondId4187BatteryBreaker4CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 4 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4187 }
|
|
|
|
lgpCondId4188BatteryCircuitBreaker5Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 5 is open."
|
|
::= { lgpFlexConditionsWellKnown 4188 }
|
|
|
|
lgpCondId4189BatteryBreaker5OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 5 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4189 }
|
|
|
|
lgpCondId4190BatteryBreaker5CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 5 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4190 }
|
|
|
|
lgpCondId4191BatteryCircuitBreaker6Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 6 is open."
|
|
::= { lgpFlexConditionsWellKnown 4191 }
|
|
|
|
lgpCondId4192BatteryBreaker6OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 6 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4192 }
|
|
|
|
lgpCondId4193BatteryBreaker6CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 6 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4193 }
|
|
|
|
lgpCondId4194BatteryCircuitBreaker7Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 7 is open."
|
|
::= { lgpFlexConditionsWellKnown 4194 }
|
|
|
|
lgpCondId4195BatteryBreaker7OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 7 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4195 }
|
|
|
|
lgpCondId4196BatteryBreaker7CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 7 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4196 }
|
|
|
|
lgpCondId4197BatteryCircuitBreaker8Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 8 is open."
|
|
::= { lgpFlexConditionsWellKnown 4197 }
|
|
|
|
lgpCondId4198BatteryBreaker8OpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 8 failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4198 }
|
|
|
|
lgpCondId4199BatteryBreaker8CloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery circuit breaker 8 failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4199 }
|
|
|
|
lgpCondId4200BatteryChargingInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery charging is inhibited due to an external inhibit signal."
|
|
::= { lgpFlexConditionsWellKnown 4200 }
|
|
|
|
lgpCondId4213SystemShutdownEPO OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System shutdown due to Emergency Power Off (EPO)."
|
|
::= { lgpFlexConditionsWellKnown 4213 }
|
|
|
|
lgpCondId4214SystemShutdownREPO OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System shutdown due to Remote Emergency Power Off (REPO)."
|
|
::= { lgpFlexConditionsWellKnown 4214 }
|
|
|
|
lgpCondId4215SystemOutputOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system output is off."
|
|
::= { lgpFlexConditionsWellKnown 4215 }
|
|
|
|
lgpCondId4216BypassBackfeedDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system detected a voltage on the bypass when none was expected."
|
|
::= { lgpFlexConditionsWellKnown 4216 }
|
|
|
|
lgpCondId4217BypassManualXfrInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual transfer from inverter to bypass is inhibited - bypass not
|
|
qualified."
|
|
::= { lgpFlexConditionsWellKnown 4217 }
|
|
|
|
lgpCondId4218BypassManualRexfrInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual transfer from bypass to inverter is inhibited - inverter
|
|
output not qualified."
|
|
::= { lgpFlexConditionsWellKnown 4218 }
|
|
|
|
lgpCondId4219BatteryOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor is reporting a value above a
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4219 }
|
|
|
|
lgpCondId4220BatteryExternalMonitor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External battery monitor 1 - battery maintenance required."
|
|
::= { lgpFlexConditionsWellKnown 4220 }
|
|
|
|
lgpCondId4221BatteryExternalMonitor2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External battery monitor 2 - battery maintenance required."
|
|
::= { lgpFlexConditionsWellKnown 4221 }
|
|
|
|
lgpCondId4222BatteryGroundFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery system ground fault amperage exceeds the threshold."
|
|
::= { lgpFlexConditionsWellKnown 4222 }
|
|
|
|
lgpCondId4229EmergencyPowerOffLatched OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System output is off - 'Emergency Power Off (EPO) - latched'
|
|
requires manual reset."
|
|
::= { lgpFlexConditionsWellKnown 4229 }
|
|
|
|
lgpCondId4230SystemOutputLowPowerFactor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system output power factor is low, resulting in reduced output
|
|
capacity."
|
|
::= { lgpFlexConditionsWellKnown 4230 }
|
|
|
|
lgpCondId4231OutputCurrentExceedsThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output current for one or more phases exceeds a threshold."
|
|
::= { lgpFlexConditionsWellKnown 4231 }
|
|
|
|
lgpCondId4233InverterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter failure - inverter output is off."
|
|
::= { lgpFlexConditionsWellKnown 4233 }
|
|
|
|
lgpCondId4234InverterOverloadPhaseA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is operating with an overload on phase A."
|
|
::= { lgpFlexConditionsWellKnown 4234 }
|
|
|
|
lgpCondId4235InverterOverloadPhaseB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is operating with an overload on phase B."
|
|
::= { lgpFlexConditionsWellKnown 4235 }
|
|
|
|
lgpCondId4236InverterOverloadPhaseC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is operating with an overload on phase C."
|
|
::= { lgpFlexConditionsWellKnown 4236 }
|
|
|
|
lgpCondId4237InverterInhibitExternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Restart of the inverter is inhibited by an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4237 }
|
|
|
|
lgpCondId4238InverterOutBreakerOpenFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter output breaker failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4238 }
|
|
|
|
lgpCondId4239InverterOutBreakerCloseFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter output breaker failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4239 }
|
|
|
|
lgpCondId4270InputContact01 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 1."
|
|
::= { lgpFlexConditionsWellKnown 4270 }
|
|
|
|
lgpCondId4271InputContact02 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 2."
|
|
::= { lgpFlexConditionsWellKnown 4271 }
|
|
|
|
lgpCondId4272InputContact03 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 3."
|
|
::= { lgpFlexConditionsWellKnown 4272 }
|
|
|
|
lgpCondId4273InputContact04 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 4."
|
|
::= { lgpFlexConditionsWellKnown 4273 }
|
|
|
|
lgpCondId4274InputContact05 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 5."
|
|
::= { lgpFlexConditionsWellKnown 4274 }
|
|
|
|
lgpCondId4275InputContact06 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 6."
|
|
::= { lgpFlexConditionsWellKnown 4275 }
|
|
|
|
lgpCondId4276InputContact07 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 7."
|
|
::= { lgpFlexConditionsWellKnown 4276 }
|
|
|
|
lgpCondId4277InputContact08 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 8."
|
|
::= { lgpFlexConditionsWellKnown 4277 }
|
|
|
|
lgpCondId4278InputContact09 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 9."
|
|
::= { lgpFlexConditionsWellKnown 4278 }
|
|
|
|
lgpCondId4279InputContact10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 10."
|
|
::= { lgpFlexConditionsWellKnown 4279 }
|
|
|
|
lgpCondId4280InputContact11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 11."
|
|
::= { lgpFlexConditionsWellKnown 4280 }
|
|
|
|
lgpCondId4281InputContact12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 12."
|
|
::= { lgpFlexConditionsWellKnown 4281 }
|
|
|
|
lgpCondId4282InputContact13 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 13."
|
|
::= { lgpFlexConditionsWellKnown 4282 }
|
|
|
|
lgpCondId4283InputContact14 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 14."
|
|
::= { lgpFlexConditionsWellKnown 4283 }
|
|
|
|
lgpCondId4284InputContact15 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 15."
|
|
::= { lgpFlexConditionsWellKnown 4284 }
|
|
|
|
lgpCondId4285InputContact16 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external input contact 16."
|
|
::= { lgpFlexConditionsWellKnown 4285 }
|
|
|
|
lgpCondId4286OutputAmpOverUserLimitPhsA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase A output has exceeded the user amperage threshold."
|
|
::= { lgpFlexConditionsWellKnown 4286 }
|
|
|
|
lgpCondId4287OutputAmpOverUserLimitPhsB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase B output has exceeded the user amperage threshold."
|
|
::= { lgpFlexConditionsWellKnown 4287 }
|
|
|
|
lgpCondId4288OutputAmpOverUserLimitPhsC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The phase C output has exceeded the user amperage threshold."
|
|
::= { lgpFlexConditionsWellKnown 4288 }
|
|
|
|
lgpCondId4289InverterTransferInhibitExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transfer of critical bus source to inverter is inhibited by an
|
|
external signal."
|
|
::= { lgpFlexConditionsWellKnown 4289 }
|
|
|
|
lgpCondId4290InverterShutdownOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter has shutdown due to a sustained overload."
|
|
::= { lgpFlexConditionsWellKnown 4290 }
|
|
|
|
lgpCondId4294InletAirOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inlet air exceeds the maximum temperature threshold."
|
|
::= { lgpFlexConditionsWellKnown 4294 }
|
|
|
|
lgpCondId4295RectifierFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier failure - rectifier is off."
|
|
::= { lgpFlexConditionsWellKnown 4295 }
|
|
|
|
lgpCondId4296RectifierOperationInhibitExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The operation of the rectifier is inhibited by an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4296 }
|
|
|
|
lgpCondId4297UPSOutputonInverter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output power is supplied by the inverter."
|
|
::= { lgpFlexConditionsWellKnown 4297 }
|
|
|
|
lgpCondId4298UPSOutputonBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output power is supplied by the bypass."
|
|
::= { lgpFlexConditionsWellKnown 4298 }
|
|
|
|
lgpCondId4299OutputLoadonMaintBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output power is supplied by the maintenance bypass."
|
|
::= { lgpFlexConditionsWellKnown 4299 }
|
|
|
|
lgpCondId4300InternalCommunicationsFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The control has detected a communication failure of a component on
|
|
the internal communication bus."
|
|
::= { lgpFlexConditionsWellKnown 4300 }
|
|
|
|
lgpCondId4308DCBusGroundFaultPositive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A ground fault has been detected on the positive DC Bus link."
|
|
::= { lgpFlexConditionsWellKnown 4308 }
|
|
|
|
lgpCondId4309DCBusGroundFaultNegative OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A ground fault has been detected on the negative DC Bus link."
|
|
::= { lgpFlexConditionsWellKnown 4309 }
|
|
|
|
lgpCondId4310EquipmentOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Equipment over temperature summary event."
|
|
::= { lgpFlexConditionsWellKnown 4310 }
|
|
|
|
lgpCondId4311SystemFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System fan failure - one or more fans have failed."
|
|
::= { lgpFlexConditionsWellKnown 4311 }
|
|
|
|
lgpCondId4313PasswordChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Password changed."
|
|
::= { lgpFlexConditionsWellKnown 4313 }
|
|
|
|
lgpCondId4314PowerSupplyFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power supply failure."
|
|
::= { lgpFlexConditionsWellKnown 4314 }
|
|
|
|
lgpCondId4315OnGenerator OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A generator is supplying the power to the system."
|
|
::= { lgpFlexConditionsWellKnown 4315 }
|
|
|
|
lgpCondId4316AutoRestartInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Auto restart is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4316 }
|
|
|
|
lgpCondId4317AutoRestartInhibitedExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Auto restart inhibited due to an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4317 }
|
|
|
|
lgpCondId4320InitiatedTransfertoBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User initiated manual transfer to bypass."
|
|
::= { lgpFlexConditionsWellKnown 4320 }
|
|
|
|
lgpCondId4321InitiatedTransfertoInverter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User initiated manual transfer to inverter."
|
|
::= { lgpFlexConditionsWellKnown 4321 }
|
|
|
|
lgpCondId4322BatteryTestPassed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test passed."
|
|
::= { lgpFlexConditionsWellKnown 4322 }
|
|
|
|
lgpCondId4323BatteryTestFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery test failed."
|
|
::= { lgpFlexConditionsWellKnown 4323 }
|
|
|
|
lgpCondId4324BatteryTestManuallyStopped OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery test was manually stopped prior to completion."
|
|
::= { lgpFlexConditionsWellKnown 4324 }
|
|
|
|
lgpCondId4325BackfeedBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The backfeed breaker is in the open position."
|
|
::= { lgpFlexConditionsWellKnown 4325 }
|
|
|
|
lgpCondId4341VelocityAuthenticationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Notification of a message rejected by Velocity due to an
|
|
authentication failure."
|
|
::= { lgpFlexConditionsWellKnown 4341 }
|
|
|
|
lgpCondId4360ReceptacleOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a receptacle over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4360 }
|
|
|
|
lgpCondId4361ReceptacleUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a receptacle under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4361 }
|
|
|
|
lgpCondId4382SystemInputCurrentImbalance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Input Currents are Imbalanced."
|
|
::= { lgpFlexConditionsWellKnown 4382 }
|
|
|
|
lgpCondId4383BypassStaticSwitchOffExtrnl OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass static switch is off due to the state of an external signal."
|
|
::= { lgpFlexConditionsWellKnown 4383 }
|
|
|
|
lgpCondId4384BatteryEoDDisconnect OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery disconnect due to end-of-discharge."
|
|
::= { lgpFlexConditionsWellKnown 4384 }
|
|
|
|
lgpCondId4389SystemOutputFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A fault has been detected in the system output."
|
|
::= { lgpFlexConditionsWellKnown 4389 }
|
|
|
|
lgpCondId4390InverterOffExternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter is off (operation is inhibited) due to external signal
|
|
state."
|
|
::= { lgpFlexConditionsWellKnown 4390 }
|
|
|
|
lgpCondId4391InverterStaticSwitchSCRShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short across one or more inverter static
|
|
switch Silicon Controlled Rectifiers (SCR)."
|
|
::= { lgpFlexConditionsWellKnown 4391 }
|
|
|
|
lgpCondId4392TemperatureSensorError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more temperature sensors cannot provide a valid temperature
|
|
reading (i.e. sensor failure, wiring failure, sense circuit
|
|
failure, etc)."
|
|
::= { lgpFlexConditionsWellKnown 4392 }
|
|
|
|
lgpCondId4406BranchOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4406 }
|
|
|
|
lgpCondId4407BranchUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4407 }
|
|
|
|
lgpCondId4416BranchOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4416 }
|
|
|
|
lgpCondId4417BranchUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4417 }
|
|
|
|
lgpCondId4421BranchFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more conditions indicate a Branch Receptacle Module failure
|
|
, service is required."
|
|
::= { lgpFlexConditionsWellKnown 4421 }
|
|
|
|
lgpCondId4436PDUOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4436 }
|
|
|
|
lgpCondId4437PDUUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4437 }
|
|
|
|
lgpCondId4438SystemInternalTemperatureRise OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Excessive temperature rise internal to the system (i.e. difference
|
|
between the output versus input temperature is too large)."
|
|
::= { lgpFlexConditionsWellKnown 4438 }
|
|
|
|
lgpCondId4439AutomaticRestartFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic restart failed."
|
|
::= { lgpFlexConditionsWellKnown 4439 }
|
|
|
|
lgpCondId4440FuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A summary event indicating one or more fuse failures."
|
|
::= { lgpFlexConditionsWellKnown 4440 }
|
|
|
|
lgpCondId4441SystemControllerError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System controller internal error."
|
|
::= { lgpFlexConditionsWellKnown 4441 }
|
|
|
|
lgpCondId4442SystemBreakersOpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more breakers in the system failed to open."
|
|
::= { lgpFlexConditionsWellKnown 4442 }
|
|
|
|
lgpCondId4448PDUOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4448 }
|
|
|
|
lgpCondId4449PDUUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4449 }
|
|
|
|
lgpCondId4468PDUOverCurrentL1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition on line 1."
|
|
::= { lgpFlexConditionsWellKnown 4468 }
|
|
|
|
lgpCondId4469PDUOverCurrentL2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition on line 2."
|
|
::= { lgpFlexConditionsWellKnown 4469 }
|
|
|
|
lgpCondId4470PDUOverCurrentL3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module over current condition on line 3."
|
|
::= { lgpFlexConditionsWellKnown 4470 }
|
|
|
|
lgpCondId4471PDUUnderCurrentL1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition on line 1."
|
|
::= { lgpFlexConditionsWellKnown 4471 }
|
|
|
|
lgpCondId4472PDUUnderCurrentL2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition on line 2."
|
|
::= { lgpFlexConditionsWellKnown 4472 }
|
|
|
|
lgpCondId4473PDUUnderCurrentL3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under current condition on line 3."
|
|
::= { lgpFlexConditionsWellKnown 4473 }
|
|
|
|
lgpCondId4492ReceptaclePowerStateOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle power state changed to the ON state."
|
|
::= { lgpFlexConditionsWellKnown 4492 }
|
|
|
|
lgpCondId4493ReceptaclePowerStateOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle power state changed to the OFF state."
|
|
::= { lgpFlexConditionsWellKnown 4493 }
|
|
|
|
lgpCondId4494BranchBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Branch Receptacle Module's input breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 4494 }
|
|
|
|
lgpCondId4495DeviceConfigurationChange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Device Configuration Change."
|
|
::= { lgpFlexConditionsWellKnown 4495 }
|
|
|
|
lgpCondId4496BasicDisplayModuleRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Basic Display Module Removed."
|
|
::= { lgpFlexConditionsWellKnown 4496 }
|
|
|
|
lgpCondId4497BasicDisplayModuleDiscovered OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Basic Display Module Discovered."
|
|
::= { lgpFlexConditionsWellKnown 4497 }
|
|
|
|
lgpCondId4500PDUOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a power module over current condition."
|
|
::= { lgpFlexConditionsWellKnown 4500 }
|
|
|
|
lgpCondId4501PDUUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a power module under current condition."
|
|
::= { lgpFlexConditionsWellKnown 4501 }
|
|
|
|
lgpCondId4502PDUFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more conditions indicate a power module failure, service is
|
|
required."
|
|
::= { lgpFlexConditionsWellKnown 4502 }
|
|
|
|
lgpCondId4503PDUCommunicationFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Internal communications failure with the Power Module."
|
|
::= { lgpFlexConditionsWellKnown 4503 }
|
|
|
|
lgpCondId4504BranchRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch Receptacle Module Removed."
|
|
::= { lgpFlexConditionsWellKnown 4504 }
|
|
|
|
lgpCondId4505BranchDiscovered OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Branch Receptacle Module Discovered."
|
|
::= { lgpFlexConditionsWellKnown 4505 }
|
|
|
|
lgpCondId4506BranchOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a Branch Receptacle Module over current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4506 }
|
|
|
|
lgpCondId4507BranchCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a Branch Receptacle Module under current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4507 }
|
|
|
|
lgpCondId4508ReceptacleLoadRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle's load stopped drawing power."
|
|
::= { lgpFlexConditionsWellKnown 4508 }
|
|
|
|
lgpCondId4509ReceptacleLoadAdded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle's load started to draw power."
|
|
::= { lgpFlexConditionsWellKnown 4509 }
|
|
|
|
lgpCondId4523ModuleRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module Removed."
|
|
::= { lgpFlexConditionsWellKnown 4523 }
|
|
|
|
lgpCondId4524ModuleAdded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module Added."
|
|
::= { lgpFlexConditionsWellKnown 4524 }
|
|
|
|
lgpCondId4550FirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module compatibility error requires a system firmware update to
|
|
resolve."
|
|
::= { lgpFlexConditionsWellKnown 4550 }
|
|
|
|
lgpCondId4551GenericTestEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A generic test event designed to evaluate system handling of
|
|
events."
|
|
::= { lgpFlexConditionsWellKnown 4551 }
|
|
|
|
lgpCondId4580OverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over temperature condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4580 }
|
|
|
|
lgpCondId4581UnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An under temperature condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4581 }
|
|
|
|
lgpCondId4588OverRelativeHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over relative humidity condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4588 }
|
|
|
|
lgpCondId4589UnderRelativeHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An under relative humidity condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 4589 }
|
|
|
|
lgpCondId4601ExternalAirSensorAOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Temperature] has exceeded [External Air Over
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4601 }
|
|
|
|
lgpCondId4604ExternalAirSensorBOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor B Temperature] has exceeded [External Air Over
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4604 }
|
|
|
|
lgpCondId4608ExtAirSensorAUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Temperature] has dropped below [Ext Air Under
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4608 }
|
|
|
|
lgpCondId4611ExtAirSensorBUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor B Temperature] has dropped below [Ext Air Under
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4611 }
|
|
|
|
lgpCondId4615ExtDewPointOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"At least one dew point temperature reading ([Ext Air Sensor A Dew
|
|
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded
|
|
[Ext Dew Point Over Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4615 }
|
|
|
|
lgpCondId4618ExternalAirSensorAIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor A is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 4618 }
|
|
|
|
lgpCondId4621ExternalAirSensorBIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor B is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 4621 }
|
|
|
|
lgpCondId4626SupplyChilledWaterOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Fluid Temperature] has exceeded [High Supply Fluid
|
|
Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4626 }
|
|
|
|
lgpCondId4629SupplyChilledWaterTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply chilled water temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 4629 }
|
|
|
|
lgpCondId4634SupplyRefrigerantOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event that is activated when [Supply Refrigerant Temperature]
|
|
exceeds [Supply Refrig Over Temp Threshold]. The event is
|
|
deactivated when the temperature drops below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 4634 }
|
|
|
|
lgpCondId4637SupplyRefrigerantUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] has dropped below a specified
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 4637 }
|
|
|
|
lgpCondId4640SupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply refrigeramt temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 4640 }
|
|
|
|
lgpCondId4645SupplyFluidOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 4645 }
|
|
|
|
lgpCondId4648SupplyFluidUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Fluid Temperature] has dropped below a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 4648 }
|
|
|
|
lgpCondId4651SupplyFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply fluid temperature sensor is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 4651 }
|
|
|
|
lgpCondId4656Pump1LossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of flow is detected in pump 1. The loss of flow condition
|
|
occurs when no differential pressure is detected across the pump."
|
|
::= { lgpFlexConditionsWellKnown 4656 }
|
|
|
|
lgpCondId4659Pump2LossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of flow is detected in pump 2. The loss of flow condition
|
|
occurs when no differential pressure is detected across the pump."
|
|
::= { lgpFlexConditionsWellKnown 4659 }
|
|
|
|
lgpCondId4662PumpShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pumps have short cycled. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4662 }
|
|
|
|
lgpCondId4669Compressor1AHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1A high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4669 }
|
|
|
|
lgpCondId4672Compressor1BHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1B high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4672 }
|
|
|
|
lgpCondId4675Compressor2AHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2A high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4675 }
|
|
|
|
lgpCondId4678Compressor2BHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2B high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 4678 }
|
|
|
|
lgpCondId4681Compressor1AShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1A short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4681 }
|
|
|
|
lgpCondId4684Compressor1BShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1B short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4684 }
|
|
|
|
lgpCondId4687Compressor2AShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2A short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4687 }
|
|
|
|
lgpCondId4690Compressor2BShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2B short cycle. A short cycle is defined as turning on
|
|
and off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 4690 }
|
|
|
|
lgpCondId4693Tandem1LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"'Tandem compressors' 1 low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 4693 }
|
|
|
|
lgpCondId4696Tandem2LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"'Tandem compressors' 2 low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 4696 }
|
|
|
|
lgpCondId4703ChilledWaterControlValvePosition OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water valve out of position. Chilled water control valve
|
|
position does not match expected value."
|
|
::= { lgpFlexConditionsWellKnown 4703 }
|
|
|
|
lgpCondId4711SystemCondensationDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System condensation detected."
|
|
::= { lgpFlexConditionsWellKnown 4711 }
|
|
|
|
lgpCondId4714ShutdownLossOfPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System lost power. This event becomes active when the unit is
|
|
powered on following an unexpected loss of power."
|
|
::= { lgpFlexConditionsWellKnown 4714 }
|
|
|
|
lgpCondId4720SmokeDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Smoke detected."
|
|
::= { lgpFlexConditionsWellKnown 4720 }
|
|
|
|
lgpCondId4723WaterUnderFloor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water under the floor is detected."
|
|
::= { lgpFlexConditionsWellKnown 4723 }
|
|
|
|
lgpCondId4726ServiceRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit requires servicing."
|
|
::= { lgpFlexConditionsWellKnown 4726 }
|
|
|
|
lgpCondId4729FanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more fans are not operating within their operational
|
|
parameters."
|
|
::= { lgpFlexConditionsWellKnown 4729 }
|
|
|
|
lgpCondId4732ReceptacleLoadDropped OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle's load is not drawing power."
|
|
::= { lgpFlexConditionsWellKnown 4732 }
|
|
|
|
lgpCondId4740BatteryAutomaticTestInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic (scheduled) battery tests are inhibited."
|
|
::= { lgpFlexConditionsWellKnown 4740 }
|
|
|
|
lgpCondId4741BatterySelfTest OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery self test is in progress."
|
|
::= { lgpFlexConditionsWellKnown 4741 }
|
|
|
|
lgpCondId4742BatteryLowShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery disconnect due to end-of-discharge."
|
|
::= { lgpFlexConditionsWellKnown 4742 }
|
|
|
|
lgpCondId4747EquipmentTemperatureSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more temperature sensors report a temperature outside of
|
|
the range of expected operation."
|
|
::= { lgpFlexConditionsWellKnown 4747 }
|
|
|
|
lgpCondId4749SystemFanFailureRedundant OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Redundant system fan failure."
|
|
::= { lgpFlexConditionsWellKnown 4749 }
|
|
|
|
lgpCondId4750MultipleFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multiple fan failure."
|
|
::= { lgpFlexConditionsWellKnown 4750 }
|
|
|
|
lgpCondId4753MainControllerFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Main Controller fault has been detected."
|
|
::= { lgpFlexConditionsWellKnown 4753 }
|
|
|
|
lgpCondId4754SystemBreakersCloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more breakers in the system failed to close."
|
|
::= { lgpFlexConditionsWellKnown 4754 }
|
|
|
|
lgpCondId4755InputFilterCycleLock OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input filter disconnect is open due to exceeding the maximum
|
|
number of cycles."
|
|
::= { lgpFlexConditionsWellKnown 4755 }
|
|
|
|
lgpCondId4756ServiceCodeActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Service code is running."
|
|
::= { lgpFlexConditionsWellKnown 4756 }
|
|
|
|
lgpCondId4757LBSActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Load Bus Sync option is active."
|
|
::= { lgpFlexConditionsWellKnown 4757 }
|
|
|
|
lgpCondId4758LBSInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that conditions to perform Load Bus Sync
|
|
are not satisfied."
|
|
::= { lgpFlexConditionsWellKnown 4758 }
|
|
|
|
lgpCondId4759LeadingPowerFactor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The leading output Power Factor has fallen below a specified value."
|
|
::= { lgpFlexConditionsWellKnown 4759 }
|
|
|
|
lgpCondId4760ControlsResetRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A controls reset is required due to one or more critical settings
|
|
changing."
|
|
::= { lgpFlexConditionsWellKnown 4760 }
|
|
|
|
lgpCondId4823ParallelCommWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Parallel communication bus warning."
|
|
::= { lgpFlexConditionsWellKnown 4823 }
|
|
|
|
lgpCondId4824SystemCommFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Failure of a device on the multi-module system communication bus."
|
|
::= { lgpFlexConditionsWellKnown 4824 }
|
|
|
|
lgpCondId4825LossofRedundancy OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module collection doesn't have enough modules to satisfy
|
|
the redundancy configuration."
|
|
::= { lgpFlexConditionsWellKnown 4825 }
|
|
|
|
lgpCondId4826BPSSStartupInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass Static Switch startup is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 4826 }
|
|
|
|
lgpCondId4827MMSTransferInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical load can not be manually transferred from inverter to
|
|
bypass."
|
|
::= { lgpFlexConditionsWellKnown 4827 }
|
|
|
|
lgpCondId4828MMSRetransferInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical load can not be manually retransferred from bypass to
|
|
inverter."
|
|
::= { lgpFlexConditionsWellKnown 4828 }
|
|
|
|
lgpCondId4830MMSLossofSyncPulse OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multi-module system loss of sync pulse."
|
|
::= { lgpFlexConditionsWellKnown 4830 }
|
|
|
|
lgpCondId4831MMSOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multi-module system overload."
|
|
::= { lgpFlexConditionsWellKnown 4831 }
|
|
|
|
lgpCondId4834MMSOnBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system is on battery."
|
|
::= { lgpFlexConditionsWellKnown 4834 }
|
|
|
|
lgpCondId4835MMSLowBatteryWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multi-module system low battery warning."
|
|
::= { lgpFlexConditionsWellKnown 4835 }
|
|
|
|
lgpCondId4906LowAmbientTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low ambient temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4906 }
|
|
|
|
lgpCondId4907HighAmbientTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high ambient temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4907 }
|
|
|
|
lgpCondId4908LowOverallVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low battery string overall voltage
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4908 }
|
|
|
|
lgpCondId4909HighOverallVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string overall voltage
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4909 }
|
|
|
|
lgpCondId4910HighBatteryStringCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string current condition."
|
|
::= { lgpFlexConditionsWellKnown 4910 }
|
|
|
|
lgpCondId4911LowBatteryStringFloatCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low battery string float current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4911 }
|
|
|
|
lgpCondId4912HighBatteryStringFloatCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string float current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4912 }
|
|
|
|
lgpCondId4913HighBatteryStringRippleCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string ripple current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 4913 }
|
|
|
|
lgpCondId4914BatteryStringDischargeDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery string discharge condition."
|
|
::= { lgpFlexConditionsWellKnown 4914 }
|
|
|
|
lgpCondId4915MaximumDischargeTimeExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an excessive discharge time condition."
|
|
::= { lgpFlexConditionsWellKnown 4915 }
|
|
|
|
lgpCondId4916DischargeLowOverallVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low battery string overall voltage
|
|
condition during a discharge."
|
|
::= { lgpFlexConditionsWellKnown 4916 }
|
|
|
|
lgpCondId4917DischargeLowCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell voltage condition during a
|
|
discharge."
|
|
::= { lgpFlexConditionsWellKnown 4917 }
|
|
|
|
lgpCondId4918DischargeHighBatteryStringCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high battery string current condition
|
|
during a discharge."
|
|
::= { lgpFlexConditionsWellKnown 4918 }
|
|
|
|
lgpCondId4919ExcessiveCelltoCellTemperatureDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an excessive cell to cell temperature
|
|
deviation condition."
|
|
::= { lgpFlexConditionsWellKnown 4919 }
|
|
|
|
lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an excessive cell to ambient temperature
|
|
deviation condition."
|
|
::= { lgpFlexConditionsWellKnown 4920 }
|
|
|
|
lgpCondId4964LowCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell voltage condition."
|
|
::= { lgpFlexConditionsWellKnown 4964 }
|
|
|
|
lgpCondId4965HighCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high cell voltage condition."
|
|
::= { lgpFlexConditionsWellKnown 4965 }
|
|
|
|
lgpCondId4966LowCellTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4966 }
|
|
|
|
lgpCondId4967HighCellTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high cell temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 4967 }
|
|
|
|
lgpCondId4968LowInternalResistance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low internal resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4968 }
|
|
|
|
lgpCondId4969HighInternalResistance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high internal resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4969 }
|
|
|
|
lgpCondId4970HighIntercellResistance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high intercell resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4970 }
|
|
|
|
lgpCondId4978IntertierResistanceHigh OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high intertier resistance condition."
|
|
::= { lgpFlexConditionsWellKnown 4978 }
|
|
|
|
lgpCondId4980SupplyChilledWaterLossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply chilled water or glycol flow is too low."
|
|
::= { lgpFlexConditionsWellKnown 4980 }
|
|
|
|
lgpCondId4983SupplyRefrigOverTempBand1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is above the upper threshold
|
|
specified by [Supply Refrig Temp Band 1]."
|
|
::= { lgpFlexConditionsWellKnown 4983 }
|
|
|
|
lgpCondId4986SupplyRefrigUnderTempBand1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is below the lower threshold
|
|
specified by [Supply Refrig Temp Band 1]."
|
|
::= { lgpFlexConditionsWellKnown 4986 }
|
|
|
|
lgpCondId4990SupplyRefrigOverTempBand2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is above the upper threshold
|
|
specified by [Supply Refrig Temp Band 2]."
|
|
::= { lgpFlexConditionsWellKnown 4990 }
|
|
|
|
lgpCondId4993SupplyRefrigUnderTempBand2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Refrigerant Temperature] is below the lower threshold
|
|
specified by [Supply Refrig Temp Band 2]."
|
|
::= { lgpFlexConditionsWellKnown 4993 }
|
|
|
|
lgpCondId4996Inverter1ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter for pump 1 has short cycled and is temporarily locked out
|
|
from further operation to protect from thermal overload. A short
|
|
cycle is defined as powering on and off a number of times over a
|
|
set time period."
|
|
::= { lgpFlexConditionsWellKnown 4996 }
|
|
|
|
lgpCondId4999Inverter2ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter for pump 2 has short cycled and is temporarily locked out
|
|
from further operation to protect from thermal overload. A short
|
|
cycle is defined as powering on and off a number of times over a
|
|
set time period."
|
|
::= { lgpFlexConditionsWellKnown 4999 }
|
|
|
|
lgpCondId5015SupplyAirOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Air Temperature] has exceeded [High Supply Air Temperature
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5015 }
|
|
|
|
lgpCondId5019SupplyAirUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Supply Air Temperature] has dropped below [Low Supply Air
|
|
Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5019 }
|
|
|
|
lgpCondId5023ReturnAirOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Air Temperature] has exceeded [High Return Air Temperature
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5023 }
|
|
|
|
lgpCondId5026SupplyAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air sensor at the outlet of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5026 }
|
|
|
|
lgpCondId5034HighReturnHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Humidity] has exceeded [High Return Humidity Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5034 }
|
|
|
|
lgpCondId5036LowReturnHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Humidity] has dropped below [Low Return Humidity
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5036 }
|
|
|
|
lgpCondId5037HumidifierHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the humidifier have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5037 }
|
|
|
|
lgpCondId5038DehumidifierHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the dehumidifier have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5038 }
|
|
|
|
lgpCondId5039HumidifierUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The electrical current to the humidifier has dropped below its
|
|
lower threshold."
|
|
::= { lgpFlexConditionsWellKnown 5039 }
|
|
|
|
lgpCondId5040HumidifierOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The electrical current to the humidifier has exceeded its upper
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5040 }
|
|
|
|
lgpCondId5041HumidifierLowWater OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The water level in the humidifier has dropped below its threshold."
|
|
::= { lgpFlexConditionsWellKnown 5041 }
|
|
|
|
lgpCondId5042HumidifierCylinderWorn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidifier cylinder is not operating properly and needs to be
|
|
replaced."
|
|
::= { lgpFlexConditionsWellKnown 5042 }
|
|
|
|
lgpCondId5043HumidifierIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidifier issue detected, causing it to be locked out."
|
|
::= { lgpFlexConditionsWellKnown 5043 }
|
|
|
|
lgpCondId5044ExtHumidifierLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidifier is shut down and disabled by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5044 }
|
|
|
|
lgpCondId5045HumidifierControlBoardNotDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidifier control board is required to be connected, but no
|
|
signal is detected."
|
|
::= { lgpFlexConditionsWellKnown 5045 }
|
|
|
|
lgpCondId5046ReturnHumidityOutOfProportionalBand OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Humidity] has exceeded the upper limit of
|
|
[Dehumidification Proportional Band], or has dropped below the
|
|
lower limit of [Humidification Proportional Band] ], for an
|
|
extended period of time."
|
|
::= { lgpFlexConditionsWellKnown 5046 }
|
|
|
|
lgpCondId5053LossofAirFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No air flow through the unit due to failure of all fans."
|
|
::= { lgpFlexConditionsWellKnown 5053 }
|
|
|
|
lgpCondId5054FanHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the unit blower fan have exceeded the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5054 }
|
|
|
|
lgpCondId5055TopFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The top fan is not operating within its normal parameters."
|
|
::= { lgpFlexConditionsWellKnown 5055 }
|
|
|
|
lgpCondId5056BottomFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bottom fan is not operating within its normal parameters."
|
|
::= { lgpFlexConditionsWellKnown 5056 }
|
|
|
|
lgpCondId5060RemoteSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5060 }
|
|
|
|
lgpCondId5062Compressor1LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 5062 }
|
|
|
|
lgpCondId5063Compressor1HoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for compressor 1 have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5063 }
|
|
|
|
lgpCondId5064DigScrollComp1TempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor 1 temperature sensor is disconnected or
|
|
the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5064 }
|
|
|
|
lgpCondId5065DigScrollComp1OverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor 1 shut off because its head temperature
|
|
has exceeded the upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5065 }
|
|
|
|
lgpCondId5066Compressor1LowPressureTransducerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 low pressure transducer is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5066 }
|
|
|
|
lgpCondId5067ExtCompressorLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compressor is shut down and disabled by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5067 }
|
|
|
|
lgpCondId5068ReheaterOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature of the reheater has exceeded its threshold."
|
|
::= { lgpFlexConditionsWellKnown 5068 }
|
|
|
|
lgpCondId5069ElectricReheater1HoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for electric reheater 1 have exceeded the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5069 }
|
|
|
|
lgpCondId5070ExtReheatLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reheater is shut down and disabled by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5070 }
|
|
|
|
lgpCondId5071Condenser1Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser 1 is not operating within its normal parameters."
|
|
::= { lgpFlexConditionsWellKnown 5071 }
|
|
|
|
lgpCondId5072CondenserVFDIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser fan Variable Frequency Drive is offline."
|
|
::= { lgpFlexConditionsWellKnown 5072 }
|
|
|
|
lgpCondId5073CondenserTVSSIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser Transient Voltage Surge Suppressor or Surge
|
|
Protection Device has failed."
|
|
::= { lgpFlexConditionsWellKnown 5073 }
|
|
|
|
lgpCondId5104ExtOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature has exceeded its threshold, as indicated by an
|
|
external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5104 }
|
|
|
|
lgpCondId5105ExtLossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of flow is detected, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5105 }
|
|
|
|
lgpCondId5106ExtCondenserPumpHighWater OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High water is detected in the condensate pump by the auxiliary
|
|
float, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5106 }
|
|
|
|
lgpCondId5107ExtStandbyGlycolPumpOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The standby glycol pump is on, as indicated by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5107 }
|
|
|
|
lgpCondId5108ExternalFireDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fire detected, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5108 }
|
|
|
|
lgpCondId5109UnitOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit was turned on."
|
|
::= { lgpFlexConditionsWellKnown 5109 }
|
|
|
|
lgpCondId5110UnitOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit was turned off."
|
|
::= { lgpFlexConditionsWellKnown 5110 }
|
|
|
|
lgpCondId5111UnitStandby OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit was placed in standby mode."
|
|
::= { lgpFlexConditionsWellKnown 5111 }
|
|
|
|
lgpCondId5112UnitPartialShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An event has occurred requiring some system components to be
|
|
shutdown and disabled."
|
|
::= { lgpFlexConditionsWellKnown 5112 }
|
|
|
|
lgpCondId5113UnitShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An event has occurred requiring the unit to be shutdown and
|
|
disabled to prevent damage to the system."
|
|
::= { lgpFlexConditionsWellKnown 5113 }
|
|
|
|
lgpCondId5114WaterLeakageDetectorSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The water leakage detector sensor is disconnected or the signal is
|
|
out of range."
|
|
::= { lgpFlexConditionsWellKnown 5114 }
|
|
|
|
lgpCondId5115BMSCommunicationsTimeout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Building Management System (or external monitoring system) has not
|
|
communicated with the system within the expected timeframe."
|
|
::= { lgpFlexConditionsWellKnown 5115 }
|
|
|
|
lgpCondId5116MaintenanceDue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The calculated maintenance date has been reached."
|
|
::= { lgpFlexConditionsWellKnown 5116 }
|
|
|
|
lgpCondId5117MaintenanceCompleted OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maintenance has been completed on the unit."
|
|
::= { lgpFlexConditionsWellKnown 5117 }
|
|
|
|
lgpCondId5118CloggedAirFilter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air filter is dirty and needs to be (cleaned or) replaced."
|
|
::= { lgpFlexConditionsWellKnown 5118 }
|
|
|
|
lgpCondId5119RAMBatteryIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RAM or RAM backup battery is not operating correctly."
|
|
::= { lgpFlexConditionsWellKnown 5119 }
|
|
|
|
lgpCondId5120MasterUnitCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with master unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5120 }
|
|
|
|
lgpCondId5121HighPowerShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply to high power components has been shutdown."
|
|
::= { lgpFlexConditionsWellKnown 5121 }
|
|
|
|
lgpCondId5126DigScrollComp2OverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor 2 shut off because its head temperature
|
|
has exceeded the upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5126 }
|
|
|
|
lgpCondId5144OutputOfUf OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output frequency has exceeded a specified range for a
|
|
specified period of time."
|
|
::= { lgpFlexConditionsWellKnown 5144 }
|
|
|
|
lgpCondId5145MMSModuleAlarmActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Active alarm or fault of any module in a multi-module system."
|
|
::= { lgpFlexConditionsWellKnown 5145 }
|
|
|
|
lgpCondId5146CompressorPumpDownIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unable to pump down suction-side pressure during compressor
|
|
shutdown."
|
|
::= { lgpFlexConditionsWellKnown 5146 }
|
|
|
|
lgpCondId5147ReturnAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air sensor at the inlet of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5147 }
|
|
|
|
lgpCondId5148CompressorHighPressureTransducerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor high pressure transducer is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5148 }
|
|
|
|
lgpCondId5149BatteryNotQualified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS battery voltage is not qualified. This event will be
|
|
detected even in the absence of battery disconnect or when it is
|
|
open."
|
|
::= { lgpFlexConditionsWellKnown 5149 }
|
|
|
|
lgpCondId5150BatteryTerminalsReversed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The measured battery voltage is a negative value due to reverse
|
|
battery terminal connections."
|
|
::= { lgpFlexConditionsWellKnown 5150 }
|
|
|
|
lgpCondId5151BatteryConverterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery converter failure. This is a summary event caused by one
|
|
or more power sub-modules in a UPS module."
|
|
::= { lgpFlexConditionsWellKnown 5151 }
|
|
|
|
lgpCondId5152InverterSCROpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an open across one or more inverter static
|
|
switch Silicon Controlled Rectifiers."
|
|
::= { lgpFlexConditionsWellKnown 5152 }
|
|
|
|
lgpCondId5153LoadSharingFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Difference between any phase inverter current of unit and the
|
|
relevant average output current of parallel system is more than a
|
|
specific percent of nominal current."
|
|
::= { lgpFlexConditionsWellKnown 5153 }
|
|
|
|
lgpCondId5154DCBusAbnormal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an abnormal DC Bus Voltage."
|
|
::= { lgpFlexConditionsWellKnown 5154 }
|
|
|
|
lgpCondId5155MainsInputNeutralLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of neutral in the input source is detected."
|
|
::= { lgpFlexConditionsWellKnown 5155 }
|
|
|
|
lgpCondId5156LoadImpactTransfer OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"On bypass as result of load impact."
|
|
::= { lgpFlexConditionsWellKnown 5156 }
|
|
|
|
lgpCondId5157UserOperationInvalid OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"User attempted an invalid operation."
|
|
::= { lgpFlexConditionsWellKnown 5157 }
|
|
|
|
lgpCondId5158PowerSubModuleFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more failures detected in power module, inverter or
|
|
rectifier."
|
|
::= { lgpFlexConditionsWellKnown 5158 }
|
|
|
|
lgpCondId5178OutputOvervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the output phase voltages has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5178 }
|
|
|
|
lgpCondId5179OutputUndervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the output phase voltages has dropped below the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5179 }
|
|
|
|
lgpCondId5180OutputOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase currents has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5180 }
|
|
|
|
lgpCondId5181NeutralOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system's neutral current has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5181 }
|
|
|
|
lgpCondId5182GroundOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System ground current has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5182 }
|
|
|
|
lgpCondId5183OutputVoltageTHD OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Total Harmonic Distortion of the voltage on one or more of the
|
|
output phases has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5183 }
|
|
|
|
lgpCondId5184OutputFrequencyError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output frequency is outside a specified range."
|
|
::= { lgpFlexConditionsWellKnown 5184 }
|
|
|
|
lgpCondId5185TransformerOvertemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates a unit transformer overtemperature condition."
|
|
::= { lgpFlexConditionsWellKnown 5185 }
|
|
|
|
lgpCondId5212PanelSummaryStatus OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status for the panel. Detects and annunciates upon occurrence
|
|
of any branch or panelboard main breaker active event."
|
|
::= { lgpFlexConditionsWellKnown 5212 }
|
|
|
|
lgpCondId5213PanelOvervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase voltages of this panel has exceeded the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5213 }
|
|
|
|
lgpCondId5214PanelUndervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase voltages of this panel is less than the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5214 }
|
|
|
|
lgpCondId5215PanelOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase currents of this panel has exceeded the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5215 }
|
|
|
|
lgpCondId5216PanelNeutralOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Neutral current of this panel has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5216 }
|
|
|
|
lgpCondId5217PanelGroundOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Ground current of this panel has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5217 }
|
|
|
|
lgpCondId5226BranchOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current in one or more phases of this branch exceeds the limit."
|
|
::= { lgpFlexConditionsWellKnown 5226 }
|
|
|
|
lgpCondId5227BranchUndercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current in one or more phases of this branch is less than the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5227 }
|
|
|
|
lgpCondId5245SubfeedPhaseOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the phase currents in this subfeed has exceeded the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5245 }
|
|
|
|
lgpCondId5246SubfeedNeutralOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Neutral current in this subfeed has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5246 }
|
|
|
|
lgpCondId5247SubfeedGroundOvercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Ground current of this subfeed has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5247 }
|
|
|
|
lgpCondId5249EventState OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present state of this digital event input."
|
|
::= { lgpFlexConditionsWellKnown 5249 }
|
|
|
|
lgpCondId5263CompressorNotStopping OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor commanded to stop, but continues to run."
|
|
::= { lgpFlexConditionsWellKnown 5263 }
|
|
|
|
lgpCondId5269CompressorHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Compressor Hours] has exceeded [Compressor Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5269 }
|
|
|
|
lgpCondId5270CompressorHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to high head pressure."
|
|
::= { lgpFlexConditionsWellKnown 5270 }
|
|
|
|
lgpCondId5271CompressorLowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to low suction pressure."
|
|
::= { lgpFlexConditionsWellKnown 5271 }
|
|
|
|
lgpCondId5272CompressorThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 5272 }
|
|
|
|
lgpCondId5273CompressorLowOilPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor low oil pressure."
|
|
::= { lgpFlexConditionsWellKnown 5273 }
|
|
|
|
lgpCondId5274CompressorHeadPressureOverThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor head pressure has exceeded an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5274 }
|
|
|
|
lgpCondId5275CompressorLossofDifferentialPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor is shut down due to low differential pressure."
|
|
::= { lgpFlexConditionsWellKnown 5275 }
|
|
|
|
lgpCondId5277CondenserFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser fan is not operating within its operational parameters."
|
|
::= { lgpFlexConditionsWellKnown 5277 }
|
|
|
|
lgpCondId5278LowCondenserRefrigerantPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Refrigerant pressure in condenser coil is too low."
|
|
::= { lgpFlexConditionsWellKnown 5278 }
|
|
|
|
lgpCondId5280LowFluidPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Fluid Pressure] has dropped below a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5280 }
|
|
|
|
lgpCondId5293ReturnFluidOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Fluid Temperature] has exceeded a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5293 }
|
|
|
|
lgpCondId5294ReturnFluidUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Fluid Temperature] has dropped below a specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5294 }
|
|
|
|
lgpCondId5295ReturnFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return fluid temperature sensor is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5295 }
|
|
|
|
lgpCondId5296TeamworkReturnFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The return fluid temperature sensors for all Teamwork units are
|
|
disconnected or the signals are out of range."
|
|
::= { lgpFlexConditionsWellKnown 5296 }
|
|
|
|
lgpCondId5297AllPumpsLossofFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System is shut down due to loss of flow in all available pumps."
|
|
::= { lgpFlexConditionsWellKnown 5297 }
|
|
|
|
lgpCondId5300PumpHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Pump Hours] has exceeded [Pump Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5300 }
|
|
|
|
lgpCondId5306FreeCoolingValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5306 }
|
|
|
|
lgpCondId5308EvaporatorInletTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator inlet temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5308 }
|
|
|
|
lgpCondId5309TeamworkEvaporatorInletTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The evaporator inlet temperature sensors for all Teamwork units
|
|
are disconnected or the signals are out of range."
|
|
::= { lgpFlexConditionsWellKnown 5309 }
|
|
|
|
lgpCondId5310EvaporatorFluidFreezeAutoReset OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Evaporator outlet fluid temperature has dropped below the freeze
|
|
threshold. Evaporator has been shut down, but will restart when
|
|
the temperature rises above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5310 }
|
|
|
|
lgpCondId5311EvaporatorFluidFreezeManualResetRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Evaporator outlet fluid temperature has dropped below the freeze
|
|
threshold. Evaporator has been shut down and requires a manual
|
|
reset."
|
|
::= { lgpFlexConditionsWellKnown 5311 }
|
|
|
|
lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"While subgroup unit communication was lost, an event occurred on
|
|
the subgroup unit. Please check subgroup unit event log."
|
|
::= { lgpFlexConditionsWellKnown 5315 }
|
|
|
|
lgpCondId5335ReturnAirUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Return Air Temperature] has dropped below [Low Return Air
|
|
Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5335 }
|
|
|
|
lgpCondId5349ExtAirSensorAHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High
|
|
Humidity Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5349 }
|
|
|
|
lgpCondId5351ExtAirSensorALowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A
|
|
Low Humidity Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5351 }
|
|
|
|
lgpCondId5352CompressorShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor short cycle. A short cycle is defined as turning on and
|
|
off a number of times over a set time period."
|
|
::= { lgpFlexConditionsWellKnown 5352 }
|
|
|
|
lgpCondId5354DigScrollCompDischargeTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor discharge temperature sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5354 }
|
|
|
|
lgpCondId5355DigScrollCompOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital scroll compressor is shut down due to head temperature
|
|
exceeding an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5355 }
|
|
|
|
lgpCondId5361ExtFreeCoolingLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Free cooling is disabled by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5361 }
|
|
|
|
lgpCondId5362FreeCoolingTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The free cooling fluid temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5362 }
|
|
|
|
lgpCondId5365HotWaterHotGasValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot
|
|
Gas Valve Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5365 }
|
|
|
|
lgpCondId5368ElectricReheaterHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Electric Reheater Hours] has exceeded [Electric Reheaters Hours
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5368 }
|
|
|
|
lgpCondId5376MainFanOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Main fan is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 5376 }
|
|
|
|
lgpCondId5377Condenser OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser is not operating within its operational parameters."
|
|
::= { lgpFlexConditionsWellKnown 5377 }
|
|
|
|
lgpCondId5415ExtLossofAirBlower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of air blower is detected, as indicated by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 5415 }
|
|
|
|
lgpCondId5416ExtStandbyUnitOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Standby unit is on, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5416 }
|
|
|
|
lgpCondId5417DigitalOutputBoardNotDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Digital output board is required to be connected, but no signal is
|
|
detected."
|
|
::= { lgpFlexConditionsWellKnown 5417 }
|
|
|
|
lgpCondId5418UnitCodeMissing OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit code has not been entered and saved."
|
|
::= { lgpFlexConditionsWellKnown 5418 }
|
|
|
|
lgpCondId5419UnitCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Master has lost communication with one or more networked units."
|
|
::= { lgpFlexConditionsWellKnown 5419 }
|
|
|
|
lgpCondId5422OvertemperaturePowerOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power turned off because equipment over temperature limit."
|
|
::= { lgpFlexConditionsWellKnown 5422 }
|
|
|
|
lgpCondId5423TooManySensors OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of sensors connected to the PDU exceeds the allowable
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5423 }
|
|
|
|
lgpCondId5432TransformerOvertemperaturePowerOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output power shutdown due to high transformer temperature."
|
|
::= { lgpFlexConditionsWellKnown 5432 }
|
|
|
|
lgpCondId5433TransformerOvertemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transformer temperature has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5433 }
|
|
|
|
lgpCondId5434TransformerTemperatureSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Transformer temperature sensor has failed."
|
|
::= { lgpFlexConditionsWellKnown 5434 }
|
|
|
|
lgpCondId5436LowAmbientTemperatureProbeTwo OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low ambient temperature condition on
|
|
temperature probe 2."
|
|
::= { lgpFlexConditionsWellKnown 5436 }
|
|
|
|
lgpCondId5437HighAmbientTemperatureProbeTwo OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high ambient temperature condition on
|
|
temperature probe 2."
|
|
::= { lgpFlexConditionsWellKnown 5437 }
|
|
|
|
lgpCondId5438ThermalRunawayDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a thermal runaway condition."
|
|
::= { lgpFlexConditionsWellKnown 5438 }
|
|
|
|
lgpCondId5439BatteryStringEqualize OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery string equalize condition."
|
|
::= { lgpFlexConditionsWellKnown 5439 }
|
|
|
|
lgpCondId5440BatteryStringOffline OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the battery string is offline."
|
|
::= { lgpFlexConditionsWellKnown 5440 }
|
|
|
|
lgpCondId5442DischargeLowCellVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low cell voltage condition during a
|
|
discharge."
|
|
::= { lgpFlexConditionsWellKnown 5442 }
|
|
|
|
lgpCondId5447MMSPowerSharing OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A module is not sharing power with the other modules in a multi
|
|
-module system."
|
|
::= { lgpFlexConditionsWellKnown 5447 }
|
|
|
|
lgpCondId5453ModuleInStandbyIntelligentParalleling OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Module is placed into standby operation per Intelligent
|
|
Paralleling."
|
|
::= { lgpFlexConditionsWellKnown 5453 }
|
|
|
|
lgpCondId5456ECOModeActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Conditions for Activation or Automatic Reactivation have been
|
|
satisfied."
|
|
::= { lgpFlexConditionsWellKnown 5456 }
|
|
|
|
lgpCondId5457ECOModeSuspended OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ECO Mode session is suspended."
|
|
::= { lgpFlexConditionsWellKnown 5457 }
|
|
|
|
lgpCondId5458ExcessECOSuspends OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of automatic suspensions has exceeded the ECO Mode -
|
|
Maximum Auto Suspensions setting."
|
|
::= { lgpFlexConditionsWellKnown 5458 }
|
|
|
|
lgpCondId5471DoorOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An open door was detected."
|
|
::= { lgpFlexConditionsWellKnown 5471 }
|
|
|
|
lgpCondId5472DoorSensorDisconnected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Door sensor disconnect detected."
|
|
::= { lgpFlexConditionsWellKnown 5472 }
|
|
|
|
lgpCondId5479ContactClosureOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An open circuit was detected."
|
|
::= { lgpFlexConditionsWellKnown 5479 }
|
|
|
|
lgpCondId5480ContactClosureClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A closed circuit was detected."
|
|
::= { lgpFlexConditionsWellKnown 5480 }
|
|
|
|
lgpCondId5492ExtSystemCondensationDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External system condensation detected."
|
|
::= { lgpFlexConditionsWellKnown 5492 }
|
|
|
|
lgpCondId5495ExtFanIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more fans are not operating within their operational
|
|
parameters."
|
|
::= { lgpFlexConditionsWellKnown 5495 }
|
|
|
|
lgpCondId5500ExtRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 5500 }
|
|
|
|
lgpCondId5505HotAisleTempOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air temperature in the Hot aisle is either above [Hot Aisle
|
|
Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5505 }
|
|
|
|
lgpCondId5508ColdAisleTempOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air temperature in the cold aisle is either above [Cold Aisle
|
|
Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5508 }
|
|
|
|
lgpCondId5512RemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 5512 }
|
|
|
|
lgpCondId5513CompressorCapacityReduced OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor capacity has been reduced."
|
|
::= { lgpFlexConditionsWellKnown 5513 }
|
|
|
|
lgpCondId5514CompressorLowPressureTransducerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor low pressure transducer is disconnected or the signal
|
|
is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5514 }
|
|
|
|
lgpCondId5524PDUNeutralOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a neutral over current condition."
|
|
::= { lgpFlexConditionsWellKnown 5524 }
|
|
|
|
lgpCondId5531CondenserCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with condenser unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5531 }
|
|
|
|
lgpCondId5535CondenserOutsideAirTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser outside air temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5535 }
|
|
|
|
lgpCondId5536CondenserOutsideAirTempOutofOperatingRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Condenser Outside Air Temperature] is either above an upper
|
|
threshold or below a lower threshold."
|
|
::= { lgpFlexConditionsWellKnown 5536 }
|
|
|
|
lgpCondId5537CondenserControlBoardIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser control board is reporting an issue."
|
|
::= { lgpFlexConditionsWellKnown 5537 }
|
|
|
|
lgpCondId5539CondenserRefrigerantPressureOverThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser refrigerant pressure has exceeded a threshold."
|
|
::= { lgpFlexConditionsWellKnown 5539 }
|
|
|
|
lgpCondId5540CondenserRefrigerantPressureUnderThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser refrigerant pressure has dropped below a threshold."
|
|
::= { lgpFlexConditionsWellKnown 5540 }
|
|
|
|
lgpCondId5541CondenserRefrigerantPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser refrigerant pressure sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5541 }
|
|
|
|
lgpCondId5542CondenserSupplyRefrigerantOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser supply refrigerant temperature has exceeded a threshold."
|
|
::= { lgpFlexConditionsWellKnown 5542 }
|
|
|
|
lgpCondId5543CondenserSupplyRefrigerantUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser supply refrigerant temperature has dropped below a
|
|
specified threshold."
|
|
::= { lgpFlexConditionsWellKnown 5543 }
|
|
|
|
lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser supply refrigerant temperature sensor is disconnected or
|
|
the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5544 }
|
|
|
|
lgpCondId5545CondenserMaxFanSpeedOverride OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fan speed exceeding the maximum set point in order to alleviate a
|
|
high temperature or pressure condition."
|
|
::= { lgpFlexConditionsWellKnown 5545 }
|
|
|
|
lgpCondId5559EvaporatorReturnFluidOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Evaporator Return Fluid Temperature] has exceeded a threshold.
|
|
The event is deactivated when the temperature drops below the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5559 }
|
|
|
|
lgpCondId5560EvaporatorReturnFluidUnderTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Evaporator Return Fluid Temperature] has dropped below a
|
|
threshold. The event is deactivated when the temperature rises
|
|
above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 5560 }
|
|
|
|
lgpCondId5561LBSActiveMaster OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This UPS system has been selected as the functional Master Load
|
|
Bus Synchronization (LBS) system."
|
|
::= { lgpFlexConditionsWellKnown 5561 }
|
|
|
|
lgpCondId5562LBSActiveSlave OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This UPS system is synchronized to the output bus of the UPS
|
|
system that has been selected as the Master Load Bus
|
|
Synchronization (LBS) system."
|
|
::= { lgpFlexConditionsWellKnown 5562 }
|
|
|
|
lgpCondId5563DCBusLowFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The DC Bus voltage has reached a critical low level."
|
|
::= { lgpFlexConditionsWellKnown 5563 }
|
|
|
|
lgpCondId5564FanContactorOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan contactor is open."
|
|
::= { lgpFlexConditionsWellKnown 5564 }
|
|
|
|
lgpCondId5565FanContactorOpenFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan contactor failed to open."
|
|
::= { lgpFlexConditionsWellKnown 5565 }
|
|
|
|
lgpCondId5566FanContactorCloseFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fan contactor failed to close."
|
|
::= { lgpFlexConditionsWellKnown 5566 }
|
|
|
|
lgpCondId5567IPInhibit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The intelligent paralleling operation is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 5567 }
|
|
|
|
lgpCondId5568InputUndervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the input phase voltages has dropped below the
|
|
limit."
|
|
::= { lgpFlexConditionsWellKnown 5568 }
|
|
|
|
lgpCondId5569InputOvervoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more of the input phase voltages has exceeded the limit."
|
|
::= { lgpFlexConditionsWellKnown 5569 }
|
|
|
|
lgpCondId5573AmbientAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ambient air sensor is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5573 }
|
|
|
|
lgpCondId5577ExtDewPointUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"At least one dew point temperature reading ([Ext Air Sensor A Dew
|
|
Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped
|
|
below [Ext Dew Point Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5577 }
|
|
|
|
lgpCondId5578DewPointOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dew point temperature reading has exceeded the upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5578 }
|
|
|
|
lgpCondId5579DewPointUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Dew point temperature reading has dropped below the lower
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 5579 }
|
|
|
|
lgpCondId5588UnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified events active. See local unit display for
|
|
further details."
|
|
::= { lgpFlexConditionsWellKnown 5588 }
|
|
|
|
lgpCondId5593RemoteSensorAverageOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Average Temperature] has exceeded [Remote Sensor
|
|
Over Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5593 }
|
|
|
|
lgpCondId5594RemoteSensorAverageUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Average Temperature] has dropped below [Remote
|
|
Sensor Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5594 }
|
|
|
|
lgpCondId5595RemoteSensorSystemAverageOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor System Average Temperature] has exceeded [Remote
|
|
Sensor Over Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5595 }
|
|
|
|
lgpCondId5596RemoteSensorSystemAverageUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor System Average Temperature] has dropped below
|
|
[Remote Sensor Under Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5596 }
|
|
|
|
lgpCondId5597RemoteSensorOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
|
|
Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5597 }
|
|
|
|
lgpCondId5598RemoteSensorUnderTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Remote Sensor Temperature] has dropped below [Remote Sensor Under
|
|
Temp Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 5598 }
|
|
|
|
lgpCondId5600AirEconomizerEmergencyOverride OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indoor room temperature has exceeded its upper threshold and the
|
|
outdoor air damper has been opened for emergency cooling."
|
|
::= { lgpFlexConditionsWellKnown 5600 }
|
|
|
|
lgpCondId5601AirEconomizerReducedAirflow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air economizer filter is dirty and needs to be cleaned or replaced."
|
|
::= { lgpFlexConditionsWellKnown 5601 }
|
|
|
|
lgpCondId5604CompressorSuperheatOverThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor discharge refrigerant superheat temperature has
|
|
exceeded an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 5604 }
|
|
|
|
lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delta temperature between a cell temperature and the ambient
|
|
temperature has exceeded the thermal runaway cell to ambient
|
|
temperature threshold."
|
|
::= { lgpFlexConditionsWellKnown 5609 }
|
|
|
|
lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The delta temperature between two cells has exceeded the thermal
|
|
runaway cell to cell temperature threshold."
|
|
::= { lgpFlexConditionsWellKnown 5610 }
|
|
|
|
lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery-String charger current has exceeded the thermal
|
|
runaway charger current level one threshold."
|
|
::= { lgpFlexConditionsWellKnown 5611 }
|
|
|
|
lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery-String charger current has exceeded the thermal
|
|
runaway charger current level two threshold."
|
|
::= { lgpFlexConditionsWellKnown 5612 }
|
|
|
|
lgpCondId5617TemperatureControlSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The air sensor selected for cooling control is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5617 }
|
|
|
|
lgpCondId5621EEVSuperheatBelowThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve refrigerant low superheat event."
|
|
::= { lgpFlexConditionsWellKnown 5621 }
|
|
|
|
lgpCondId5622EEVDischargeTempAboveThreshold OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve refrigerant high discharge temperature
|
|
event."
|
|
::= { lgpFlexConditionsWellKnown 5622 }
|
|
|
|
lgpCondId5623EEVBatteryIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve battery cannot be recharged and needs
|
|
to be replaced."
|
|
::= { lgpFlexConditionsWellKnown 5623 }
|
|
|
|
lgpCondId5624EEVPowerIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic expansion valve lost power and is running on battery
|
|
backup."
|
|
::= { lgpFlexConditionsWellKnown 5624 }
|
|
|
|
lgpCondId5625EEVUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified electronic expansion valve events active.
|
|
See local unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5625 }
|
|
|
|
lgpCondId5629StaticPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The static pressure sensor is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 5629 }
|
|
|
|
lgpCondId5630HighStaticPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High static pressure event."
|
|
::= { lgpFlexConditionsWellKnown 5630 }
|
|
|
|
lgpCondId5631LowStaticPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low static pressure event."
|
|
::= { lgpFlexConditionsWellKnown 5631 }
|
|
|
|
lgpCondId5636PumpUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified pump events active. See local unit display
|
|
for further details."
|
|
::= { lgpFlexConditionsWellKnown 5636 }
|
|
|
|
lgpCondId5637CondenserUnitUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified condenser unit events active. See local
|
|
unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5637 }
|
|
|
|
lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified condenser circuit events active. See local
|
|
unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5638 }
|
|
|
|
lgpCondId5642SFAReservedEvent1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5642 }
|
|
|
|
lgpCondId5643SFAReservedEvent2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5643 }
|
|
|
|
lgpCondId5644SFAReservedEvent3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5644 }
|
|
|
|
lgpCondId5645SFAReservedEvent4 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5645 }
|
|
|
|
lgpCondId5646SFAReservedEvent5 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5646 }
|
|
|
|
lgpCondId5647SFAReservedEvent6 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5647 }
|
|
|
|
lgpCondId5648SFAReservedEvent7 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5648 }
|
|
|
|
lgpCondId5649SFAReservedEvent8 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5649 }
|
|
|
|
lgpCondId5650SFAReservedEvent9 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5650 }
|
|
|
|
lgpCondId5651SFAReservedEvent10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5651 }
|
|
|
|
lgpCondId5652SFAReservedEvent11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5652 }
|
|
|
|
lgpCondId5653SFAReservedEvent12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5653 }
|
|
|
|
lgpCondId5654SFAReservedEvent13 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5654 }
|
|
|
|
lgpCondId5655SFAReservedEvent14 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5655 }
|
|
|
|
lgpCondId5656SFAReservedEvent15 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5656 }
|
|
|
|
lgpCondId5657SFAReservedEvent16 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5657 }
|
|
|
|
lgpCondId5658SFAReservedEvent17 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5658 }
|
|
|
|
lgpCondId5659SFAReservedEvent18 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5659 }
|
|
|
|
lgpCondId5660SFAReservedEvent19 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5660 }
|
|
|
|
lgpCondId5661SFAReservedEvent20 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5661 }
|
|
|
|
lgpCondId5662SFAReservedEvent21 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5662 }
|
|
|
|
lgpCondId5663SFAReservedEvent22 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5663 }
|
|
|
|
lgpCondId5664SFAReservedEvent23 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5664 }
|
|
|
|
lgpCondId5665SFAReservedEvent24 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5665 }
|
|
|
|
lgpCondId5666SFAReservedEvent25 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 5666 }
|
|
|
|
lgpCondId5768OutletAirOvertemperatureLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The difference between the outlet air temperature and inlet air
|
|
temperature exceeds a specified maximum temperature."
|
|
::= { lgpFlexConditionsWellKnown 5768 }
|
|
|
|
lgpCondId5769EMOShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An Emergency Module Off command has been detected."
|
|
::= { lgpFlexConditionsWellKnown 5769 }
|
|
|
|
lgpCondId5770TopOutletFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Top outlet fan fault - one or more top outlet fans have failed."
|
|
::= { lgpFlexConditionsWellKnown 5770 }
|
|
|
|
lgpCondId5771MMSOverCapacity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system load is larger than the apparent power
|
|
limit setting."
|
|
::= { lgpFlexConditionsWellKnown 5771 }
|
|
|
|
lgpCondId5773CompressorCapacityNormal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor has returned to normal load capacity."
|
|
::= { lgpFlexConditionsWellKnown 5773 }
|
|
|
|
lgpCondId5774CompressorContactorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor contactor is not closing during compressor startup or
|
|
is not opening during compressor shutdown."
|
|
::= { lgpFlexConditionsWellKnown 5774 }
|
|
|
|
lgpCondId5775UnitShutdownUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified unit shutdown events active. See local
|
|
unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 5775 }
|
|
|
|
lgpCondId5776PDULowVoltageLN OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LN)."
|
|
::= { lgpFlexConditionsWellKnown 5776 }
|
|
|
|
lgpCondId5777PDULowVoltageLL OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LL)."
|
|
::= { lgpFlexConditionsWellKnown 5777 }
|
|
|
|
lgpCondId5778PDULowVoltageL1L2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line under voltage condition (L1
|
|
-L2)."
|
|
::= { lgpFlexConditionsWellKnown 5778 }
|
|
|
|
lgpCondId5779PDULowVoltageL2L3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line under voltage condition (L2
|
|
-L3)."
|
|
::= { lgpFlexConditionsWellKnown 5779 }
|
|
|
|
lgpCondId5780PDULowVoltageL3L1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line under voltage condition (L3
|
|
-L1)."
|
|
::= { lgpFlexConditionsWellKnown 5780 }
|
|
|
|
lgpCondId5781PDULowVoltageL1N OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line to neutral under voltage condition
|
|
(L1-N)."
|
|
::= { lgpFlexConditionsWellKnown 5781 }
|
|
|
|
lgpCondId5782PDULowVoltageL2N OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line to neutral under voltage condition
|
|
(L2-N)."
|
|
::= { lgpFlexConditionsWellKnown 5782 }
|
|
|
|
lgpCondId5783PDULowVoltageL3N OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line to neutral under voltage condition
|
|
(L3-N)."
|
|
::= { lgpFlexConditionsWellKnown 5783 }
|
|
|
|
lgpCondId5784BranchLowVoltageLN OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LN)."
|
|
::= { lgpFlexConditionsWellKnown 5784 }
|
|
|
|
lgpCondId5785BranchLowVoltageLL OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LL)."
|
|
::= { lgpFlexConditionsWellKnown 5785 }
|
|
|
|
lgpCondId5786BranchLowVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition."
|
|
::= { lgpFlexConditionsWellKnown 5786 }
|
|
|
|
lgpCondId5788ContTieActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Continuous Power Tie Active."
|
|
::= { lgpFlexConditionsWellKnown 5788 }
|
|
|
|
lgpCondId5792UserkWhReset OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The user kWh accumulator was reset to zero by the operator."
|
|
::= { lgpFlexConditionsWellKnown 5792 }
|
|
|
|
lgpCondId5796PeakkWReset OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Peak kW was reset."
|
|
::= { lgpFlexConditionsWellKnown 5796 }
|
|
|
|
lgpCondId5798BypassOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass overloaded, reduce load immediately."
|
|
::= { lgpFlexConditionsWellKnown 5798 }
|
|
|
|
lgpCondId5801LowBatteryShutdownImminent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"If active and guaranteed shutdown is enabled, a low battery
|
|
reserve condition exists that will shutdown the UPS."
|
|
::= { lgpFlexConditionsWellKnown 5801 }
|
|
|
|
lgpCondId5806OutputOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An overload exists on the output."
|
|
::= { lgpFlexConditionsWellKnown 5806 }
|
|
|
|
lgpCondId5807OutputOffPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output off pending - shutdown imminent."
|
|
::= { lgpFlexConditionsWellKnown 5807 }
|
|
|
|
lgpCondId5808SystemShutdownOutputShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to a short on the output."
|
|
::= { lgpFlexConditionsWellKnown 5808 }
|
|
|
|
lgpCondId5809SystemShutdownLowBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to a low battery condition."
|
|
::= { lgpFlexConditionsWellKnown 5809 }
|
|
|
|
lgpCondId5810SystemShutdownRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to a remote communications shutdown command."
|
|
::= { lgpFlexConditionsWellKnown 5810 }
|
|
|
|
lgpCondId5811SystemShutdownHardwareFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown was due to an externally applied hardware control signal."
|
|
::= { lgpFlexConditionsWellKnown 5811 }
|
|
|
|
lgpCondId5817LossofRedundancy OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has an insufficient number of power modules to provide
|
|
redundancy."
|
|
::= { lgpFlexConditionsWellKnown 5817 }
|
|
|
|
lgpCondId5818PowerModuleFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more conditions indicate a power module failure, service is
|
|
required."
|
|
::= { lgpFlexConditionsWellKnown 5818 }
|
|
|
|
lgpCondId5819PowerModuleWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more power modules is reporting a warning condition."
|
|
::= { lgpFlexConditionsWellKnown 5819 }
|
|
|
|
lgpCondId5838PowerModuleFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Power Module has detected a fan fault."
|
|
::= { lgpFlexConditionsWellKnown 5838 }
|
|
|
|
lgpCondId5839PowerModuleOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Power Module has detected an over temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 5839 }
|
|
|
|
lgpCondId5840PowerModuleShutdownOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power Module has shutdown due to over temperature."
|
|
::= { lgpFlexConditionsWellKnown 5840 }
|
|
|
|
lgpCondId5842ChargerModuleFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Charger Module has detected a fan fault."
|
|
::= { lgpFlexConditionsWellKnown 5842 }
|
|
|
|
lgpCondId5847BatteryModuleTemperatureSensorFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Battery Module temperature sensor fault has been detected."
|
|
::= { lgpFlexConditionsWellKnown 5847 }
|
|
|
|
lgpCondId5848BatteryModuleOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery Module has detected an over temperature condition."
|
|
::= { lgpFlexConditionsWellKnown 5848 }
|
|
|
|
lgpCondId5849ReplaceBatteryModule OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Battery Module needs to be replaced."
|
|
::= { lgpFlexConditionsWellKnown 5849 }
|
|
|
|
lgpCondId5850SystemShutdownTransformerOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System shutdown due to transformer over temperature."
|
|
::= { lgpFlexConditionsWellKnown 5850 }
|
|
|
|
lgpCondId5851MaximumLoadAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Maximum load alarm indicating load setting has been exceeded."
|
|
::= { lgpFlexConditionsWellKnown 5851 }
|
|
|
|
lgpCondId5856BatteryModuleFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more battery modules are reporting a fault condition."
|
|
::= { lgpFlexConditionsWellKnown 5856 }
|
|
|
|
lgpCondId5857BatteryModuleWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more battery modules are reporting a warning condition."
|
|
::= { lgpFlexConditionsWellKnown 5857 }
|
|
|
|
lgpCondId5862CheckAirFilter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Please check air filter, it may need to be cleaned or replaced."
|
|
::= { lgpFlexConditionsWellKnown 5862 }
|
|
|
|
lgpCondId5863TransformerFanFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The transformer fan has failed."
|
|
::= { lgpFlexConditionsWellKnown 5863 }
|
|
|
|
lgpCondId5865NoLoadWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indicates the UPS has output voltage but the output current is
|
|
below a set threshold [No Load Warning Current Threshold] for a
|
|
set period of time [No Load Warning Delay]."
|
|
::= { lgpFlexConditionsWellKnown 5865 }
|
|
|
|
lgpCondId5871BatteryOverTemperatureLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor is reporting a value above a
|
|
predetermined limit."
|
|
::= { lgpFlexConditionsWellKnown 5871 }
|
|
|
|
lgpCondId5873UnexpectedMainBatteryDisconnectClosure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The main battery disconnect has closed unexpectedly."
|
|
::= { lgpFlexConditionsWellKnown 5873 }
|
|
|
|
lgpCondId5874BatteryOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that the battery voltage has exceeded a
|
|
predetermined limit."
|
|
::= { lgpFlexConditionsWellKnown 5874 }
|
|
|
|
lgpCondId5875BatteryFuseFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more battery fuse faults has occurred."
|
|
::= { lgpFlexConditionsWellKnown 5875 }
|
|
|
|
lgpCondId5878MainBatteryDisconnectForcedToUnlock OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The main battery disconnect is forced to the unlocked state."
|
|
::= { lgpFlexConditionsWellKnown 5878 }
|
|
|
|
lgpCondId5879VdcBackfeed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage between battery and DC bus measurements is out of
|
|
tolerance."
|
|
::= { lgpFlexConditionsWellKnown 5879 }
|
|
|
|
lgpCondId5880RectifierConfigurationChangeRequest OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This event indicates that the battery is not configured and PFC is
|
|
not enabled."
|
|
::= { lgpFlexConditionsWellKnown 5880 }
|
|
|
|
lgpCondId5881RegenerationActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Regeneration operation is active."
|
|
::= { lgpFlexConditionsWellKnown 5881 }
|
|
|
|
lgpCondId5882RegenerationOperationTerminated OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Regeneration operation is not active."
|
|
::= { lgpFlexConditionsWellKnown 5882 }
|
|
|
|
lgpCondId5883RegenerationOperationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Regeneration operation has been terminated due to bypass source
|
|
instability or unit misoperation."
|
|
::= { lgpFlexConditionsWellKnown 5883 }
|
|
|
|
lgpCondId5884ProgramInputContact01 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 01] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5884 }
|
|
|
|
lgpCondId5885ProgramInputContact02 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 02] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5885 }
|
|
|
|
lgpCondId5886ProgramInputContact03 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 03] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5886 }
|
|
|
|
lgpCondId5887ProgramInputContact04 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 04] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5887 }
|
|
|
|
lgpCondId5888ProgramInputContact05 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 05] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5888 }
|
|
|
|
lgpCondId5889ProgramInputContact06 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 06] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5889 }
|
|
|
|
lgpCondId5890ProgramInputContact07 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 07] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5890 }
|
|
|
|
lgpCondId5891ProgramInputContact08 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 08] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5891 }
|
|
|
|
lgpCondId5892ProgramInputContact09 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 09] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5892 }
|
|
|
|
lgpCondId5893ProgramInputContact10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 10] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5893 }
|
|
|
|
lgpCondId5894ProgramInputContact11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 11] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5894 }
|
|
|
|
lgpCondId5895ProgramInputContact12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"When the signal from [Program Input Contact 12] is active the
|
|
function assigned to this contact is executed."
|
|
::= { lgpFlexConditionsWellKnown 5895 }
|
|
|
|
lgpCondId5896GroundFaultDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a ground fault on a Battery-String."
|
|
::= { lgpFlexConditionsWellKnown 5896 }
|
|
|
|
lgpCondId5902ReturnHumiditySensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity sensor at the inlet of the unit is disconnected or
|
|
the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5902 }
|
|
|
|
lgpCondId5903CompressorLowDifferentialPressureLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor exceeded maximum startup attempts due to low
|
|
differential pressure. Compressor is shutdown and has been
|
|
disabled."
|
|
::= { lgpFlexConditionsWellKnown 5903 }
|
|
|
|
lgpCondId5906AirflowSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Airflow sensor is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 5906 }
|
|
|
|
lgpCondId5907ExtAirDamperPositionIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air damper position does not match expected value, as indicated by
|
|
an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 5907 }
|
|
|
|
lgpCondId5908ExtPowerSourceAFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit main power source A failure, as indicated by an external
|
|
input signal."
|
|
::= { lgpFlexConditionsWellKnown 5908 }
|
|
|
|
lgpCondId5909ExtPowerSourceBFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit main power source B failure, as indicated by an external
|
|
input signal."
|
|
::= { lgpFlexConditionsWellKnown 5909 }
|
|
|
|
lgpCondId5910StaticPressureSensorOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Static pressure sensor signal is out of its configured range."
|
|
::= { lgpFlexConditionsWellKnown 5910 }
|
|
|
|
lgpCondId5911FluidTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fluid temperature sensor is disconnected or the signal is out
|
|
of range."
|
|
::= { lgpFlexConditionsWellKnown 5911 }
|
|
|
|
lgpCondId5912FluidFlowSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The fluid flow sensor is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 5912 }
|
|
|
|
lgpCondId5914OverDifferentialPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over differential pressure condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 5914 }
|
|
|
|
lgpCondId5915UnderDifferentialPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An under differential pressure condition was detected."
|
|
::= { lgpFlexConditionsWellKnown 5915 }
|
|
|
|
lgpCondId5924MixedModeLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mixed mode has been entered too many times over a rolling time
|
|
period and has been temporarily disabled. Mixed mode is defined
|
|
as the use of a compressor on one refrigeration circuit and the
|
|
use of a refrigerant pump on the other circuit."
|
|
::= { lgpFlexConditionsWellKnown 5924 }
|
|
|
|
lgpCondId5928UnbalancedLoadCondition OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a line-to-line unbalanced load condition."
|
|
::= { lgpFlexConditionsWellKnown 5928 }
|
|
|
|
lgpCondId5939BranchOverCurrentProtection OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Branch Receptacle Module's over current protection is
|
|
triggered."
|
|
::= { lgpFlexConditionsWellKnown 5939 }
|
|
|
|
lgpCondId5948BranchLowVoltageLL OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a module under voltage condition (LL)."
|
|
::= { lgpFlexConditionsWellKnown 5948 }
|
|
|
|
lgpCondId5957BypassInputVoltageFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the bypass voltage is unqualified."
|
|
::= { lgpFlexConditionsWellKnown 5957 }
|
|
|
|
lgpCondId5958BatteryTemperatureOutofRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery temperature is outside of acceptable range."
|
|
::= { lgpFlexConditionsWellKnown 5958 }
|
|
|
|
lgpCondId5960InverterOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter in overload fault."
|
|
::= { lgpFlexConditionsWellKnown 5960 }
|
|
|
|
lgpCondId5966AuxAirTempDeviceCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with external auxiliary device providing an air
|
|
temperature value has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5966 }
|
|
|
|
lgpCondId5967ModbusPowerMeterCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with Modbus power meter has been lost."
|
|
::= { lgpFlexConditionsWellKnown 5967 }
|
|
|
|
lgpCondId5968InverterDesaturation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Inverter Desaturation."
|
|
::= { lgpFlexConditionsWellKnown 5968 }
|
|
|
|
lgpCondId5969GenericDICFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The control board reports a fault - Service required."
|
|
::= { lgpFlexConditionsWellKnown 5969 }
|
|
|
|
lgpCondId5970GroundFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An AC phase to ground fault or three phase fault to ground exists
|
|
on the output of the UPS."
|
|
::= { lgpFlexConditionsWellKnown 5970 }
|
|
|
|
lgpCondId5973InputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The main input breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 5973 }
|
|
|
|
lgpCondId5974NeutralBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The neutral breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 5974 }
|
|
|
|
lgpCondId5975OutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 5975 }
|
|
|
|
lgpCondId5976MaintenanceBypassBreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The maintenance bypass breaker is closed."
|
|
::= { lgpFlexConditionsWellKnown 5976 }
|
|
|
|
lgpCondId5977BatteryBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery circuit is open."
|
|
::= { lgpFlexConditionsWellKnown 5977 }
|
|
|
|
lgpCondId5978RectifierIsolationBreakerRFBOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rectifier isolation breaker (RFB) indicates that it is in the
|
|
open position."
|
|
::= { lgpFlexConditionsWellKnown 5978 }
|
|
|
|
lgpCondId5982BypassBreakerSBBOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass circuit breaker (SBB) indicates that it is in the open
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 5982 }
|
|
|
|
lgpCondId5983BypassIsolationBreakerBIBOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass isolation breaker (BIB) indicates that it is in the
|
|
open position."
|
|
::= { lgpFlexConditionsWellKnown 5983 }
|
|
|
|
lgpCondId5984BypassUndervoltageWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The voltage on one or more bypass phases is less than a specified
|
|
percentage of the nominal voltage."
|
|
::= { lgpFlexConditionsWellKnown 5984 }
|
|
|
|
lgpCondId5985BypassStaticSwitchBPSSOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Bypass Static Switch has been turned on."
|
|
::= { lgpFlexConditionsWellKnown 5985 }
|
|
|
|
lgpCondId5998BattOvtempWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A battery temperature sensor is reporting a value above the
|
|
setpoint."
|
|
::= { lgpFlexConditionsWellKnown 5998 }
|
|
|
|
lgpCondId6009InverterOutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter output breaker indicates that it is in the open
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 6009 }
|
|
|
|
lgpCondId6011EquipmentOverTempWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Equipment over temperature warning is a summary event based on the
|
|
detection of at least one measured temperature exceeding a
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 6011 }
|
|
|
|
lgpCondId6012EquipmentOvertemperatureLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The equipment air temperature has exceeded its maximum set point."
|
|
::= { lgpFlexConditionsWellKnown 6012 }
|
|
|
|
lgpCondId6045RectifierInputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rectifier isolation breaker indicates that it is in the open
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 6045 }
|
|
|
|
lgpCondId6046LoadonUPS OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The output is being supplied power from the inverter."
|
|
::= { lgpFlexConditionsWellKnown 6046 }
|
|
|
|
lgpCondId6047Core2CoreFuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Core-2-core fuse failure."
|
|
::= { lgpFlexConditionsWellKnown 6047 }
|
|
|
|
lgpCondId6052SystemOutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system output breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 6052 }
|
|
|
|
lgpCondId6059InverterRelayFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter relay has malfunctioned."
|
|
::= { lgpFlexConditionsWellKnown 6059 }
|
|
|
|
lgpCondId6060TransfertoBypassSystemOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS System has transferred to bypass because the active power
|
|
modules cannot support the critical load."
|
|
::= { lgpFlexConditionsWellKnown 6060 }
|
|
|
|
lgpCondId6061InputSourceBackfeed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is backfeeding the input source."
|
|
::= { lgpFlexConditionsWellKnown 6061 }
|
|
|
|
lgpCondId6062LossofSynchronization OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter and bypass are no longer synchronized. ."
|
|
::= { lgpFlexConditionsWellKnown 6062 }
|
|
|
|
lgpCondId6063BatteryConverterCurrentLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery converter has reached is maximum current limit. ."
|
|
::= { lgpFlexConditionsWellKnown 6063 }
|
|
|
|
lgpCondId6064LBSCableFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load Bus Sync communications is abnormal. A problem with the LBS
|
|
cable may exist."
|
|
::= { lgpFlexConditionsWellKnown 6064 }
|
|
|
|
lgpCondId6065BatteryChargeEqualizationTimeout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery equalizing is time out."
|
|
::= { lgpFlexConditionsWellKnown 6065 }
|
|
|
|
lgpCondId6066ParallelCableFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS parallel system communications is abnormal. A problem with
|
|
the parallel cable may exist."
|
|
::= { lgpFlexConditionsWellKnown 6066 }
|
|
|
|
lgpCondId6067BatteryFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A short circuit exists in the battery system."
|
|
::= { lgpFlexConditionsWellKnown 6067 }
|
|
|
|
lgpCondId6068BatteryRoomAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ambient temperature of the battery room is abnormal."
|
|
::= { lgpFlexConditionsWellKnown 6068 }
|
|
|
|
lgpCondId6080UPSCCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPSC has failed to communicate in a designated time period."
|
|
::= { lgpFlexConditionsWellKnown 6080 }
|
|
|
|
lgpCondId6092Compressor1BThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 1B is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 6092 }
|
|
|
|
lgpCondId6093Compressor2BThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 2B is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 6093 }
|
|
|
|
lgpCondId6094Compressor1BHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 1B run hours have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6094 }
|
|
|
|
lgpCondId6095Compressor2BHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fixed compressor 2B run hours have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6095 }
|
|
|
|
lgpCondId6100CondenserRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 6100 }
|
|
|
|
lgpCondId6105ExternalCondenserTVSSIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser Transient Voltage Surge Suppressor or Surge
|
|
Protection Device has failed, as indicated by an external input
|
|
signal."
|
|
::= { lgpFlexConditionsWellKnown 6105 }
|
|
|
|
lgpCondId6106ExternalCondenserVFDIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser fan Variable Frequency Drive is offline, as
|
|
indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6106 }
|
|
|
|
lgpCondId6107ExternalCondenserIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser is not operating within its operational parameters, as
|
|
indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6107 }
|
|
|
|
lgpCondId6119Slotsnotavailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of sensors exceeds the number of allocated slots and
|
|
cannot be displayed."
|
|
::= { lgpFlexConditionsWellKnown 6119 }
|
|
|
|
lgpCondId6180BatteryUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery voltage is too low."
|
|
::= { lgpFlexConditionsWellKnown 6180 }
|
|
|
|
lgpCondId6182ReplaceBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is due for replacement."
|
|
::= { lgpFlexConditionsWellKnown 6182 }
|
|
|
|
lgpCondId6186InputFrequencyDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input frequency is outside of the normal range."
|
|
::= { lgpFlexConditionsWellKnown 6186 }
|
|
|
|
lgpCondId6187ShutdownPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shutdown is pending."
|
|
::= { lgpFlexConditionsWellKnown 6187 }
|
|
|
|
lgpCondId6194SystemRebootCommandIssued OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reboot command issued to the system."
|
|
::= { lgpFlexConditionsWellKnown 6194 }
|
|
|
|
lgpCondId6203SensorAdded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor Added."
|
|
::= { lgpFlexConditionsWellKnown 6203 }
|
|
|
|
lgpCondId6204SensorRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sensor Removed."
|
|
::= { lgpFlexConditionsWellKnown 6204 }
|
|
|
|
lgpCondId6205WaterLeakDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Water leak detected."
|
|
::= { lgpFlexConditionsWellKnown 6205 }
|
|
|
|
lgpCondId6210FirmwareUpdateInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware update has started and is in progress."
|
|
::= { lgpFlexConditionsWellKnown 6210 }
|
|
|
|
lgpCondId6211FirmwareUpdateCompletedSuccessfully OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware update has completed successfully."
|
|
::= { lgpFlexConditionsWellKnown 6211 }
|
|
|
|
lgpCondId6212FirmwareUpdateCompletedUnsuccessfully OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Firmware update has completed, but was not successful."
|
|
::= { lgpFlexConditionsWellKnown 6212 }
|
|
|
|
lgpCondId6216PrechargeCircuitFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"DC Bus precharge/discharge didn't reach specified level within a
|
|
specified time."
|
|
::= { lgpFlexConditionsWellKnown 6216 }
|
|
|
|
lgpCondId6217MemoryCardRemoved OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The memory card on the control board has been removed."
|
|
::= { lgpFlexConditionsWellKnown 6217 }
|
|
|
|
lgpCondId6218AutoCalibrationActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is automatically calibrating ADC channels."
|
|
::= { lgpFlexConditionsWellKnown 6218 }
|
|
|
|
lgpCondId6219AutoCalibrationFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"ADC channel calibration has failed."
|
|
::= { lgpFlexConditionsWellKnown 6219 }
|
|
|
|
lgpCondId6220ModuleOutputBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The module output breaker is open."
|
|
::= { lgpFlexConditionsWellKnown 6220 }
|
|
|
|
lgpCondId6221NeutralVoltageFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Voltage observed on neutral line."
|
|
::= { lgpFlexConditionsWellKnown 6221 }
|
|
|
|
lgpCondId6222BranchLoadLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of load on branch detected. Branch circuit breaker might be
|
|
open."
|
|
::= { lgpFlexConditionsWellKnown 6222 }
|
|
|
|
lgpCondId6225RemoteSensorLowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor humidity has dropped below a lower threshold. The
|
|
event is deactivated when the humidity rises above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6225 }
|
|
|
|
lgpCondId6226RemoteSensorHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor humidity has exceeded an upper threshold. The event
|
|
is deactivated when the humidity drops below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6226 }
|
|
|
|
lgpCondId6227RemoteSensorAverageLowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on the cooling
|
|
unit has dropped below a lower threshold. The event is
|
|
deactivated when the humidity rises above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6227 }
|
|
|
|
lgpCondId6228RemoteSensorAverageHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on the cooling
|
|
unit has exceeded an upper threshold. The event is deactivated
|
|
when the humidity drops below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6228 }
|
|
|
|
lgpCondId6229RemoteSensorSystemAverageLowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on interconnected
|
|
cooling units in a single system has dropped below a lower
|
|
threshold. The event is deactivated when the humidity rises
|
|
above the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6229 }
|
|
|
|
lgpCondId6230RemoteSensorSystemAverageHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The average humidity of multiple remote sensors on interconnected
|
|
cooling units in a single system has exceeded an upper threshold.
|
|
The event is deactivated when the humidity drops below the
|
|
threshold."
|
|
::= { lgpFlexConditionsWellKnown 6230 }
|
|
|
|
lgpCondId6231LowCompressorSuperheat OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor suction superheat has dropped below a lower threshold."
|
|
::= { lgpFlexConditionsWellKnown 6231 }
|
|
|
|
lgpCondId6232SECUnspecifiedGeneralEvent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more unspecified events active for the Superheat and
|
|
Envelope Controller. See local unit display for further details."
|
|
::= { lgpFlexConditionsWellKnown 6232 }
|
|
|
|
lgpCondId6233SECCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with the Superheat and Envelope Controller has been
|
|
lost. The event is deactivated when communication is re
|
|
-established."
|
|
::= { lgpFlexConditionsWellKnown 6233 }
|
|
|
|
lgpCondId6236PowerSourceAIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No power is detected at power source input 'A'."
|
|
::= { lgpFlexConditionsWellKnown 6236 }
|
|
|
|
lgpCondId6237PowerSourceBIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No power is detected at power source input 'B'."
|
|
::= { lgpFlexConditionsWellKnown 6237 }
|
|
|
|
lgpCondId6239FluidValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Operating hours for the fluid valve have exceeded the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6239 }
|
|
|
|
lgpCondId6253BoosterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Booster failure - boost is off."
|
|
::= { lgpFlexConditionsWellKnown 6253 }
|
|
|
|
lgpCondId6254ChargerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Charger Failure - Charger is off."
|
|
::= { lgpFlexConditionsWellKnown 6254 }
|
|
|
|
lgpCondId6274UnitTopReturnAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return air sensor at the top of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6274 }
|
|
|
|
lgpCondId6275UnitMiddleReturnAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return air sensor in the middle of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6275 }
|
|
|
|
lgpCondId6276UnitBottomReturnAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Return air sensor at the bottom of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6276 }
|
|
|
|
lgpCondId6277UnitTopSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply air sensor at the top of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6277 }
|
|
|
|
lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"First supply air sensor in the middle of the unit is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6278 }
|
|
|
|
lgpCondId6279UnitBottomSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply air sensor at the bottom of the unit is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6279 }
|
|
|
|
lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Second supply air sensor in the middle of the unit is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6284 }
|
|
|
|
lgpCondId6293ChilledWaterControlActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature control function is enabled due to
|
|
'bad' water."
|
|
::= { lgpFlexConditionsWellKnown 6293 }
|
|
|
|
lgpCondId6294ChilledWaterFlowTransducerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water flow transducer is disconnected or the signal is out
|
|
of range."
|
|
::= { lgpFlexConditionsWellKnown 6294 }
|
|
|
|
lgpCondId6295ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature sensor is disconnected or the
|
|
signal is out of range. The sensor is mandatory for the chilled
|
|
water flow function."
|
|
::= { lgpFlexConditionsWellKnown 6295 }
|
|
|
|
lgpCondId6296ChilledWaterHighInletTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature has exceeded an upper threshold."
|
|
::= { lgpFlexConditionsWellKnown 6296 }
|
|
|
|
lgpCondId6297Modbus010VModuleCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Modbus 0-10V module for managing the second Chilled Water circuit
|
|
valve is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6297 }
|
|
|
|
lgpCondId6299RackDoorsOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rack doors opened due to supply air temperature exceeding the
|
|
[Rack Door Open High Supply Air Temperature Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 6299 }
|
|
|
|
lgpCondId6303TeamStaticPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The team static pressure sensor is disconnected or the signal is
|
|
out of range."
|
|
::= { lgpFlexConditionsWellKnown 6303 }
|
|
|
|
lgpCondId6304HeatingLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Heating is shut down and disabled."
|
|
::= { lgpFlexConditionsWellKnown 6304 }
|
|
|
|
lgpCondId6305FreeCoolingStoppedHighRoomTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Free cooling is temporarily disabled due to room temperature
|
|
exceeding a preset delta above the the set point."
|
|
::= { lgpFlexConditionsWellKnown 6305 }
|
|
|
|
lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cold aisle team sensor measuring air temperature and humidity is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6306 }
|
|
|
|
lgpCondId6309ColdAisleAirSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Cold aisle sensor measuring air temperature and humidity is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6309 }
|
|
|
|
lgpCondId6310ChilledWaterInletTemperatureControlActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature control is active."
|
|
::= { lgpFlexConditionsWellKnown 6310 }
|
|
|
|
lgpCondId6313ChilledWaterInletTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water inlet temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6313 }
|
|
|
|
lgpCondId6314ChilledWaterOutletTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water outlet temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6314 }
|
|
|
|
lgpCondId6315ChilledWaterFlowMeterSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Chilled water flow meter sensor is disconnected or the signal is
|
|
out of range."
|
|
::= { lgpFlexConditionsWellKnown 6315 }
|
|
|
|
lgpCondId6333Bypassoutofsync OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass and Inverter inputs are not in sync."
|
|
::= { lgpFlexConditionsWellKnown 6333 }
|
|
|
|
lgpCondId6348SystemOutputoffasrequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS has shutdown as requested, i.e., the output is off."
|
|
::= { lgpFlexConditionsWellKnown 6348 }
|
|
|
|
lgpCondId6349SystemOffasrequested OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The entire UPS has shutdown as commanded."
|
|
::= { lgpFlexConditionsWellKnown 6349 }
|
|
|
|
lgpCondId6350GeneralFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A general fault in the UPS has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6350 }
|
|
|
|
lgpCondId6351UPSAwaitingPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS output is off and the UPS is awaiting the return of input
|
|
power."
|
|
::= { lgpFlexConditionsWellKnown 6351 }
|
|
|
|
lgpCondId6352AutonomyCalibration OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Calibration test occurred."
|
|
::= { lgpFlexConditionsWellKnown 6352 }
|
|
|
|
lgpCondId6353GeneralWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A warning in the UPS has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6353 }
|
|
|
|
lgpCondId6354BatteryCharging OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The UPS battery is charging (battery charge percentage lower than
|
|
98)."
|
|
::= { lgpFlexConditionsWellKnown 6354 }
|
|
|
|
lgpCondId6355BackfeedRelayFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bypass SCR is wrongly on or commutated."
|
|
::= { lgpFlexConditionsWellKnown 6355 }
|
|
|
|
lgpCondId6356BatteryCircuitOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Circuit Open."
|
|
::= { lgpFlexConditionsWellKnown 6356 }
|
|
|
|
lgpCondId6357SystemRestartPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A request for UPS restart has been received."
|
|
::= { lgpFlexConditionsWellKnown 6357 }
|
|
|
|
lgpCondId6358PipeTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Air temperature sensor located in the pipe is not sending a valid
|
|
value."
|
|
::= { lgpFlexConditionsWellKnown 6358 }
|
|
|
|
lgpCondId6362SFAReservedEvent26 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6362 }
|
|
|
|
lgpCondId6363SFAReservedEvent27 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6363 }
|
|
|
|
lgpCondId6364SFAReservedEvent28 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6364 }
|
|
|
|
lgpCondId6365SFAReservedEvent29 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6365 }
|
|
|
|
lgpCondId6366SFAReservedEvent30 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6366 }
|
|
|
|
lgpCondId6367SFAReservedEvent31 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6367 }
|
|
|
|
lgpCondId6368SFAReservedEvent32 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6368 }
|
|
|
|
lgpCondId6369SFAReservedEvent33 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6369 }
|
|
|
|
lgpCondId6370SFAReservedEvent34 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6370 }
|
|
|
|
lgpCondId6371SFAReservedEvent35 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6371 }
|
|
|
|
lgpCondId6372SFAReservedEvent36 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6372 }
|
|
|
|
lgpCondId6373SFAReservedEvent37 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6373 }
|
|
|
|
lgpCondId6374SFAReservedEvent38 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6374 }
|
|
|
|
lgpCondId6375SFAReservedEvent39 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6375 }
|
|
|
|
lgpCondId6376SFAReservedEvent40 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6376 }
|
|
|
|
lgpCondId6377SFAReservedEvent41 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6377 }
|
|
|
|
lgpCondId6378SFAReservedEvent42 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6378 }
|
|
|
|
lgpCondId6379SFAReservedEvent43 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6379 }
|
|
|
|
lgpCondId6380SFAReservedEvent44 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6380 }
|
|
|
|
lgpCondId6381SFAReservedEvent45 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6381 }
|
|
|
|
lgpCondId6382SFAReservedEvent46 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6382 }
|
|
|
|
lgpCondId6383SFAReservedEvent47 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6383 }
|
|
|
|
lgpCondId6384SFAReservedEvent48 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6384 }
|
|
|
|
lgpCondId6385SFAReservedEvent49 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6385 }
|
|
|
|
lgpCondId6386SFAReservedEvent50 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reserved event for SFA use."
|
|
::= { lgpFlexConditionsWellKnown 6386 }
|
|
|
|
lgpCondId6438PowerModuleInputCurrentAbnormal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input current of the power module is abnormal."
|
|
::= { lgpFlexConditionsWellKnown 6438 }
|
|
|
|
lgpCondId6439PowerModuleBalancerofDCBusFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Balancer of DC Bus in the power module has failed."
|
|
::= { lgpFlexConditionsWellKnown 6439 }
|
|
|
|
lgpCondId6440PowerModuleFuseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A summary event indicating one or more fuse failures in the power
|
|
module."
|
|
::= { lgpFlexConditionsWellKnown 6440 }
|
|
|
|
lgpCondId6441PowerModulePowerSupplyFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Power module power supply failure."
|
|
::= { lgpFlexConditionsWellKnown 6441 }
|
|
|
|
lgpCondId6450PDUPoweredOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU was powered on."
|
|
::= { lgpFlexConditionsWellKnown 6450 }
|
|
|
|
lgpCondId6453InputWiringFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The neutral/ground conductors on the input wiring are not properly
|
|
bonded, or the line/neutral conductors have been swapped."
|
|
::= { lgpFlexConditionsWellKnown 6453 }
|
|
|
|
lgpCondId6454DCtoDCConverterFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A failure has occurred in the battery discharge circuit."
|
|
::= { lgpFlexConditionsWellKnown 6454 }
|
|
|
|
lgpCondId6455LeakSensorCableFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A fault is detected in the 'Leak Sensor' cable."
|
|
::= { lgpFlexConditionsWellKnown 6455 }
|
|
|
|
lgpCondId6518StandbyUnitActivatedDuetoChillerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External chiller unit has failed for this unit, so the standby
|
|
cooling unit has been activated."
|
|
::= { lgpFlexConditionsWellKnown 6518 }
|
|
|
|
lgpCondId6522PDUResidualOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a PDU residual over current condition."
|
|
::= { lgpFlexConditionsWellKnown 6522 }
|
|
|
|
lgpCondId6527PDUOverCurrentProtection OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The PDU over current protection is triggered."
|
|
::= { lgpFlexConditionsWellKnown 6527 }
|
|
|
|
lgpCondId6528PowerModuleLeverUnlocked OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The power module is inactive because the lever is in the unlocked
|
|
position."
|
|
::= { lgpFlexConditionsWellKnown 6528 }
|
|
|
|
lgpCondId6529HardwareMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The assigned system model settings do not match the actual
|
|
installed hardware. The module count is wrong, or a module of the
|
|
wrong type is installed."
|
|
::= { lgpFlexConditionsWellKnown 6529 }
|
|
|
|
lgpCondId6530SupplyNTCAirSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The supply NTC air sensor is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6530 }
|
|
|
|
lgpCondId6531ExternalAirSensorCIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor C is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6531 }
|
|
|
|
lgpCondId6532ExternalAirSensorDIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor D is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6532 }
|
|
|
|
lgpCondId6533ExternalAirSensorEIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The external air sensor E is disconnected or the signal is out of
|
|
range."
|
|
::= { lgpFlexConditionsWellKnown 6533 }
|
|
|
|
lgpCondId6534PumpThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down due to thermal overload."
|
|
::= { lgpFlexConditionsWellKnown 6534 }
|
|
|
|
lgpCondId6535XDModuleCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with XD Module has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6535 }
|
|
|
|
lgpCondId6536MMSCapacityExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The critical load is larger than the redundant rating of a 1+N
|
|
redundant multi-module system."
|
|
::= { lgpFlexConditionsWellKnown 6536 }
|
|
|
|
lgpCondId6538TSAControlInputIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The analog input used to set the air temperature set point for
|
|
cooling control is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6538 }
|
|
|
|
lgpCondId6539ChilledWaterValveHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"[Chilled Water Valve Hours] has exceeded [Chilled Water Valve
|
|
Operating Hours Threshold]."
|
|
::= { lgpFlexConditionsWellKnown 6539 }
|
|
|
|
lgpCondId6540FSAControlInputIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The analog input used to set the air temperature set point for fan
|
|
speed control is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6540 }
|
|
|
|
lgpCondId6541AutoTuneLicenseExpiring OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"License for the AutoTune feature has not been refreshed in 30 days
|
|
and will be expiring soon."
|
|
::= { lgpFlexConditionsWellKnown 6541 }
|
|
|
|
lgpCondId6542AutoTuneLicenseExpired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"License for the AutoTune feature has expired."
|
|
::= { lgpFlexConditionsWellKnown 6542 }
|
|
|
|
lgpCondId6543UnitInStandbyDueToCoolingLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit forced into standby because it is unable to provide any
|
|
cooling."
|
|
::= { lgpFlexConditionsWellKnown 6543 }
|
|
|
|
lgpCondId6544ControlUnitsRemoteShutdownMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The remote shutdown status of the primary control unit does not
|
|
match the remote shutdown status of the secondary control unit."
|
|
::= { lgpFlexConditionsWellKnown 6544 }
|
|
|
|
lgpCondId6545SecondaryControlUnitCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The primary control unit has lost Ethernet communications with the
|
|
secondary control unit."
|
|
::= { lgpFlexConditionsWellKnown 6545 }
|
|
|
|
lgpCondId6546ControlUnitsUnitCodeMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit codes for the primary and secondary control units do not
|
|
match."
|
|
::= { lgpFlexConditionsWellKnown 6546 }
|
|
|
|
lgpCondId6547SSAControlInputIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The analog input used to set the static pressure set point for fan
|
|
speed control is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6547 }
|
|
|
|
lgpCondId6574SubfeedPhaseUndercurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subfeed breaker phase current has dropped below the threshold."
|
|
::= { lgpFlexConditionsWellKnown 6574 }
|
|
|
|
lgpCondId6587TransferCountCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A system event indicating the transfer count has been cleared."
|
|
::= { lgpFlexConditionsWellKnown 6587 }
|
|
|
|
lgpCondId6588EnergyCounterCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A system event indicating the energy counter (e.g. KWH) has been
|
|
cleared."
|
|
::= { lgpFlexConditionsWellKnown 6588 }
|
|
|
|
lgpCondId6589HistoryLogsFull OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The history logs are full."
|
|
::= { lgpFlexConditionsWellKnown 6589 }
|
|
|
|
lgpCondId6590HistoryLogsCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"History logs have been cleared."
|
|
::= { lgpFlexConditionsWellKnown 6590 }
|
|
|
|
lgpCondId6591EventLogCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"All past alarms and faults have been cleared."
|
|
::= { lgpFlexConditionsWellKnown 6591 }
|
|
|
|
lgpCondId6592SystemDateChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system date has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6592 }
|
|
|
|
lgpCondId6593SystemTimeChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system time has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6593 }
|
|
|
|
lgpCondId6594AccessPasswordChanged OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The access password has been changed."
|
|
::= { lgpFlexConditionsWellKnown 6594 }
|
|
|
|
lgpCondId6595ConfigModified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A setpoint has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6595 }
|
|
|
|
lgpCondId6612SCRShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SCR is in a short condition."
|
|
::= { lgpFlexConditionsWellKnown 6612 }
|
|
|
|
lgpCondId6613SCROpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SCR is in an open condition."
|
|
::= { lgpFlexConditionsWellKnown 6613 }
|
|
|
|
lgpCondId6614ACPowerSupplyFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A failure of the AC Power Supply has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6614 }
|
|
|
|
lgpCondId6615DCPowerSupplyFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A failure of the DC Power Supply has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6615 }
|
|
|
|
lgpCondId6616VoltageSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A voltage sensor failure has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6616 }
|
|
|
|
lgpCondId6617SCRSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The SCR sensor module failed."
|
|
::= { lgpFlexConditionsWellKnown 6617 }
|
|
|
|
lgpCondId6618CurrentSensorFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current sensor module failed."
|
|
::= { lgpFlexConditionsWellKnown 6618 }
|
|
|
|
lgpCondId6619GateDriveFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Gate Drive module failed."
|
|
::= { lgpFlexConditionsWellKnown 6619 }
|
|
|
|
lgpCondId6620SurgeFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The surge module failed for the input source."
|
|
::= { lgpFlexConditionsWellKnown 6620 }
|
|
|
|
lgpCondId6621FastUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fast under voltage detected."
|
|
::= { lgpFlexConditionsWellKnown 6621 }
|
|
|
|
lgpCondId6622SlowUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Slow under voltage detected."
|
|
::= { lgpFlexConditionsWellKnown 6622 }
|
|
|
|
lgpCondId6623OverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Over voltage detected."
|
|
::= { lgpFlexConditionsWellKnown 6623 }
|
|
|
|
lgpCondId6624OverUnderFrequencyFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over or under frequency condition has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6624 }
|
|
|
|
lgpCondId6625GeneralSourceFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A non-specific failure has been detected in the source."
|
|
::= { lgpFlexConditionsWellKnown 6625 }
|
|
|
|
lgpCondId6626OverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An over current has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6626 }
|
|
|
|
lgpCondId6627PeakCurrentOffLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The peak current has exceeded the setpoint defined by I-PK Xfer
|
|
Lockout."
|
|
::= { lgpFlexConditionsWellKnown 6627 }
|
|
|
|
lgpCondId6628SyncFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A phase rotation/out of synchronization failure has been detected."
|
|
::= { lgpFlexConditionsWellKnown 6628 }
|
|
|
|
lgpCondId6629InputOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input over voltage."
|
|
::= { lgpFlexConditionsWellKnown 6629 }
|
|
|
|
lgpCondId6630InputUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input under voltage."
|
|
::= { lgpFlexConditionsWellKnown 6630 }
|
|
|
|
lgpCondId6631InputOverUnderFrequency OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input over/under frequency."
|
|
::= { lgpFlexConditionsWellKnown 6631 }
|
|
|
|
lgpCondId6635VoltageSenseFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output voltage sense failure."
|
|
::= { lgpFlexConditionsWellKnown 6635 }
|
|
|
|
lgpCondId6636LoadonAlternateSource OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The load is on the alternate source."
|
|
::= { lgpFlexConditionsWellKnown 6636 }
|
|
|
|
lgpCondId6637UnderVoltageFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output under voltage failure."
|
|
::= { lgpFlexConditionsWellKnown 6637 }
|
|
|
|
lgpCondId6638OutputOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Output is over current."
|
|
::= { lgpFlexConditionsWellKnown 6638 }
|
|
|
|
lgpCondId6639GroundOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ground is over current."
|
|
::= { lgpFlexConditionsWellKnown 6639 }
|
|
|
|
lgpCondId6640NeutralOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Neutral is over current."
|
|
::= { lgpFlexConditionsWellKnown 6640 }
|
|
|
|
lgpCondId6641LoadVoltageTHD OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load voltage THD has exceeded the set limit."
|
|
::= { lgpFlexConditionsWellKnown 6641 }
|
|
|
|
lgpCondId6662ControlLogicFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A control logic module has failed."
|
|
::= { lgpFlexConditionsWellKnown 6662 }
|
|
|
|
lgpCondId6663PowerSupplyLogicFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A power supply module has failed."
|
|
::= { lgpFlexConditionsWellKnown 6663 }
|
|
|
|
lgpCondId6664ExternalCommsFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External communications failure."
|
|
::= { lgpFlexConditionsWellKnown 6664 }
|
|
|
|
lgpCondId6665HeatSinkOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system heat sink temperature has exceeded design limits."
|
|
::= { lgpFlexConditionsWellKnown 6665 }
|
|
|
|
lgpCondId6666AutomaticTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic transfer is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 6666 }
|
|
|
|
lgpCondId6667InputSourceTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Input source transfer is inhibited."
|
|
::= { lgpFlexConditionsWellKnown 6667 }
|
|
|
|
lgpCondId6676CB1ShuntTrip OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB1 Shunt Trip event."
|
|
::= { lgpFlexConditionsWellKnown 6676 }
|
|
|
|
lgpCondId6677CB2ShuntTrip OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB2 Shunt Trip event."
|
|
::= { lgpFlexConditionsWellKnown 6677 }
|
|
|
|
lgpCondId6678CB6NeutralOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB6 neutral open event."
|
|
::= { lgpFlexConditionsWellKnown 6678 }
|
|
|
|
lgpCondId6679ContactorNeutralFail OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Contactor Neutral Fail event."
|
|
::= { lgpFlexConditionsWellKnown 6679 }
|
|
|
|
lgpCondId6680CB1BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB1 Breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6680 }
|
|
|
|
lgpCondId6681CB2BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB2 Breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6681 }
|
|
|
|
lgpCondId6682CB4BreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB4 breaker closed event. Normal state is breaker open. Latched
|
|
state is breaker closed."
|
|
::= { lgpFlexConditionsWellKnown 6682 }
|
|
|
|
lgpCondId6683CB5BreakerClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB5 breaker closed event. Normal state is breaker open. Latched
|
|
state is breaker closed."
|
|
::= { lgpFlexConditionsWellKnown 6683 }
|
|
|
|
lgpCondId6684CB3BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB3 breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6684 }
|
|
|
|
lgpCondId6685CB3ABreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB3A breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6685 }
|
|
|
|
lgpCondId6686CB6BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB6 breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6686 }
|
|
|
|
lgpCondId6687CB7BreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"CB7 breaker open event. Normal state is breaker closed. Latched
|
|
state is breaker open."
|
|
::= { lgpFlexConditionsWellKnown 6687 }
|
|
|
|
lgpCondId6691GroupIndependentOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The group standby/cascade state for this unit has been overridden.
|
|
The unit has been forced on."
|
|
::= { lgpFlexConditionsWellKnown 6691 }
|
|
|
|
lgpCondId6692GroupIndependentOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The group standby/cascade state for this unit has been overridden.
|
|
The unit has been forced off."
|
|
::= { lgpFlexConditionsWellKnown 6692 }
|
|
|
|
lgpCondId6693BranchResidualOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a branch residual over current condition."
|
|
::= { lgpFlexConditionsWellKnown 6693 }
|
|
|
|
lgpCondId6694ReceptacleResidualOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a receptacle residual over current
|
|
condition."
|
|
::= { lgpFlexConditionsWellKnown 6694 }
|
|
|
|
lgpCondId6728BuckOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input voltage is currently being bucked (lowered) by the
|
|
inverter."
|
|
::= { lgpFlexConditionsWellKnown 6728 }
|
|
|
|
lgpCondId6729BoostOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input voltage is currently being boosted (raised) by the
|
|
inverter."
|
|
::= { lgpFlexConditionsWellKnown 6729 }
|
|
|
|
lgpCondId6739Compressor1HighPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 High Pressure."
|
|
::= { lgpFlexConditionsWellKnown 6739 }
|
|
|
|
lgpCondId6740Compressor2HighPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2 High Pressure."
|
|
::= { lgpFlexConditionsWellKnown 6740 }
|
|
|
|
lgpCondId6741Compressor1ThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 1 Thermal Overload."
|
|
::= { lgpFlexConditionsWellKnown 6741 }
|
|
|
|
lgpCondId6742Compressor2ThermalOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor 2 Thermal Overload."
|
|
::= { lgpFlexConditionsWellKnown 6742 }
|
|
|
|
lgpCondId6758CompressorFreezeProtection OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Compressor has entered the freeze protection phase."
|
|
::= { lgpFlexConditionsWellKnown 6758 }
|
|
|
|
lgpCondId6773FanTemperatureCompensationLimitReached OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Unit is configured for fan temperature compensation, and the fan
|
|
control set point cannot be reduced any further due to high
|
|
remote air temperature sensor readings."
|
|
::= { lgpFlexConditionsWellKnown 6773 }
|
|
|
|
lgpCondId6774ModbusECFanCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with Modbus EC fan has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6774 }
|
|
|
|
lgpCondId6785AnalogTemperatureControlIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Analog input used for creating the control temperature (instead of
|
|
reading a sensor) is disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6785 }
|
|
|
|
lgpCondId6786SubgroupFirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mismatch of subgroup firmware. Both the primary and secondary
|
|
control boards must be running the same firmware version."
|
|
::= { lgpFlexConditionsWellKnown 6786 }
|
|
|
|
lgpCondId6787SubgroupSecondaryControlUnitIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subgroup secondary control unit is reporting an unspecified issue."
|
|
::= { lgpFlexConditionsWellKnown 6787 }
|
|
|
|
lgpCondId6788EEVCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with Electronic Expansion Valve unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6788 }
|
|
|
|
lgpCondId6789EEVMotorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve stepper motor issue."
|
|
::= { lgpFlexConditionsWellKnown 6789 }
|
|
|
|
lgpCondId6790EEVFeedbackIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve feedback error."
|
|
::= { lgpFlexConditionsWellKnown 6790 }
|
|
|
|
lgpCondId6791EEVPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve refrigerant pressure sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6791 }
|
|
|
|
lgpCondId6792EEVCoilTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve coil temperature sensor is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6792 }
|
|
|
|
lgpCondId6793EEVDischargeTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve discharge temperature sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6793 }
|
|
|
|
lgpCondId6794EEVSumpTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve sump temperature sensor is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6794 }
|
|
|
|
lgpCondId6795EEVBatteryTestIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve battery state cannot be determined."
|
|
::= { lgpFlexConditionsWellKnown 6795 }
|
|
|
|
lgpCondId6796EEVBatteryPersistentIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Electronic Expansion Valve has continuously detected a 'bad'
|
|
battery condition for an extended period of time."
|
|
::= { lgpFlexConditionsWellKnown 6796 }
|
|
|
|
lgpCondId6798PumpCycleLockOut OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is locked out due to multiple pump-to-compressor transitions
|
|
at cold ambient air temperature."
|
|
::= { lgpFlexConditionsWellKnown 6798 }
|
|
|
|
lgpCondId6799PumpBoardFirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mismatch of pump board firmware. All pump boards must be running
|
|
the same firmware version."
|
|
::= { lgpFlexConditionsWellKnown 6799 }
|
|
|
|
lgpCondId6800PumpControlBoardIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down due to a pump control board issue. Control
|
|
board must be rebooted."
|
|
::= { lgpFlexConditionsWellKnown 6800 }
|
|
|
|
lgpCondId6801PumpInvalidDataShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down due to invalid data."
|
|
::= { lgpFlexConditionsWellKnown 6801 }
|
|
|
|
lgpCondId6802PumpInputPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump input refrigerant pressure sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6802 }
|
|
|
|
lgpCondId6803PumpInputTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump input refrigerant temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6803 }
|
|
|
|
lgpCondId6804PumpOutputPressureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump output refrigerant pressure sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6804 }
|
|
|
|
lgpCondId6805PumpOutputTemperatureSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump output refrigerant temperature sensor is disconnected or the
|
|
signal is out of range."
|
|
::= { lgpFlexConditionsWellKnown 6805 }
|
|
|
|
lgpCondId6806PumpCommunicationLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Communication with pump unit has been lost."
|
|
::= { lgpFlexConditionsWellKnown 6806 }
|
|
|
|
lgpCondId6807PumpRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump is shut down by a remote signal."
|
|
::= { lgpFlexConditionsWellKnown 6807 }
|
|
|
|
lgpCondId6808PumpUSBEthernetPortIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump control board USB or Ethernet interface has failed."
|
|
::= { lgpFlexConditionsWellKnown 6808 }
|
|
|
|
lgpCondId6809PumpStartupFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multiple attempts to start the pump have failed."
|
|
::= { lgpFlexConditionsWellKnown 6809 }
|
|
|
|
lgpCondId6810PumpInverterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump inverter is reporting a failure."
|
|
::= { lgpFlexConditionsWellKnown 6810 }
|
|
|
|
lgpCondId6811PumpTVSSIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump Transient Voltage Surge Suppressor or Surge Protection Device
|
|
has failed."
|
|
::= { lgpFlexConditionsWellKnown 6811 }
|
|
|
|
lgpCondId6812PumpHighSuperheat OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Pump inlet refrigerant superheat temperature is too high, or the
|
|
pump has been running too long with the condenser fan off."
|
|
::= { lgpFlexConditionsWellKnown 6812 }
|
|
|
|
lgpCondId6813CondenserHighAmbientAirTempDelta OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The difference between condenser measured ambient air temperatures
|
|
has been too large for an extended period of time."
|
|
::= { lgpFlexConditionsWellKnown 6813 }
|
|
|
|
lgpCondId6814CondenserLeeTempOptionMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Lee-Temp option configured at a condenser unit does not match Lee
|
|
-Temp option configured at the control unit."
|
|
::= { lgpFlexConditionsWellKnown 6814 }
|
|
|
|
lgpCondId6815CondenserBoardFirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Mismatch of condenser board firmware. All condenser boards must
|
|
be running the same firmware version."
|
|
::= { lgpFlexConditionsWellKnown 6815 }
|
|
|
|
lgpCondId6816CondenserToPumpHighRefrigerantTempDelta OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature delta between the condenser output refrigerant and
|
|
pump inlet refrigerant is too large."
|
|
::= { lgpFlexConditionsWellKnown 6816 }
|
|
|
|
lgpCondId6817CondenserRefrigerantTypeMismatch OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Refrigerant type configured at condenser unit does not match
|
|
refrigerant type configured at the control unit."
|
|
::= { lgpFlexConditionsWellKnown 6817 }
|
|
|
|
lgpCondId6818ExternalSupplyFluidHighTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply fluid temperature has exceeded a threshold, as indicated by
|
|
an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6818 }
|
|
|
|
lgpCondId6819ExternalSupplyFluidTempSensorIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply fluid temperature sensor is disconnected or the signal is
|
|
out of range, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6819 }
|
|
|
|
lgpCondId6822AuditLogUpdate OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Audit log has been updated."
|
|
::= { lgpFlexConditionsWellKnown 6822 }
|
|
|
|
lgpCondId6824ExternalSupplyFluidFlowIssue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply fluid flow issue, as indicated by an external input signal."
|
|
::= { lgpFlexConditionsWellKnown 6824 }
|
|
|
|
END
|