- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
1549 lines
51 KiB
Text
1549 lines
51 KiB
Text
--
|
||
-- C&C Power DC_SYSTEM MIB
|
||
-- Management Information Base for SNMP Network Management
|
||
--
|
||
-- Copyright 2004 C&C Power, Inc.
|
||
--
|
||
-- C&C Power shall not be liable for technical or
|
||
-- editorial errors or omissions contained herein. The information in
|
||
-- this document is provided "as is" without warranty of any kind and
|
||
-- is subject to change without notice. The warranties for C&C Power products
|
||
-- are set forth in the express limited warranty statements
|
||
-- accompanying such products. Nothing herein should be construed as
|
||
-- constituting an additional warranty.
|
||
--
|
||
-- The C&C Power Enterprise number is 18642.
|
||
-- The ASN.1 prefix to, and including the C&C Power Enterprise is:
|
||
-- 1.3.6.1.4.1.18642
|
||
--
|
||
-- MIB Version 1.0
|
||
-- *********************************************************************
|
||
-- Release History
|
||
-- Initial Release Date: August 9, 2004 (Version 1.0)
|
||
-- Author: Jeff Gear
|
||
-- Revision History
|
||
-- Date:
|
||
-- Revision:
|
||
-- *********************************************************************
|
||
|
||
CCPOWER-MIB DEFINITIONS ::= BEGIN
|
||
|
||
IMPORTS
|
||
enterprises FROM RFC1155-SMI
|
||
DisplayString FROM RFC1213-MIB
|
||
OBJECT-TYPE FROM RFC-1212
|
||
TRAP-TYPE FROM RFC-1215;
|
||
|
||
ccpower OBJECT IDENTIFIER ::= { enterprises 18642 }
|
||
dcSystem OBJECT IDENTIFIER ::= { ccpower 1 }
|
||
|
||
-- *********************************************************************
|
||
-- readWriteObjects definition
|
||
-- *********************************************************************
|
||
|
||
readWriteObjects OBJECT IDENTIFIER ::= { dcSystem 1 }
|
||
|
||
-- *********************************************************************
|
||
-- readWriteObjects.settings definition
|
||
-- *********************************************************************
|
||
|
||
settings OBJECT IDENTIFIER ::= { readWriteObjects 1 }
|
||
|
||
floatVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier DC Output Voltage.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 1 }
|
||
|
||
overloadCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Current which when exceeded will cause an alarm.
|
||
Return value is XXXX representing XXXX amps."
|
||
::= { settings 2 }
|
||
|
||
highVoltageAlarm OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause an alarm.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 3 }
|
||
|
||
lowVoltageAlarm OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause an alarm.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 4 }
|
||
|
||
disconnect1Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause a specific load to disconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 5 }
|
||
|
||
disconnect1Temperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Temperature which when exceeded will cause a specific load to disconnect.
|
||
Return value is XX representing XX <20>C."
|
||
::= { settings 6 }
|
||
|
||
disconnect1LoadShedSundayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 7 }
|
||
|
||
disconnect1LoadShedMondayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 8 }
|
||
|
||
disconnect1LoadShedTuesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 9 }
|
||
|
||
disconnect1LoadShedWednesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 10 }
|
||
|
||
disconnect1LoadShedThursdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 11 }
|
||
|
||
disconnect1LoadShedFridayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 12 }
|
||
|
||
disconnect1LoadShedSaturdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 13 }
|
||
|
||
disconnect2Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause a specific load to disconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 14 }
|
||
|
||
disconnect2Temperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Temperature which when exceeded will cause a specific load to disconnect.
|
||
Return value is XX representing XX <20>C."
|
||
::= { settings 15 }
|
||
|
||
disconnect2LoadShedSundayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 16 }
|
||
|
||
disconnect2LoadShedMondayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 17 }
|
||
|
||
disconnect2LoadShedTuesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 18 }
|
||
|
||
disconnect2LoadShedWednesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 19 }
|
||
|
||
disconnect2LoadShedThursdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 20 }
|
||
|
||
disconnect2LoadShedFridayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 21 }
|
||
|
||
disconnect2LoadShedSaturdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 22 }
|
||
|
||
disconnect3Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when exceeded will cause a specific load to disconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 23 }
|
||
|
||
disconnect3Temperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Temperature which when exceeded will cause a specific load to disconnect.
|
||
Return value is XX representing XX <20>C."
|
||
::= { settings 24 }
|
||
|
||
disconnect3LoadShedSundayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 25 }
|
||
|
||
disconnect3LoadShedMondayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 26 }
|
||
|
||
disconnect3LoadShedTuesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 27 }
|
||
|
||
disconnect3LoadShedWednesdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 28 }
|
||
|
||
disconnect3LoadShedThursdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 29 }
|
||
|
||
disconnect3LoadShedFridayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 30 }
|
||
|
||
disconnect3LoadShedSaturdayOff OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to disconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 31 }
|
||
|
||
reconnect1Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when reached will cause a specific load to reconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 32 }
|
||
|
||
reconnect1LoadShedSundayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 33 }
|
||
|
||
reconnect1LoadShedMondayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 34 }
|
||
|
||
reconnect1LoadShedTuesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 35 }
|
||
|
||
reconnect1LoadShedWednesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 36 }
|
||
|
||
reconnect1LoadShedThursdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 37 }
|
||
|
||
reconnect1LoadShedFridayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 38 }
|
||
|
||
reconnect1LoadShedSaturdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 39 }
|
||
|
||
reconnect2Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when reached will cause a specific load to reconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 40 }
|
||
|
||
reconnect2LoadShedSundayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 41 }
|
||
|
||
reconnect2LoadShedMondayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 42 }
|
||
|
||
reconnect2LoadShedTuesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 43 }
|
||
|
||
reconnect2LoadShedWednesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 44 }
|
||
|
||
reconnect2LoadShedThursdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 45 }
|
||
|
||
reconnect2LoadShedFridayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 46 }
|
||
|
||
reconnect2LoadShedSaturdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 47 }
|
||
|
||
reconnect3Voltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Voltage which when reached will cause a specific load to reconnect.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 48 }
|
||
|
||
reconnect3LoadShedSundayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Sunday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 49 }
|
||
|
||
reconnect3LoadShedMondayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Monday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 50 }
|
||
|
||
reconnect3LoadShedTuesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Tuesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 51 }
|
||
|
||
reconnect3LoadShedWednesdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Wednesday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 52 }
|
||
|
||
reconnect3LoadShedThursdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Thursday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 53 }
|
||
|
||
reconnect3LoadShedFridayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Friday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 54 }
|
||
|
||
reconnect3LoadShedSaturdayOn OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Time on Saturday which when reached will cause a specific load to reconnect.
|
||
Return value is XX:XX representing HH:MM."
|
||
::= { settings 55 }
|
||
|
||
equalizeTime OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of hours the equalize voltage is to be applied.
|
||
Return value is XXX representing XX.X hours."
|
||
::= { settings 56 }
|
||
|
||
equalizeVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Equalize voltage to be applied.
|
||
Return value is XXX representing XX.X volts."
|
||
::= { settings 57 }
|
||
|
||
batteryResistancePercentChange OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Resistance percentange change that when reached will cause an alarm.
|
||
Return value is XXX representing XXX %."
|
||
::= { settings 58 }
|
||
|
||
batteryResistanceTestInterval OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance test interval.
|
||
Return value is XX representing XX weeks."
|
||
::= { settings 59 }
|
||
|
||
loadShedTimeControl OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
enabled(1),
|
||
disabled(2)
|
||
}
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Load shed time control enabled/disabled status.
|
||
Return value: 1 = time control enabled, 2 = time control disabled."
|
||
::= { settings 60 }
|
||
|
||
batteryFloatCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-write
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery float current.
|
||
Return value is XXX representing XXX amps."
|
||
::= { settings 61 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects definition
|
||
-- *********************************************************************
|
||
|
||
readOnlyObjects OBJECT IDENTIFIER ::= { dcSystem 2 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.rectifiers definition
|
||
-- *********************************************************************
|
||
|
||
rectifiers OBJECT IDENTIFIER ::= { readOnlyObjects 1 }
|
||
|
||
rectifierFloatVoltage OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier float voltage.
|
||
Return value is XXX representing XX.X volts. Valid ranges are 24.0 to 57.0 volts."
|
||
::= { rectifiers 1 }
|
||
|
||
rectifierLoadCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier DC load current.
|
||
Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 5000 amps."
|
||
::= { rectifiers 2}
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.batteries definition
|
||
-- *********************************************************************
|
||
|
||
batteries OBJECT IDENTIFIER ::= { readOnlyObjects 2 }
|
||
|
||
batteryCurrent OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery current.
|
||
Return value is XXXX representing XXXX amps. Valid ranges are 0000 to 1000 amps."
|
||
::= { batteries 1 }
|
||
|
||
batteryTemperature OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery temperature.
|
||
Return value is XX representing XX <20>C. Valid ranges are -40 to 99 <20>C."
|
||
::= { batteries 2 }
|
||
|
||
batteryResistanceReference OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Initial battery resistance.
|
||
Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms."
|
||
::= { batteries 3 }
|
||
|
||
batteryResistanceReading OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Last battery resistance reading.
|
||
Return value is XXXXX representing X.XXXX ohms. Valid ranges are 0.0000 to 5.0000 ohms."
|
||
::= { batteries 4 }
|
||
|
||
batteryResistanceChange OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Percent change from last battery resistance reading.
|
||
Return value is XXX representing XXX %. Valid ranges are 001 to 999 %."
|
||
::= { batteries 5 }
|
||
|
||
batteryCycles1 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles less than 1 minute.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 6 }
|
||
|
||
batteryCycles1to5 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles from 1 to 5 minutes.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 7 }
|
||
|
||
batteryCycles5to15 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles from 5 to 15 minutes.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 8 }
|
||
|
||
batteryCycles15 OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Number of discharge/recharge cycles greater than 15 minutes.
|
||
Return value is XXX representing XXX cycles. Valid ranges are 000 to 255 cycles."
|
||
::= { batteries 9 }
|
||
|
||
batteryCycles15LastCycleDate OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Last cycle date of batteryCycles15.
|
||
Return value is MM-DD-YY, HH-MM."
|
||
::= { batteries 10 }
|
||
|
||
batteryCycles15LastDuration OBJECT-TYPE
|
||
SYNTAX INTEGER
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Duration of batteryCycles15 last cycle.
|
||
Return value is XXXX representing XXXX minutes."
|
||
::= { batteries 11 }
|
||
|
||
batteryTestFault OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
abort1(1),
|
||
abort2(2),
|
||
abort3(3),
|
||
none(4)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery failure has occured during battery restistance test.
|
||
Return value: 1 = Abort 1, 2 = Abort 2, 3 = Abort 3, 4 = None."
|
||
::= { batteries 12 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.factorySettings definition
|
||
-- *********************************************************************
|
||
|
||
factorySettings OBJECT IDENTIFIER ::= { readOnlyObjects 3 }
|
||
|
||
floatVoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Float voltage factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 1 }
|
||
|
||
highVoltageAlarmPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "High voltage alarm factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 2 }
|
||
|
||
lowVoltageAlarmPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage alarm factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 3 }
|
||
|
||
disconnect1VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect voltage 1 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 4 }
|
||
|
||
disconnect1TemperaturePreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect temperature 1 factory setting.
|
||
Return value is XX <20>C."
|
||
::= { factorySettings 5 }
|
||
|
||
disconnect1LoadShedSundayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Sunday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 6 }
|
||
|
||
disconnect1LoadShedMondayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Monday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 7 }
|
||
|
||
disconnect1LoadShedTuesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Tuesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 8 }
|
||
|
||
disconnect1LoadShedWednesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Wednesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 9 }
|
||
|
||
disconnect1LoadShedThursdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Thursday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 10 }
|
||
|
||
disconnect1LoadShedFridayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Friday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 11 }
|
||
|
||
disconnect1LoadShedSaturdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 1 load shed Saturday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 12 }
|
||
|
||
reconnectVoltage1Presets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Reconnect voltage 1 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 13 }
|
||
|
||
disconnect2VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect voltage 2 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 14 }
|
||
|
||
disconnect2TemperaturePreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect temperature 2 factory setting.
|
||
Return value is XX <20>C."
|
||
::= { factorySettings 15 }
|
||
|
||
disconnect2LoadShedSundayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Sunday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 16 }
|
||
|
||
disconnect2LoadShedMondayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Monday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 17 }
|
||
|
||
disconnect2LoadShedTuesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Tuesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 18 }
|
||
|
||
disconnect2LoadShedWednesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Wednesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 19 }
|
||
|
||
disconnect2LoadShedThursdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Thursday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 20 }
|
||
|
||
disconnect2LoadShedFridayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Friday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 21 }
|
||
|
||
disconnect2LoadShedSaturdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 2 load shed Saturday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 22 }
|
||
|
||
reconnect2VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Reconnect voltage 2 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 23 }
|
||
|
||
disconnect3VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect voltage 3 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 24 }
|
||
|
||
disconnect3TemperaturePreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect temperature 3 factory setting.
|
||
Return value is XX <20>C."
|
||
::= { factorySettings 25 }
|
||
|
||
disconnect3LoadShedSundayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Sunday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 26 }
|
||
|
||
disconnect3LoadShedMondayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Monday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 27 }
|
||
|
||
disconnect3LoadShedTuesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Tuesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 28 }
|
||
|
||
disconnect3LoadShedWednesdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Wednesday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 29 }
|
||
|
||
disconnect3LoadShedThursdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Thursday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 30 }
|
||
|
||
disconnect3LoadShedFridayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Friday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 31 }
|
||
|
||
disconnect3LoadShedSaturdayPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Disconnect 3 load shed Saturday time settings.
|
||
Return value is XX:Xx off, XX:XX on."
|
||
::= { factorySettings 32 }
|
||
|
||
reconnect3VoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Reconnect voltage 3 factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 33 }
|
||
|
||
overloadCurrentPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Overload current factory setting range.
|
||
Return value is XXXX amps min, XXXX amps max."
|
||
::= { factorySettings 34 }
|
||
|
||
maximumCurrentPreset OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Maximum current factory setting.
|
||
Return value is XXXX amps."
|
||
::= { factorySettings 35 }
|
||
|
||
batteryFloatCurrentPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery float current factory settings.
|
||
Return value is XXX amps min, XXX amps max."
|
||
::= { factorySettings 36 }
|
||
|
||
equalizeTimePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Equalize time factory setting range.
|
||
Return value is 00.0 hours min, XX.X hours max."
|
||
::= { factorySettings 37 }
|
||
|
||
equalizeVoltagePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Equalize voltage factory setting range.
|
||
Return value is XX.X volts min, XX.X volts max."
|
||
::= { factorySettings 38 }
|
||
|
||
batteryResistancePresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance percent change factory setting range.
|
||
Return value is XXX % min, XXX % max."
|
||
::= { factorySettings 39 }
|
||
|
||
batteryTestIntervalPresets OBJECT-TYPE
|
||
SYNTAX DisplayString
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance test interval factory setting range.
|
||
Return value is XX weeks min, XX weeks max."
|
||
::= { factorySettings 40 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.alarmStatus definition
|
||
-- *********************************************************************
|
||
|
||
alarmStatus OBJECT IDENTIFIER ::= { readOnlyObjects 4 }
|
||
|
||
highVoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "High voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 1 }
|
||
|
||
lowVoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 2 }
|
||
|
||
overloadAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Overload alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 3 }
|
||
|
||
breakerAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Breaker alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 4 }
|
||
|
||
acFailureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "AC failure alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 5 }
|
||
|
||
fanFailureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Fan failure alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 6 }
|
||
|
||
rectifierFailureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Rectifier failure alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 7 }
|
||
|
||
majorAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Major alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 8 }
|
||
|
||
lowVoltageDisconnect1TemperatureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 1 high temperature alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 9 }
|
||
|
||
lowVoltageDisconnect2TemperatureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 2 high temperature alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 10 }
|
||
|
||
lowVoltageDisconnect3TemperatureAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 3 high temperature alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 11 }
|
||
|
||
lowVoltageDisconnect1VoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 1 low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 12 }
|
||
|
||
lowVoltageDisconnect2VoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 2 low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 13 }
|
||
|
||
lowVoltageDisconnect3VoltageAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Low voltage disconnect 3 low voltage alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 14 }
|
||
|
||
batteryResistanceAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 15 }
|
||
|
||
batteryCurrentAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery resistance alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 16 }
|
||
|
||
batteryTestAbortCondition1AlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery test abort condition 1 alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 17 }
|
||
|
||
batteryTestAbortCondition2AlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery test abort condition 2 alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 18 }
|
||
|
||
batteryTestAbortCondition3AlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery test abort condition 3 alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 19 }
|
||
|
||
batteryDisconnectAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Battery disconnect alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 20 }
|
||
|
||
fuseAlarmStatus OBJECT-TYPE
|
||
SYNTAX INTEGER {
|
||
inactive(1),
|
||
active(2)
|
||
}
|
||
ACCESS read-only
|
||
STATUS mandatory
|
||
DESCRIPTION "Fuse alarm status.
|
||
Return value 1 = alarm inactive, 2 = alarm active."
|
||
::= { alarmStatus 21 }
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.digitalSensorAlarms definition
|
||
-- *********************************************************************
|
||
|
||
digitalSensorAlarms OBJECT IDENTIFIER ::= { readOnlyObjects 5 }
|
||
|
||
breakerTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
--#SEVERITY CRITICAL
|
||
DESCRIPTION "Breaker has tripped."
|
||
::= 0
|
||
|
||
fuseTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
--#SEVERITY CRITICAL
|
||
DESCRIPTION "Fuse has opened."
|
||
::= 1
|
||
|
||
batteryDisconnectTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
--#SEVERITY CRITICAL
|
||
DESCRIPTION "Battery disconnect has operated."
|
||
::= 2
|
||
|
||
programmableTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Programmable alarm has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 3
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.SystemAlarms definition
|
||
-- *********************************************************************
|
||
|
||
systemAlarms OBJECT IDENTIFIER ::= { readOnlyObjects 6 }
|
||
|
||
highVoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Float voltage has exceeded preset value.
|
||
Return value: High voltage alarm XX.X volts."
|
||
--#SEVERITY WARNING
|
||
::= 4
|
||
|
||
lowVoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Float voltage is below preset value.
|
||
Return value: Low voltage alarm XX.X volts."
|
||
--#SEVERITY WARNING
|
||
::= 5
|
||
|
||
loadOverCurrentTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load current has exceeded preset value.
|
||
Return value: Load over current alarm XXXX amps."
|
||
--#SEVERITY WARNING
|
||
::= 6
|
||
|
||
batteryFloatCurrentTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery float current has exceeded preset value.
|
||
Return value: Battery float current alarm XXXX amps."
|
||
--#SEVERITY CRITICAL
|
||
::= 7
|
||
|
||
loadDisconnect1VoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 voltage has dropped below preset value.
|
||
Return value: Load disconnect 1 voltage XX.X volts."
|
||
--#SEVERITY CRITICAL
|
||
::= 8
|
||
|
||
loadDisconnect2VoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 voltage has dropped below preset value.
|
||
Return value: Load disconnect 2 voltage XX.X volts."
|
||
--#SEVERITY CRITICAL
|
||
::= 9
|
||
|
||
loadDisconnect3VoltageTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 voltage has dropped below preset value.
|
||
Return value: Load disconnect 3 voltage XX.X volts."
|
||
--#SEVERITY CRITICAL
|
||
::= 10
|
||
|
||
loadDisconnect1TemperatureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 temperature has exceeded preset value.
|
||
Return value: Load disconnect 1 temperature alarm XX <20>C."
|
||
--#SEVERITY CRITICAL
|
||
::= 11
|
||
|
||
loadDisconnect2TemperatureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 temperature has exceeded preset value.
|
||
Return value: Load disconnect 2 temperature alarm XX <20>C."
|
||
--#SEVERITY CRITICAL
|
||
::= 12
|
||
|
||
loadDisconnect3TemperatureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 temperature has exceeded preset value.
|
||
Return value: Load disconnect 3 temperature alarm XX <20>C."
|
||
--#SEVERITY CRITICAL
|
||
::= 13
|
||
|
||
rectifierFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectifier failure.
|
||
Return value: Rectifier failure."
|
||
--#SEVERITY WARNING
|
||
::= 14
|
||
|
||
fanFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectifier fan has failed.
|
||
Return value: Fan failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 15
|
||
|
||
acFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectifier has lost AC input power.
|
||
Return value: AC failure."
|
||
--#SEVERITY CRITICAL
|
||
::= 16
|
||
|
||
majorFailureTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Multiple failures of AC, rectififers, fans or a programmed alarm.
|
||
Return value: Multiple AC, fan, rectifier or optional alarm failures has occurred."
|
||
--#SEVERITY CRITICAL
|
||
::= 17
|
||
|
||
batteryResistanceTrap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery resistance has increased by a programmed percentage.
|
||
Return value: Battery resistance alarm X.XXXX ohms, XXX %."
|
||
--#SEVERITY WARNING
|
||
::= 18
|
||
|
||
batteryTestAbort1Trap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery failure abort 1 has occured during battery resistance test.
|
||
Return value: Battery test failure: Abort 1."
|
||
--#SEVERITY CRITICAL
|
||
::= 19
|
||
|
||
batteryTestAbort2Trap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery failure abort 2 has occured during battery resistance test.
|
||
Return value: Battery test failure: Abort 2."
|
||
--#SEVERITY CRITICAL
|
||
::= 20
|
||
|
||
batteryTestAbort3Trap TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery failure abort 3 has occured during battery resistance test.
|
||
Return value: Battery test failure: Abort 3."
|
||
--#SEVERITY CRITICAL
|
||
::= 21
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.digitalSensorAlarmClears definition
|
||
-- *********************************************************************
|
||
|
||
digitalSensorAlarmClears OBJECT IDENTIFIER ::= { readOnlyObjects 7 }
|
||
|
||
breakerTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Breaker alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 100
|
||
|
||
fuseTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Fuse alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 101
|
||
|
||
batteryDisconnectTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery disconnect alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 102
|
||
|
||
programmableTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Programmable alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 103
|
||
|
||
-- *********************************************************************
|
||
-- readOnlyObjects.SystemAlarmClears definition
|
||
-- *********************************************************************
|
||
|
||
systemAlarmClears OBJECT IDENTIFIER ::= { readOnlyObjects 8 }
|
||
|
||
highVoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "High voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 104
|
||
|
||
lowVoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Low voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 105
|
||
|
||
loadOverCurrentTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load over current alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 106
|
||
|
||
batteryFloatCurrentTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery float current alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 107
|
||
|
||
loadDisconnect1VoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 108
|
||
|
||
loadDisconnect2VoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 109
|
||
|
||
loadDisconnect3VoltageTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 voltage alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 110
|
||
|
||
loadDisconnect1TemperatureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 1 temperature alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 111
|
||
|
||
loadDisconnect2TemperatureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 2 temperature alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 112
|
||
|
||
loadDisconnect3TemperatureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Load disconnect 3 temperature alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 113
|
||
|
||
rectifierFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Rectififer failure alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 114
|
||
|
||
fanFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Fan failure alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 115
|
||
|
||
acFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "AC failure alarm been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 116
|
||
|
||
majorFailureTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Major failure alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 117
|
||
|
||
batteryResistanceTrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery resistance alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 118
|
||
|
||
batteryTestAbort1TrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery test abort 1 alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 119
|
||
|
||
batteryTestAbort2TrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery test abort 2 alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 120
|
||
|
||
batteryTestAbort3TrapClear TRAP-TYPE
|
||
ENTERPRISE ccpower
|
||
DESCRIPTION "Battery test abort 3 alarm has been cleared."
|
||
--#SEVERITY INFORMATIONAL
|
||
::= 121
|
||
|
||
END
|
||
|
||
|