- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
773 lines
22 KiB
Text
773 lines
22 KiB
Text
-- Title: DPS_V41.MIB
|
|
-- Version: v4.1
|
|
--
|
|
-- Copyright @ 1997-2004 DPS Inc. All Rights Reserved
|
|
--
|
|
-- This MIB defines objects for the DPS products.
|
|
--
|
|
--
|
|
|
|
DPS-MIB-V38 DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
DisplayString,
|
|
sysDescr,
|
|
sysLocation
|
|
FROM RFC1213-MIB
|
|
OBJECT-TYPE
|
|
FROM RFC1212-MIB
|
|
enterprises
|
|
FROM RFC1155-SMI
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
dpsInc OBJECT IDENTIFIER ::= {enterprises 2682}
|
|
|
|
dpsAlarmControl OBJECT IDENTIFIER ::= {dpsInc 1}
|
|
|
|
tmonXM OBJECT IDENTIFIER ::= {dpsAlarmControl 1}
|
|
|
|
tmonIdent OBJECT IDENTIFIER ::= {tmonXM 1}
|
|
|
|
tmonIdentManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The TMON/XM Unit manufacturer."
|
|
::= {tmonIdent 1}
|
|
|
|
tmonIdentModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The TMON/XM model designation."
|
|
::= {tmonIdent 2}
|
|
|
|
tmonIdentSoftwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The TMON/XM SNMP Agent software version."
|
|
::= {tmonIdent 3}
|
|
|
|
tmonAlarmTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF TMonAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "A table of TMon Alarm-specific information."
|
|
::= {tmonXM 2}
|
|
|
|
tmonAlarmEntry OBJECT-TYPE
|
|
SYNTAX TMonAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Information about a particular TMon alarm."
|
|
INDEX {tmonAIndex}
|
|
::= {tmonAlarmTable 1}
|
|
|
|
TMonAlarmEntry ::= SEQUENCE { tmonAIndex INTEGER,
|
|
tmonASite DisplayString,
|
|
tmonADesc DisplayString,
|
|
tmonAState DisplayString,
|
|
tmonASeverity DisplayString,
|
|
tmonAChgDate DisplayString,
|
|
tmonAChgTime DisplayString,
|
|
tmonAAuxDesc DisplayString,
|
|
tmonADispDesc DisplayString,
|
|
tmonAPntType INTEGER,
|
|
tmonAPort INTEGER,
|
|
tmonAAddress INTEGER,
|
|
tmonADisplay INTEGER,
|
|
tmonAPoint INTEGER,
|
|
tmonAIPAddr DisplayString,
|
|
tmonADevDesc DisplayString
|
|
}
|
|
|
|
tmonAIndex OBJECT-TYPE
|
|
SYNTAX INTEGER (0..2147483647)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon alarm table index (1..NumberOfAlarms)."
|
|
::={tmonAlarmEntry 1}
|
|
|
|
tmonASite OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The site of the alarm (i.e. Atlanta Hub, Sub-Station H32)."
|
|
::= {tmonAlarmEntry 2}
|
|
|
|
tmonADesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A user-defined text string associated with the alarm
|
|
(i.e. South Door, Generator, Power Grid 1)."
|
|
::= {tmonAlarmEntry 3}
|
|
|
|
tmonAState OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current alarm state."
|
|
::= {tmonAlarmEntry 4}
|
|
|
|
tmonASeverity OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The severity of the last alarm event."
|
|
::= {tmonAlarmEntry 5}
|
|
|
|
tmonAChgDate OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The date (mm/dd/yy) of the last alarm event."
|
|
::= {tmonAlarmEntry 6}
|
|
|
|
tmonAChgTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The time (hh:mm:ss) of the last alarm event."
|
|
::= {tmonAlarmEntry 7}
|
|
|
|
tmonAAuxDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
|
alarm (i.e. This remote needs servicing)."
|
|
::= {tmonAlarmEntry 8}
|
|
|
|
tmonADispDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of the display on which this point appears."
|
|
::= {tmonAlarmEntry 9}
|
|
|
|
tmonAPntType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Type of this point."
|
|
::={tmonAlarmEntry 10}
|
|
|
|
tmonAPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Port on which this point is reported."
|
|
::={tmonAlarmEntry 11}
|
|
|
|
tmonAAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Address of unit reporting this point."
|
|
::={tmonAlarmEntry 12}
|
|
|
|
tmonADisplay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Display on which this point appears."
|
|
::={tmonAlarmEntry 13}
|
|
|
|
tmonAPoint OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Index into display of this point."
|
|
::={tmonAlarmEntry 14}
|
|
|
|
tmonAIPAddr OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The IP Address of the device on which this point appears."
|
|
::= {tmonAlarmEntry 16}
|
|
|
|
tmonADevDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of the device on which this point appears."
|
|
::= {tmonAlarmEntry 17}
|
|
|
|
-- structure used to issue a command to tmonXM element
|
|
|
|
tmonCommandGrid OBJECT IDENTIFIER ::= {tmonXM 3}
|
|
|
|
tmonCPType OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon point type."
|
|
::= {tmonCommandGrid 1}
|
|
|
|
tmonCPort OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon port number."
|
|
::= {tmonCommandGrid 2}
|
|
|
|
tmonCAddress OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon_port address number."
|
|
::= {tmonCommandGrid 3}
|
|
|
|
tmonCDisplay OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon_port_address display number."
|
|
::= {tmonCommandGrid 4}
|
|
|
|
tmonCPoint OBJECT-TYPE
|
|
SYNTAX INTEGER (1..64)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon_port_display point number (1-64)."
|
|
::= {tmonCommandGrid 5}
|
|
|
|
tmonCEvent OBJECT-TYPE
|
|
SYNTAX INTEGER
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Tmon event ID."
|
|
::= {tmonCommandGrid 6}
|
|
|
|
tmonCAction OBJECT-TYPE
|
|
SYNTAX INTEGER { latch(1),
|
|
release(2),
|
|
momentary(3),
|
|
ack(17),
|
|
tag(18),
|
|
untag(19)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Requested command action (tmonXM will ignore if invalid)."
|
|
::= {tmonCommandGrid 7}
|
|
|
|
tmonCAuxText OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "An auxiliary user-defined text string associated with the
|
|
command (i.e. User_initials)."
|
|
::= {tmonCommandGrid 8}
|
|
|
|
tmonCResult OBJECT-TYPE
|
|
SYNTAX INTEGER { success(1),
|
|
failure(2),
|
|
pending(3)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Command result."
|
|
::= {tmonCommandGrid 9}
|
|
|
|
|
|
|
|
dpsRTU OBJECT IDENTIFIER ::= {dpsAlarmControl 2}
|
|
|
|
dpsRTUIdent OBJECT IDENTIFIER ::= {dpsRTU 1}
|
|
|
|
dpsRTUManufacturer OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The Remote Telemetry Unit manufacturer."
|
|
::= {dpsRTUIdent 1}
|
|
|
|
dpsRTUModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The RTU model designation."
|
|
::= {dpsRTUIdent 2}
|
|
|
|
dpsRTUFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The RTU firmware version."
|
|
::= {dpsRTUIdent 3}
|
|
|
|
dpsRTUDateTime OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "The RTU system date and time."
|
|
::= {dpsRTUIdent 4}
|
|
|
|
dpsRTUSyncReq OBJECT-TYPE
|
|
SYNTAX INTEGER { sync(1)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Caution: SETting this object initiates traps for all
|
|
standing alarms."
|
|
::= {dpsRTUIdent 5}
|
|
|
|
|
|
-- structure used to access displays managed by this RTU
|
|
|
|
dpsRTUDisplayGrid OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DPSrtuDispEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Holds information on displays managed by the RTU."
|
|
::= {dpsRTU 2}
|
|
|
|
dpsRTUDisplayEntry OBJECT-TYPE
|
|
SYNTAX DPSrtuDispEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Information about a particular RTU display."
|
|
INDEX {dpsRTUPort, dpsRTUAddress, dpsRTUDisplay}
|
|
::= {dpsRTUDisplayGrid 1}
|
|
|
|
DPSrtuDispEntry ::= SEQUENCE { dpsRTUPort INTEGER,
|
|
dpsRTUAddress INTEGER,
|
|
dpsRTUDisplay INTEGER,
|
|
dpsRTUDispDesc DisplayString,
|
|
dpsRTUPntMap DisplayString
|
|
}
|
|
|
|
dpsRTUPort OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUDisplayEntry 1}
|
|
|
|
dpsRTUAddress OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUDisplayEntry 2}
|
|
|
|
dpsRTUDisplay OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUDisplayEntry 3}
|
|
|
|
dpsRTUDispDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of the associated display."
|
|
::= {dpsRTUDisplayEntry 4}
|
|
|
|
dpsRTUPntMap OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "A map of the points appearing in this display."
|
|
::= {dpsRTUDisplayEntry 5}
|
|
|
|
|
|
-- structure used to issue a control to a managed point
|
|
|
|
dpsRTUControlGrid OBJECT IDENTIFIER ::= {dpsRTU 3}
|
|
|
|
dpsRTUCPort OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUControlGrid 1}
|
|
|
|
dpsRTUCAddress OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUControlGrid 2}
|
|
|
|
dpsRTUCDisplay OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUControlGrid 3}
|
|
|
|
dpsRTUCPoint OBJECT-TYPE
|
|
SYNTAX INTEGER (1..64)
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_display point number (1-64)."
|
|
::= {dpsRTUControlGrid 4}
|
|
|
|
dpsRTUCAction OBJECT-TYPE
|
|
SYNTAX INTEGER { latch(1),
|
|
release(2),
|
|
momentary(3)
|
|
}
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "Requested action on point (RTU will ignore if invalid)."
|
|
::= {dpsRTUControlGrid 5}
|
|
|
|
dpsRTUAlarmGrid OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF DPSrtuAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Holds individual alarm point information."
|
|
::= {dpsRTU 5}
|
|
|
|
dpsRTUAlarmEntry OBJECT-TYPE
|
|
SYNTAX DPSrtuAlarmEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Detailed information about a particular RTU display."
|
|
INDEX {dpsRTUAPort, dpsRTUAAddress, dpsRTUADisplay, dpsRTUAPoint}
|
|
::= {dpsRTUAlarmGrid 1}
|
|
|
|
DPSrtuAlarmEntry ::= SEQUENCE { dpsRTUAPort INTEGER,
|
|
dpsRTUAAddress INTEGER,
|
|
dpsRTUADisplay INTEGER,
|
|
dpsRTUAPoint INTEGER,
|
|
dpsRTUAPntDesc DisplayString,
|
|
dpsRTUAState DisplayString
|
|
}
|
|
|
|
dpsRTUAPort OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU port number."
|
|
::= {dpsRTUAlarmEntry 1}
|
|
|
|
dpsRTUAAddress OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port address number."
|
|
::= {dpsRTUAlarmEntry 2}
|
|
|
|
dpsRTUADisplay OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address display number."
|
|
::= {dpsRTUAlarmEntry 3}
|
|
|
|
dpsRTUAPoint OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "RTU_port_address_display point number."
|
|
::= {dpsRTUAlarmEntry 4}
|
|
|
|
dpsRTUAPntDesc OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-write
|
|
STATUS mandatory
|
|
DESCRIPTION "A description of this point."
|
|
::= {dpsRTUAlarmEntry 5}
|
|
|
|
dpsRTUAState OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current state of this point."
|
|
::= {dpsRTUAlarmEntry 6}
|
|
|
|
--Table for accessing analog channel value
|
|
|
|
analogChannels OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF ChannelEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Holds information on analog channels"
|
|
::= {dpsRTU 6}
|
|
|
|
channelEntry OBJECT-TYPE
|
|
SYNTAX ChannelEntry
|
|
ACCESS not-accessible
|
|
STATUS mandatory
|
|
DESCRIPTION "Information about a particular channel"
|
|
INDEX {channelNumber}
|
|
::= {analogChannels 1}
|
|
|
|
ChannelEntry ::= SEQUENCE { channelNumber INTEGER,
|
|
enabled INTEGER,
|
|
description DisplayString,
|
|
value DisplayString,
|
|
thresholds INTEGER
|
|
}
|
|
|
|
channelNumber OBJECT-TYPE
|
|
SYNTAX INTEGER (0..999)
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Input channel number"
|
|
::= {channelEntry 1}
|
|
|
|
enabled OBJECT-TYPE
|
|
SYNTAX INTEGER { disabled (0),
|
|
enabled (1)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Enable status of channel"
|
|
::= {channelEntry 2}
|
|
|
|
description OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The user defined description of the channel"
|
|
::= {channelEntry 3}
|
|
|
|
value OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "The current value of the channel"
|
|
::= {channelEntry 4}
|
|
|
|
thresholds OBJECT-TYPE
|
|
SYNTAX INTEGER { noAlarms (0),
|
|
minorUnder (1),
|
|
minorOver (2),
|
|
majorUnder (3),
|
|
majorOver (4),
|
|
notDetected (5)
|
|
}
|
|
ACCESS read-only
|
|
STATUS mandatory
|
|
DESCRIPTION "Highest threshold level crossed, if MJ, MN is assumed"
|
|
::= {channelEntry 5}
|
|
|
|
-- TRAP definitions
|
|
|
|
tmonCRalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a critical alarm is set."
|
|
::= 10
|
|
|
|
tmonCRalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a critical alarm clears."
|
|
::= 11
|
|
|
|
tmonMJalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a major alarm is set."
|
|
::= 12
|
|
|
|
tmonMJalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a major alarm clears."
|
|
::= 13
|
|
|
|
tmonMNalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a minor alarm is set."
|
|
::= 14
|
|
|
|
tmonMNalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a minor alarm clears."
|
|
::= 15
|
|
|
|
tmonSTalarmSet TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a status alarm is set."
|
|
::= 16
|
|
|
|
tmonSTalarmClr TRAP-TYPE
|
|
ENTERPRISE tmonXM
|
|
VARIABLES { tmonASite, tmonADesc, tmonAState, tmonASeverity, tmonAChgDate,
|
|
tmonAChgTime, tmonAAuxDesc, tmonADispDesc, tmonAPntType,
|
|
tmonAPort, tmonAAddress, tmonADisplay, tmonAPoint, tmonCEvent,
|
|
tmonAIPAddr, tmonADevDesc }
|
|
DESCRIPTION "Generated when a status alarm clears."
|
|
::= 17
|
|
|
|
dpsRTUPointSet TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
dpsRTUAPort, dpsRTUAAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
dpsRTUAPntDesc, dpsRTUAState }
|
|
DESCRIPTION "Generated when a point is set."
|
|
::= 20
|
|
|
|
dpsRTUPointClr TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
dpsRTUAPntDesc, dpsRTUAState }
|
|
DESCRIPTION "Generated when a point clears."
|
|
::= 21
|
|
|
|
dpsRTUsumPSet TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when any point is set."
|
|
::= 101
|
|
|
|
dpsRTUsumPClr TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when all points clear."
|
|
::= 102
|
|
|
|
dpsRTUcomFailed TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when polled unit fails to respond."
|
|
::= 103
|
|
|
|
dpsRTUcomRestored TRAP-TYPE
|
|
ENTERPRISE dpsRTU
|
|
VARIABLES { sysDescr, sysLocation, dpsRTUDateTime }
|
|
DESCRIPTION "Generated when failed unit resumes responding."
|
|
::= 104
|
|
|
|
-- **************************************************************************
|
|
-- Granular TRAP definitions
|
|
--
|
|
-- The following section supports granular trapping available on selected
|
|
-- DPS remote telemetry units. This software selectable facility changes the
|
|
-- trap sent by a remote so equipped. The standard trap identifies a SET or
|
|
-- CLR event in the trap ID and binds variables identifying the specific
|
|
-- remote point associated with the event. A granular trap identifies a SET
|
|
-- or CLR event and the specific point associated with the event all in the
|
|
-- trap ID. This is accomplished by mapping all SET event/points into the
|
|
-- trap ID range 10001-19999 and all CLR event/points into the trap ID range
|
|
-- 20001-29999.
|
|
-- If the unit manages multiple displays, the displays are mapped
|
|
-- sequentially with each display occupying a 64 point range. For example, a
|
|
-- standalone standard or timestamp KDA which manages two displays, reports
|
|
-- SET event/points in the first display (discrete alarm points) in the range
|
|
-- 10001-10064. The CLR event/points for the same display would be reported
|
|
-- in the range 20001-20064. The second display (controls & housekeeping
|
|
-- alarm points) would have its SET event/points reported in the range 10065-
|
|
-- 10128 and its CLR event/points reported in the range 20065-20128.
|
|
-- SET and CLR definitions for the first 64 points have been included and
|
|
-- can be used as is for driving most SNMP manager mechanisms designed to key
|
|
-- on the trap ID for distinguishing and managing events. Additional events
|
|
-- can be added simply by editing the following trap definitions prior to
|
|
-- compiling this file into your SNMP manager. We recommend managing the SET
|
|
-- and CLR event definitions for a specific point as a single unit and using
|
|
-- the following simple rules:
|
|
-- + Adjust the numeric portion of the label preceeding TRAP-TYPE.
|
|
-- + Adjust the numeric reference in the DESCRIPTION text.
|
|
-- + Adjust the number on the last line of the definition.
|
|
--
|
|
-- Using these rules a definition for the 65th point would be:
|
|
--
|
|
-- dpsRTUp0065Set TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 65 is set."
|
|
-- ::= 10065
|
|
--
|
|
-- dpsRTUp0065Clr TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 65 clears."
|
|
-- ::= 20065
|
|
--
|
|
-- This editing can can be accomplished quite easily using a plain ASCII
|
|
-- file editor. The repetitive structure of the definitions also makes for
|
|
-- rapid scripted or programmed generation if any such tools are available.
|
|
-- A compressed file containing event/point definitions for 144 displays is
|
|
-- available (DPS_G36.zip 150K) which uncompressed (DPS_G36.mib 6.2M) can be
|
|
-- used for cut-and-paste editing if desired.
|
|
-- The definitions can be further customized if desired by similar editing
|
|
-- prior to compiling carefully observing the following conventions:
|
|
-- + The label preceeding the TRAP-TYPE designator can be edited with some
|
|
-- freedom but the label must be utterly unique among all trap definitions.
|
|
-- + The ENTERPRISE and VARIABLES sections must not be changed.
|
|
-- + The DESCRIPTION can be edited with complete freedom and is typically
|
|
-- ignored within the context of standard SNMP manager trap handling. The
|
|
-- quote mark before and after the text of the description are required.
|
|
-- + The number on the last line of the definition is the actual trap ID
|
|
-- defined and must also be utterly unique.
|
|
--
|
|
-- For example:
|
|
--
|
|
-- dpsRTUp0001Set TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 1 is set."
|
|
-- ::= 10001
|
|
--
|
|
-- dpsRTUp0001Clr TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when granular point 1 clears."
|
|
-- ::= 20001
|
|
--
|
|
-- Could be customized as:
|
|
--
|
|
-- dpsRTUFireAlarm TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when smoke detector activates."
|
|
-- ::= 10001
|
|
--
|
|
-- dpsRTUFireOut TRAP-TYPE
|
|
-- ENTERPRISE dpsRTU
|
|
-- VARIABLES { sysDescr, sysLocation, dpsRTUDateTime,
|
|
-- dpsRTUAPort, dpsRTUCAddress, dpsRTUADisplay, dpsRTUAPoint,
|
|
-- dpsRTUAPntDesc, dpsRTUAState }
|
|
-- DESCRIPTION "Generated when smoke detector deactivates."
|
|
-- ::= 20001
|
|
-- **************************************************************************
|
|
|
|
|
|
END
|