- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1115 lines
30 KiB
Text
1115 lines
30 KiB
Text
------------------------------------------------------------
|
|
-- Emerson Energy Systems (EES)
|
|
-- Power MIB
|
|
------------------------------------------------------------
|
|
|
|
EES-POWER-MIB DEFINITIONS ::= BEGIN
|
|
|
|
|
|
IMPORTS
|
|
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
|
|
Integer32, Counter32, enterprises
|
|
FROM SNMPv2-SMI
|
|
TEXTUAL-CONVENTION, DisplayString, DateAndTime
|
|
FROM SNMPv2-TC;
|
|
|
|
|
|
powerMIB MODULE-IDENTITY
|
|
LAST-UPDATED "201504100857Z"
|
|
ORGANIZATION "
|
|
Emerson Energy Systems (EES)"
|
|
CONTACT-INFO "
|
|
Emerson Energy Systems
|
|
141 82 Stockholm
|
|
Sweden"
|
|
DESCRIPTION "
|
|
Emerson Energy Systems (EES) Power MIB, revision D."
|
|
::= { enterprises 6302 2 1 }
|
|
|
|
------------------------------------------------------------
|
|
-- Node definitions
|
|
------------------------------------------------------------
|
|
|
|
ees OBJECT IDENTIFIER ::= { enterprises 6302 }
|
|
|
|
global OBJECT IDENTIFIER ::= { ees 2 }
|
|
|
|
------------------------------------------------------------
|
|
-- Textual conventions
|
|
------------------------------------------------------------
|
|
|
|
Status ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION "
|
|
This integer value represents the operational or administrative
|
|
status of the system. Also used as alarm severity.
|
|
Depending on situation there may be limits on allowed values.
|
|
Operational values:
|
|
(1) unknown - status has not yet been defined
|
|
(2) normal - there are no activated alarms
|
|
(3) warning - OA, lowest level of 'abnormal' status
|
|
(4) minor - A3
|
|
(5) major - MA
|
|
(6) critical - CA, highest level of 'abnormal' status
|
|
Administrative values:
|
|
(7) unmanaged
|
|
(8) restricted
|
|
(9) testing
|
|
(10) disabled"
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
normal(2),
|
|
warning(3),
|
|
minor(4),
|
|
major(5),
|
|
critical(6),
|
|
unmanaged(7),
|
|
restricted(8),
|
|
testing(9),
|
|
disabled(10) }
|
|
|
|
StatusChange ::= TEXTUAL-CONVENTION
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Indicates 'activated' (1) or 'deactivated' (2) alarm events."
|
|
SYNTAX INTEGER {
|
|
activated(1),
|
|
deactivated(2) }
|
|
|
|
|
|
------------------------------------------------------------
|
|
-- 1.1 Identification of the plant { powerMIB 1 }
|
|
------------------------------------------------------------
|
|
|
|
ident OBJECT IDENTIFIER ::= { powerMIB 1 }
|
|
|
|
identManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The name of the equipment manufacturer."
|
|
::= { ident 1 }
|
|
|
|
identModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The manufacturers model designation of the power system."
|
|
::= { ident 2 }
|
|
|
|
identControllerFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The firmware (software) version of the controller."
|
|
::= { ident 3 }
|
|
|
|
identName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The name of the power plant. This object should be set by
|
|
the administrator."
|
|
::= { ident 4 }
|
|
|
|
identSNMPCfgVer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The snmp cfg version"
|
|
::= { ident 5 }
|
|
|
|
identControllerSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The serial number of this controller"
|
|
::= { ident 6 }
|
|
|
|
------------------------------------------------------------
|
|
-- 1.2 System values { powerMIB 2 }
|
|
------------------------------------------------------------
|
|
|
|
system OBJECT IDENTIFIER ::= { powerMIB 2 }
|
|
|
|
systemStatus OBJECT-TYPE
|
|
SYNTAX Status
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Status of the complete plant (highest alarm). One of
|
|
(1) unknown - status has not yet been defined
|
|
(2) normal - there are no activated alarms
|
|
(3) warning - OA, lowest level of 'abnormal' status
|
|
(4) minor - A3
|
|
(5) major - MA
|
|
(6) critical - CA, highest level of 'abnormal' status
|
|
(7) unmanaged
|
|
(8) restricted
|
|
(9) testing
|
|
(10) disabled"
|
|
::= { system 1 }
|
|
|
|
systemVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
System voltage, stored as mV, including positive or negative
|
|
sign. The integer 2147483647 represents invalid value."
|
|
::= { system 2 }
|
|
|
|
systemCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
System current, stored as mA, including positive or negative
|
|
sign. The integer 2147483647 represents invalid value."
|
|
::= { system 3 }
|
|
|
|
systemUsedCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Used capacity, stored as % of the total capacity.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { system 4 }
|
|
|
|
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.5. Battery group
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psBattery OBJECT IDENTIFIER ::= { system 5 }
|
|
|
|
psBatteryVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery voltage, stored as mV, including positive or negative
|
|
sign. The integer 2147483647 represents invalid value."
|
|
::= { psBattery 1 }
|
|
|
|
psTotalBatteryCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery current, stored as mA, including positive or negative
|
|
sign. The integer 2147483647 represents invalid value."
|
|
::= { psBattery 2 }
|
|
|
|
psBatteryCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Calculated capacity, stored as % of the total capacity.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psBattery 3 }
|
|
|
|
psBatteryNominalCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
nominal installed capacity, stored as mAh.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psBattery 4 }
|
|
|
|
psBatteryTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSBatteryEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Table."
|
|
::= { psBattery 5 }
|
|
|
|
psBatteryEntry OBJECT-TYPE
|
|
SYNTAX PSBatteryEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery Measurement Table Entry."
|
|
INDEX { psBatteryIndex }
|
|
::= { psBatteryTable 1 }
|
|
|
|
PSBatteryEntry ::= SEQUENCE {
|
|
psBatteryIndex Integer32,
|
|
psBatteryCurrent Integer32,
|
|
psBatteryName DisplayString
|
|
}
|
|
|
|
psBatteryIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..16777215)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatically generated index object."
|
|
::= { psBatteryEntry 1 }
|
|
|
|
psBatteryCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery current in Amps."
|
|
::= { psBatteryEntry 2 }
|
|
|
|
psBatteryName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Battery shunt name."
|
|
::= { psBatteryEntry 3 }
|
|
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.6. the psInput group
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psInput OBJECT IDENTIFIER ::= { system 6 }
|
|
|
|
psInputLineAVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The AC line A voltage, stored as mV. The integer 2147483647
|
|
represents invalid value."
|
|
::= { psInput 1 }
|
|
|
|
psInputLineBVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The AC line B voltage, stored as mV. The integer 2147483647
|
|
represents invalid value."
|
|
::= { psInput 2 }
|
|
|
|
psInputLineCVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The AC line C voltage, stored as mV. The integer 2147483647
|
|
represents invalid value."
|
|
::= { psInput 3 }
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.7. the temperatures
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psTemperature OBJECT IDENTIFIER ::= { system 7 }
|
|
|
|
psTemperature1 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The first route temperature, stored as 0.001 Celsius degree.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psTemperature 1 }
|
|
|
|
psTemperature2 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The second route temperature, stored as 0.001 Celsius degree.
|
|
The integer 2147483647 represents invalid value.."
|
|
::= { psTemperature 2 }
|
|
|
|
|
|
psTemperatureTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSTemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Measurement Table."
|
|
::= { psTemperature 3 }
|
|
|
|
psTemperatureEntry OBJECT-TYPE
|
|
SYNTAX PSTemperatureEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Measurement Table Entry."
|
|
INDEX { psTemperatureIndex }
|
|
::= { psTemperatureTable 1 }
|
|
|
|
PSTemperatureEntry ::= SEQUENCE {
|
|
psTemperatureIndex Integer32,
|
|
psTemperatureMeasurement Integer32,
|
|
psTemperatureName DisplayString,
|
|
psTemperatureType INTEGER,
|
|
psTemperatureAlarmStatus INTEGER
|
|
}
|
|
|
|
psTemperatureIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..71)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Probe Number "
|
|
::= { psTemperatureEntry 1 }
|
|
|
|
psTemperatureMeasurement OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Value In Centigrade."
|
|
::= { psTemperatureEntry 2 }
|
|
|
|
psTemperatureName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configured Temperature Probe Name."
|
|
::= { psTemperatureEntry 3 }
|
|
|
|
psTemperatureType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(0),
|
|
ambient(1),
|
|
battery(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Probe Type "
|
|
::= { psTemperatureEntry 4 }
|
|
|
|
psTemperatureAlarmStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
high(0),
|
|
low(1),
|
|
fail(2),
|
|
none(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Temperature Probe Alarm Status "
|
|
::= { psTemperatureEntry 5 }
|
|
|
|
psStatusCommunication OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
normal(2),
|
|
interrupt(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of communication with the Power System. interrupt(3) indicates
|
|
some errors occurred between Power System and agent."
|
|
::= { system 8 }
|
|
|
|
psStatusBatteryMode OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
unknown(1),
|
|
floatCharging(2),
|
|
shortTest(3),
|
|
bcForTest(4),
|
|
manualTesting(5),
|
|
planTesting(6),
|
|
acFailTesting(7),
|
|
acFail(8),
|
|
manualBC(9),
|
|
autoBC(10),
|
|
cyclicBC(11),
|
|
masterBC(12),
|
|
masterBT(13)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of battery modes,
|
|
FloatCharging(2),
|
|
ShortTest(3),
|
|
BoostChargingForTest(4),
|
|
ManualTesting(5),
|
|
PlanTesting(6),
|
|
ACFailTesting(7),
|
|
ACFail(8),
|
|
ManualBoostCharging(9),
|
|
AutoBoostCharging(10),
|
|
CyclicBoostCharging(11),
|
|
MasterBoostCharging(12),
|
|
MasterBateryTesting(13)."
|
|
::= { system 9 }
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.10. the SM series group(only get number of SM series)
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psSMNumber OBJECT IDENTIFIER ::= { system 10 }
|
|
|
|
psSMACNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of SM AC module."
|
|
::= { psSMNumber 1 }
|
|
|
|
psSMBATNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of SM BAT module."
|
|
::= { psSMNumber 2 }
|
|
|
|
psSMIONumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of SM IO module."
|
|
::= { psSMNumber 3 }
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.11. Rectifier group
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psRectifier OBJECT IDENTIFIER ::= { system 11 }
|
|
|
|
numberOfInstalledRectifiers OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
number of rectifiers, stored as integer.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psRectifier 1 }
|
|
|
|
numberOfRectifiersCommunicating OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
number of rectifiers communicating, stored as integer.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psRectifier 2 }
|
|
|
|
rectifiersUsedCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Used capacity, stored as % of the total capacity.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psRectifier 3 }
|
|
|
|
psRectifierTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSRectifierEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Table holding information about indivual rectifiers."
|
|
::= { psRectifier 4 }
|
|
|
|
psRectifierEntry OBJECT-TYPE
|
|
SYNTAX PSRectifierEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
An entry (conceptual row) in the rectifierInfoTable."
|
|
INDEX { psRectifierIndex }
|
|
::= { psRectifierTable 1 }
|
|
|
|
PSRectifierEntry ::= SEQUENCE {
|
|
psRectifierIndex Integer32,
|
|
psRectifierProductNumber DisplayString,
|
|
psRectifierHWVersion DisplayString,
|
|
psRectifierSWVersion DisplayString,
|
|
psRectifierSerialNumber DisplayString,
|
|
psRectifierCurrent Integer32,
|
|
psRectifierIdent DisplayString,
|
|
psRectifierFail StatusChange
|
|
}
|
|
|
|
psRectifierIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..16777215)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Automatically generated index object."
|
|
::= { psRectifierEntry 1 }
|
|
|
|
psRectifierProductNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Product Number."
|
|
::= { psRectifierEntry 2}
|
|
|
|
psRectifierHWVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Hardware Revision."
|
|
::= { psRectifierEntry 3}
|
|
|
|
psRectifierSWVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Software Revision."
|
|
::= { psRectifierEntry 4}
|
|
|
|
psRectifierSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Serial Number."
|
|
::= { psRectifierEntry 5}
|
|
|
|
psRectifierCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier Current."
|
|
::= { psRectifierEntry 6}
|
|
|
|
psRectifierIdent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Rectifier physical location identifier."
|
|
::= { psRectifierEntry 7}
|
|
|
|
psRectifierFail OBJECT-TYPE
|
|
SYNTAX StatusChange
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The type of alarm change. One of
|
|
(1) activated
|
|
(2) deactivated"
|
|
::= { psRectifierEntry 8}
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.12. the Distribution
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psDistribution OBJECT IDENTIFIER ::= { system 12 }
|
|
|
|
psTotalLoadCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Total Load current, stored as integer.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psDistribution 1 }
|
|
psDistributionLoadTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSDistributionLoadEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution Table."
|
|
::= { psDistribution 2 }
|
|
|
|
psDistributionLoadEntry OBJECT-TYPE
|
|
SYNTAX PSDistributionLoadEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution Measurement Table Entry."
|
|
INDEX { psDistributionLoadIndex }
|
|
::= { psDistributionLoadTable 1 }
|
|
|
|
PSDistributionLoadEntry ::= SEQUENCE {
|
|
psDistributionLoadIndex Integer32,
|
|
psDistributionLoadCurrent Integer32,
|
|
psDistributionLoadName DisplayString
|
|
}
|
|
|
|
psDistributionLoadIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..268386303)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatically generated index object."
|
|
::= { psDistributionLoadEntry 1 }
|
|
|
|
psDistributionLoadCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution current in Amps."
|
|
::= { psDistributionLoadEntry 2 }
|
|
|
|
psDistributionLoadName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution name."
|
|
::= { psDistributionLoadEntry 3 }
|
|
|
|
psDistributionGeneralTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSDistributionGeneralEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution Table."
|
|
::= { psDistribution 3 }
|
|
|
|
psDistributionGeneralEntry OBJECT-TYPE
|
|
SYNTAX PSDistributionGeneralEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution Measurement Table Entry."
|
|
INDEX { psDistributionGeneralIndex }
|
|
::= { psDistributionGeneralTable 1 }
|
|
|
|
PSDistributionGeneralEntry ::= SEQUENCE {
|
|
psDistributionGeneralIndex Integer32,
|
|
psDistributionGeneralCurrent Integer32,
|
|
psDistributionGeneralName DisplayString
|
|
}
|
|
|
|
psDistributionGeneralIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..268386303)
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Automatically generated index object."
|
|
::= { psDistributionGeneralEntry 1 }
|
|
|
|
psDistributionGeneralCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution current in Amps."
|
|
::= { psDistributionGeneralEntry 2 }
|
|
|
|
psDistributionGeneralName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Distribution name."
|
|
::= { psDistributionGeneralEntry 3 }
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.13. Converter group
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psConverter OBJECT IDENTIFIER ::= { system 13 }
|
|
|
|
numberOfInstalledConverters OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
number of converters, stored as integer.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psConverter 1 }
|
|
|
|
numberOfConvertersCommunicating OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
number of converters communicating, stored as integer.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psConverter 2 }
|
|
|
|
convertersUsedCapacity OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Used capacity, stored as % of the total capacity.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psConverter 3 }
|
|
|
|
psConverterVoltage OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Converter voltage in mV.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psConverter 4 }
|
|
|
|
psTotalConverterCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Total Converter current in Amps.
|
|
The integer 2147483647 represents invalid value."
|
|
::= { psConverter 5 }
|
|
|
|
psConverterTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF PSConverterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Table holding information about indivual converters."
|
|
::= { psConverter 6 }
|
|
|
|
psConverterEntry OBJECT-TYPE
|
|
SYNTAX PSConverterEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
An entry (conceptual row) in the ConverterInfoTable."
|
|
INDEX { psConverterIndex }
|
|
::= { psConverterTable 1 }
|
|
|
|
PSConverterEntry ::= SEQUENCE {
|
|
psConverterIndex Integer32,
|
|
psConverterProductNumber DisplayString,
|
|
psConverterHWVersion DisplayString,
|
|
psConverterSWVersion DisplayString,
|
|
psConverterSerialNumber DisplayString,
|
|
psConverterCurrent Integer32,
|
|
psConverterIdent DisplayString,
|
|
psConverterFail StatusChange }
|
|
|
|
psConverterIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..100)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Automatically generated index object."
|
|
::= { psConverterEntry 1 }
|
|
|
|
psConverterProductNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Converter Product Number."
|
|
::= { psConverterEntry 2}
|
|
|
|
psConverterHWVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Converter Hardware Revision."
|
|
::= { psConverterEntry 3}
|
|
|
|
psConverterSWVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Converter Software Revision."
|
|
::= { psConverterEntry 4}
|
|
|
|
psConverterSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Converter Serial Number."
|
|
::= { psConverterEntry 5}
|
|
|
|
psConverterCurrent OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Converter Current."
|
|
::= { psConverterEntry 6}
|
|
|
|
psConverterIdent OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Converter physical location identifier."
|
|
::= { psConverterEntry 7}
|
|
|
|
psConverterFail OBJECT-TYPE
|
|
SYNTAX StatusChange
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The type of alarm change. One of
|
|
(1) activated
|
|
(2) deactivated"
|
|
::= { psConverterEntry 8}
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.14. Control group
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psControl OBJECT IDENTIFIER ::= { system 14 }
|
|
|
|
controlBatteryTest OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Control battery test, start(1), stop (0)."
|
|
::= { psControl 1 }
|
|
|
|
controlRelay8 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Control relay8, close(1), open(0)."
|
|
::= { psControl 2 }
|
|
|
|
controlRelay7 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Control relay7, close(1), open(0)."
|
|
::= { psControl 3 }
|
|
|
|
controlRelay6 OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Control relay6, close(1), open(0)."
|
|
::= { psControl 4 }
|
|
|
|
controlRelayTest OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Control Relay test, start(1), stop (0)."
|
|
::= { psControl 5 }
|
|
|
|
|
|
-- ------------------------------------------------------------------------
|
|
-- 1.2.15. EquipmentSignalTable
|
|
-- ------------------------------------------------------------------------
|
|
|
|
psEquipmentSignalTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF EquipmentSignalTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Table of indexed equipment signal values."
|
|
::= { system 15 }
|
|
|
|
equipmentSignalTableEntry OBJECT-TYPE
|
|
SYNTAX EquipmentSignalTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
An entry (conceptual row) in the psEquipment Signal Table."
|
|
INDEX { psEquipmentSignalTableEntryIndex }
|
|
::= { psEquipmentSignalTable 1 }
|
|
|
|
EquipmentSignalTableEntry ::= SEQUENCE {
|
|
psEquipmentSignalTableEntryIndex Integer32,
|
|
psEquipmentSignalValue Integer32 }
|
|
|
|
psEquipmentSignalTableEntryIndex OBJECT-TYPE
|
|
SYNTAX Integer32(1..268386303)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The unique sequence number of this equipment signal."
|
|
::= { equipmentSignalTableEntry 1 }
|
|
|
|
psEquipmentSignalValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Indexed equipment signal value."
|
|
::= { equipmentSignalTableEntry 2 }
|
|
|
|
------------------------------------------------------------
|
|
-- Alarm trap counter { powerMIB 3 }
|
|
------------------------------------------------------------
|
|
|
|
alarmLastTrapNo OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The sequence number of last submitted alarm trap,
|
|
also last row in alarmTrapTable."
|
|
::= { powerMIB 3 }
|
|
|
|
------------------------------------------------------------
|
|
-- Active Alarm table { powerMIB 4 }
|
|
------------------------------------------------------------
|
|
|
|
alarmActiveAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ActiveAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Table holding information about the currently active alarms."
|
|
::= { powerMIB 4 }
|
|
|
|
activeAlarmEntry OBJECT-TYPE
|
|
SYNTAX ActiveAlarmEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION "
|
|
An entry (conceptual row) in the alarmTrapTable."
|
|
INDEX { alarmIndex }
|
|
::= { alarmActiveAlarmTable 1 }
|
|
|
|
ActiveAlarmEntry ::= SEQUENCE {
|
|
alarmIndex Counter32,
|
|
alarmTime DateAndTime,
|
|
alarmStatusChange StatusChange,
|
|
alarmSeverity Status,
|
|
alarmDescription DisplayString,
|
|
alarmType Integer32 }
|
|
|
|
alarmIndex OBJECT-TYPE
|
|
SYNTAX Counter32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The unique sequence number of this alarm trap."
|
|
::= { activeAlarmEntry 1 }
|
|
|
|
alarmTime OBJECT-TYPE
|
|
SYNTAX DateAndTime
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Date and time when event occured (local time), including
|
|
timezone if supported by controller."
|
|
::= { activeAlarmEntry 2 }
|
|
|
|
alarmStatusChange OBJECT-TYPE
|
|
SYNTAX StatusChange
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The type of alarm change. One of
|
|
(1) activated
|
|
(2) deactivated"
|
|
::= { activeAlarmEntry 3 }
|
|
|
|
alarmSeverity OBJECT-TYPE
|
|
SYNTAX Status
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
The severity of the alarm. One of
|
|
(3) warning - OA, lowest level of alarm severity
|
|
(4) minor - A3
|
|
(5) major - MA
|
|
(6) critical - CA, highest level of alarm severity"
|
|
::= { activeAlarmEntry 4 }
|
|
|
|
alarmDescription OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Free-text description of alarm."
|
|
::= { activeAlarmEntry 5 }
|
|
|
|
alarmType OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "
|
|
Alarm type, i.e. an integer specifying the type of alarm."
|
|
::= { activeAlarmEntry 6 }
|
|
|
|
------------------------------------------------------------
|
|
-- Events/traps { powerMIB 5 }
|
|
------------------------------------------------------------
|
|
|
|
powerEvents OBJECT IDENTIFIER ::= { powerMIB 5 }
|
|
|
|
alarmTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
alarmIndex,
|
|
alarmTime,
|
|
alarmStatusChange,
|
|
alarmSeverity,
|
|
alarmDescription,
|
|
alarmType }
|
|
STATUS current
|
|
DESCRIPTION "
|
|
An alarm trap is sent when an alarm occurs (activated) or
|
|
returns to normal state (deactivated). Alarm traps are logged
|
|
in alarmTrapTable. Variables in this trap:
|
|
* alarmIndex - The unique sequence number of this alarm trap.
|
|
* alarmTime - Date and time when event occured (local time),
|
|
including timezone if supported by controller.
|
|
* alarmStatusChange - (1) activated or (2) deactivated.
|
|
* alarmSeverity - Integer describing the severity of the alarm.
|
|
* alarmDescription - Free-text description of alarm.
|
|
* alarmType - Integer indicating type of alarm."
|
|
::= { powerEvents 1 }
|
|
|
|
alarmActiveTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
alarmTime,
|
|
alarmSeverity,
|
|
alarmDescription,
|
|
alarmType }
|
|
STATUS current
|
|
DESCRIPTION "
|
|
An alarm trap is sent when an alarm occurs (activated)
|
|
Variables in this trap
|
|
* alarmTime - Date and time when event occured (local time),
|
|
including timezone if supported by controller.
|
|
* alarmSeverity - Integer describing the severity of the alarm.
|
|
* alarmDescription - Free-text description of alarm.
|
|
* alarmType - Integer indicating type of alarm."
|
|
::= { powerEvents 2 }
|
|
|
|
alarmCeaseTrap NOTIFICATION-TYPE
|
|
OBJECTS {
|
|
alarmTime,
|
|
alarmSeverity,
|
|
alarmDescription,
|
|
alarmType }
|
|
STATUS current
|
|
DESCRIPTION "
|
|
An alarm trap is sent when an alarm returns to normal state (clear, deactivated).
|
|
Variables in this trap:
|
|
* alarmTime - Date and time when event occured (local time),
|
|
including timezone if supported by controller.
|
|
* alarmSeverity - Integer describing the severity of the alarm.
|
|
* alarmDescription - Free-text description of alarm.
|
|
* alarmType - Integer indicating type of alarm."
|
|
::= { powerEvents 3 }
|
|
|
|
------------------------------------------------------------
|
|
-- End of MIB definitions
|
|
------------------------------------------------------------
|
|
|
|
END
|