- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
4816 lines
180 KiB
Text
4816 lines
180 KiB
Text
LIEBERT-GP-CONDITIONS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY,
|
|
OBJECT-IDENTITY,
|
|
OBJECT-TYPE,
|
|
Gauge32,
|
|
TimeTicks,
|
|
Unsigned32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
lgpConditions,
|
|
liebertConditionsModuleReg
|
|
FROM LIEBERT-GP-REGISTRATION-MIB
|
|
;
|
|
|
|
-- =============================================================================
|
|
-- Module Identification and Registration
|
|
-- =============================================================================
|
|
|
|
liebertGlobalProductsConditionsModule MODULE-IDENTITY
|
|
LAST-UPDATED "201302120000Z"
|
|
ORGANIZATION "Liebert Corporation"
|
|
CONTACT-INFO
|
|
"Contact: Technical Support
|
|
|
|
Postal:
|
|
Liebert Corporation
|
|
1050 Dearborn Drive
|
|
P.O. Box 29186
|
|
Columbus OH, 43229
|
|
US
|
|
|
|
Tel: +1 (800) 222-5877
|
|
|
|
E-mail: liebert.monitoring@vertivco.com
|
|
Web: www.vertivco.com
|
|
|
|
Author: Gregory M. Hoge"
|
|
|
|
DESCRIPTION
|
|
"The MIB module used to register Liebert SNMP OIDs.
|
|
|
|
Copyright 2000-2008,2013 Liebert Corporation. All rights reserved.
|
|
Reproduction of this document is authorized on the condition
|
|
that the forgoing copyright notice is included.
|
|
|
|
This Specification is supplied 'AS IS' and Liebert Corporation
|
|
makes no warranty, either express or implied, as to the use,
|
|
operation, condition, or performance of the Specification."
|
|
|
|
REVISION "201302120000Z"
|
|
DESCRIPTION
|
|
"Added Surge Protection Device to lgpConditionCondenserTVSSFailure
|
|
DESCRIPTION"
|
|
|
|
REVISION "200811170000Z"
|
|
DESCRIPTION
|
|
"Added support for NXL unit."
|
|
|
|
REVISION "200807020000Z"
|
|
DESCRIPTION
|
|
"o Expanded condtions table with new columns with a set of richer
|
|
alarm/condition properties.
|
|
o Added additional reference columns to conditions table to allow the
|
|
same alarm to be active on multiple instances of an item.
|
|
"
|
|
|
|
REVISION "200801100000Z"
|
|
DESCRIPTION
|
|
"Modified contact email address and added lgpNetworkName object."
|
|
|
|
REVISION "200705290000Z"
|
|
DESCRIPTION
|
|
"Added support for XDF Unit."
|
|
|
|
REVISION "200608150000Z"
|
|
DESCRIPTION
|
|
"Added support for HP release and a condition for firmware corrupt."
|
|
|
|
REVISION "200602220000Z"
|
|
DESCRIPTION
|
|
"Added support for Liebert DS Unit."
|
|
|
|
::= { liebertConditionsModuleReg 1 }
|
|
|
|
-- =============================================================================
|
|
-- lgpConditions - Liebert Conditions Registrations
|
|
-- =============================================================================
|
|
|
|
lgpConditionsWellKnown OBJECT IDENTIFIER
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Liebert well known conditions are defined by OIDs that reside
|
|
-- in this sub-tree."
|
|
::= { lgpConditions 1 }
|
|
|
|
lgpConditionsPresent OBJECT-TYPE
|
|
SYNTAX Gauge32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The present number of conditions (rows) in the lgpConditionsTable."
|
|
::= { lgpConditions 2 }
|
|
|
|
lgpConditionsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpConditionEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of condition table entries. The table contains zero, one,
|
|
or many rows at any moment, depending upon the number of conditions
|
|
in effect. The number of rows in the table is given by
|
|
(lgpConditionsPresent). The table is initially empty at agent startup.
|
|
The agent creates a row in the table each time a condition is detected
|
|
and deletes that row subject to the following rules:
|
|
|
|
Rows are removed from the table based on the following rules:
|
|
1. If a condition does not require acknowledgement
|
|
(see 'lgpConditionAckReq') the condition is removed as soon as
|
|
the issue clears (see 'lgpConditionCurrentState').
|
|
2. If a condition requires acknowledgement (see 'lgpConditionAckReq')
|
|
the condition is removed as soon as the issue clears
|
|
(see 'lgpConditionCurrentState') AND the condition is acknowledged
|
|
(see 'lgpConditionAcknowledged').
|
|
3. If the columns 'lgpConditionCurrentState' and
|
|
'lgpConditionAcknowledged' are not present for the condition
|
|
then the condition will be removed as soon as the issue causing
|
|
the condition clears.
|
|
|
|
The agent creates the first row with lgpConditionId equal to 1,
|
|
and increments the value of 'lgpConditionId' each time a new row is
|
|
created, wrapping to the first free value greater than or equal to 1
|
|
when the maximum value of lgpConditionId would otherwise be exceeded.
|
|
The number of rows in the table at any given time is reflected by
|
|
the value of 'lgpConditionsPresent'.
|
|
"
|
|
::= { lgpConditions 3 }
|
|
|
|
lgpConditionEntry OBJECT-TYPE
|
|
SYNTAX LgpConditionEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the rows for the table
|
|
'lgpConditionsTable'. A row in this table cannot be created
|
|
or deleted by SNMP operations on columns of the table."
|
|
INDEX { lgpConditionId }
|
|
::= { lgpConditionsTable 1 }
|
|
|
|
LgpConditionEntry ::= SEQUENCE {
|
|
lgpConditionId Unsigned32,
|
|
lgpConditionDescr OBJECT IDENTIFIER,
|
|
lgpConditionTime TimeTicks,
|
|
lgpConditionTableRef OBJECT IDENTIFIER,
|
|
lgpConditionTableRowRef OBJECT IDENTIFIER,
|
|
lgpConditionType INTEGER,
|
|
lgpConditionCurrentState INTEGER,
|
|
lgpConditionSeverity INTEGER,
|
|
|
|
lgpConditionAcknowledged INTEGER,
|
|
lgpConditionAckReq INTEGER
|
|
}
|
|
|
|
lgpConditionId OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique identifier for a condition. This value must remain
|
|
constant between agent initializations. This OID is used as
|
|
an index to identify a row in the table 'lgpConditionsTable'."
|
|
::= { lgpConditionEntry 1 }
|
|
|
|
lgpConditionDescr OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to a condition description object. The object
|
|
referenced should not be accessible, but rather be used to provide
|
|
a unique description."
|
|
::= { lgpConditionEntry 2 }
|
|
|
|
lgpConditionTime OBJECT-TYPE
|
|
SYNTAX TimeTicks
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value of sysUpTime when the condition occurred (became active)."
|
|
::= { lgpConditionEntry 3 }
|
|
|
|
lgpConditionTableRef OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This object will be included as a varbind in some
|
|
rows of the table. It is a reference to a table object in
|
|
the MIB. The value of this object will be the OID of a table
|
|
that the object that the condition applies to is defined.
|
|
The table row corresponding to this object will also contain
|
|
a varbind 'lgpConditionTableRowRef' that will specify which
|
|
instance (row) in the referenced table the object is defined in.
|
|
|
|
Example:
|
|
TABLE ROW:
|
|
lgpConditionId 5
|
|
lgpConditionDescr lgpConditionRcpBranchBreakerOpen
|
|
lgpConditionTime 393884848
|
|
lgpConditionTableRef lgpPduRbTable
|
|
lgpConditionTableRowRef lgpPduRbEntryId.1.4
|
|
lgpConditionType alarm
|
|
lgpConditionCurrentState active
|
|
lgpConditionSeverity major
|
|
lgpConditionAcknowledged acknowledged
|
|
lgpConditionAckReq required
|
|
|
|
In the above example the breaker opened for a Receptacle branch.
|
|
The specific receptacle branch is specified by the additional
|
|
varbind (lgpEventParmTableRowRef). In this case the notification
|
|
is for the 4th receptacle branch on the 1st PDU in the cluster.
|
|
"
|
|
::= { lgpConditionEntry 5 }
|
|
|
|
lgpConditionTableRowRef OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a reference to the (cell) in the table specified by the
|
|
companion varbind (lgpConditionTableRef) in this condition.
|
|
The row in the table where this cell exists represents the object
|
|
that this condition applies to.
|
|
|
|
Example:
|
|
TABLE ROW:
|
|
lgpConditionId 5
|
|
lgpConditionDescr lgpConditionRcpBranchBreakerOpen
|
|
lgpConditionTime 393884848
|
|
lgpConditionTableRef lgpPduRbTable
|
|
lgpConditionTableRowRef lgpPduRbEntryId.1.4
|
|
lgpConditionType
|
|
lgpConditionCurrentState active
|
|
lgpConditionSeverity major
|
|
lgpConditionAcknowledged acknowledged
|
|
lgpConditionAckReq required
|
|
|
|
The table containing the definition of the receptacle branch
|
|
(lgpPduRbTable) is given by the varbind (lgpConditionTableRef)
|
|
|
|
The specific receptacle branch (instance) is specified by the
|
|
varbind (lgpConditionTableRowRef). In this case the condition
|
|
is for the 4th receptacle branch on the 1st PDU in the PDU cluster.
|
|
|
|
If one wanted to retrieve the serial number for this
|
|
receptacle branch the OID would be: lgpPduRbEntrySerialNum.1.4.
|
|
"
|
|
::= { lgpConditionEntry 6 }
|
|
|
|
lgpConditionType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
message(2),
|
|
warning(4),
|
|
alarm(6),
|
|
fault(8)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The type of condition in this row in the table."
|
|
::= { lgpConditionEntry 10 }
|
|
|
|
lgpConditionCurrentState OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
active(1),
|
|
inactive(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Indication of the current state of the event. If the state
|
|
is 'active' then the condition currently exists. If the
|
|
state is 'inactive' then the condition no longer exists (i.e.
|
|
the situation causing the condition has cleared or been
|
|
resolved). The behavior of some devices is to remove
|
|
the condition from this table when the condition clears.
|
|
The behavior of other devices is to leave the condition
|
|
entry in the table until the condition is acknowledged (
|
|
see lgpConditionAcknowledged and lgpConditionAckReq)."
|
|
::= { lgpConditionEntry 12 }
|
|
|
|
lgpConditionSeverity OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-applicable(0),
|
|
minor(3),
|
|
major(6),
|
|
critical(9)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This represents the relative severity of the condition."
|
|
::= { lgpConditionEntry 14 }
|
|
|
|
lgpConditionAcknowledged OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
notAcknowledged(1),
|
|
acknowledged(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This indicates if the condition has been acknowledged.
|
|
If the value is 'notAcknowledged' then the condition has
|
|
not been acknowledged. If the value is 'acknowledged'
|
|
then the condition has been acknowledged. Writing a value
|
|
of 'acknowledged' to this object acknowledges the condition
|
|
and the value will be changed to 'acknowledged'.
|
|
|
|
If the current state of the condition is 'active'
|
|
(see lgpConditionCurrentState) the condition will, for all
|
|
devices remain in the table regardless of the state of the
|
|
'lgpConditionAcknowledged' object.
|
|
|
|
If the 'lgpConditionAckReq' is 'notRequired' or this column
|
|
does not exist for the row then this object has no affect on
|
|
the duration the condition stays in the lgpConditionsTable.
|
|
|
|
If the 'lgpConditionAckReq' is 'required' then the condition
|
|
will remain in the condition table until both the
|
|
'lgpConditionCurrentState' is 'inactive' AND
|
|
'lgpConditionAcknowledged' is 'acknowledged'.
|
|
"
|
|
::= { lgpConditionEntry 18 }
|
|
|
|
lgpConditionAckReq OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
required(1),
|
|
notRequired(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This indicates if the corresponding condition does or does not
|
|
require user acknowledgement. Conditions that require
|
|
user acknowledgement will have a value of 'required'. Those
|
|
conditions that do not require user acknowledgement will have
|
|
a value of 'notRequired' or in some devices the column may
|
|
not be present at all.
|
|
|
|
If a condition requires acknowledgement it will remain in the
|
|
table until both the 'lgpConditionCurrentState' and
|
|
'lgpConditionAcknowledged' are 'inactive' and 'acknowledged'
|
|
respectively (see lgpConditionAcknowledged).
|
|
|
|
If a condition does not require acknowledgement it will
|
|
be removed from the table as soon as its
|
|
'lgpConditionCurrentState' is 'inactive'.
|
|
"
|
|
::= { lgpConditionEntry 19 }
|
|
|
|
-- =============================================================================
|
|
-- lgpConditionControl - Condition Control Group
|
|
-- =============================================================================
|
|
|
|
lgpConditionControl OBJECT IDENTIFIER
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Items under this sub-tree allow the user to control actions
|
|
-- associated with conditions."
|
|
::= { lgpConditions 4 }
|
|
|
|
lgpConditionControlEventReset OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
noAction(1),
|
|
resetAll(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event Reset Command. This command will reset all of the
|
|
device's events. On some units, when an event is activated, a
|
|
'set' field is also marked and maintained even when the event has
|
|
become inactive. The 'set' field is only cleared when the user
|
|
clears it and the event is no longer active. This item will clear
|
|
the 'set' field for all events that are not active."
|
|
::= { lgpConditionControl 1 }
|
|
|
|
lgpConditionControlEventAck OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
noAction(1),
|
|
ackAll(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Event Acknowledge Command. This command will acknowledge all of the
|
|
device's events."
|
|
::= { lgpConditionControl 2 }
|
|
|
|
lgpConditionControlTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF LgpConditionControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A list of condition control table entries. The table contains zero, one,
|
|
or many rows at any moment, depending upon the number of conditions that
|
|
are controllable by the unit. This table does not necessarily contain all
|
|
conditions supported by the unit. This table only contains conditions that
|
|
are end-user modifiable."
|
|
::= { lgpConditionControl 20 }
|
|
|
|
lgpConditionControlEntry OBJECT-TYPE
|
|
SYNTAX LgpConditionControlEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This entry defines the contents of the rows for the table
|
|
'lgpConditionControlTable'. A row in this table cannot be created
|
|
or deleted by user initiated SNMP operations on columns of the table."
|
|
INDEX { lgpConditionControlIndex }
|
|
::= { lgpConditionControlTable 1 }
|
|
|
|
LgpConditionControlEntry ::= SEQUENCE {
|
|
lgpConditionControlIndex Unsigned32,
|
|
lgpConditionControlDescr OBJECT IDENTIFIER,
|
|
lgpConditionControlEnableStatus INTEGER,
|
|
lgpConditionControlType INTEGER,
|
|
lgpConditionControlEnableCapability INTEGER
|
|
}
|
|
|
|
lgpConditionControlIndex OBJECT-TYPE
|
|
SYNTAX Unsigned32
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is the index indicating the nth element of the table."
|
|
::= { lgpConditionControlEntry 1 }
|
|
|
|
lgpConditionControlDescr OBJECT-TYPE
|
|
SYNTAX OBJECT IDENTIFIER
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reference to an Object Identifier (OID) representing a unique
|
|
condition. The referenced OID is used solely for identification
|
|
purposes.
|
|
|
|
The object identifier referenced here will be the same object
|
|
identifier referenced in the lgpConditionsTable (column:
|
|
lgpConditionDescr) when the condition is activated."
|
|
::= { lgpConditionControlEntry 2 }
|
|
|
|
lgpConditionControlEnableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
enabled(1),
|
|
disabled(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The value in this column determines if the device is currently
|
|
capable of generating this event. If the value is 'enabled' then
|
|
the event will be generated if the condition indicated by
|
|
lgpConditionControlDescr becomes active. If the value is
|
|
'disabled' the device will never generate the event. This value is
|
|
stored on the managed device.
|
|
Some devices do not allow write access to some entries in this
|
|
column. The 'lgpConditionControlEnableCapability' column indicates
|
|
whether this entry can be written."
|
|
::= { lgpConditionControlEntry 3 }
|
|
|
|
lgpConditionControlType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
message(2),
|
|
warning(4),
|
|
alarm(6),
|
|
fault(8)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The 'type' assigned or configured for this condition. The value
|
|
assigned to the condition here is displayed in the
|
|
lgpConditionsTable (column: lgpConditionType). For some units this
|
|
is user configurable. This value is stored on the managed device."
|
|
::= { lgpConditionControlEntry 4 }
|
|
|
|
lgpConditionControlEnableCapability OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
{
|
|
not-specified(0),
|
|
readonly(1),
|
|
readwrite(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Some devices do not allow write access to some entries in the
|
|
'lgpConditionControlEnableStatus' column. This column indicates
|
|
whether the 'lgpConditionControlEnableStatus' entry for this row
|
|
can be written."
|
|
::= { lgpConditionControlEntry 5 }
|
|
|
|
lgpConditionDescription OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The ASCII text description for the condition."
|
|
::= { lgpConditions 5 }
|
|
|
|
lgpNetworkName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (255))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The network name in a node.domain.com like format. This object is
|
|
intended to be used as a varbind object by other notifications that
|
|
have a context of a network address. As an example the
|
|
lgpAgentDnsLookupFailure trap which describes a network name that
|
|
is failing or has failed to be resolved from a Domain Name Service (DNS)
|
|
lookup.
|
|
|
|
Refer to RFC 952 for further information."
|
|
::= { lgpConditions 6 }
|
|
|
|
-- =============================================================================
|
|
-- lgpConditions - Additional Liebert Conditions Registrations
|
|
-- =============================================================================
|
|
|
|
lgpFlexConditions OBJECT IDENTIFIER
|
|
-- STATUS current
|
|
-- DESCRIPTION
|
|
-- "Liebert well known Flexible conditions are defined by OIDs that reside
|
|
-- in this sub-tree. These OIDs can be found in the
|
|
-- LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB which is located in the file
|
|
-- LIEBERT_GP_FLEXIBLE_COND.MIB."
|
|
::= { lgpConditions 7 }
|
|
|
|
-- =============================================================================
|
|
-- lgpConditionsWellKnown - Liebert "well-known" conditions
|
|
-- =============================================================================
|
|
|
|
lgpConditionHighTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold."
|
|
::= { lgpConditionsWellKnown 1 }
|
|
|
|
lgpConditionLowTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature is below the low temperature threshold."
|
|
::= { lgpConditionsWellKnown 2 }
|
|
|
|
lgpConditionHighHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity has exceeded the high humidity threshold."
|
|
::= { lgpConditionsWellKnown 3 }
|
|
|
|
lgpConditionLowHumidity OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity is below the low humidity threshold."
|
|
::= { lgpConditionsWellKnown 4 }
|
|
|
|
lgpConditionLossOfAirflow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of air flow."
|
|
::= { lgpConditionsWellKnown 5 }
|
|
|
|
lgpConditionLossOfAirflow1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of air flow at sensor 1."
|
|
::= { lgpConditionLossOfAirflow 1 }
|
|
|
|
lgpConditionLossOfAirflow2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of air flow at sensor 2."
|
|
::= { lgpConditionLossOfAirflow 2 }
|
|
|
|
lgpConditionLossOfAirflowBlower1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of air flow from blower 1."
|
|
::= { lgpConditionLossOfAirflow 3 }
|
|
|
|
lgpConditionLossOfAirflowAllBlowers OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No air flow through the unit due to failure of all blowers."
|
|
::= { lgpConditionLossOfAirflow 4 }
|
|
|
|
lgpConditionChangeFilter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a condition indicating the air filter
|
|
should be changed."
|
|
::= { lgpConditionsWellKnown 6 }
|
|
|
|
lgpConditionCompressorHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an excessive head pressure condition."
|
|
::= { lgpConditionsWellKnown 7 }
|
|
|
|
lgpConditionCompressor1HighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 1."
|
|
::= { lgpConditionCompressorHighHeadPressure 1 }
|
|
|
|
lgpConditionCompressor1AHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 1A."
|
|
::= { lgpConditionCompressor1HighHeadPressure 1 }
|
|
|
|
lgpConditionCompressor1BHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 1B."
|
|
::= { lgpConditionCompressor1HighHeadPressure 2 }
|
|
|
|
lgpConditionCompressor2HighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 2."
|
|
::= { lgpConditionCompressorHighHeadPressure 2 }
|
|
|
|
lgpConditionCompressor2AHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 2A."
|
|
::= { lgpConditionCompressor2HighHeadPressure 1 }
|
|
|
|
lgpConditionCompressor2BHighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 2B."
|
|
::= { lgpConditionCompressor2HighHeadPressure 2 }
|
|
|
|
lgpConditionCompressor3HighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 3."
|
|
::= { lgpConditionCompressorHighHeadPressure 3 }
|
|
|
|
lgpConditionCompressor4HighHeadPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected excessive head pressure in compressor 4."
|
|
::= { lgpConditionCompressorHighHeadPressure 4 }
|
|
|
|
lgpConditionCompressorOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a compressor overload condition."
|
|
::= { lgpConditionsWellKnown 8 }
|
|
|
|
lgpConditionCompressor1Overload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an overload condition on compressor 1."
|
|
::= { lgpConditionCompressorOverload 1 }
|
|
|
|
lgpConditionCompressor2Overload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an overload condition on compressor 2."
|
|
::= { lgpConditionCompressorOverload 2 }
|
|
|
|
lgpConditionCompressor3Overload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an overload condition on compressor 3."
|
|
::= { lgpConditionCompressorOverload 3 }
|
|
|
|
lgpConditionCompressor4Overload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an overload condition on compressor 4."
|
|
::= { lgpConditionCompressorOverload 4 }
|
|
|
|
lgpConditionCompressorShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A compressor has exceeded the maximum number of starts in a
|
|
minimum time period."
|
|
::= { lgpConditionsWellKnown 9 }
|
|
|
|
lgpConditionCompressor1ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 1.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressorShortCycle 1 }
|
|
|
|
lgpConditionCompressor1AShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 1A.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressor1ShortCycle 1 }
|
|
|
|
lgpConditionCompressor1BShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 1B.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressor1ShortCycle 2 }
|
|
|
|
lgpConditionCompressor2ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 2.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressorShortCycle 2 }
|
|
|
|
lgpConditionCompressor2AShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 2A.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressor2ShortCycle 1 }
|
|
|
|
lgpConditionCompressor2BShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 2B.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressor2ShortCycle 2 }
|
|
|
|
lgpConditionCompressor3ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 3.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressorShortCycle 3 }
|
|
|
|
lgpConditionCompressor4ShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycle event on compressor 4.
|
|
The compressor has exceeded the maximum number of starts for
|
|
specified amount of time."
|
|
::= { lgpConditionCompressorShortCycle 4 }
|
|
|
|
lgpConditionCompressorLowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure at a compressor inlet has dropped below the
|
|
minimum setting."
|
|
::= { lgpConditionsWellKnown 10 }
|
|
|
|
lgpConditionCompressor1LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure at compressor 1 inlet has dropped below the
|
|
minimum setting."
|
|
::= { lgpConditionCompressorLowSuctionPressure 1 }
|
|
|
|
lgpConditionCompressor2LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure at compressor 2 inlet has dropped below the
|
|
minimum setting."
|
|
::= { lgpConditionCompressorLowSuctionPressure 2 }
|
|
|
|
lgpConditionCompressor3LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure at compressor 3 inlet has dropped below the
|
|
minimum setting."
|
|
::= { lgpConditionCompressorLowSuctionPressure 3 }
|
|
|
|
lgpConditionCompressor4LowSuctionPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The pressure at compressor 4 inlet has dropped below the
|
|
minimum setting."
|
|
::= { lgpConditionCompressorLowSuctionPressure 4 }
|
|
|
|
lgpConditionMainFanOverLoad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a main fan overload condition."
|
|
::= { lgpConditionsWellKnown 11 }
|
|
|
|
lgpConditionManualOverride OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a manual override condition."
|
|
::= { lgpConditionsWellKnown 12 }
|
|
|
|
lgpConditionStandbyGlycoolPumpOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The standby Glycol or Glycool pump is activated."
|
|
::= { lgpConditionsWellKnown 13 }
|
|
|
|
lgpConditionWaterUnderFloor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Moisture has been detected under the floor."
|
|
::= { lgpConditionsWellKnown 14 }
|
|
|
|
lgpConditionHumidifierProblem OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a humidifier problem."
|
|
::= { lgpConditionsWellKnown 15 }
|
|
|
|
lgpConditionLowWaterInHumidifier OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low water condition in the humidifier
|
|
reservoir."
|
|
::= { lgpConditionsWellKnown 16 }
|
|
|
|
lgpConditionSmokeDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected smoke."
|
|
::= { lgpConditionsWellKnown 17 }
|
|
|
|
lgpConditionLowWaterFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low water flow rate condition."
|
|
::= { lgpConditionsWellKnown 18 }
|
|
|
|
lgpConditionLostPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has lost power before being switched off using the
|
|
controls. This condition is activated when power is restored."
|
|
::= { lgpConditionsWellKnown 19 }
|
|
|
|
lgpGeneralFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A fault condition has been detected that is not identified
|
|
in the well known list."
|
|
::= { lgpConditionsWellKnown 20 }
|
|
|
|
lgpConditionLocalAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a local, or customer, alarm condition."
|
|
::= { lgpConditionsWellKnown 21 }
|
|
|
|
lgpConditionLocalAlarm1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 1 is active."
|
|
::= { lgpConditionLocalAlarm 1 }
|
|
|
|
lgpConditionLocalAlarm2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 2 is active."
|
|
::= { lgpConditionLocalAlarm 2 }
|
|
|
|
lgpConditionLocalAlarm3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 3 is active."
|
|
::= { lgpConditionLocalAlarm 3 }
|
|
|
|
lgpConditionLocalAlarm4 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 4 is active."
|
|
::= { lgpConditionLocalAlarm 4 }
|
|
|
|
lgpConditionLocalAlarm5 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 5 is active."
|
|
::= { lgpConditionLocalAlarm 5 }
|
|
|
|
lgpConditionLocalAlarm6 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 6 is active."
|
|
::= { lgpConditionLocalAlarm 6 }
|
|
|
|
lgpConditionLocalAlarm7 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 7 is active."
|
|
::= { lgpConditionLocalAlarm 7 }
|
|
|
|
lgpConditionLocalAlarm8 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that customer alarm condition 8 is active."
|
|
::= { lgpConditionLocalAlarm 8 }
|
|
|
|
lgpConditionStandbyUnitOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the standby unit is operating."
|
|
::= { lgpConditionsWellKnown 22 }
|
|
|
|
lgpConditionCompressorLowPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a low head compressor condition."
|
|
::= { lgpConditionsWellKnown 23 }
|
|
|
|
lgpConditionCompressor1LowPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected low pressure in compressor 1."
|
|
::= { lgpConditionCompressorLowPressure 1 }
|
|
|
|
lgpConditionTandemCompressorCircuit1LowPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected low pressure in tandem compressor circuit 1."
|
|
::= { lgpConditionCompressor1LowPressure 1 }
|
|
|
|
lgpConditionCompressor2LowPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected low pressure in compressor 2."
|
|
::= { lgpConditionCompressorLowPressure 2 }
|
|
|
|
lgpConditionTandemCompressorCircuit2LowPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected low pressure in tandem compressor circuit 2."
|
|
::= { lgpConditionCompressor2LowPressure 1 }
|
|
|
|
lgpConditionCompressor3LowPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected low pressure in compressor 3."
|
|
::= { lgpConditionCompressorLowPressure 3 }
|
|
|
|
lgpConditionCompressor4LowPressure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected low pressure in compressor 4."
|
|
::= { lgpConditionCompressorLowPressure 4 }
|
|
|
|
lgpConditionHighWaterInPan OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high water condition in the condenser pan."
|
|
::= { lgpConditionsWellKnown 24 }
|
|
|
|
lgpConditionFaultySensor OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a faulty temperature/humidity sensor."
|
|
::= { lgpConditionsWellKnown 25 }
|
|
|
|
lgpConditionServiceCooling OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Cooling system requires scheduled maintenance."
|
|
::= { lgpConditionsWellKnown 26 }
|
|
|
|
lgpConditionServiceHumidifier OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Humidifier requires scheduled maintenance."
|
|
::= { lgpConditionsWellKnown 27 }
|
|
|
|
lgpConditionSystemControlBatteryLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Charge level of the system control's battery is below the
|
|
alarm set point."
|
|
::= { lgpConditionsWellKnown 28 }
|
|
|
|
lgpConditionGroundSystemFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a ground system fault."
|
|
::= { lgpConditionsWellKnown 29 }
|
|
|
|
lgpConditionGroundFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a ground failure."
|
|
::= { lgpConditionsWellKnown 30 }
|
|
|
|
lgpConditionSecurityBreach OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a security breach."
|
|
::= { lgpConditionsWellKnown 31 }
|
|
|
|
lgpConditionEmergencyShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an emergency shutdown condition. The System
|
|
is shutting down as a result of this emergency."
|
|
::= { lgpConditionsWellKnown 32 }
|
|
|
|
lgpConditionOnBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected the load is being powered by a bypass
|
|
source."
|
|
::= { lgpConditionsWellKnown 33 }
|
|
|
|
lgpConditionLoadOnBypass OBJECT-IDENTITY
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"The load is being powered by a bypass source."
|
|
::= { lgpConditionOnBypass 1 }
|
|
|
|
lgpConditionLoadOnMaintenceBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The load is being powered by a maintenance bypass source."
|
|
::= { lgpConditionOnBypass 2 }
|
|
|
|
lgpConditionParallelSysLoadOnBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parallel system has transferred to bypass."
|
|
::= { lgpConditionOnBypass 3 }
|
|
|
|
lgpConditionLoadOnBypassByImpact OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a load impact and has transferred the
|
|
load to the bypass source."
|
|
::= { lgpConditionOnBypass 4 }
|
|
|
|
lgpConditionLoadTransferedToBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has transferred to bypass. The load is being powered by
|
|
the bypass source."
|
|
::= { lgpConditionOnBypass 5 }
|
|
|
|
lgpConditionEmergencyTransferToBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has performed an emergency transfer to bypass."
|
|
::= { lgpConditionOnBypass 6 }
|
|
|
|
lgpConditionOutputToLoadVoltTHD OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The total harmonic distortion (THD) of the output voltage has exceeded a
|
|
pre-determined threshold for a device, or system, defined amount of
|
|
time."
|
|
::= { lgpConditionsWellKnown 34 }
|
|
|
|
lgpConditionLogicFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a control logic failure."
|
|
::= { lgpConditionsWellKnown 35 }
|
|
|
|
lgpConditionPowerSupplyFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system had detected a power supply fault condition."
|
|
::= { lgpConditionsWellKnown 36 }
|
|
|
|
lgpConditionPowerSupply1Fault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected power supply 1 is in a fault condition."
|
|
::= { lgpConditionPowerSupplyFault 1 }
|
|
|
|
lgpConditionPowerSupply2Fault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected power supply 2 is in a fault condition."
|
|
::= { lgpConditionPowerSupplyFault 2 }
|
|
|
|
lgpConditionPowerSupplyFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a power supply failure condition."
|
|
::= { lgpConditionsWellKnown 37 }
|
|
|
|
lgpConditionPowerSupply1Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected power supply 1 has failed."
|
|
::= { lgpConditionPowerSupplyFailure 1 }
|
|
|
|
lgpConditionPowerSupply2Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected power supply 2 has failed."
|
|
::= { lgpConditionPowerSupplyFailure 2 }
|
|
|
|
lgpConditionSource1PowerSupplyInputFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 1 Power supply input has failed."
|
|
::= { lgpConditionPowerSupplyFailure 3 }
|
|
|
|
lgpConditionSource2PowerSupplyInputFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 2 Power supply input has failed."
|
|
::= { lgpConditionPowerSupplyFailure 4 }
|
|
|
|
lgpConditionPowerSupplyLogicFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a power supply logic failure."
|
|
::= { lgpConditionPowerSupplyFailure 5 }
|
|
|
|
lgpConditionCompressorPowerSupplyFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the power supply to the compressors
|
|
has failed."
|
|
::= { lgpConditionPowerSupplyFailure 6 }
|
|
|
|
lgpConditionOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an over voltage condition."
|
|
::= { lgpConditionsWellKnown 38 }
|
|
|
|
lgpConditionSource1OverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage condition on source 1.
|
|
The voltage measurement has risen above a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverVoltage 1 }
|
|
|
|
lgpConditionSource2OverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage condition on source 2.
|
|
The voltage measurement has risen above a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverVoltage 2 }
|
|
|
|
lgpConditionOutputToLoadOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load is in an over-voltage
|
|
condition. The voltage for the load has risen above a
|
|
pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOverVoltage 3 }
|
|
|
|
lgpConditionInputOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an input over voltage condition. The
|
|
voltage measurement has risen above a pre-determined threshold for
|
|
a specified amount of time."
|
|
::= { lgpConditionOverVoltage 4 }
|
|
|
|
lgpConditionBypassOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage condition on the bypass.
|
|
The voltage measurement has risen above a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverVoltage 5 }
|
|
|
|
lgpConditionBypassOverVoltageFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage failure condition on the
|
|
bypass. The voltage measurement has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverVoltage 6 }
|
|
|
|
lgpConditionBatteryOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery over voltage condition."
|
|
::= { lgpConditionOverVoltage 7 }
|
|
|
|
lgpConditionDcBusOverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a DC Bus over voltage condition."
|
|
::= { lgpConditionOverVoltage 8 }
|
|
|
|
lgpConditionDcBus1OverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage condition on DC Bus
|
|
1."
|
|
::= { lgpConditionDcBusOverVoltage 1 }
|
|
|
|
lgpConditionDcBus2OverVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage condition on DC Bus
|
|
2."
|
|
::= { lgpConditionDcBusOverVoltage 2 }
|
|
|
|
lgpConditionDcBus1OverVoltageFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage failure condition
|
|
on DC Bus 1."
|
|
::= { lgpConditionDcBusOverVoltage 3 }
|
|
|
|
lgpConditionDcBus2OverVoltageFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over voltage failure condition
|
|
on DC Bus 2."
|
|
::= { lgpConditionDcBusOverVoltage 4 }
|
|
|
|
lgpConditionUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an under voltage condition."
|
|
::= { lgpConditionsWellKnown 39 }
|
|
|
|
lgpConditionSource1UnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage condition on source 1.
|
|
The voltage measurement has fallen below a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionUnderVoltage 1 }
|
|
|
|
lgpConditionSource2UnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage condition on source 2.
|
|
The voltage measurement has fallen below a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionUnderVoltage 2 }
|
|
|
|
lgpConditionOutputToLoadUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load is in an under-voltage
|
|
condition. The voltage for the load has fallen below a
|
|
pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionUnderVoltage 3 }
|
|
|
|
lgpConditionSource1UnderVoltageRMS OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage condition on source 1.
|
|
The voltage measurement has fallen below a pre-determined threshold
|
|
for a specified amount of time."
|
|
::= { lgpConditionUnderVoltage 4 }
|
|
|
|
lgpConditionSource2UnderVoltageRMS OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage condition on source 2.
|
|
The voltage measurement has fallen below a pre-determined threshold
|
|
for a specified amount of time."
|
|
::= { lgpConditionUnderVoltage 5 }
|
|
|
|
lgpConditionInputUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an input under voltage condition.
|
|
The voltage measurement has fallen below a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionUnderVoltage 6 }
|
|
|
|
lgpConditionBypassUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage condition on the bypass.
|
|
The voltage measurement has fallen below a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionUnderVoltage 7 }
|
|
|
|
lgpConditionBypassUnderVoltageFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage failure condition on the
|
|
bypass. The voltage measurement has fallen below a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionUnderVoltage 8 }
|
|
|
|
lgpConditionBatteryUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery under voltage condition."
|
|
::= { lgpConditionUnderVoltage 9 }
|
|
|
|
lgpConditionDcBusUnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a DC bus under voltage condition"
|
|
::= { lgpConditionUnderVoltage 10 }
|
|
|
|
lgpConditionDcBus1UnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage condition on DC Bus
|
|
1."
|
|
::= { lgpConditionDcBusUnderVoltage 1 }
|
|
|
|
lgpConditionDcBus2UnderVoltage OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage condition on DC Bus
|
|
2."
|
|
::= { lgpConditionDcBusUnderVoltage 2 }
|
|
|
|
lgpConditionDcBus1UnderVoltageFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage failure condition
|
|
on DC Bus 1."
|
|
::= { lgpConditionDcBusUnderVoltage 3 }
|
|
|
|
lgpConditionDcBus2UnderVoltageFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an under voltage failure condition
|
|
on DC Bus 2."
|
|
::= { lgpConditionDcBusUnderVoltage 4 }
|
|
|
|
lgpConditionOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an overload condition."
|
|
::= { lgpConditionsWellKnown 40 }
|
|
|
|
lgpConditionSource1Overload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an overload condition on source 1. The
|
|
power requirement for this source has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverload 1 }
|
|
|
|
lgpConditionSystemOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an overload condition."
|
|
::= { lgpConditionOverload 2 }
|
|
|
|
lgpConditionSource1PeakCurrentOverLoad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected source 1 in is experiencing a peak over load
|
|
condition. The current has risen above a pre-determined threshold for
|
|
a specified amount of time."
|
|
::= { lgpConditionOverload 3 }
|
|
|
|
lgpConditionSource2PeakCurrentOverLoad OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected source 2 in is experiencing a peak over load
|
|
condition. The current has risen above a pre-determined threshold for
|
|
a specified amount of time."
|
|
::= { lgpConditionOverload 4 }
|
|
|
|
lgpConditionOutputToLoadOverLimit OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system had detected that the output to the load has exceeded the
|
|
lgpPwrOutputToLoadUserOverloadLimit."
|
|
::= { lgpConditionOverload 5 }
|
|
|
|
lgpConditionOutputToLoadOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an output overload condition."
|
|
::= { lgpConditionOverload 6 }
|
|
|
|
lgpConditionParallelSysOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parallel system has detected an overload condition."
|
|
::= { lgpConditionOverload 7 }
|
|
|
|
lgpConditionBypassCurrentOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"With the load on bypass static switch, the measured output
|
|
RMS current has exceeded a specified percentage of the nominal
|
|
RMS current."
|
|
::= { lgpConditionOverload 8 }
|
|
|
|
lgpConditionBypassCurrentOverloadPhsA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"With the load on bypass static switch, the measured phase A output
|
|
RMS current has exceeded a specified percentage of the nominal
|
|
per-phase RMS current."
|
|
::= { lgpConditionBypassCurrentOverload 1 }
|
|
|
|
lgpConditionBypassCurrentOverloadPhsB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"With the load on bypass static switch, the measured phase B output
|
|
RMS current has exceeded a specified percentage of the nominal
|
|
per-phase RMS current."
|
|
::= { lgpConditionBypassCurrentOverload 2 }
|
|
|
|
lgpConditionBypassCurrentOverloadPhsC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"With the load on bypass static switch, the measured phase C output
|
|
RMS current has exceeded a specified percentage of the nominal
|
|
per-phase RMS current."
|
|
::= { lgpConditionBypassCurrentOverload 3 }
|
|
|
|
lgpConditionScrShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a Silicon Controlled Rectifier (SCR)
|
|
short condition."
|
|
::= { lgpConditionsWellKnown 41 }
|
|
|
|
lgpConditionSource1ScrShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 1 Silicon Controlled Rectifier
|
|
(SCR) short condition."
|
|
::= { lgpConditionScrShort 1 }
|
|
|
|
lgpConditionSource2ScrShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 2 Silicon Controlled Rectifier
|
|
(SCR) short condition."
|
|
::= { lgpConditionScrShort 2 }
|
|
|
|
lgpConditionBypassScrShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a Silicon Controlled Rectifier (SCR) short
|
|
condition on the bypass."
|
|
::= { lgpConditionScrShort 3 }
|
|
|
|
lgpConditionInvStaticSwScrShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short across one or more inverter static
|
|
switch Silicon Controlled Rectifiers (SCRs)."
|
|
::= { lgpConditionScrShort 4 }
|
|
|
|
lgpConditionSource1NeutralScrShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 1 Silicon Controlled Rectifier
|
|
(SCR) short condition on the neutral line."
|
|
::= { lgpConditionScrShort 5 }
|
|
|
|
lgpConditionSource2NeutralScrShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 2 Silicon Controlled Rectifier
|
|
(SCR) short condition on the neutral line."
|
|
::= { lgpConditionScrShort 6 }
|
|
|
|
lgpConditionScrOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a Silicon Controlled Rectifier (SCR)
|
|
open condition."
|
|
::= { lgpConditionsWellKnown 42 }
|
|
|
|
lgpConditionSource1ScrOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 1 Silicon Controlled Rectifier
|
|
(SCR) open condition."
|
|
::= { lgpConditionScrOpen 1 }
|
|
|
|
lgpConditionSource2ScrOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 2 Silicon Controlled Rectifier
|
|
(SCR) open condition."
|
|
::= { lgpConditionScrOpen 2 }
|
|
|
|
lgpConditionBypassScrOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a Silicon Controlled Rectifier (SCR) open
|
|
condition on the bypass."
|
|
::= { lgpConditionScrOpen 3 }
|
|
|
|
lgpConditionSource1NeutralScrOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 1 Silicon Controlled Rectifier
|
|
(SCR) open condition on the neutral line."
|
|
::= { lgpConditionScrOpen 4 }
|
|
|
|
lgpConditionSource2NeutralScrOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 2 Silicon Controlled Rectifier
|
|
(SCR) open condition on the neutral line."
|
|
::= { lgpConditionScrOpen 5 }
|
|
|
|
lgpConditionFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a fan failure condition."
|
|
::= { lgpConditionsWellKnown 43 }
|
|
|
|
lgpConditionFan1Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a fan 1 failure condition."
|
|
::= { lgpConditionFanFailure 1 }
|
|
|
|
lgpConditionRedundantFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A failure has occurred in a fan that cools the system's internal
|
|
components and has resulted in a loss of fan redundancy."
|
|
::= { lgpConditionFanFailure 2 }
|
|
|
|
lgpConditionMultipleFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Multiple fans have failed resulting in a decreased ability to cool
|
|
the system's internal components."
|
|
::= { lgpConditionFanFailure 3 }
|
|
|
|
lgpConditionBlowerFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a problem with one or more of the blower
|
|
fans. These are not the system internal cooling fans."
|
|
::= { lgpConditionFanFailure 4 }
|
|
|
|
lgpConditionBottomBlowerFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bottom environmental unit blower fan is not operating
|
|
within its normal parameters."
|
|
::= { lgpConditionBlowerFanFailure 1 }
|
|
|
|
lgpConditionTopBlowerFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The top environmental unit blower fan is not operating
|
|
within its normal parameters."
|
|
::= { lgpConditionBlowerFanFailure 2 }
|
|
|
|
lgpConditionCondenserFanVFDFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a problem with the Variable Frequency
|
|
Drive system for the condenser fan."
|
|
::= { lgpConditionFanFailure 5 }
|
|
|
|
lgpConditionFanPowerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a power failure on one or more fans."
|
|
::= { lgpConditionFanFailure 6 }
|
|
|
|
lgpConditionTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is preventing a transfer of the load to the alternate
|
|
source."
|
|
::= { lgpConditionsWellKnown 44 }
|
|
|
|
lgpConditionAutoReTransferPrimed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is capable to retransfer to the preferred source."
|
|
::= { lgpConditionsWellKnown 45 }
|
|
|
|
lgpConditionSourcesOutOfSync OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that the input sources are not within the
|
|
specified phase difference (synchronization window)."
|
|
::= { lgpConditionsWellKnown 46 }
|
|
|
|
lgpConditionSourceFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an input source failure condition."
|
|
::= { lgpConditionsWellKnown 47 }
|
|
|
|
lgpConditionSource1Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected source 1 has failed."
|
|
::= { lgpConditionSourceFailure 1 }
|
|
|
|
lgpConditionSource2Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected source 2 has failed."
|
|
::= { lgpConditionSourceFailure 2 }
|
|
|
|
lgpConditionAutoReTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is preventing a retransfer of the load back to the
|
|
preferred source."
|
|
::= { lgpConditionsWellKnown 48 }
|
|
|
|
lgpConditionAutoReTransferFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is failing to automatically retransfer the load back to the
|
|
preferred source."
|
|
::= { lgpConditionsWellKnown 49 }
|
|
|
|
lgpConditionFuseOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an open fuse condition."
|
|
::= { lgpConditionsWellKnown 50 }
|
|
|
|
lgpConditionControlFuse1Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a control power fuse 1 open condition."
|
|
::= { lgpConditionFuseOpen 1 }
|
|
|
|
lgpConditionControlFuse2Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a control power fuse 2 open condition."
|
|
::= { lgpConditionFuseOpen 2 }
|
|
|
|
lgpConditionRectifierFuseOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a rectifier fuse open condition."
|
|
::= { lgpConditionFuseOpen 3 }
|
|
|
|
lgpConditionInverterFuseOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter fuse open condition."
|
|
::= { lgpConditionFuseOpen 4 }
|
|
|
|
lgpConditionOutputToLoadFuseOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an output to load fuse open condition."
|
|
::= { lgpConditionFuseOpen 5 }
|
|
|
|
lgpConditionDcCapacitorFuseOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a DC capacitor fuse open condition."
|
|
::= { lgpConditionFuseOpen 6 }
|
|
|
|
lgpConditionDisconnect OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a disconnect condition."
|
|
::= { lgpConditionsWellKnown 51 }
|
|
|
|
lgpConditionSource1DisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 1 disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 1 }
|
|
|
|
lgpConditionSource2DisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 2 disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 2 }
|
|
|
|
lgpConditionSource1PduDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 1 PDU (Power Distribution Unit)
|
|
disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 3 }
|
|
|
|
lgpConditionSource2PduDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 2 PDU (Power Distribution Unit)
|
|
disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 4 }
|
|
|
|
lgpConditionOutputToLoadDisconnect1Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected Output to load disconnect 1 is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 5 }
|
|
|
|
lgpConditionOutputToLoadDisconnect2Open OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected Output to load disconnect 2 is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 6 }
|
|
|
|
lgpConditionSource1BypassDisconnectClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 1 bypass disconnect is closed.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 7 }
|
|
|
|
lgpConditionSource2BypassDisconnectClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the source 2 bypass disconnect is closed.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 8 }
|
|
|
|
lgpConditionOutputToLoadNeutralDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load neutral disconnect is
|
|
open. A disconnect is a device which disconnects a conductor of a
|
|
circuit from its supply (ex. circuit breaker, contactor, isolating
|
|
switch, disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 9 }
|
|
|
|
lgpConditionBatteryDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the battery disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a
|
|
circuit from its supply (ex. circuit breaker, contactor, isolating
|
|
switch, disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 10 }
|
|
|
|
lgpConditionBatteryDiscOpenCab01 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 1 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 1 }
|
|
|
|
lgpConditionBatteryDiscOpenCab02 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 2 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 2 }
|
|
|
|
lgpConditionBatteryDiscOpenCab03 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 3 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 3 }
|
|
|
|
lgpConditionBatteryDiscOpenCab04 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 4 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 4 }
|
|
|
|
lgpConditionBatteryDiscOpenCab05 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 5 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 5 }
|
|
|
|
lgpConditionBatteryDiscOpenCab06 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 6 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 6 }
|
|
|
|
lgpConditionBatteryDiscOpenCab07 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 7 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 7 }
|
|
|
|
lgpConditionBatteryDiscOpenCab08 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the cabinet 8 battery disconnect is
|
|
open."
|
|
::= { lgpConditionBatteryDisconnectOpen 8 }
|
|
|
|
lgpConditionInputDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the input disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a
|
|
circuit from its supply (ex. circuit breaker, contactor, isolating
|
|
switch, disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 11 }
|
|
|
|
lgpConditionOutputToLoadDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the Output to load disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 12 }
|
|
|
|
lgpConditionBypassDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the bypass disconnect is open. A
|
|
disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 13 }
|
|
|
|
lgpConditionStaticSwitchDisconnectOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the static switch disconnect is open.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnect 14 }
|
|
|
|
lgpConditionBreakerOpenFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A breaker in the system has failed to respond to an Open signal."
|
|
::= { lgpConditionDisconnect 15 }
|
|
|
|
lgpConditionBreakerCloseFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A breaker in the system has failed to respond to a Close signal."
|
|
::= { lgpConditionDisconnect 16 }
|
|
|
|
lgpConditionFrequencyDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a frequency deviation condition.
|
|
The frequency of a source is outside of the pre-determined thresholds
|
|
for a specified amount of time."
|
|
::= { lgpConditionsWellKnown 52 }
|
|
|
|
lgpConditionSource1FrequencyDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The frequency for source 1 has been outside of the pre-determined
|
|
thresholds for a specified period of time."
|
|
::= { lgpConditionFrequencyDeviation 1 }
|
|
|
|
lgpConditionSource2FrequencyDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The frequency for source 2 has been outside of the pre-determined
|
|
thresholds for a specified period of time."
|
|
::= { lgpConditionFrequencyDeviation 2 }
|
|
|
|
lgpConditionInputFrequencyDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The frequency for the input has been outside of the pre-determined
|
|
thresholds for a specified period of time."
|
|
::= { lgpConditionFrequencyDeviation 3 }
|
|
|
|
lgpConditionOutputToLoadFrequencyDeviation
|
|
OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The frequency for the output has been outside of the pre-determined
|
|
thresholds for a specified period of time."
|
|
::= { lgpConditionFrequencyDeviation 4 }
|
|
|
|
lgpConditionBypassFrequencyDeviation OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The frequency for the bypass input has been outside of the
|
|
pre-determined thresholds for a specified period of time."
|
|
::= { lgpConditionFrequencyDeviation 5 }
|
|
|
|
lgpConditionOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an over-current condition. The current of a
|
|
source has risen above a pre-determined threshold for a device,
|
|
or system, defined amount of time."
|
|
::= { lgpConditionsWellKnown 53 }
|
|
|
|
lgpConditionSource1OverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over current condition on source 1.
|
|
The current of a source has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverCurrent 1 }
|
|
|
|
lgpConditionSource2OverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over current condition on source 2.
|
|
The current of a source has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverCurrent 2 }
|
|
|
|
lgpConditionOutputToLoadOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load is in an over-current
|
|
condition. The current for the load has risen above a
|
|
pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOverCurrent 3 }
|
|
|
|
lgpConditionOutputToLoadOverCurrentPhsA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load on phase A is in an
|
|
over-current condition. The current on this phase has risen above
|
|
a pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOutputToLoadOverCurrent 1 }
|
|
|
|
lgpConditionOutputToLoadOverCurrentPhsB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load on phase B is in an
|
|
over-current condition. The current on this phase has risen above
|
|
a pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOutputToLoadOverCurrent 2 }
|
|
|
|
lgpConditionOutputToLoadOverCurrentPhsC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load on phase C is in an
|
|
over-current condition. The current on this phase has risen above
|
|
a pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOutputToLoadOverCurrent 3 }
|
|
|
|
lgpConditionGroundOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A ground source is experiencing an over-current condition. The
|
|
current for the ground line has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverCurrent 4 }
|
|
|
|
lgpConditionRectifierOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a rectifier over current condition.
|
|
The current for the rectifier has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverCurrent 5 }
|
|
|
|
lgpConditionInverterOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter over current condition.
|
|
The current for the inverter has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverCurrent 6 }
|
|
|
|
lgpConditionInverterOverCurrentPhsA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter over current condition on
|
|
phase A. The current for the this phase in the inverter has risen
|
|
above a pre-determined threshold for a device, or system, defined
|
|
amount of time."
|
|
::= { lgpConditionInverterOverCurrent 1 }
|
|
|
|
lgpConditionInverterOverCurrentPhsB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter over current condition on
|
|
phase B. The current for the this phase in the inverter has risen
|
|
above a pre-determined threshold for a device, or system, defined
|
|
amount of time."
|
|
::= { lgpConditionInverterOverCurrent 2 }
|
|
|
|
lgpConditionInverterOverCurrentPhsC OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter over current condition on
|
|
phase C. The current for the this phase in the inverter has risen
|
|
above a pre-determined threshold for a device, or system, defined
|
|
amount of time."
|
|
::= { lgpConditionInverterOverCurrent 3 }
|
|
|
|
lgpConditionBatteryConverterOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over current condition on the battery
|
|
converter. The current of the converter has risen above a
|
|
pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOverCurrent 7 }
|
|
|
|
lgpConditionBatteryBalancerOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery balancer over current condition.
|
|
The current at this point has risen above a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverCurrent 8 }
|
|
|
|
lgpConditionHumidifierOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over current condition on the
|
|
humidifier. The current of the humidifier has risen above
|
|
a pre-determined threshold for a defined amount of time."
|
|
::= { lgpConditionOverCurrent 9 }
|
|
|
|
lgpConditionInputOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"There is an over current condition on the system input power.
|
|
The input current has risen above a pre-determined threshold for
|
|
a pre-defined amount of time."
|
|
::= { lgpConditionOverCurrent 10 }
|
|
|
|
lgpConditionSource1NeutralOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over current condition on the neutral
|
|
line of source 1. The neutral current at source 1 has risen above
|
|
a pre-determined threshold for a pre-defined amount of time."
|
|
::= { lgpConditionOverCurrent 11 }
|
|
|
|
lgpConditionSource2NeutralOverCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over current condition on the neutral
|
|
line of source 2. The neutral current at source 2 has risen above
|
|
a pre-determined threshold for a pre-defined amount of time."
|
|
::= { lgpConditionOverCurrent 12 }
|
|
|
|
lgpConditionSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a sensor failure condition."
|
|
::= { lgpConditionsWellKnown 54 }
|
|
|
|
lgpConditionOutputToLoadVoltageSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system had detected an output to load voltage sensor failure."
|
|
::= { lgpConditionSensorFailure 1 }
|
|
|
|
lgpConditionSource1VoltageSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system had detected a source 1 voltage sensor failure."
|
|
::= { lgpConditionSensorFailure 2 }
|
|
|
|
lgpConditionSource2VoltageSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system had detected a source 2 voltage sensor failure."
|
|
::= { lgpConditionSensorFailure 3 }
|
|
|
|
lgpConditionSource1ScrSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system had detected a source 1 SCR (Silicon Controlled
|
|
Rectifier) sensor failure."
|
|
::= { lgpConditionSensorFailure 4 }
|
|
|
|
lgpConditionSource2ScrSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system had detected a source 2 SCR (Silicon Controlled
|
|
Rectifier) sensor failure."
|
|
::= { lgpConditionSensorFailure 5 }
|
|
|
|
lgpConditionSource1CurrentSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 1 current sensor failure."
|
|
::= { lgpConditionSensorFailure 6 }
|
|
|
|
lgpConditionSource2CurrentSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 2 current sensor failure."
|
|
::= { lgpConditionSensorFailure 7 }
|
|
|
|
lgpConditionRoomTempHumiditySensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a device temperature and humidity sensor
|
|
failure."
|
|
::= { lgpConditionSensorFailure 8 }
|
|
|
|
lgpConditionGlycolTempSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a glycol temperature sensor failure."
|
|
::= { lgpConditionSensorFailure 9 }
|
|
|
|
lgpConditionLocal1SensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a local 1 sensor failure."
|
|
::= { lgpConditionSensorFailure 10 }
|
|
|
|
lgpConditionCompressor1SensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a compressor 1 digital scroll sensor
|
|
failure condition."
|
|
::= { lgpConditionSensorFailure 11 }
|
|
|
|
lgpConditionCompressor2SensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a compressor 2 digital scroll sensor
|
|
failure condition."
|
|
::= { lgpConditionSensorFailure 12 }
|
|
|
|
lgpConditionSupplySensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a supply sensor failure."
|
|
::= { lgpConditionSensorFailure 13 }
|
|
|
|
lgpConditionCabinetTemperatureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a cabinet temperature sensor failure."
|
|
::= { lgpConditionSensorFailure 14 }
|
|
|
|
lgpConditionCabinetHumiditySensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a cabinet humidity sensor failure."
|
|
::= { lgpConditionSensorFailure 15 }
|
|
|
|
lgpConditionRoomTempSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a room temperature sensor failure."
|
|
::= { lgpConditionSensorFailure 16 }
|
|
|
|
lgpConditionBatteryTempSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery temperature sensor failure."
|
|
::= { lgpConditionSensorFailure 17 }
|
|
|
|
lgpConditionAirSensorAFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a failure with air sensor A. The sensor
|
|
may have been disconnected or the signal is out of range."
|
|
::= { lgpConditionSensorFailure 18 }
|
|
|
|
lgpConditionAirSensorBFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a failure with air sensor B. The sensor
|
|
may have been disconnected or the signal is out of range."
|
|
::= { lgpConditionSensorFailure 19 }
|
|
|
|
lgpConditionChilledWaterSupplySensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a failure with the chilled water supply
|
|
sensor. The sensor may have been disconnected or the signal is out
|
|
of range."
|
|
::= { lgpConditionSensorFailure 20 }
|
|
|
|
lgpConditionRefrigerantSupplySensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a failure with the refrigerant supply
|
|
sensor. The sensor may have been disconnected or the signal is out
|
|
of range."
|
|
::= { lgpConditionSensorFailure 21 }
|
|
|
|
lgpConditionFluidSupplySensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a failure with the fluid supply
|
|
sensor. The sensor may have been disconnected or the signal is out
|
|
of range."
|
|
::= { lgpConditionSensorFailure 22 }
|
|
|
|
lgpConditionCompressorLowPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that a compressor low pressure
|
|
transducer is disconnected or the signal is out of range."
|
|
::= { lgpConditionSensorFailure 23 }
|
|
|
|
lgpConditionCompressor1LowPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 1 low pressure
|
|
transducer is disconnected or the signal is out of range."
|
|
::= { lgpConditionCompressorLowPressureSensorFailure 1 }
|
|
|
|
lgpConditionRemoteSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that a remote sensor is disconnected
|
|
or the signal is out of range."
|
|
::= { lgpConditionSensorFailure 24 }
|
|
|
|
lgpConditionAirSupplyTempSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that the supply air temperature sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpConditionSensorFailure 25 }
|
|
|
|
lgpConditionAirReturnTempSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that the return air temperature sensor is
|
|
disconnected or the signal is out of range."
|
|
::= { lgpConditionSensorFailure 26 }
|
|
|
|
lgpConditionCompressorHighPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that a compressor high pressure
|
|
transducer is disconnected or the signal is out of range."
|
|
::= { lgpConditionSensorFailure 27 }
|
|
|
|
lgpConditionCompressor2HighPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 2 high pressure
|
|
transducer is disconnected or the signal is out of range."
|
|
::= { lgpConditionCompressorHighPressureSensorFailure 2 }
|
|
|
|
lgpConditionCompressor3HighPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 3 high pressure
|
|
transducer is disconnected or the signal is out of range."
|
|
::= { lgpConditionCompressorHighPressureSensorFailure 3 }
|
|
|
|
lgpConditionCompressor4HighPressureSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 4 high pressure
|
|
transducer is disconnected or the signal is out of range."
|
|
::= { lgpConditionCompressorHighPressureSensorFailure 4 }
|
|
|
|
|
|
lgpConditionInternalCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an internal communication failure condition."
|
|
::= { lgpConditionsWellKnown 55 }
|
|
|
|
lgpConditionExternalCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an external communication failure condition."
|
|
::= { lgpConditionsWellKnown 56 }
|
|
|
|
lgpConditionSourceGateDriveFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a source gate drive failure condition."
|
|
::= { lgpConditionsWellKnown 57 }
|
|
|
|
lgpConditionSource1GateDriveFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 1 gate drive failure."
|
|
::= { lgpConditionSourceGateDriveFailure 1 }
|
|
|
|
lgpConditionSource2GateDriveFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a source 2 gate drive failure."
|
|
::= { lgpConditionSourceGateDriveFailure 2 }
|
|
|
|
lgpConditionDisconnectFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a disconnect failure condition.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionsWellKnown 58 }
|
|
|
|
lgpConditionOutputToLoadNeutralDisconnectFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the output to load neutral disconnect has
|
|
failed.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnectFailure 1 }
|
|
|
|
lgpConditionSource1DisconnectShuntTripFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a shunt trip failure of a disconnecting device
|
|
on source 1.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnectFailure 2 }
|
|
|
|
lgpConditionSource2DisconnectShuntTripFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a shunt trip failure of a disconnecting device
|
|
on source 2.
|
|
A disconnect is a device which disconnects a conductor of a circuit
|
|
from its supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnectFailure 3 }
|
|
|
|
lgpConditionInverterDisconnectFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter disconnect failure. A disconnect
|
|
is a device which disconnects a conductor of a circuit from its
|
|
supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnectFailure 4 }
|
|
|
|
lgpConditionBatteryDisconnectFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery disconnect failure. A disconnect
|
|
is a device which disconnects a conductor of a circuit from its
|
|
supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnectFailure 5 }
|
|
|
|
lgpConditionRectifierDisconnectFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a rectifier disconnect failure. A disconnect
|
|
is a device which disconnects a conductor of a circuit from its
|
|
supply (ex. circuit breaker, contactor, isolating switch,
|
|
disconnecting switch, etc.)."
|
|
::= { lgpConditionDisconnectFailure 6 }
|
|
|
|
lgpConditionOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an over temperature condition."
|
|
::= { lgpConditionsWellKnown 59 }
|
|
|
|
lgpConditionHeatSink1OverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a heat sink 1 over temperature condition."
|
|
::= { lgpConditionOverTemperature 1 }
|
|
|
|
lgpConditionAmbient1OverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an ambient over temperature condition at
|
|
location 1."
|
|
::= { lgpConditionOverTemperature 2 }
|
|
|
|
lgpConditionSystemOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system or a component of the system has detected an over
|
|
temperature condition. The temperature measurement has risen
|
|
above a pre-determined threshold for a device, or system, defined
|
|
amount of time."
|
|
::= { lgpConditionOverTemperature 3 }
|
|
|
|
lgpConditionTransformerOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The transformer is experiencing an over temperature condition.
|
|
The transformer's temperature has exceeded a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverTemperature 4 }
|
|
|
|
lgpConditionBatteryOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is experiencing an over temperature condition.
|
|
The battery's temperature has exceeded a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverTemperature 5 }
|
|
|
|
lgpConditionRectifierOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a rectifier over temperature condition.
|
|
The rectifier's temperature has exceeded a pre-determined threshold
|
|
for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverTemperature 6 }
|
|
|
|
lgpConditionInverterOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter over temperature condition.
|
|
The inverter's temperature has exceeded a pre-determined
|
|
threshold for a device, or system, defined amount of time."
|
|
::= { lgpConditionOverTemperature 7 }
|
|
|
|
lgpConditionRectifierInductorOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a rectifier inductor over temperature
|
|
condition. The rectifier's inductor temperature has exceeded a
|
|
pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOverTemperature 8 }
|
|
|
|
lgpConditionInverterInductorOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter inductor over temperature
|
|
condition. The inverter's inductor temperature has exceeded a
|
|
pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOverTemperature 9 }
|
|
|
|
lgpConditionBatteryConverterOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery converter over temperature
|
|
condition. The battery converter's temperature has exceeded a
|
|
pre-determined threshold for a device, or system, defined amount
|
|
of time."
|
|
::= { lgpConditionOverTemperature 10 }
|
|
|
|
lgpConditionBatteryBalancerInductorOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery balancer Inductor over
|
|
temperature condition. The battery balancer Inductor's temperature
|
|
has exceeded a pre-determined threshold for a specified amount of
|
|
time."
|
|
::= { lgpConditionOverTemperature 11 }
|
|
|
|
lgpConditionChilledWaterOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a chilled water over temperature
|
|
condition."
|
|
::= { lgpConditionOverTemperature 12 }
|
|
|
|
lgpConditionElectricHeatersOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an electric heater over temperature
|
|
condition."
|
|
::= { lgpConditionOverTemperature 13 }
|
|
|
|
lgpConditionInletAirOverTemperature OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inlet air over temperature condition."
|
|
::= { lgpConditionOverTemperature 14 }
|
|
|
|
lgpConditionSystemOverTempWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system or a component of the system has detected an over
|
|
temperature condition. The temperature measurement has risen
|
|
above a normal operating range for a device, or system, defined
|
|
amount of time. The system is still operational but a threshold has
|
|
been exceeded."
|
|
::= { lgpConditionOverTemperature 15 }
|
|
|
|
lgpConditionHighTemperatureBattString OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high temperature on a battery string.
|
|
The temperature has exceeded a specified temperature threshold."
|
|
::= { lgpConditionOverTemperature 16 }
|
|
|
|
lgpConditionLoadOnAlternateSource OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that the load is being supplied by the
|
|
alternate source."
|
|
::= { lgpConditionsWellKnown 60 }
|
|
|
|
lgpConditionPhaseRotationError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a phase rotation error condition."
|
|
::= { lgpConditionsWellKnown 61 }
|
|
|
|
lgpConditionSource1PhaseRotationError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a phase rotation error on source 1."
|
|
::= { lgpConditionPhaseRotationError 1 }
|
|
|
|
lgpConditionSource2PhaseRotationError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a phase rotation error on source 2."
|
|
::= { lgpConditionPhaseRotationError 2 }
|
|
|
|
lgpConditionBypassPhaseRotationError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a phase rotation error on the bypass."
|
|
::= { lgpConditionPhaseRotationError 3 }
|
|
|
|
lgpConditionInputPhaseRotationError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a phase rotation error on the input."
|
|
::= { lgpConditionPhaseRotationError 4 }
|
|
|
|
lgpConditionControlModuleFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a control module failure condition."
|
|
::= { lgpConditionsWellKnown 62 }
|
|
|
|
lgpConditionControlModule1Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a control module 1 failure."
|
|
::= { lgpConditionControlModuleFailure 1 }
|
|
|
|
lgpConditionHistoryLogFull OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the history log is full."
|
|
::= { lgpConditionsWellKnown 63 }
|
|
|
|
lgpConditionConfigurationModified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the configuration has been modified."
|
|
::= { lgpConditionsWellKnown 64 }
|
|
|
|
lgpConditionPasswordModified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the password has been modified."
|
|
::= { lgpConditionsWellKnown 65 }
|
|
|
|
lgpConditionTimeModified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the time has been modified."
|
|
::= { lgpConditionsWellKnown 66 }
|
|
|
|
lgpConditionDateModified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the date has been modified."
|
|
::= { lgpConditionsWellKnown 67 }
|
|
|
|
lgpConditionEventLogCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the event log has been cleared."
|
|
::= { lgpConditionsWellKnown 68 }
|
|
|
|
lgpConditionHistoryLogCleared OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the history log has been cleared."
|
|
::= { lgpConditionsWellKnown 69 }
|
|
|
|
lgpConditionUtilityFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a utility failure."
|
|
::= { lgpConditionsWellKnown 70 }
|
|
|
|
lgpConditionBatteryTestInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is performing a battery test at this time."
|
|
::= { lgpConditionsWellKnown 71 }
|
|
|
|
lgpConditionLoadOnBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system load is being supported by the battery."
|
|
::= { lgpConditionsWellKnown 72 }
|
|
|
|
lgpConditionReplaceBattery OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the batteries are due to be replaced."
|
|
::= { lgpConditionsWellKnown 74 }
|
|
|
|
lgpConditionUpsShutdownPending OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is in a shutdown pending condition."
|
|
::= { lgpConditionsWellKnown 75 }
|
|
|
|
lgpConditionBatteryChargerFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the battery charger has failed."
|
|
::= { lgpConditionsWellKnown 76 }
|
|
|
|
lgpConditionBypassVoltageUnqualified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the bypass voltage is unqualified.
|
|
The voltage measurement is outside a pre-determined threshold range for
|
|
a specified amount of time."
|
|
::= { lgpConditionsWellKnown 77 }
|
|
|
|
lgpConditionCheckAirFilter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected it is time to check the air filter."
|
|
::= { lgpConditionsWellKnown 78 }
|
|
|
|
lgpConditionBrownOut OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a brown out condition."
|
|
::= { lgpConditionsWellKnown 79 }
|
|
|
|
lgpConditionMultipleTransferLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has locked out transfers to bypass. Too many transfers
|
|
have occurred over a specified amount of time."
|
|
::= { lgpConditionsWellKnown 80 }
|
|
|
|
lgpConditionBypassPhaseLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected one or more bypass phases are missing."
|
|
::= { lgpConditionsWellKnown 81 }
|
|
|
|
lgpConditionMaintenceBypassInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is preventing a transfer of the load to maintenance bypass."
|
|
::= { lgpConditionsWellKnown 82 }
|
|
|
|
lgpConditionLoadLockedOnBypass OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An error has been detected requiring the system to be put into a
|
|
'locked on bypass' state."
|
|
::= { lgpConditionsWellKnown 83 }
|
|
|
|
lgpConditionOutputToLoadShort OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an output to load short circuit condition."
|
|
::= { lgpConditionsWellKnown 84 }
|
|
|
|
lgpConditionEmergencyTransferToInverter OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an emergency transfer of the load to
|
|
inverter."
|
|
::= { lgpConditionsWellKnown 85 }
|
|
|
|
lgpConditonEmergencyPowerOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an Emergency Power Off (EPO) condition.
|
|
An external EPO switch has cut off the power source to the system."
|
|
::= { lgpConditionsWellKnown 86 }
|
|
|
|
lgpConditionInverterBackFeed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter back-feed condition. The inverter
|
|
is feeding power through the bypass back to the input."
|
|
::= { lgpConditionsWellKnown 87 }
|
|
|
|
lgpConditionDcGroundFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a DC ground fault."
|
|
::= { lgpConditionsWellKnown 88 }
|
|
|
|
lgpConditionDcGroundFaultPos OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ground fault current has been detected in the positive DC link to
|
|
ground."
|
|
::= { lgpConditionDcGroundFault 1 }
|
|
|
|
lgpConditionDcGroundFaultNeg OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Ground fault current has been detected in the negative DC link to
|
|
ground."
|
|
::= { lgpConditionDcGroundFault 2 }
|
|
|
|
lgpConditionStaticTransferSwitchInhibited
|
|
OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is preventing the use of the static transfer switch."
|
|
::= { lgpConditionsWellKnown 89 }
|
|
|
|
lgpConditionBatteryLogFullWarning
|
|
OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the battery log is approaching the maximum
|
|
record limit."
|
|
::= { lgpConditionsWellKnown 90 }
|
|
|
|
lgpConditionInputCurrentUnbalanced
|
|
OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an unbalanced input current condition.
|
|
The currents of input phases are out of tolerance."
|
|
::= { lgpConditionsWellKnown 91 }
|
|
|
|
lgpConditionSelfTestFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a self-test failure."
|
|
::= { lgpConditionsWellKnown 92 }
|
|
|
|
lgpConditionInverterOutOfSynchronization
|
|
OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an Inverter out of sync condition."
|
|
::= { lgpConditionsWellKnown 93 }
|
|
|
|
lgpConditionModuleAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected an alarm within the multi-module system."
|
|
::= { lgpConditionsWellKnown 94 }
|
|
|
|
lgpConditioniModuleUnit1Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 1."
|
|
::= { lgpConditionModuleAlarm 1 }
|
|
|
|
lgpConditioniModuleUnit2Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 2."
|
|
::= { lgpConditionModuleAlarm 2 }
|
|
|
|
lgpConditioniModuleUnit3Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 3."
|
|
::= { lgpConditionModuleAlarm 3 }
|
|
|
|
lgpConditioniModuleUnit4Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 4."
|
|
::= { lgpConditionModuleAlarm 4 }
|
|
|
|
lgpConditioniModuleUnit5Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 5."
|
|
::= { lgpConditionModuleAlarm 5 }
|
|
|
|
lgpConditioniModuleUnit6Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 6."
|
|
::= { lgpConditionModuleAlarm 6 }
|
|
|
|
lgpConditioniModuleUnit7Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 7."
|
|
::= { lgpConditionModuleAlarm 7 }
|
|
|
|
lgpConditioniModuleUnit8Alarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The multi-module system has detected an alarm condition on
|
|
unit 8."
|
|
::= { lgpConditionModuleAlarm 8 }
|
|
|
|
lgpConditionActiveModuleAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an active alarm in one, or more, of the
|
|
sub-modules of the multi-module system."
|
|
::= { lgpConditionsWellKnown 95 }
|
|
|
|
lgpConditionControlFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a control failure condition."
|
|
::= { lgpConditionsWellKnown 96 }
|
|
|
|
lgpConditionMainControlFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a main control failure condition."
|
|
::= { lgpConditionControlFailure 1 }
|
|
|
|
lgpConditionRedundantControlFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a redundant control failure condition."
|
|
::= { lgpConditionControlFailure 2 }
|
|
|
|
lgpConditionParallelSysControlFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parallel system has detected a control failure condition with
|
|
one of the controls."
|
|
::= { lgpConditionControlFailure 3 }
|
|
|
|
lgpConditionMainControlCommFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"One or more communications failures have occurred in the main
|
|
control."
|
|
::= { lgpConditionControlFailure 4 }
|
|
|
|
lgpConditionControlBoardFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a control board failure."
|
|
::= { lgpConditionControlFailure 5 }
|
|
|
|
lgpConditionHumidifierControlBdFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Humidifier control board is required to be connected,
|
|
but no signal is detected."
|
|
::= { lgpConditionControlBoardFailure 1 }
|
|
|
|
lgpConditionControlWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This system has detected a control warning conditions."
|
|
::= { lgpConditionsWellKnown 97 }
|
|
|
|
lgpConditionMainControlWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a main control warning condition."
|
|
::= { lgpConditionControlWarning 1 }
|
|
|
|
lgpConditionRedundantControlWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a redundant control warning condition."
|
|
::= { lgpConditionControlWarning 2 }
|
|
|
|
lgpConditionUserInterfaceFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a user interface control failure condition."
|
|
::= { lgpConditionsWellKnown 98 }
|
|
|
|
lgpConditionLostPowerRedundancy OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the number of redundant power modules has
|
|
fallen below the minimum redundant power module setting."
|
|
::= { lgpConditionsWellKnown 99 }
|
|
|
|
lgpConditionPowerModuleFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a power module failure condition in the
|
|
system."
|
|
::= { lgpConditionsWellKnown 100 }
|
|
|
|
lgpConditionBatteryModuleFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery module failure condition in the
|
|
system."
|
|
::= { lgpConditionsWellKnown 101 }
|
|
|
|
lgpConditionOutputToLoadOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that there is no power being supplied to the
|
|
load."
|
|
::= { lgpConditionsWellKnown 102 }
|
|
|
|
lgpConditionSystemOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is off."
|
|
::= { lgpConditionsWellKnown 103 }
|
|
|
|
lgpConditionRectifierStartupFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a rectifier under voltage start-up failure
|
|
condition."
|
|
::= { lgpConditionsWellKnown 104 }
|
|
|
|
lgpConditionRectifierFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a rectifier fault condition."
|
|
::= { lgpConditionsWellKnown 105 }
|
|
|
|
lgpConditionInverterShutdownLowDc OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has shutdown the inverter due to a DC bus under voltage."
|
|
::= { lgpConditionsWellKnown 106 }
|
|
|
|
lgpConditionInverterFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an inverter fault condition."
|
|
::= { lgpConditionsWellKnown 107 }
|
|
|
|
lgpConditionInverterDcOffsetOverrun OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an over run of the inverter DC offset
|
|
voltage."
|
|
::= { lgpConditionsWellKnown 108 }
|
|
|
|
lgpConditionParallelSysLowBatteryWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parallel system has detected a low battery warning condition."
|
|
::= { lgpConditionsWellKnown 109 }
|
|
|
|
lgpConditionParallelSysLoadShareFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parallel system has detected a load share fault condition."
|
|
::= { lgpConditionsWellKnown 110 }
|
|
|
|
lgpConditionBatteryFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery fault condition. The battery
|
|
conductors are either reversed or disconnected."
|
|
::= { lgpConditionsWellKnown 111 }
|
|
|
|
lgpConditionBatteryConverterFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery converter failure condition."
|
|
::= { lgpConditionsWellKnown 112 }
|
|
|
|
lgpConditionBatteryBalancerFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery balancer fault condition."
|
|
::= { lgpConditionsWellKnown 113 }
|
|
|
|
lgpConditionpsUpsOperationFault OBJECT-IDENTITY
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The system has detected an operation fault. The UPS attempted to
|
|
transfer to maintenance bypass without following the proper sequence."
|
|
::= { lgpConditionsWellKnown 114 }
|
|
|
|
lgpConditionOutputToLoadOnJointMode OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system load is being supported by both the battery and rectifier."
|
|
::= { lgpConditionsWellKnown 115 }
|
|
|
|
lgpConditionInputNeutralLost OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system had detected the main input neutral is disconnected."
|
|
::= { lgpConditionsWellKnown 116 }
|
|
|
|
lgpConditionLowBatteryWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery's remaining charge is less than or equal to the
|
|
configured low threshold."
|
|
::= { lgpConditionsWellKnown 117 }
|
|
|
|
lgpConditionInternalFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an internal fault."
|
|
::= { lgpConditionsWellKnown 118 }
|
|
|
|
lgpConditionBatteryTestFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a battery self-test failure."
|
|
::= { lgpConditionsWellKnown 119 }
|
|
|
|
lgpConditionPowerModuleWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an alarm condition on one, or more,
|
|
power modules."
|
|
::= { lgpConditionsWellKnown 120 }
|
|
|
|
lgpConditionBatteryModuleWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an alarm condition on one, or more,
|
|
battery modules."
|
|
::= { lgpConditionsWellKnown 121 }
|
|
|
|
lgpConditionControlModuleWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a control module warning."
|
|
::= { lgpConditionsWellKnown 122 }
|
|
|
|
lgpConditionUpsOperationFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an operation fault. The UPS attempted to
|
|
transfer to maintenance bypass without following the proper sequence."
|
|
::= { lgpConditionsWellKnown 123 }
|
|
|
|
lgpConditionActiveAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an alarm condition."
|
|
::= { lgpConditionsWellKnown 124 }
|
|
|
|
lgpConditionRectifierCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an internal communication failure
|
|
condition with the rectifier."
|
|
::= { lgpConditionsWellKnown 125 }
|
|
|
|
lgpConditionInverterCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an internal communication failure
|
|
condition with the inverter."
|
|
::= { lgpConditionsWellKnown 126 }
|
|
|
|
lgpConditionParallelSysConnectionFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parallel system has detected a connection fault.
|
|
One or more of the devices are not properly connected."
|
|
::= { lgpConditionsWellKnown 127 }
|
|
|
|
lgpConditionParallelSysCommunicationFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The parallel system has detected a communication failure."
|
|
::= { lgpConditionsWellKnown 128 }
|
|
|
|
lgpConditionLostBatteryRedundancy OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the number of redundant battery modules has
|
|
fallen below the configured redundant battery module threshold."
|
|
::= { lgpConditionsWellKnown 129 }
|
|
|
|
lgpConditionCompPumpDownFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that a compressor has failed to pump down."
|
|
::= { lgpConditionsWellKnown 130 }
|
|
|
|
lgpConditionComp1PumpDownFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 1 has failed to pump
|
|
down."
|
|
::= { lgpConditionCompPumpDownFailure 1 }
|
|
|
|
lgpConditionComp2PumpDownFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 2 has failed to pump
|
|
down."
|
|
::= { lgpConditionCompPumpDownFailure 2 }
|
|
|
|
lgpConditionComp3PumpDownFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 3 has failed to pump
|
|
down."
|
|
::= { lgpConditionCompPumpDownFailure 3 }
|
|
|
|
lgpConditionComp4PumpDownFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that compressor 4 has failed to pump
|
|
down."
|
|
::= { lgpConditionCompPumpDownFailure 4 }
|
|
|
|
lgpConditionChilledWaterLowWaterFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a chilled water low water flow condition."
|
|
::= { lgpConditionsWellKnown 131 }
|
|
|
|
lgpConditionChilledWaterLowWaterFlowCircuit2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a chilled water low water flow condition for circuit 2."
|
|
::= { lgpConditionChilledWaterLowWaterFlow 2 }
|
|
|
|
lgpConditionAirFilterClogged OBJECT-IDENTITY
|
|
STATUS deprecated
|
|
DESCRIPTION
|
|
"The system has detected a air filter clogged condition."
|
|
::= { lgpConditionsWellKnown 132 }
|
|
|
|
lgpConditionHumidifierFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a humidifier failure condition."
|
|
::= { lgpConditionsWellKnown 133 }
|
|
|
|
lgpConditionRunHoursExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a pre-determined run hours threshold has been
|
|
exceeded."
|
|
::= { lgpConditionsWellKnown 134 }
|
|
|
|
lgpConditionUnitRunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the system run hours has exceeded the
|
|
pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 1 }
|
|
|
|
lgpConditionComp1RunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the compressor 1 run hours has exceeded
|
|
the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 2 }
|
|
|
|
lgpConditionComp2RunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the compressor 2 run hours has exceeded
|
|
the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 3 }
|
|
|
|
lgpConditionFreeCoolRunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the free cooling run hours has exceeded
|
|
the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 4 }
|
|
|
|
lgpConditionElectricalHeater1RunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the electrical heater's run hours have
|
|
exceeded the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 5 }
|
|
|
|
lgpConditionElectricalHeater2RunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the electrical heater's run hours have
|
|
exceeded the pre-determined limit."
|
|
::= { lgpConditionRunHoursExceeded 6 }
|
|
|
|
lgpConditionElectricalHeater3RunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the electrical heater's run hours have
|
|
exceeded the pre-determined limit."
|
|
::= { lgpConditionRunHoursExceeded 7 }
|
|
|
|
lgpConditionHotWaterRunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the hot water run hours have exceeded
|
|
the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 8 }
|
|
|
|
lgpConditionHotGasRunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the hot gas run hours have exceeded the
|
|
pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 9 }
|
|
|
|
lgpConditionHumidifierRunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the humidifier run hours have exceeded
|
|
the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 10 }
|
|
|
|
lgpConditionDehumidiferRunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the dehumidifier run hours have exceeded
|
|
the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 11 }
|
|
|
|
lgpConditionFanRunHrsExceeded OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the unit blower fan run hours have
|
|
exceeded the pre-determined threshold."
|
|
::= { lgpConditionRunHoursExceeded 12 }
|
|
|
|
lgpConditionCommWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with another
|
|
module."
|
|
::= { lgpConditionsWellKnown 135 }
|
|
|
|
lgpConditionCommWarningUnit1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 1."
|
|
::= { lgpConditionCommWarning 1 }
|
|
|
|
lgpConditionCommWarningUnit2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 2."
|
|
::= { lgpConditionCommWarning 2 }
|
|
|
|
lgpConditionCommWarningUnit3 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 3."
|
|
::= { lgpConditionCommWarning 3 }
|
|
|
|
lgpConditionCommWarningUnit4 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 4."
|
|
::= { lgpConditionCommWarning 4 }
|
|
|
|
lgpConditionCommWarningUnit5 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 5."
|
|
::= { lgpConditionCommWarning 5 }
|
|
|
|
lgpConditionCommWarningUnit6 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 6."
|
|
::= { lgpConditionCommWarning 6 }
|
|
|
|
lgpConditionCommWarningUnit7 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 7."
|
|
::= { lgpConditionCommWarning 7 }
|
|
|
|
lgpConditionCommWarningUnit8 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 8."
|
|
::= { lgpConditionCommWarning 8 }
|
|
|
|
lgpConditionCommWarningUnit9 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 9."
|
|
::= { lgpConditionCommWarning 9 }
|
|
|
|
lgpConditionCommWarningUnit10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 10."
|
|
::= { lgpConditionCommWarning 10 }
|
|
|
|
lgpConditionCommWarningUnit11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 11."
|
|
::= { lgpConditionCommWarning 11 }
|
|
|
|
lgpConditionCommWarningUnit12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 12."
|
|
::= { lgpConditionCommWarning 12 }
|
|
|
|
lgpConditionCommWarningUnit13 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 13."
|
|
::= { lgpConditionCommWarning 13 }
|
|
|
|
lgpConditionCommWarningUnit14 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 14."
|
|
::= { lgpConditionCommWarning 14 }
|
|
|
|
lgpConditionCommWarningUnit15 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 15."
|
|
::= { lgpConditionCommWarning 15 }
|
|
|
|
lgpConditionCommWarningUnit16 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of communications with unit 16."
|
|
::= { lgpConditionCommWarning 16 }
|
|
|
|
lgpConditionUnitOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The unit is on."
|
|
::= { lgpConditionsWellKnown 136 }
|
|
|
|
lgpConditionUnitOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The unit is off."
|
|
::= { lgpConditionsWellKnown 137 }
|
|
|
|
lgpConditionSleepModeOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system sleep mode operation has been turned off."
|
|
::= { lgpConditionsWellKnown 138 }
|
|
|
|
lgpConditionPowerOn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system power is on."
|
|
::= { lgpConditionsWellKnown 139 }
|
|
|
|
lgpConditionSystemOnStanby OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is on standby."
|
|
::= { lgpConditionsWellKnown 140 }
|
|
|
|
lgpConditionPowerOff OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system power is off."
|
|
::= { lgpConditionsWellKnown 141 }
|
|
|
|
lgpConditionHighTemperatureGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high temperature condition. This group
|
|
contains various high temperature conditions."
|
|
::= { lgpConditionsWellKnown 142 }
|
|
|
|
lgpConditionHighTemperatureSensor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for sensor 1."
|
|
::= { lgpConditionHighTemperatureGroup 1 }
|
|
|
|
lgpConditionHighTemperatureDigitalScroll1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high temperature event on Digital
|
|
Scroll Compressor 1. The temperature has exceeded a specified
|
|
temperature threshold."
|
|
::= { lgpConditionHighTemperatureGroup 2 }
|
|
|
|
lgpConditionHighTemperatureDigitalScroll2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high temperature event on Digital
|
|
Scroll Compressor 2. The temperature has exceeded a specified
|
|
temperature threshold."
|
|
::= { lgpConditionHighTemperatureGroup 3 }
|
|
|
|
lgpConditionHighTemperatureUser1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for user configured temperature sensor 1."
|
|
::= { lgpConditionHighTemperatureGroup 4 }
|
|
|
|
lgpConditionHighTemperatureInternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high internal temperature condition.
|
|
The temperature has exceeded a specified temperature threshold."
|
|
::= { lgpConditionHighTemperatureGroup 5 }
|
|
|
|
lgpConditionHighTemperatureExternalAirSensorA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for external air sensor A."
|
|
::= { lgpConditionHighTemperatureGroup 6 }
|
|
|
|
lgpConditionHighTemperatureExternalAirSensorB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for external air sensor B."
|
|
::= { lgpConditionHighTemperatureGroup 7 }
|
|
|
|
lgpConditionHighTemperatureRefrigerantSupply OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for the refrigerant supply."
|
|
::= { lgpConditionHighTemperatureGroup 8 }
|
|
|
|
lgpConditionHighTemperatureFluidSupply OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for the fluid supply."
|
|
::= { lgpConditionHighTemperatureGroup 9 }
|
|
|
|
lgpConditionHighTemperatureSupplyAir OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for the supply air."
|
|
::= { lgpConditionHighTemperatureGroup 10 }
|
|
|
|
lgpConditionHighTemperatureReturnAir OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature has exceeded the high temperature threshold
|
|
for the return air."
|
|
::= { lgpConditionHighTemperatureGroup 11 }
|
|
|
|
lgpConditionLowTemperatureGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low temperature condition. This group
|
|
contains various low temperature conditions."
|
|
::= { lgpConditionsWellKnown 143 }
|
|
|
|
lgpConditionLowTemperatureSensor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature is below the low temperature threshold for
|
|
sensor 1."
|
|
::= { lgpConditionLowTemperatureGroup 1 }
|
|
|
|
lgpConditionLowTemperatureInternal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low internal temperature condition.
|
|
The temperature is below a specified temperature threshold."
|
|
::= { lgpConditionLowTemperatureGroup 2 }
|
|
|
|
lgpConditionLowTemperatureExternalAirSensorA OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature is below the low temperature threshold for
|
|
external air sensor A."
|
|
::= { lgpConditionLowTemperatureGroup 3 }
|
|
|
|
lgpConditionLowTemperatureExternalAirSensorB OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature is below the low temperature threshold for
|
|
external air sensor B."
|
|
::= { lgpConditionLowTemperatureGroup 4 }
|
|
|
|
lgpConditionLowTemperatureRefrigerantSupply OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature is below the low temperature threshold for
|
|
the refrigerant supply."
|
|
::= { lgpConditionLowTemperatureGroup 5 }
|
|
|
|
lgpConditionLowTemperatureFluidSupply OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature is below the low temperature threshold for
|
|
the fluid supply."
|
|
::= { lgpConditionLowTemperatureGroup 6 }
|
|
|
|
lgpConditionLowTemperatureSupplyAir OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature is below the low temperature threshold for
|
|
the supply air."
|
|
::= { lgpConditionLowTemperatureGroup 7 }
|
|
|
|
lgpConditionHighHumidityGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high humidity condition. This group
|
|
contains various high humidity conditions."
|
|
::= { lgpConditionsWellKnown 144 }
|
|
|
|
lgpConditionHighHumiditySensor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity has exceeded the high humidity threshold for
|
|
sensor 1."
|
|
::= { lgpConditionHighHumidityGroup 1 }
|
|
|
|
lgpConditionHighHumidityReturnAir OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity has exceeded the high humidity threshold for
|
|
the return air."
|
|
::= { lgpConditionHighHumidityGroup 2 }
|
|
|
|
lgpConditionLowHumidityGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low humidity condition. This group
|
|
contains various high humidity conditions."
|
|
::= { lgpConditionsWellKnown 145 }
|
|
|
|
lgpConditionLowHumiditySensor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity is below the low humidity threshold for sensor 1."
|
|
::= { lgpConditionLowHumidityGroup 1 }
|
|
|
|
lgpConditionLowHumidityReturnAir OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidity is below the low humidity threshold for the return
|
|
air."
|
|
::= { lgpConditionLowHumidityGroup 2 }
|
|
|
|
lgpConditionPeerNetworkNoMaster OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is unable to communicate with the master on the peer to
|
|
peer network."
|
|
::= { lgpConditionsWellKnown 146 }
|
|
|
|
lgpConditionNoOnOffPermissions OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system lacks the permissions to execute the on/off operation."
|
|
::= { lgpConditionsWellKnown 147 }
|
|
|
|
lgpConditionPeerNetworkFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a communication failure on the peer to
|
|
peer network."
|
|
::= { lgpConditionsWellKnown 148 }
|
|
|
|
lgpConditionUnitDisabled OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The unit is disabled."
|
|
::= { lgpConditionsWellKnown 149 }
|
|
|
|
lgpConditionUnitShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has shutdown."
|
|
::= { lgpConditionsWellKnown 150 }
|
|
|
|
lgpConditionPeerNetworkDiscovered OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has established communications on the peer to peer
|
|
network."
|
|
::= { lgpConditionsWellKnown 151 }
|
|
|
|
lgpConditionLossOfWaterFlow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of water flow condition."
|
|
::= { lgpConditionsWellKnown 152 }
|
|
|
|
lgpConditionCondensatePumpHighWater OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected high water in the condensate pump."
|
|
::= { lgpConditionsWellKnown 153 }
|
|
|
|
lgpConditionGeneralAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a general alarm condition."
|
|
::= { lgpConditionsWellKnown 154 }
|
|
|
|
lgpConditionProductSpecific OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a product specific condition. This condition
|
|
is not currently available via the agent card."
|
|
::= { lgpConditionsWellKnown 155 }
|
|
|
|
lgpConditionReheatLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has locked out the electrical reheat operation for a
|
|
specified amount of time."
|
|
::= { lgpConditionsWellKnown 156 }
|
|
|
|
lgpConditionHumidifierLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has locked out the humidifier operation for a
|
|
specified amount of time."
|
|
::= { lgpConditionsWellKnown 157 }
|
|
|
|
lgpConditionCompressorsLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has locked out compressor operation for a specified amount
|
|
of time."
|
|
::= { lgpConditionsWellKnown 158 }
|
|
|
|
lgpConditionCallService OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a condition that requires a service
|
|
representative be contacted."
|
|
::= { lgpConditionsWellKnown 159 }
|
|
|
|
lgpConditionLowMemoryGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains various low memory conditions."
|
|
::= { lgpConditionsWellKnown 160 }
|
|
|
|
lgpConditionLowMemory1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low memory condition. The control
|
|
board is low in memory resources."
|
|
::= { lgpConditionLowMemoryGroup 1 }
|
|
|
|
lgpConditionMemoryFailureGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains various memory device failure conditions."
|
|
::= { lgpConditionsWellKnown 161 }
|
|
|
|
lgpConditionMemory1Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a memory 1 module failure."
|
|
::= { lgpConditionMemoryFailureGroup 1 }
|
|
|
|
lgpConditionMemory2Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a memory 2 module failure."
|
|
::= { lgpConditionMemoryFailureGroup 2 }
|
|
|
|
lgpConditionUnitCodeErrorGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains various memory device failure conditions."
|
|
::= { lgpConditionsWellKnown 162 }
|
|
|
|
lgpConditionUnitCodeNotConfigured OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the unit code is not configured. The unit
|
|
code must be configured before system start-up."
|
|
::= { lgpConditionUnitCodeErrorGroup 1 }
|
|
|
|
lgpConditionUnitCode01OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 2 }
|
|
|
|
lgpConditionUnitCode02OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 3 }
|
|
|
|
lgpConditionUnitCode03OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 4 }
|
|
|
|
lgpConditionUnitCode04OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 5 }
|
|
|
|
lgpConditionUnitCode05OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 6 }
|
|
|
|
lgpConditionUnitCode06OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 7 }
|
|
|
|
lgpConditionUnitCode07OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 8 }
|
|
|
|
lgpConditionUnitCode08OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 9 }
|
|
|
|
lgpConditionUnitCode09OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 10 }
|
|
|
|
lgpConditionUnitCode10OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 11 }
|
|
|
|
lgpConditionUnitCode11OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 12 }
|
|
|
|
lgpConditionUnitCode12OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 13 }
|
|
|
|
lgpConditionUnitCode13OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 14 }
|
|
|
|
lgpConditionUnitCode14OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 15 }
|
|
|
|
lgpConditionUnitCode15OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 16 }
|
|
|
|
lgpConditionUnitCode16OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 17 }
|
|
|
|
lgpConditionUnitCode17OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 18 }
|
|
|
|
lgpConditionUnitCode18OutOfRange OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a unit code error. This digit of the unit
|
|
code value is out of range."
|
|
::= { lgpConditionUnitCodeErrorGroup 19 }
|
|
|
|
lgpConditionHighExternalDewPoint OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a high external dew point condition.
|
|
The room dew point has exceeded the specified threshold."
|
|
::= { lgpConditionsWellKnown 163 }
|
|
|
|
lgpConditionHcbDisconnected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the humidifier control board is disconnected
|
|
or not installed."
|
|
::= { lgpConditionsWellKnown 164 }
|
|
|
|
lgpConditionBmsResetTimerExpired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The BMS fan speed control reset counter has timed out."
|
|
::= { lgpConditionsWellKnown 165 }
|
|
|
|
lgpConditionAgentFirmwareCorrupt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The firmware update to the agent card has failed and the firmware is now
|
|
corrupt."
|
|
::= { lgpConditionsWellKnown 166 }
|
|
|
|
lgpConditionSystemAccessGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains various system access conditions. An examples is
|
|
an open access panel."
|
|
::= { lgpConditionsWellKnown 175 }
|
|
|
|
lgpConditionFrontAccessOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the front access panel/door is open."
|
|
::= { lgpConditionSystemAccessGroup 1 }
|
|
|
|
lgpConditionRearAccessOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the rear access panel/door is open."
|
|
::= { lgpConditionSystemAccessGroup 2 }
|
|
|
|
lgpConditionsDamperFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains various damper failure conditions."
|
|
::= { lgpConditionsWellKnown 176 }
|
|
|
|
lgpConditionEmergencyDamperFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an emergency damper failure. The damper is
|
|
in the wrong position."
|
|
::= { lgpConditionsDamperFailure 1 }
|
|
|
|
lgpConditionRemoteShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A remote shutdown occurred."
|
|
::= { lgpConditionsWellKnown 177 }
|
|
|
|
lgpConditionFireAlarm OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fire Alarm."
|
|
::= { lgpConditionsWellKnown 178 }
|
|
|
|
lgpConditionHeatersOverheated OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Heaters Overheated."
|
|
::= { lgpConditionsWellKnown 179 }
|
|
|
|
lgpConditionCondenserFailureGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains condenser failure conditions."
|
|
::= { lgpConditionsWellKnown 180 }
|
|
|
|
lgpConditionCondenser1Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser 1 Failure."
|
|
::= { lgpConditionCondenserFailureGroup 1 }
|
|
|
|
lgpConditionCondenser2Failure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser 2 Failure."
|
|
::= { lgpConditionCondenserFailureGroup 2 }
|
|
|
|
lgpConditionCondenserTVSSFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The condenser Transient Voltage Surge Suppressor or Surge
|
|
Protection Device has failed."
|
|
::= { lgpConditionCondenserFailureGroup 3 }
|
|
|
|
lgpConditionHumidifierCyclinderWorn OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected the humidifier cylinder is worn."
|
|
::= { lgpConditionsWellKnown 181 }
|
|
|
|
lgpConditionUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low current condition. The current of
|
|
one or more sources in the system has fallen below a threshold for
|
|
a specified amount of time. The threshold and time that triggered
|
|
this condition is system dependent."
|
|
::= { lgpConditionsWellKnown 182 }
|
|
|
|
lgpConditionHumidifierUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a low current condition on the
|
|
humidifier. The current of the humidifier has fallen below
|
|
a pre-determined threshold for a defined amount of time."
|
|
::= { lgpConditionUnderCurrent 1 }
|
|
|
|
lgpConditionInputUnderCurrent OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"There is a low current condition on the input power source. The
|
|
current of the input power source has fallen below a
|
|
pre-determined threshold for a defined amount of time."
|
|
::= { lgpConditionUnderCurrent 2 }
|
|
|
|
lgpConditionHeatRejectorGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains failure conditions for the heat rejection unit."
|
|
::= { lgpConditionsWellKnown 183 }
|
|
|
|
lgpConditionHeatRejectorFanFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The heat rejecter fan has failed."
|
|
::= { lgpConditionHeatRejectorGroup 1 }
|
|
|
|
lgpConditionHeatRejectorVoltageSuppressionFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The heat rejecter voltage suppression has failed and is no longer
|
|
able to protect the unit from power fluctuations."
|
|
::= { lgpConditionHeatRejectorGroup 2 }
|
|
|
|
lgpConditionFreeCoolLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The free cooling capability has been disabled."
|
|
::= { lgpConditionsWellKnown 184 }
|
|
|
|
lgpConditionWaterLeakSensorFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The sensor used to detect water leaks is not connected or has failed."
|
|
::= { lgpConditionsWellKnown 185 }
|
|
|
|
lgpConditionNoLoadDetectedWarning OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"There is no load detected on the output. This can be an indication
|
|
that the output is being powered by an external bypass source and has
|
|
inadvertently been left on external bypass. This warning is triggered
|
|
after a delay. The delay is specified by the object
|
|
'lgpPwrNoLoadWarningDelay'. The alarm is triggered when the output
|
|
current falls below a certain threshold specified by the object
|
|
'lgpPwrNoLoadWarningLimit'"
|
|
::= { lgpConditionsWellKnown 186 }
|
|
|
|
lgpConditionFirmwareGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Grouping level for firmware related conditions."
|
|
::= { lgpConditionsWellKnown 187 }
|
|
|
|
lgpConditionFirmwareUpdateRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The firmware on the system or one or more components of the
|
|
system must be updated. This typically indicates that one or more
|
|
components of the system contain corrupted firmware or the
|
|
firmware on one or more components are incompatible with one
|
|
another. When this condition is active the system may not be able
|
|
to function to its full capacity or may not be able to function at
|
|
all."
|
|
::= { lgpConditionFirmwareGroup 3 }
|
|
|
|
lgpConditionTestGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Objects in this group of conditions are related to testing or test
|
|
events. This object is never active."
|
|
::= { lgpConditionsWellKnown 188 }
|
|
|
|
lgpConditionTest01 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This is a 'test' condition. It is a generic test event that can
|
|
be utilized to evaluate system handling of events. Some products
|
|
will support the activation of this event upon user request so that
|
|
user management stations can execute end-to-end event handling
|
|
tests."
|
|
::= { lgpConditionTestGroup 5 }
|
|
|
|
lgpConditionReceptacleBranchGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Grouping level for receptacle branch conditions."
|
|
::= { lgpConditionsWellKnown 190 }
|
|
|
|
lgpConditionRcpBranchFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle branch module or control system has failed.
|
|
Service is required."
|
|
::= { lgpConditionReceptacleBranchGroup 5 }
|
|
|
|
lgpConditionRcpBranchBreakerOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The receptacle branch breaker is open."
|
|
::= { lgpConditionReceptacleBranchGroup 10 }
|
|
|
|
lgpConditionInputUnqualified OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input is not qualified to provide power to the system. This may
|
|
be due to system input over-voltage, system input under-voltage,
|
|
system input frequency out of range, or other similar issues."
|
|
::= { lgpConditionsWellKnown 192 }
|
|
|
|
lgpConditionBypassUnavailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This summary event is asserted when the bypass is not available.
|
|
Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass
|
|
Overvoltage, Bypass Undervoltage, Bypass Phase Rotation Error, or
|
|
other similar causes."
|
|
::= { lgpConditionsWellKnown 193 }
|
|
|
|
lgpConditionAutoTransferFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is failing to automatically transfer the load to the
|
|
alternate source."
|
|
::= { lgpConditionsWellKnown 194 }
|
|
|
|
lgpConditionSBSUnavailable OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Static Bypass Switch (SBS) Failure has been detected. Possible
|
|
causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier)
|
|
Shorted, SBS Overload Exceeded, Bypass Power Supply
|
|
Fail, Static Bypass Switch Fuse Failure, or other similar causes."
|
|
::= { lgpConditionsWellKnown 195 }
|
|
|
|
lgpConditionSBSOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"On at least one phase of the static bypass switch (SBS), the power
|
|
dissipation limit has been exceeded."
|
|
::= { lgpConditionsWellKnown 196 }
|
|
|
|
lgpConditionExcessPulseParallel OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has performed too many pulse parallel operations within
|
|
the specified time interval. A pulse parallel operation is a
|
|
momentary operation of the static bypass switch (SBS) in parallel with
|
|
the inverter."
|
|
::= { lgpConditionsWellKnown 197 }
|
|
|
|
lgpConditionRemoteBypassSwitchOffExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The static bypass switch is off due to the state of an external
|
|
signal."
|
|
::= { lgpConditionsWellKnown 198 }
|
|
|
|
lgpConditionManTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual transfer from inverter to bypass is inhibited. Bypass is not
|
|
qualified."
|
|
::= { lgpConditionsWellKnown 199 }
|
|
|
|
lgpConditionManReTransferInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Manual retransfer from bypass to inverter is inhibited."
|
|
::= { lgpConditionsWellKnown 200 }
|
|
|
|
lgpConditionBatteryChargeError OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery is not charging properly. Some reasons for this condition
|
|
include, but are not limited to: battery charger failure,
|
|
battery failure, etc."
|
|
::= { lgpConditionsWellKnown 201 }
|
|
|
|
lgpConditionBatteryAutoTestInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatic (scheduled) battery tests are inhibited."
|
|
::= { lgpConditionsWellKnown 202 }
|
|
|
|
lgpConditionBatteryChargeReducedExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A reduced battery charging algorithm is being used due to an external
|
|
signal."
|
|
::= { lgpConditionsWellKnown 203 }
|
|
|
|
lgpConditionBatteryCapacityLow OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The battery capacity is low. Some reasons for this condition include,
|
|
but are not limited to: a battery is offline, the battery age has
|
|
reduced its capabilities, etc."
|
|
::= { lgpConditionsWellKnown 204 }
|
|
|
|
lgpConditionBatteryTempImbalance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The temperature difference between two batteries in the system
|
|
exceeds the predefined threshold."
|
|
::= { lgpConditionsWellKnown 205 }
|
|
|
|
lgpConditionBatteryEqualize OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The rectifier output voltage has been increased to equalize the battery
|
|
voltage level."
|
|
::= { lgpConditionsWellKnown 206 }
|
|
|
|
lgpConditionBatteryChargeInhibitedExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery charging is inhibited due to an external inhibit signal."
|
|
::= { lgpConditionsWellKnown 207 }
|
|
|
|
lgpConditionServiceExtBatteryMonitorGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains battery monitor service conditions."
|
|
::= { lgpConditionsWellKnown 208 }
|
|
|
|
lgpConditionServiceExtBatteryMonitor1 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External battery monitor 1 indicates battery maintenance is
|
|
required."
|
|
::= { lgpConditionServiceExtBatteryMonitorGroup 1 }
|
|
|
|
lgpConditionServiceExtBatteryMonitor2 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"External battery monitor 2 indicates battery maintenance is
|
|
required."
|
|
::= { lgpConditionServiceExtBatteryMonitorGroup 2 }
|
|
|
|
lgpConditionBatteryGroundFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery system ground fault amperage exceeds the threshold."
|
|
::= { lgpConditionsWellKnown 209 }
|
|
|
|
lgpConditionBatteryLowShutdown OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"With the battery breaker closed, the battery voltage has dropped
|
|
below the calculated End-Of-Discharge (EOD) limit."
|
|
::= { lgpConditionsWellKnown 210 }
|
|
|
|
lgpConditionEmergencyPowerOffLocal OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an Emergency Power Off (EPO) condition.
|
|
The local EPO switch has cut off the power source to the system."
|
|
::= { lgpConditionsWellKnown 211 }
|
|
|
|
lgpConditionOutputLowPFLagging OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a lagging output power factor below the
|
|
threshold, resulting in reduced load capacity."
|
|
::= { lgpConditionsWellKnown 212 }
|
|
|
|
lgpConditionOutputLowPFLeading OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a leading output power factor below the
|
|
threshold, resulting in reduced load capacity."
|
|
::= { lgpConditionsWellKnown 213 }
|
|
|
|
lgpConditionOutputToLoadFault OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an output to load fault. This could be
|
|
caused by over or under voltage, or by over or under frequency."
|
|
::= { lgpConditionsWellKnown 214 }
|
|
|
|
lgpConditionInvRestartInhibitedExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Restart of the inverter is inhibited by an external signal."
|
|
::= { lgpConditionsWellKnown 215 }
|
|
|
|
lgpConditionInverterShutdownOverload OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has shutdown the inverter due to a sustained overload.
|
|
This event does not indicate if the load has been dropped or
|
|
transferred to bypass. At least one phase of the inverter power
|
|
dissipation limit has been exceeded."
|
|
::= { lgpConditionsWellKnown 216 }
|
|
|
|
lgpConditionInverterOffExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The inverter is off due to the state of an external signal."
|
|
::= { lgpConditionsWellKnown 217 }
|
|
|
|
lgpConditionInputContactGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an active input contact."
|
|
::= { lgpConditionsWellKnown 218 }
|
|
|
|
lgpConditionInputContact01 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 1 is active."
|
|
::= { lgpConditionInputContactGroup 1 }
|
|
|
|
lgpConditionInputContact02 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 2 is active."
|
|
::= { lgpConditionInputContactGroup 2 }
|
|
|
|
lgpConditionInputContact03 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 3 is active."
|
|
::= { lgpConditionInputContactGroup 3 }
|
|
|
|
lgpConditionInputContact04 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 4 is active."
|
|
::= { lgpConditionInputContactGroup 4 }
|
|
|
|
lgpConditionInputContact05 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 5 is active."
|
|
::= { lgpConditionInputContactGroup 5 }
|
|
|
|
lgpConditionInputContact06 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 6 is active."
|
|
::= { lgpConditionInputContactGroup 6 }
|
|
|
|
lgpConditionInputContact07 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 7 is active."
|
|
::= { lgpConditionInputContactGroup 7 }
|
|
|
|
lgpConditionInputContact08 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 8 is active."
|
|
::= { lgpConditionInputContactGroup 8 }
|
|
|
|
lgpConditionInputContact09 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 9 is active."
|
|
::= { lgpConditionInputContactGroup 9 }
|
|
|
|
lgpConditionInputContact10 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 10 is active."
|
|
::= { lgpConditionInputContactGroup 10 }
|
|
|
|
lgpConditionInputContact11 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 11 is active."
|
|
::= { lgpConditionInputContactGroup 11 }
|
|
|
|
lgpConditionInputContact12 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 12 is active."
|
|
::= { lgpConditionInputContactGroup 12 }
|
|
|
|
lgpConditionInputContact13 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 13 is active."
|
|
::= { lgpConditionInputContactGroup 13 }
|
|
|
|
lgpConditionInputContact14 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 14 is active."
|
|
::= { lgpConditionInputContactGroup 14 }
|
|
|
|
lgpConditionInputContact15 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 15 is active."
|
|
::= { lgpConditionInputContactGroup 15 }
|
|
|
|
lgpConditionInputContact16 OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that input contact 16 is active."
|
|
::= { lgpConditionInputContactGroup 16 }
|
|
|
|
lgpConditionRectifierOperInhibited
|
|
OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The operation of the rectifier is inhibited by an external signal."
|
|
::= { lgpConditionsWellKnown 219 }
|
|
|
|
lgpConditionBypassBackFeedBrkrOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The bypass backfeed breaker is in the open position."
|
|
::= { lgpConditionsWellKnown 220 }
|
|
|
|
lgpConditionAutoRestartInProgress OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Auto restart is in progress. Becomes inactive when auto restart
|
|
completes or fails."
|
|
::= { lgpConditionsWellKnown 221 }
|
|
|
|
lgpConditionAutoRestartInhibitedExt OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Auto restart is inhibited due to an external signal."
|
|
::= { lgpConditionsWellKnown 222 }
|
|
|
|
lgpConditionAutoRestartFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Auto restart has failed."
|
|
::= { lgpConditionsWellKnown 223 }
|
|
|
|
lgpConditionInputOnGenerator OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A generator is supplying the power to the system."
|
|
::= { lgpConditionsWellKnown 224 }
|
|
|
|
lgpConditionInputFilterCycleLock OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The input filter disconnect has opened too many times within a given
|
|
period of time."
|
|
::= { lgpConditionsWellKnown 225 }
|
|
|
|
lgpConditionServiceCodeActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system is in an operational mode intended for testing. In normal
|
|
operating conditions, the system should not be in this state."
|
|
::= { lgpConditionsWellKnown 226 }
|
|
|
|
lgpConditionLoadBusSyncActive OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Load Bus Sync Operation is active. This synchronizes the UPS output
|
|
with the output of another UPS."
|
|
::= { lgpConditionsWellKnown 227 }
|
|
|
|
lgpConditionLoadBusSyncInhibited OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected that conditions to perform Load Bus Sync
|
|
Operation are not satisfied."
|
|
::= { lgpConditionsWellKnown 228 }
|
|
|
|
lgpConditionControlsResetRequired OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A controls reset is required because one or more critical settings
|
|
have changed."
|
|
::= { lgpConditionsWellKnown 229 }
|
|
|
|
lgpConditionEquipTempSensorFailed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature sensor is reporting a value outside the bounds of a
|
|
properly operating sensor."
|
|
::= { lgpConditionsWellKnown 230 }
|
|
|
|
lgpConditionInputCurrentImbalance OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The current on one input phase is much greater or lower than the
|
|
average current of all the phases. This may indicate improper operation
|
|
of the rectifier or input filter."
|
|
::= { lgpConditionsWellKnown 231 }
|
|
|
|
lgpConditionPumpGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an alarm with one of the pumps."
|
|
::= { lgpConditionsWellKnown 232 }
|
|
|
|
lgpConditionPumpFlowLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of flow with one or more pumps."
|
|
::= { lgpConditionPumpGroup 1 }
|
|
|
|
lgpConditionPump1FlowLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of flow with pump 1."
|
|
::= { lgpConditionPumpFlowLoss 1 }
|
|
|
|
lgpConditionPump2FlowLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a loss of flow with pump 2."
|
|
::= { lgpConditionPumpFlowLoss 2 }
|
|
|
|
lgpConditionPumpShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycling of the pumps. One or more
|
|
of the pumps has been turned on and off a number of times within a
|
|
specified time period."
|
|
::= { lgpConditionPumpGroup 2 }
|
|
|
|
lgpConditionPumpInverterShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycling of one or more pump
|
|
inverters and has temporarily locked out further pump operation
|
|
to protect from thermal overload. A short cycle is defined as
|
|
powering on and off a number of times over a set time period."
|
|
::= { lgpConditionPumpGroup 3 }
|
|
|
|
lgpConditionPump1InverterShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycling of the inverter for
|
|
pump 1 and has temporarily locked out further pump operation
|
|
to protect from thermal overload. A short cycle is defined as
|
|
powering on and off a number of times over a set time period."
|
|
::= { lgpConditionPumpInverterShortCycle 1 }
|
|
|
|
lgpConditionPump2InverterShortCycle OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a short cycling of the inverter for
|
|
pump 2 and has temporarily locked out further pump operation
|
|
to protect from thermal overload. A short cycle is defined as
|
|
powering on and off a number of times over a set time period."
|
|
::= { lgpConditionPumpInverterShortCycle 2 }
|
|
|
|
lgpConditionValveGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected an alarm with one of the valves."
|
|
::= { lgpConditionsWellKnown 233 }
|
|
|
|
lgpConditionChilledWaterValvePosition OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a problem with the chilled water valve
|
|
position. The position of the chilled water control valve does not
|
|
match an expected value."
|
|
::= { lgpConditionValveGroup 1 }
|
|
|
|
lgpConditionCondensationDetected OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected condensation."
|
|
::= { lgpConditionsWellKnown 234 }
|
|
|
|
lgpConditionMaintenanceGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a maintenance condition. This group
|
|
contains various maintenance conditions."
|
|
::= { lgpConditionsWellKnown 235 }
|
|
|
|
lgpConditionMaintenanceDue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System is due for maintenance."
|
|
::= { lgpConditionMaintenanceGroup 1 }
|
|
|
|
lgpConditionMaintenanceComplete OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system maintenance has been completed."
|
|
::= { lgpConditionMaintenanceGroup 2 }
|
|
|
|
lgpConditionExternalEventSignalGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains various conditions signalled by external inputs.
|
|
Each event is deactivated when the signal is inactive."
|
|
::= { lgpConditionsWellKnown 236 }
|
|
|
|
lgpConditionExternalFireDetect OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Fire detected, as indicated by an external input signal."
|
|
::= { lgpConditionExternalEventSignalGroup 1 }
|
|
|
|
lgpConditionExternalFlowLoss OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Loss of flow is detected, as indicated by an external input signal."
|
|
::= { lgpConditionExternalEventSignalGroup 2 }
|
|
|
|
lgpConditionExternalReheatLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The reheater is shut down and disabled by an external input signal."
|
|
::= { lgpConditionExternalEventSignalGroup 3 }
|
|
|
|
lgpConditionExternalOverTemp OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A temperature has exceeded its threshold, as indicated by an
|
|
external input signal."
|
|
::= { lgpConditionExternalEventSignalGroup 4 }
|
|
|
|
lgpConditionExternalCompLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The compressor is shut down and disabled by an external input signal."
|
|
::= { lgpConditionExternalEventSignalGroup 5 }
|
|
|
|
lgpConditionExternalHumidifierLockout OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The humidifier is shut down and disabled by an external input signal."
|
|
::= { lgpConditionExternalEventSignalGroup 6 }
|
|
|
|
lgpConditionComponentShutdownGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains conditions signaling shutdown of various system
|
|
components."
|
|
::= { lgpConditionsWellKnown 237 }
|
|
|
|
lgpConditionComponentShutdownPartial OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An event has occurred requiring some system components to be
|
|
shutdown and disabled."
|
|
::= { lgpConditionComponentShutdownGroup 1 }
|
|
|
|
lgpConditionComponentShutdownHighPower OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Supply to high power components has been shutdown."
|
|
::= { lgpConditionComponentShutdownGroup 2 }
|
|
|
|
lgpConditionCondenserProblemGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains condenser conditions."
|
|
::= { lgpConditionsWellKnown 238 }
|
|
|
|
lgpConditionCondenser1Problem OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Condenser 1 is not operating within its normal parameters."
|
|
::= { lgpConditionCondenserProblemGroup 1 }
|
|
|
|
lgpConditionHumidityOutOfPropBand OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The system has detected a humidity reading that remained outside of
|
|
the proportional control band for an extended period of time."
|
|
::= { lgpConditionsWellKnown 239 }
|
|
|
|
lgpConditionEnvRemoteSensorGroup OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This group contains remote sensors."
|
|
::= { lgpConditionsWellKnown 240 }
|
|
|
|
lgpConditionEnvRemoteSensor1Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 1 }
|
|
|
|
lgpConditionEnvRemoteSensor2Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 2 }
|
|
|
|
lgpConditionEnvRemoteSensor3Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 3 }
|
|
|
|
lgpConditionEnvRemoteSensor4Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 4 }
|
|
|
|
lgpConditionEnvRemoteSensor5Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 5 }
|
|
|
|
lgpConditionEnvRemoteSensor6Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 6 }
|
|
|
|
lgpConditionEnvRemoteSensor7Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 7 }
|
|
|
|
lgpConditionEnvRemoteSensor8Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 8 }
|
|
|
|
lgpConditionEnvRemoteSensor9Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 9 }
|
|
|
|
lgpConditionEnvRemoteSensor10Issue OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote sensor is disconnected or the signal is out of range. The
|
|
event is deactivated when sensor signal is re-established."
|
|
::= { lgpConditionEnvRemoteSensorGroup 10 }
|
|
|
|
lgpConditionNeutralSnubberBoardCommFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Neutral Snubber board has stopped communicating."
|
|
::= { lgpConditionsWellKnown 241 }
|
|
|
|
lgpConditionRedundantChargerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The redundant charger has failed."
|
|
::= { lgpConditionsWellKnown 242 }
|
|
|
|
lgpConditionBoardInputContactorPowerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Board input contactor power failure."
|
|
::= { lgpConditionsWellKnown 243 }
|
|
|
|
lgpConditionBoard1InputContactorPowerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Board1 input contactor power failure."
|
|
::= { lgpConditionBoardInputContactorPowerFailure 1 }
|
|
|
|
lgpConditionBoard2InputContactorPowerFailure OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Board2 input contactor power failure."
|
|
::= { lgpConditionBoardInputContactorPowerFailure 2 }
|
|
|
|
lgpConditionTooManySensors OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of sensors installed on the device has exceeded the
|
|
pre-determined limit."
|
|
::= { lgpConditionsWellKnown 5423 }
|
|
|
|
lgpConditionDoorSwitchOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An open door has been detected."
|
|
::= { lgpConditionsWellKnown 5471 }
|
|
|
|
lgpConditionContactClosureOpen OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"An open circuit has been detected."
|
|
::= { lgpConditionsWellKnown 5479 }
|
|
|
|
lgpConditionContactClosureClosed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A closed circuit has been detected."
|
|
::= { lgpConditionsWellKnown 5480 }
|
|
|
|
lgpConditionSensorsNotDisplayed OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of sensors that can be displayed (monitored) on the
|
|
device has exceeded the pre-determined limit. Note this condition
|
|
differs from the lgpConditionTooManySensors in that the system may
|
|
currently have less than the maximum of installed sensors present but
|
|
one or more of those sensors can not be displayed because the display
|
|
order table (lgpPduAuxMeasOrderTable) contains entries for sensors
|
|
that are not currently installed. This condition effectively
|
|
prevents one or more installed sensors from being presented in the
|
|
lgpPduAuxMeasTable. It is possible for both this condition and the
|
|
lgpConditionTooManySensors condition to be active at the same time."
|
|
::= { lgpConditionsWellKnown 6119 }
|
|
|
|
END
|
|
|