- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1132 lines
31 KiB
Text
1132 lines
31 KiB
Text
-- *****************************************************************************
|
|
-- FILE NAME : mca.mib
|
|
-- DATE : December 20, 2004
|
|
-- AUTHOR : Greg Saltis
|
|
-- PROJECT : Vortex Ethernet Card
|
|
-- PUBLIC :
|
|
-- PRIVATE :
|
|
-- COPYRIGHT : Copyright (C) 2004 by Emerson Network Power
|
|
-- ******************************************************************************
|
|
|
|
-- ******************************************************************************
|
|
-- MODIFICATION HISTORY
|
|
--
|
|
-- v1.0.0.0 09-06-04 grs New File.
|
|
-- v1.0.0.1 12-20-04 grs Add Modification history
|
|
-- Add
|
|
-- vecMCAInformation
|
|
-- vecMCAMessageRequests
|
|
-- vecMCAMessageTransmissions
|
|
-- vecMCAMessageTransmissions
|
|
-- vecMCAMessageBadCRCs
|
|
-- vecMCAMessageLinkErrors
|
|
-- vecMCAMessagePartialResponses
|
|
-- vecMCAMessageWrongPackets
|
|
-- v1.0.0.2 01-29-05 gp
|
|
-- Add
|
|
-- vecMCAMessageErrorReplies
|
|
-- Remove
|
|
-- vecAlarmLVDAlarm
|
|
-- vecAlarmPCUFailAlarm
|
|
-- vecAlarmAudibleAlarmsAreQuiet
|
|
-- vecAlarmACFail
|
|
-- vecAlarmPasswordHasBeenViewed
|
|
-- vecAlarmAudibleRelayDeEnergized
|
|
-- v1.0.0.3 07-05-05 gp
|
|
-- Add vecAnalogBatteryReserveHours
|
|
--
|
|
-- v2.0.0.3 07-12-05 gp
|
|
-- Add
|
|
-- vecAlarmBatteryPoorHealth
|
|
-- vecAlarmBatteryReserveLow
|
|
--
|
|
-- Grouped all battery related traps together.
|
|
--
|
|
-- v2.0.0.4 10-05-05 gp
|
|
-- Add versioning mechanism to MIB. Version information is
|
|
-- added to DEFINITIONS statement as follows:
|
|
-- VEC-MIBvX DEFINITIONS ::=
|
|
--
|
|
-- v3.0 10-31-05 gp
|
|
-- Add
|
|
-- vecHVSActive
|
|
-- vecRemoteHVSActive
|
|
-- vecRemoteEstopActive
|
|
--
|
|
-- v4.0 12-13-05 gp
|
|
-- Changed company name
|
|
-- Revamped to highlight power system information.
|
|
--
|
|
-- 12-15-05 gp
|
|
-- Corrected incorrect labeling for PCU Total current.
|
|
--
|
|
-- v5.0 12-16-05 gp
|
|
-- VEC no longer issues traps for the following MCA alarm conditions:
|
|
-- general LVD No Reply alarm
|
|
-- general LVD Board Fail alarm
|
|
-- general Temperature Sensor Hi or Lo alarm
|
|
-- general Temperature Sensor High alarm
|
|
-- general Temperature Sensor Low alarm
|
|
-- general Temperature Sensor No Reply alarm
|
|
-- general Shunt Type alarm
|
|
-- general Shunt No Reply alarm
|
|
--
|
|
-- v5.1 8-04-08 jws
|
|
-- Update IMPORTS
|
|
-- Added module identity
|
|
-- Removed SIZE clause
|
|
--
|
|
-- v5.4 9-22-08 jws
|
|
-- Changed trap object tables to NOTIFICATION-TYPE
|
|
--
|
|
-- v5.5 9-23-08 jws
|
|
-- Typo correction on psAlarmSysInfoString2
|
|
--
|
|
-- v5.6 10-01-08 gp
|
|
-- Corrected vecMIB OID. Replaced references to vec OID with vecMIB.
|
|
--
|
|
-- v5.7 02-11-11 gp
|
|
-- Add
|
|
-- psAlarm
|
|
-- psHighestSeverityLevel
|
|
-- psTemperatureAlarmStatus
|
|
-- psLVDCircuitAAlarmStatus
|
|
-- psLVDCircuitBAlarmStatus
|
|
-- psShuntAlarmStatus
|
|
--
|
|
--
|
|
-- v5.7 08-28-12 jws
|
|
-- Corrected Syntax error invalues of INTEGER
|
|
-- spaces removed
|
|
-- ******************************************************************************
|
|
|
|
VEC-MIBv5-9 DEFINITIONS ::=
|
|
BEGIN
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
|
|
Integer32, Counter32, enterprises
|
|
FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION, DisplayString, DateAndTime
|
|
FROM SNMPv2-TC;
|
|
|
|
vecMIB MODULE-IDENTITY
|
|
LAST-UPDATED "201401140823Z"
|
|
ORGANIZATION "
|
|
Emerson Energy Systems North America (ESNA)"
|
|
CONTACT-INFO "
|
|
Emerson Energy Systems North America
|
|
1510 Kansas Ave.
|
|
Lorain, OH 44052
|
|
USA "
|
|
DESCRIPTION "
|
|
Emerson Energy Systems North America(ESNA) VEC MIB. revision 5.9"
|
|
|
|
::= { enterprises 885 3 }
|
|
|
|
-- OBJECTS
|
|
emersonESNA OBJECT IDENTIFIER ::= { enterprises 885 }
|
|
|
|
vecInformation OBJECT IDENTIFIER ::= { vecMIB 1 }
|
|
vecMessageStats OBJECT IDENTIFIER ::= { vecInformation 2 }
|
|
psStatus OBJECT IDENTIFIER ::= { vecMIB 2 }
|
|
psMeasurement OBJECT IDENTIFIER ::= { psStatus 1 }
|
|
psTraps OBJECT IDENTIFIER ::= { vecMIB 3 }
|
|
psAlarmsGeneral1 OBJECT IDENTIFIER ::= { psTraps 1 }
|
|
psAlarmsGeneral2 OBJECT IDENTIFIER ::= { psTraps 2 }
|
|
psAlarmsBattery OBJECT IDENTIFIER ::= { psTraps 3 }
|
|
|
|
-- ENTRIES
|
|
|
|
vecFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"VEC System Firmware Version."
|
|
::= { vecInformation 1}
|
|
|
|
vecMessageRequests OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of message requests."
|
|
::= { vecMessageStats 1 }
|
|
|
|
vecMessageTransmissions OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of messages transmitted."
|
|
::= { vecMessageStats 2 }
|
|
|
|
vecMessageNoResponses OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of no responses."
|
|
::= { vecMessageStats 3 }
|
|
|
|
vecMessageBadCRCs OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of bad CRC checks."
|
|
::= { vecMessageStats 4 }
|
|
|
|
vecMessageLinkErrors OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of link errors."
|
|
::= { vecMessageStats 5 }
|
|
|
|
vecMessagePartialResponses OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of partial responses received."
|
|
::= { vecMessageStats 6 }
|
|
|
|
vecMessageWrongPackets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of wrong packet numbers detected."
|
|
::= { vecMessageStats 7 }
|
|
|
|
vecMessageErrorReplies OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of error responses received."
|
|
::= { vecMessageStats 8 }
|
|
|
|
psSystemVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Voltage."
|
|
::= { psMeasurement 1}
|
|
|
|
psSystemCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Current."
|
|
::= { psMeasurement 2}
|
|
|
|
psSubsystemVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sub System Voltage."
|
|
::= { psMeasurement 3}
|
|
|
|
psSubsystemCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sub System Current."
|
|
::= { psMeasurement 4}
|
|
|
|
psSenseVoltage OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sense Voltage."
|
|
::= { psMeasurement 5}
|
|
|
|
psPCUTotalCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total PCU Current."
|
|
::= { psMeasurement 6}
|
|
|
|
psBatteryCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total Battery Current."
|
|
::= { psMeasurement 7}
|
|
|
|
psBatteryReserveHours OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Reserve Time."
|
|
::= { psMeasurement 8}
|
|
|
|
psAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
false(0),
|
|
true(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A Power System Alarm Is Active."
|
|
::= { psMeasurement 9 }
|
|
|
|
psHighestSeverityLevel OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(0),
|
|
minor(1),
|
|
major(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The severity level is the highest active alarm level.
|
|
Values: 0 = Normal, 1 = Minor, 2 = Major"
|
|
::= { psMeasurement 10}
|
|
|
|
psNumberOfPCUsInstalled OBJECT-TYPE
|
|
SYNTAX Integer32(0..80)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of PCUs installed"
|
|
::= { psMeasurement 11}
|
|
|
|
psNumberOfPCUsCommunicating OBJECT-TYPE
|
|
SYNTAX Integer32(0..80)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of PCUs communicating"
|
|
::= { psMeasurement 12}
|
|
|
|
psTemperatureTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSTemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Measurement Table."
|
|
::= { psStatus 2 }
|
|
|
|
psTemperatureEntry OBJECT-TYPE
|
|
SYNTAX PSTemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Measurement Table Entry."
|
|
INDEX { psTemperatureIndex }
|
|
::= { psTemperatureTable 1 }
|
|
|
|
PSTemperatureEntry ::= SEQUENCE {
|
|
psTemperatureIndex Integer32,
|
|
psTemperatureMeasurement DisplayString,
|
|
psTemperatureAlarmStatus Integer32
|
|
}
|
|
|
|
psTemperatureIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..8)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Probe Number "
|
|
::= { psTemperatureEntry 1 }
|
|
|
|
psTemperatureMeasurement OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Value In Centigrade."
|
|
::= { psTemperatureEntry 2 }
|
|
|
|
psTemperatureAlarmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
high(0),
|
|
low(1),
|
|
noreply(2),
|
|
none(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Probe Alarm Status "
|
|
::= { psTemperatureEntry 3 }
|
|
|
|
psLVDTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSLVDEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low Voltage Disconnect Table."
|
|
::= { psStatus 3 }
|
|
|
|
psLVDEntry OBJECT-TYPE
|
|
SYNTAX PSLVDEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Low Voltage Disconnect Table Entry."
|
|
INDEX { psLVDIndex }
|
|
::= { psLVDTable 1 }
|
|
|
|
PSLVDEntry ::= SEQUENCE {
|
|
psLVDIndex Integer32,
|
|
psLVDCircuitA DisplayString,
|
|
psLVDCircuitB DisplayString,
|
|
psLVDCircuitAAlarmStatus Integer32,
|
|
psLVDCircuitBAlarmStatus Integer32
|
|
}
|
|
|
|
psLVDIndex OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Number "
|
|
::= { psLVDEntry 1 }
|
|
|
|
psLVDCircuitA OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit A Disconnect Voltage "
|
|
::= { psLVDEntry 2 }
|
|
|
|
psLVDCircuitB OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit B Disconnect Voltage "
|
|
::= { psLVDEntry 3 }
|
|
|
|
psLVDCircuitAAlarmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disconnected(0),
|
|
noreply(1),
|
|
boardfail(2),
|
|
none(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit A Alarm Status "
|
|
::= { psLVDEntry 4 }
|
|
|
|
psLVDCircuitBAlarmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disconnected(0),
|
|
noreply(1),
|
|
boardfail(2),
|
|
none(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit B Alarm Status "
|
|
::= { psLVDEntry 5 }
|
|
|
|
psDistributionTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSShuntEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt Pod Table"
|
|
::= { psStatus 4 }
|
|
|
|
psShuntEntry OBJECT-TYPE
|
|
SYNTAX PSShuntEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt Pod Table Entry."
|
|
INDEX { psShuntIndex }
|
|
::= { psDistributionTable 1 }
|
|
|
|
PSShuntEntry ::= SEQUENCE {
|
|
psShuntIndex Integer32,
|
|
psShuntCurrent DisplayString,
|
|
psShuntAlarmStatus Integer32,
|
|
psShuntType Integer32
|
|
}
|
|
|
|
psShuntIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..16)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt Pod Number."
|
|
::= { psShuntEntry 1 }
|
|
|
|
psShuntCurrent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt POD Current."
|
|
::= { psShuntEntry 2 }
|
|
|
|
psShuntAlarmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
type(0),
|
|
noreply(1),
|
|
none(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt POD Alarm Status.
|
|
Values: 0 = Type, 1 = No Reply, 2 = No Alarm"
|
|
::= { psShuntEntry 3 }
|
|
|
|
psShuntType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
system(1),
|
|
subsystem(2),
|
|
battery(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt POD Alarm Status.
|
|
Values: 0 = System, 1 = Subsystem, 2 = Battery"
|
|
::= { psShuntEntry 4 }
|
|
|
|
psPCUTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSPCUEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Table."
|
|
::= { psStatus 5 }
|
|
|
|
psPCUEntry OBJECT-TYPE
|
|
SYNTAX PSPCUEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Table Entry."
|
|
INDEX { psPCUIndex }
|
|
::= { psPCUTable 1 }
|
|
|
|
PSPCUEntry ::= SEQUENCE {
|
|
psPCUIndex Integer32,
|
|
psPCUFail Integer32,
|
|
psPCUCurrent Integer32,
|
|
psPCUFerroGateway Integer32,
|
|
psPCUProductNumber DisplayString,
|
|
psPCUSWVersion DisplayString,
|
|
psPCUSerialNumber DisplayString,
|
|
psPCUCapacity DisplayString
|
|
}
|
|
|
|
psPCUIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..80)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Number."
|
|
::= { psPCUEntry 1 }
|
|
|
|
psPCUFail OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
false(0),
|
|
true(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Fail Alarm"
|
|
::= { psPCUEntry 2 }
|
|
|
|
psPCUCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Current"
|
|
::= { psPCUEntry 3 }
|
|
|
|
psPCUFerroGateway OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
false(0),
|
|
true(1)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU is a Ferro Gateway Rectifier."
|
|
::= { psPCUEntry 4 }
|
|
|
|
psPCUProductNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Product Number."
|
|
::= { psPCUEntry 5}
|
|
|
|
psPCUSWVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Software Revision."
|
|
::= { psPCUEntry 6}
|
|
|
|
psPCUSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Serial Number."
|
|
::= { psPCUEntry 7}
|
|
|
|
psPCUCapacity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Rated Current"
|
|
::= { psPCUEntry 8 }
|
|
|
|
psEmergencyStop NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Emergency Stop Alarm."
|
|
::= { psAlarmsGeneral1 1 }
|
|
|
|
psAlarmVeryLowVoltage NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"50 Percent Battery On Discharge Alarm."
|
|
::= { psAlarmsGeneral1 2 }
|
|
|
|
psAlarmLowVoltage NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery On Discharge Alarm."
|
|
::= { psAlarmsGeneral1 3 }
|
|
|
|
psAlarmSystemHighVoltage1 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High Voltage 1 Alarm."
|
|
::= { psAlarmsGeneral1 4 }
|
|
|
|
psAlarmSystemHighVoltage2 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High Voltage 2 Alarm."
|
|
::= { psAlarmsGeneral1 5 }
|
|
|
|
psAlarmSubsystemLowVoltage NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subsystem Low Voltage Alarm."
|
|
::= { psAlarmsGeneral1 6 }
|
|
|
|
psAlarmSubsystemHighVoltage NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subsystem High Voltage Alarm."
|
|
::= { psAlarmsGeneral1 7 }
|
|
|
|
psAlarmSystemFuse NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Fuse Alarm."
|
|
::= { psAlarmsGeneral1 8 }
|
|
|
|
psAlarmSubsystemFuse NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subsystem Fuse Alarm."
|
|
::= { psAlarmsGeneral1 9 }
|
|
|
|
psAlarmAllACOff NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"All AC Off Alarm."
|
|
::= { psAlarmsGeneral1 10 }
|
|
|
|
psAlarmSystemOverCurrent NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Over Current Alarm."
|
|
::= { psAlarmsGeneral1 11 }
|
|
|
|
psAlarmSubsystemOverCurrent NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subsystem Over Current Alarm."
|
|
::= { psAlarmsGeneral1 12 }
|
|
|
|
psAlarmLVDsAreInhibited NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVDs Are Inhibited Alarm."
|
|
::= { psAlarmsGeneral1 13 }
|
|
|
|
psAlarmTestEqualizeMode NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Test/Equalize Mode Active."
|
|
::= { psAlarmsGeneral1 14 }
|
|
|
|
psAlarmMinor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Minor Alarm."
|
|
::= { psAlarmsGeneral1 15 }
|
|
|
|
psAlarmMajor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Major Alarm."
|
|
::= { psAlarmsGeneral1 16 }
|
|
|
|
psAlarmSenseVoltageFuse NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sense Voltage Fuse Alarm."
|
|
::= { psAlarmsGeneral1 17 }
|
|
|
|
psAlarmSystemVoltageFuse NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"System Voltage Fuse Alarm."
|
|
::= { psAlarmsGeneral1 18 }
|
|
|
|
psAlarmNoSystemVoltage NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No System Voltage Alarm."
|
|
::= { psAlarmsGeneral1 19 }
|
|
|
|
psAlarmNoSubsystemVoltage NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No Subsystem Voltage Alarm."
|
|
::= { psAlarmsGeneral1 20 }
|
|
|
|
psAlarmNoSenseVoltage NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"No Sense Voltage Alarm."
|
|
::= { psAlarmsGeneral1 21 }
|
|
|
|
psAlarmDisplayNoReply NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Display Communications Alarm."
|
|
::= { psAlarmsGeneral1 22 }
|
|
|
|
psAlarmSubsystemMajor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subsystem Major Alarm."
|
|
::= { psAlarmsGeneral1 23 }
|
|
|
|
psAlarmSubsystemMinor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Subsystem Minor Alarm."
|
|
::= { psAlarmsGeneral1 24 }
|
|
|
|
psAlarmHighACLine NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
" High AC Line Alarm."
|
|
::= { psAlarmsGeneral1 25 }
|
|
|
|
psAlarmSenseVoltageError NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Sense Voltage Error Alarm."
|
|
::= { psAlarmsGeneral1 26 }
|
|
|
|
psTestEqualizeHardwareInput NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The MCA Test Equalize Hardware Input Active."
|
|
::= { psAlarmsGeneral2 1 }
|
|
|
|
psPCUFailMajor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Fail Major Alarm."
|
|
::= { psAlarmsGeneral2 2 }
|
|
|
|
psPCUFailMinor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Fail Minor Alarm."
|
|
::= { psAlarmsGeneral2 3 }
|
|
|
|
psLVDAlarmMajor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Major Alarm."
|
|
::= { psAlarmsGeneral2 4 }
|
|
|
|
psLVDAlarmMinor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Minor Alarm."
|
|
::= { psAlarmsGeneral2 5 }
|
|
|
|
psPCULoadShare NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Load Share Alarm."
|
|
::= { psAlarmsGeneral2 6 }
|
|
|
|
psACFailMajor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC Fail Major Alarm."
|
|
::= { psAlarmsGeneral2 7 }
|
|
|
|
psACFailMinor NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"AC Fail Minor Alarm."
|
|
::= { psAlarmsGeneral2 8 }
|
|
|
|
psMCACommFail NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"MCA Communications Failure Alarm."
|
|
::= { psAlarmsGeneral2 9 }
|
|
|
|
psHVSActive NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"High Voltage Shutdown Active."
|
|
::= { psAlarmsGeneral2 10 }
|
|
|
|
psRemoteHVSActive NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote High Voltage Shutdown Active."
|
|
::= { psAlarmsGeneral2 11 }
|
|
|
|
psRemoteEstopActive NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Remote Emergency Stop Active."
|
|
::= { psAlarmsGeneral2 12 }
|
|
|
|
psAlarmBatteryChargeOverCurrent NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Charge Over Current Alarm."
|
|
::= { psAlarmsBattery 1 }
|
|
|
|
psBatteryCurrentLimitInhibited NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Current Limit Inhibited Alarm."
|
|
::= { psAlarmsBattery 2 }
|
|
|
|
psAlarmBatteryPoorHealth NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Poor Health Alarm."
|
|
::= { psAlarmsBattery 3 }
|
|
|
|
psAlarmBatteryReserveLow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Reserve Low Alarm."
|
|
::= { psAlarmsBattery 4 }
|
|
|
|
psPCUSummaryTypeTraps OBJECT IDENTIFIER ::= { psTraps 4 }
|
|
psPCUSummaryTraps OBJECT IDENTIFIER ::= { psPCUSummaryTypeTraps 1 }
|
|
|
|
psAlarmPCUSummary NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Alarm Active."
|
|
::= { psPCUSummaryTraps 2 }
|
|
|
|
psPCUNodeTypeTraps OBJECT IDENTIFIER ::= { psTraps 5 }
|
|
psPCUTraps OBJECT IDENTIFIER ::= { psPCUNodeTypeTraps 1 }
|
|
|
|
psAlarmPCUId OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Number."
|
|
::= { psPCUTraps 1 }
|
|
|
|
psAlarmPCUHighACLine NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU High AC Line Alarm."
|
|
::= { psPCUTraps 2 }
|
|
|
|
psAlarmPCUControllerFailure NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Controller Failure Alarm."
|
|
::= { psPCUTraps 3 }
|
|
|
|
psAlarmPCUFanSlowOrStopped NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Fan Slow Or Stopped Alarm."
|
|
::= { psPCUTraps 4 }
|
|
|
|
psAlarmPCUTurnedOffByMca NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Turned Off By MCA."
|
|
::= { psPCUTraps 5 }
|
|
|
|
psAlarmPCUCircuitBreakerOff NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Circuit Breaker Off Alarm."
|
|
::= { psPCUTraps 6 }
|
|
|
|
psAlarmPCUDCorACConvertFail NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Converter Fail Alarm."
|
|
::= { psPCUTraps 7 }
|
|
|
|
psAlarmPCUThermalAlarmorCurrentLimit NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Thermal Current Limit Alarm."
|
|
::= { psPCUTraps 8 }
|
|
|
|
psAlarmPCUEmergencyStop NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Emergency Stop Alarm."
|
|
::= { psPCUTraps 9 }
|
|
|
|
psAlarmPCUInputSwitchOff NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Input Switch Off Alarm."
|
|
::= { psPCUTraps 10 }
|
|
|
|
psAlarmPCUHighVoltageShutdown NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU High Voltage Shutdown Alarm."
|
|
::= { psPCUTraps 11 }
|
|
|
|
psAlarmPCUACInputIsOffOrLow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU AC Input Is Off Or Low Alarm."
|
|
::= { psPCUTraps 12 }
|
|
|
|
psAlarmPCUCommunicationFailureWithMCA NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Communication Failure Alarm."
|
|
::= { psPCUTraps 13 }
|
|
|
|
psAlarmPCUSenseLeadOpen NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PCU Sense Lead Open Alarm."
|
|
::= { psPCUTraps 14 }
|
|
|
|
psShuntTypeTraps OBJECT IDENTIFIER ::= { psTraps 6 }
|
|
psShuntTraps OBJECT IDENTIFIER ::= { psShuntTypeTraps 1 }
|
|
|
|
psAlarmShuntId OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt POD Number."
|
|
::= { psShuntTraps 1 }
|
|
|
|
psAlarmShuntType NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt POD Type Alarm."
|
|
::= { psShuntTraps 2 }
|
|
|
|
psAlarmShuntNoReply NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Shunt POD Communications Alarm."
|
|
::= { psShuntTraps 3 }
|
|
|
|
|
|
psLVDTypeTraps OBJECT IDENTIFIER ::= { psTraps 7 }
|
|
psLVDTraps OBJECT IDENTIFIER ::= { psLVDTypeTraps 1 }
|
|
|
|
psAlarmLVDId OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The Analog LVD Number "
|
|
::= { psLVDTraps 1 }
|
|
|
|
psAlarmLVDDisconnectedA NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit A Disconnected Alarm."
|
|
::= { psLVDTraps 2 }
|
|
|
|
psAlarmLVDNoReplyA NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit A Communications Alarm."
|
|
::= { psLVDTraps 3 }
|
|
|
|
psAlarmLVDBoardFailA NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Board Circuit A Fail Alarm."
|
|
::= { psLVDTraps 4 }
|
|
|
|
psAlarmLVDDisconnectedB NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit B Disconnected Alarm."
|
|
::= { psLVDTraps 5 }
|
|
|
|
psAlarmLVDNoReplyB NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Circuit B No Communications Alarm."
|
|
::= { psLVDTraps 6 }
|
|
|
|
psAlarmLVDBoardFailB NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"LVD Board Circuit B Fail Alarm."
|
|
::= { psLVDTraps 7 }
|
|
|
|
psTemperatureTypeTraps OBJECT IDENTIFIER ::= { psTraps 8 }
|
|
psTemperatureTraps OBJECT IDENTIFIER ::= { psTemperatureTypeTraps 1 }
|
|
|
|
psAlarmTemperatureId OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Probe Number."
|
|
::= { psTemperatureTraps 1 }
|
|
|
|
psAlarmTemperatureHigh NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature High Alarm."
|
|
::= { psTemperatureTraps 2 }
|
|
|
|
psAlarmTemperatureLow NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Low Alarm."
|
|
::= { psTemperatureTraps 3 }
|
|
|
|
psAlarmTemperatureNoReply NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Communications Alarm."
|
|
::= { psTemperatureTraps 4 }
|
|
|
|
psSysInfoTypeTraps OBJECT IDENTIFIER ::= { psTraps 9 }
|
|
psSysInfoTraps OBJECT IDENTIFIER ::= { psSysInfoTypeTraps 1 }
|
|
|
|
psAlarmSysInfoError1 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo Error 1."
|
|
::= { psSysInfoTraps 1 }
|
|
|
|
psAlarmSysInfoError2 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo Error 2."
|
|
::= { psSysInfoTraps 2 }
|
|
|
|
psAlarmSysInfoString1 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 1."
|
|
::= { psSysInfoTraps 3 }
|
|
|
|
psAlarmSysInfoString2 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 2."
|
|
::= { psSysInfoTraps 4 }
|
|
|
|
psAlarmSysInfoString3 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 3."
|
|
::= { psSysInfoTraps 5 }
|
|
|
|
psAlarmSysInfoString4 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 4."
|
|
::= { psSysInfoTraps 6 }
|
|
|
|
psAlarmSysInfoString5 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 5."
|
|
::= { psSysInfoTraps 7 }
|
|
|
|
psAlarmSysInfoString6 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 6."
|
|
::= { psSysInfoTraps 8 }
|
|
|
|
psAlarmSysInfoString7 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 7."
|
|
::= { psSysInfoTraps 9 }
|
|
|
|
psAlarmSysInfoString8 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 8."
|
|
::= { psSysInfoTraps 10 }
|
|
|
|
psAlarmSysInfoString9 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 9."
|
|
::= { psSysInfoTraps 11 }
|
|
|
|
psAlarmSysInfoString10 NOTIFICATION-TYPE
|
|
STATUS current
|
|
DESCRIPTION
|
|
"SysInfo String 10."
|
|
::= { psSysInfoTraps 12 }
|
|