- Remove PVC volume mount from k8s/deployment.yaml - Delete k8s/mib-pvc.yaml (no longer needed) - Update .gitignore to commit MIB files to git - Add mix import_mibs task to copy MIBs from LibreNMS - Add all MIB files from priv/mibs/ to git This fixes the multi-attach volume error in Kubernetes where new pods couldn't start because the RWO (ReadWriteOnce) PVC was attached to the old pod. MIBs are now part of the Docker image and can be used by all pods simultaneously.
2572 lines
96 KiB
Text
2572 lines
96 KiB
Text
--------------------------------------------------------------------------------
|
|
-- Avocent ACS MIB
|
|
-- Copyright 2009 Avocent Corporation
|
|
-- Revision: 2.0.1
|
|
-- Last Modified: October 10, 2010
|
|
--------------------------------------------------------------------------------
|
|
|
|
ACS-MIB DEFINITIONS ::= BEGIN
|
|
|
|
IMPORTS
|
|
Gauge,TimeTicks,IpAddress,Counter,NetworkAddress
|
|
FROM RFC1155-SMI
|
|
PhysAddress
|
|
FROM RFC1213-MIB
|
|
enterprises, MODULE-IDENTITY
|
|
FROM SNMPv2-SMI
|
|
OBJECT-TYPE, MODULE-IDENTITY, OBJECT-IDENTITY, Integer32
|
|
FROM SNMPv2-SMI
|
|
DisplayString
|
|
FROM SNMPv2-TC
|
|
InterfaceIndex, InterfaceIndexOrZero
|
|
FROM IF-MIB
|
|
TRAP-TYPE
|
|
FROM RFC-1215;
|
|
|
|
--------------------------------------------------------------------------------
|
|
-- Object Groupings
|
|
--------------------------------------------------------------------------------
|
|
|
|
--@ Note: every product type should be uniquely identified underneath the
|
|
--@ acsProducts object group. Each product should report its unique acsProducts
|
|
--@ OBJECT IDENTIFIER in mib-2.system.sysObjectID. Please see the file
|
|
--@ "_Avocent Enterprise Object Identifier Assignment.txt" for a list of the
|
|
--@ IDs that have been assigned.
|
|
|
|
-- enterprises .1.3.6.1.4.1
|
|
|
|
-- avocent OBJECT IDENTIFIER ::= { enterprises 10418 }
|
|
|
|
acs MODULE-IDENTITY
|
|
LAST-UPDATED "201010100000Z"
|
|
ORGANIZATION "Avocent Corporation"
|
|
CONTACT-INFO "postal : Avocent Corporation
|
|
47281 Bayside Parkway
|
|
Fremont, CA 94538, USA
|
|
e-mail : Technical Support
|
|
techsupport@avocent.com"
|
|
DESCRIPTION
|
|
"This module defines the Avocent MIB extensions to
|
|
ACS60xx products."
|
|
REVISION "201010100000Z"
|
|
DESCRIPTION "Add products acs6004 and acs6008"
|
|
REVISION "200912110000Z"
|
|
DESCRIPTION "Extended acsPowerMgmt to support data monitoring
|
|
and Avocent PM-PDUs"
|
|
REVISION "200709170000Z"
|
|
DESCRIPTION "First Draft"
|
|
::= { enterprises 10418 16 }
|
|
|
|
acsProducts OBJECT IDENTIFIER ::= { acs 1 }
|
|
acsManagement OBJECT IDENTIFIER ::= { acs 2 }
|
|
--
|
|
acs6016 OBJECT IDENTIFIER ::= { acsProducts 1 } -- 10418.16.1.1
|
|
acs6032 OBJECT IDENTIFIER ::= { acsProducts 2 } -- 10418.16.1.2
|
|
acs6048 OBJECT IDENTIFIER ::= { acsProducts 3 } -- 10418.16.1.3
|
|
acs6004 OBJECT IDENTIFIER ::= { acsProducts 4 } -- 10418.16.1.4
|
|
acs6008 OBJECT IDENTIFIER ::= { acsProducts 5 } -- 10418.16.1.5
|
|
|
|
acsAppliance OBJECT IDENTIFIER ::= { acsManagement 1 } -- 10418.16.2.1
|
|
acsSessions OBJECT IDENTIFIER ::= { acsManagement 2 } -- 10418.16.2.2
|
|
acsSerialPort OBJECT IDENTIFIER ::= { acsManagement 3 } -- 10418.16.2.3
|
|
acsPowerMgmt OBJECT IDENTIFIER ::= { acsManagement 5 } -- 10418.16.2.5
|
|
|
|
-- objects under acsPowerMgmt
|
|
-- acsPowerMgmtNumSerialPorts ::= { acsPowerMgmt 1 }
|
|
-- acsPowerMgmtSerialTable ::= { acsPowerMgmt 2 }
|
|
-- acsPowerMgmtPDUTable ::= { acsPowerMgmt 3 }
|
|
-- acsPowerMgmtTotalNumberOfOutlets ::= { acsPowerMgmt 4 }
|
|
-- acsPowerMgmtOutletsTable ::= { acsPowerMgmt 5 }
|
|
-- acsPowerMgmtNumberOfOutletGroup ::= { acsPowerMgmt 6 }
|
|
-- acsPowerMgmtGroupTable ::= { acsPowerMgmt 7 }
|
|
-- acsPowerMgmtPhasesTable ::= { acsPowerMgmt 8 }
|
|
-- acsPowerMgmtBanksTable ::= { acsPowerMgmt 9 }
|
|
-- acsPowerMgmtEnvMonTable ::= { acsPowerMgmt 10 }
|
|
-- acsPowerMgmtOutElecMonTable ::= { acsPowerMgmt 11 }
|
|
|
|
|
|
--
|
|
-- Note that traps are defined in a separate trap MIB
|
|
--
|
|
acsTrapObject OBJECT IDENTIFIER ::= { acsManagement 6 } -- 10418.16.2.6
|
|
|
|
--
|
|
-- Type Definitions
|
|
--
|
|
|
|
--
|
|
-- Each enumeration represents the states of the appliance power supplies.
|
|
PowerSupplyState ::= INTEGER
|
|
{
|
|
statePowerOn(1),
|
|
statePowerOff(2),
|
|
powerNotInstaled(9999)
|
|
}
|
|
|
|
--
|
|
-- Each enumeration represents the speed of the serial port.
|
|
SerialPortSpeed ::= INTEGER
|
|
{
|
|
speed300bps(300),
|
|
speed600bps(600),
|
|
speed1200bps(1200),
|
|
speed2400bps(2400),
|
|
speed4800bps(4800),
|
|
speed9600bps(9600),
|
|
speed19200bps(19200),
|
|
speed38400bps(38400),
|
|
speed57600bps(57600),
|
|
speed115200bps(115200),
|
|
speed230400bps(230400),
|
|
speed460800bps(460800)
|
|
}
|
|
|
|
--
|
|
-- Each enumeration represents the state of the RS-232C signal.
|
|
SerialPortSignalState ::=INTEGER
|
|
{
|
|
up(1),
|
|
down(2)
|
|
}
|
|
|
|
--
|
|
-- Each enumeration represents the RJ-45 pin-out
|
|
SerialPortPinOut ::=INTEGER
|
|
{
|
|
cyclades(1),
|
|
cisco(2)
|
|
}
|
|
|
|
--
|
|
-- acsAppliance
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 1 } 10418.16.2.1
|
|
--
|
|
acsHostName OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The appliance name"
|
|
::= { acsAppliance 1 }
|
|
|
|
acsProductModel OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..50) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The appliance product model"
|
|
::= { acsAppliance 2 }
|
|
|
|
acsPartNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The part number of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { acsAppliance 3 }
|
|
|
|
acsSerialNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The serial number of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { acsAppliance 4 }
|
|
|
|
acsEIDNumber OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The electronic ID number (EID) of this appliance as shown on the label
|
|
attached or imprinted on the appliance."
|
|
::= { acsAppliance 5 }
|
|
|
|
acsBootcodeVersion OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the bootcode of this appliance."
|
|
::= { acsAppliance 6 }
|
|
|
|
acsFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The version of the firmware of this appliance."
|
|
::= { acsAppliance 7 }
|
|
|
|
acsPowerSupply OBJECT-IDENTITY
|
|
STATUS current
|
|
DESCRIPTION
|
|
"It gives information about Power Supply of this appliance"
|
|
::= { acsAppliance 8 }
|
|
|
|
acsPowerSupplyNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the power supplies of this appliance"
|
|
::= { acsPowerSupply 1 }
|
|
|
|
acsPowerSupplyStatePw1 OBJECT-TYPE
|
|
SYNTAX PowerSupplyState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the first power supply"
|
|
::= { acsPowerSupply 2 }
|
|
|
|
acsPowerSupplyStatePw2 OBJECT-TYPE
|
|
SYNTAX PowerSupplyState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the second power supply"
|
|
::= { acsPowerSupply 3 }
|
|
|
|
acsReboot OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reboot(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of reboot(2) will reboot the appliance.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
reboot(2) = when SET the appliance immediately reboots."
|
|
::= { acsAppliance 9 }
|
|
|
|
--
|
|
-- acsSessions
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 2 } 10418.16.2.2
|
|
--
|
|
acsActiveSessionsNumberOfSession OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of active sessions."
|
|
::= { acsSessions 1 }
|
|
|
|
acsActiveSessionsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsActiveSessionsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the list of active sessions."
|
|
::= { acsSessions 2 }
|
|
|
|
acsActiveSessionsTableEntry OBJECT-TYPE
|
|
SYNTAX AcsActiveSessionsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the active session"
|
|
INDEX { acsActiveSessionsTableIndex }
|
|
::= { acsActiveSessionsTable 1 }
|
|
|
|
AcsActiveSessionsTableEntry ::= SEQUENCE {
|
|
acsActiveSessionsTableIndex InterfaceIndexOrZero,
|
|
acsActiveSessionsTableUser DisplayString, -- user name
|
|
acsActiveSessionsTableGroup DisplayString, -- group name
|
|
acsActiveSessionsTableType DisplayString, -- RO/RW-ssh,telnet or web
|
|
acsActiveSessionsTableConnection DisplayString, -- type + target name
|
|
acsActiveSessionsTableSessionTime DisplayString, -- time of session
|
|
acsActiveSessionsTableFrom DisplayString, -- source of the session
|
|
acsActiveSessionsTableKill INTEGER
|
|
}
|
|
|
|
acsActiveSessionsTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique index representing an entry in this table."
|
|
::= { acsActiveSessionsTableEntry 1 }
|
|
|
|
acsActiveSessionsTableUser OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the user that opens this session."
|
|
::= { acsActiveSessionsTableEntry 2 }
|
|
|
|
acsActiveSessionsTableGroup OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The name of the group that the user belongs to."
|
|
::= { acsActiveSessionsTableEntry 3 }
|
|
|
|
acsActiveSessionsTableType OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The session type."
|
|
::= { acsActiveSessionsTableEntry 4 }
|
|
|
|
acsActiveSessionsTableConnection OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Connection type."
|
|
::= { acsActiveSessionsTableEntry 5 }
|
|
|
|
acsActiveSessionsTableSessionTime OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Time of the session"
|
|
::= { acsActiveSessionsTableEntry 6 }
|
|
|
|
acsActiveSessionsTableFrom OBJECT-TYPE
|
|
SYNTAX DisplayString ( SIZE (0..32) )
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The source IP address of the session."
|
|
::= { acsActiveSessionsTableEntry 7 }
|
|
|
|
acsActiveSessionsTableKill OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
killSession(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of killSession(2) will kill the session.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
killSession(2)= when SET the appliance immediately kills the session."
|
|
::= { acsActiveSessionsTableEntry 8 }
|
|
|
|
--
|
|
-- acsSerialPort
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 3 } 10418.16.2.3
|
|
--
|
|
|
|
acsSerialPortNumberOfPorts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of Serial Ports (physical serial port plus Aux Port."
|
|
::= { acsSerialPort 1 }
|
|
|
|
acsSerialPortTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsSerialPortTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains information about serial ports."
|
|
::= { acsSerialPort 2 }
|
|
|
|
acsSerialPortTableEntry OBJECT-TYPE
|
|
SYNTAX AcsSerialPortTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about specific serial port."
|
|
INDEX { acsSerialPortTableNumber }
|
|
::= { acsSerialPortTable 1 }
|
|
|
|
AcsSerialPortTableEntry ::= SEQUENCE {
|
|
acsSerialPortTableNumber Integer32, -- serial port number
|
|
acsSerialPortTableDeviceName DisplayString, -- associated device name
|
|
acsSerialPortTableStatus INTEGER, -- status of serial port
|
|
acsSerialPortTableName DisplayString, -- associated name
|
|
acsSerialPortTableProfile INTEGER, -- configured profile
|
|
acsSerialPortTablePinOut SerialPortPinOut, -- configure RJ45 pin-out
|
|
acsSerialPortTableComSpeed SerialPortSpeed, -- configured speed
|
|
acsSerialPortTableComParity INTEGER, -- configured parity
|
|
acsSerialPortTableComDataSize Integer32, -- configured data size
|
|
acsSerialPortTableComStopBits Integer32, -- configured stop bits
|
|
acsSerialPortTableComFlowControl INTEGER, -- configured flow control
|
|
acsSerialPortTableSignalStateDTR SerialPortSignalState, -- state of DTR RS-232C signal
|
|
acsSerialPortTableSignalStateDCD SerialPortSignalState, -- state of DCD RS-232C signal
|
|
acsSerialPortTableSignalStateRTS SerialPortSignalState, -- state of RTS RS-232C signal
|
|
acsSerialPortTableSignalStateCTS SerialPortSignalState, -- state of CTS RS-232C signal
|
|
acsSerialPortTableTxBytes Integer32, -- number of transmitted bytes
|
|
acsSerialPortTableRxBytes Integer32, -- number of received bytes
|
|
acsSerialPortTableFrameError Integer32, -- number of detected frame errors
|
|
acsSerialPortTableParityError Integer32, -- number of detected parity errors
|
|
acsSerialPortTableBreak Integer32, -- number of detected break
|
|
acsSerialPortTableOverrun Integer32 -- number of detected overrun errors
|
|
}
|
|
|
|
acsSerialPortTableNumber OBJECT-TYPE
|
|
SYNTAX Integer32 (1..49)
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A unique index representing an entry in this table.
|
|
It is the number of the serial port. For AUX port,
|
|
the number will be the number of physical serial ports plus 1."
|
|
::= { acsSerialPortTableEntry 1 }
|
|
|
|
acsSerialPortTableDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The associated device name for the serial port."
|
|
::= { acsSerialPortTableEntry 2 }
|
|
|
|
acsSerialPortTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
disabled(1),
|
|
idle(2),
|
|
inUse(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The status of the serial port:
|
|
disabled(1) = it was configured as disable.
|
|
idle(2) = there is not any session opened in this port.
|
|
inUse(3) = there is session(s) opened in this port."
|
|
::= { acsSerialPortTableEntry 3 }
|
|
|
|
acsSerialPortTableName OBJECT-TYPE
|
|
SYNTAX DisplayString (SIZE (0..25))
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name associated with this serial port."
|
|
::= { acsSerialPortTableEntry 4 }
|
|
|
|
acsSerialPortTableProfile OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
casProfile(1),
|
|
tsProfile(2),
|
|
dialInProfile(3),
|
|
powerProfile(4)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Configured profile for this serial port."
|
|
::= { acsSerialPortTableEntry 5 }
|
|
|
|
acsSerialPortTablePinOut OBJECT-TYPE
|
|
SYNTAX SerialPortPinOut
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"RJ45 Pin-out configured for this serial port."
|
|
::= { acsSerialPortTableEntry 6 }
|
|
|
|
acsSerialPortTableComSpeed OBJECT-TYPE
|
|
SYNTAX SerialPortSpeed
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Speed configured for this serial port."
|
|
::= { acsSerialPortTableEntry 7 }
|
|
|
|
acsSerialPortTableComParity OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
odd(2),
|
|
even(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Parity configured for this serial port."
|
|
::= { acsSerialPortTableEntry 8 }
|
|
|
|
acsSerialPortTableComDataSize OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Data Size configured for this serial port."
|
|
::= { acsSerialPortTableEntry 9 }
|
|
|
|
acsSerialPortTableComStopBits OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of Stop Bits configured for this serial port."
|
|
::= { acsSerialPortTableEntry 10 }
|
|
|
|
acsSerialPortTableComFlowControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none(1),
|
|
hardware(2),
|
|
software(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Flow Control configured for this serial port."
|
|
::= { acsSerialPortTableEntry 11 }
|
|
|
|
acsSerialPortTableSignalStateDTR OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the DTR RS-232C signal."
|
|
::= { acsSerialPortTableEntry 12 }
|
|
|
|
acsSerialPortTableSignalStateDCD OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the DCD RS-232C signal."
|
|
::= { acsSerialPortTableEntry 13 }
|
|
|
|
acsSerialPortTableSignalStateRTS OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the RTS RS-232C signal."
|
|
::= { acsSerialPortTableEntry 14 }
|
|
|
|
acsSerialPortTableSignalStateCTS OBJECT-TYPE
|
|
SYNTAX SerialPortSignalState
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"State of the CTS RS-232C signal."
|
|
::= { acsSerialPortTableEntry 15 }
|
|
|
|
acsSerialPortTableTxBytes OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of transmited bytes by the serial port."
|
|
::= { acsSerialPortTableEntry 16 }
|
|
|
|
acsSerialPortTableRxBytes OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of received bytes by the serial port."
|
|
::= { acsSerialPortTableEntry 17 }
|
|
|
|
acsSerialPortTableFrameError OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of frame error detected in the serial port."
|
|
::= { acsSerialPortTableEntry 18 }
|
|
|
|
acsSerialPortTableParityError OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of parity error detected in the serial port."
|
|
::= { acsSerialPortTableEntry 19 }
|
|
|
|
acsSerialPortTableBreak OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of break detected in the serial port."
|
|
::= { acsSerialPortTableEntry 20 }
|
|
|
|
acsSerialPortTableOverrun OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of overrun error detected in the serial port."
|
|
::= { acsSerialPortTableEntry 21 }
|
|
|
|
--
|
|
-- acsPowerMgmt
|
|
-- OBJECT IDENTIFIER ::= { acsManagement 5 } 10418.16.2.5
|
|
--
|
|
acsPowerMgmtNumSerialPorts OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of Serial Ports that has PDU connected on the appliance."
|
|
::= { acsPowerMgmt 1 }
|
|
|
|
acsPowerMgmtSerialTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtSerialTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information about each serial port thas has PDU connect."
|
|
::= { acsPowerMgmt 2 }
|
|
|
|
acsPowerMgmtSerialTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtSerialTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Information about each serial port thas has PDU connect."
|
|
INDEX { acsPowerMgmtSerialTableIndex }
|
|
::= { acsPowerMgmtSerialTable 1 }
|
|
|
|
AcsPowerMgmtSerialTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtSerialTableIndex InterfaceIndex,
|
|
acsPowerMgmtSerialTablePortNumber Integer32,
|
|
acsPowerMgmtSerialTableDeviceName DisplayString,
|
|
acsPowerMgmtSerialTableNumberPDUs Integer32
|
|
}
|
|
|
|
acsPowerMgmtSerialTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The index of the register."
|
|
::= { acsPowerMgmtSerialTableEntry 1 }
|
|
|
|
acsPowerMgmtSerialTablePortNumber OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The number of the serial port when the PDU is connected."
|
|
::= { acsPowerMgmtSerialTableEntry 2 }
|
|
|
|
acsPowerMgmtSerialTableDeviceName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"The device name of this serial port."
|
|
::= { acsPowerMgmtSerialTableEntry 3 }
|
|
|
|
acsPowerMgmtSerialTableNumberPDUs OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Total number of units connected in this serial port."
|
|
::= { acsPowerMgmtSerialTableEntry 4 }
|
|
|
|
acsPowerMgmtPDUTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtPDUTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the list of detected PDUs."
|
|
::= { acsPowerMgmt 3 }
|
|
|
|
acsPowerMgmtPDUTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtPDUTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the PDU."
|
|
INDEX { acsPowerMgmtPDUTablePortNumber, acsPowerMgmtPDUTablePduIndex }
|
|
::= { acsPowerMgmtPDUTable 1 }
|
|
|
|
AcsPowerMgmtPDUTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtPDUTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtPDUTablePduIndex InterfaceIndexOrZero,
|
|
acsPowerMgmtPDUTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtPDUTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtPDUTableModel DisplayString, -- PDU model
|
|
acsPowerMgmtPDUTableVendor DisplayString, -- Vendor
|
|
acsPowerMgmtPDUTableFirmwareVersion DisplayString, -- Firmware Version
|
|
acsPowerMgmtPDUTableNumberOfOutlets Integer32,
|
|
acsPowerMgmtPDUTableCurrentNOS Integer32, -- OBSOLETED number of current sensors
|
|
acsPowerMgmtPDUTableCurrent1Value Integer32, -- OBSOLETED actual value for current of the sensor 1
|
|
acsPowerMgmtPDUTableCurrent1Max Integer32, -- OBSOLETED max value for current of the sensor 1
|
|
acsPowerMgmtPDUTableCurrent2Value Integer32, -- OBSOLETED actual value for current of the sensor 2
|
|
acsPowerMgmtPDUTableCurrent2Max Integer32, -- OBSOLETED max value for current of the sensor 2
|
|
acsPowerMgmtPDUTableCurrent3Value Integer32, -- OBSOLETED actual value for current of the sensor 3
|
|
acsPowerMgmtPDUTableCurrent3Max Integer32, -- OBSOLETED max value for current of the sensor 3
|
|
acsPowerMgmtPDUTableTemperatureNOS Integer32, -- OBSOLETED number of temperature sensors
|
|
acsPowerMgmtPDUTableTemperature1Value Integer32, -- OBSOLETED actual value for Temperature 1
|
|
acsPowerMgmtPDUTableTemperature1Max Integer32, -- OBSOLETED max value for Temperature 1
|
|
acsPowerMgmtPDUTableTemperature2Value Integer32, -- OBSOLETED actual value for Temperaturet 2
|
|
acsPowerMgmtPDUTableTemperature2Max Integer32, -- OBSOLETED max value for Temperature 2
|
|
acsPowerMgmtPDUTableTemperature3Value Integer32, -- OBSOLETED actual value for Temperature 3
|
|
acsPowerMgmtPDUTableTemperature3Max Integer32, -- OBSOLETED max value for Temperature 3
|
|
acsPowerMgmtPDUTableHumidityNOS Integer32, -- OBSOLETED humidity number of humidity sensors
|
|
acsPowerMgmtPDUTableHumidity1Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 1
|
|
acsPowerMgmtPDUTableHumidity1Max Integer32, -- OBSOLETED max value for Humidityof the sensor 1
|
|
acsPowerMgmtPDUTableHumidity2Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 2
|
|
acsPowerMgmtPDUTableHumidity2Max Integer32, -- OBSOLETED max value for Humidity of the sensor 2
|
|
acsPowerMgmtPDUTableHumidity3Value Integer32, -- OBSOLETED actual value for Humidity of the sensor 3
|
|
acsPowerMgmtPDUTableHumidity3Max Integer32, -- OBSOLETED max value for Humidity of the sensor 3
|
|
acsPowerMgmtPDUTableVoltageNOS Integer32, -- OBSOLETED number of voltage sensor
|
|
acsPowerMgmtPDUTableVoltage1Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 1
|
|
acsPowerMgmtPDUTableVoltage1Max Integer32, -- OBSOLETED max value for Voltage of the sensor 1
|
|
acsPowerMgmtPDUTableVoltage2Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 2
|
|
acsPowerMgmtPDUTableVoltage2Max Integer32, -- OBSOLETED max value for Voltaget of the sensor 2
|
|
acsPowerMgmtPDUTableVoltage3Value Integer32, -- OBSOLETED actual value for Voltage of the sensor 3
|
|
acsPowerMgmtPDUTableVoltage3Max Integer32, -- OBSOLETED max value for Voltage of the sensor 3
|
|
acsPowerMgmtPDUTableNumberOfPhases Integer32, -- number of phases (single or 3-phases)
|
|
acsPowerMgmtPDUTableNumberOfBanks Integer32, -- number of banks
|
|
acsPowerMgmtPDUTableCurrentValue Integer32, -- actual value of PDU current sensor
|
|
acsPowerMgmtPDUTableCurrentMax Integer32, -- max detected value of current sensor
|
|
acsPowerMgmtPDUTableCurrentMin Integer32, -- min detected value of current sensor
|
|
acsPowerMgmtPDUTableCurrentAvg Integer32, -- average value for current sensor
|
|
acsPowerMgmtPDUTableCurrentReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTableVoltageType INTEGER, -- type of PDU voltage
|
|
acsPowerMgmtPDUTableVoltageValue Integer32, -- actual value of PDU voltage
|
|
acsPowerMgmtPDUTableVoltageMax Integer32, -- max value of voltage sensor
|
|
acsPowerMgmtPDUTableVoltageMin Integer32, -- min value of voltage sensor
|
|
acsPowerMgmtPDUTableVoltageAvg Integer32, -- avg value of voltage sensor
|
|
acsPowerMgmtPDUTableVoltageReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTablePowerType INTEGER, -- type of PDU power consumption
|
|
acsPowerMgmtPDUTablePowerValue Integer32, -- actual value of PDU power consumption
|
|
acsPowerMgmtPDUTablePowerMax Integer32, -- max value
|
|
acsPowerMgmtPDUTablePowerMin Integer32, -- min value
|
|
acsPowerMgmtPDUTablePowerAvg Integer32, -- average value
|
|
acsPowerMgmtPDUTablePowerReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTablePowerFactorType INTEGER, -- type of PDU power factor
|
|
acsPowerMgmtPDUTablePowerFactorValue Integer32, -- actual value of PDU power factor
|
|
acsPowerMgmtPDUTablePowerFactorMax Integer32, -- max value for power factor
|
|
acsPowerMgmtPDUTablePowerFactorMin Integer32, -- min value for power factor
|
|
acsPowerMgmtPDUTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtPDUTablePowerFactorReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPDUTableAlarm INTEGER, -- status of PDU alarm
|
|
acsPowerMgmtPDUTableEnvSensors Integer32 -- number of environmental sensors
|
|
}
|
|
|
|
acsPowerMgmtPDUTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPDUTableEntry 1 }
|
|
|
|
acsPowerMgmtPDUTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtPDUTableEntry 2 }
|
|
|
|
acsPowerMgmtPDUTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtPDUTableEntry 3 }
|
|
|
|
acsPowerMgmtPDUTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPDUTableEntry 4 }
|
|
|
|
acsPowerMgmtPDUTableModel OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Model of the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 5 }
|
|
|
|
acsPowerMgmtPDUTableVendor OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Vendor of the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 6 }
|
|
|
|
acsPowerMgmtPDUTableFirmwareVersion OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Version of the PDU firmware."
|
|
::= { acsPowerMgmtPDUTableEntry 7 }
|
|
|
|
acsPowerMgmtPDUTableNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets of the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 8 }
|
|
|
|
acsPowerMgmtPDUTableCurrentNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of current sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 9 }
|
|
|
|
acsPowerMgmtPDUTableCurrent1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 1 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)"
|
|
::= { acsPowerMgmtPDUTableEntry 10 }
|
|
|
|
acsPowerMgmtPDUTableCurrent1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 1 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value."
|
|
::= { acsPowerMgmtPDUTableEntry 11 }
|
|
|
|
acsPowerMgmtPDUTableCurrent2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 2 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)"
|
|
::= { acsPowerMgmtPDUTableEntry 12 }
|
|
|
|
acsPowerMgmtPDUTableCurrent2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 2 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value."
|
|
::= { acsPowerMgmtPDUTableEntry 13}
|
|
|
|
acsPowerMgmtPDUTableCurrent3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Current of the sensor 3 in this PDU unit in AMP.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)"
|
|
::= { acsPowerMgmtPDUTableEntry 14 }
|
|
|
|
acsPowerMgmtPDUTableCurrent3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum current of the sensor 3 in this PDU unit in AMP.
|
|
When the PDU does not have support for maximum value,
|
|
the value will be 0.
|
|
The value of this object is the actual current in
|
|
AMP * 10. You need to translate the readed value
|
|
(Ex. : value is 5, the current is 0.5 AMP.)
|
|
Clear this value, set it with Zero value."
|
|
::= { acsPowerMgmtPDUTableEntry 15 }
|
|
|
|
acsPowerMgmtPDUTableTemperatureNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of temperature sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 16 }
|
|
|
|
acsPowerMgmtPDUTableTemperature1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { acsPowerMgmtPDUTableEntry 17 }
|
|
|
|
acsPowerMgmtPDUTableTemperature1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 18 }
|
|
|
|
acsPowerMgmtPDUTableTemperature2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { acsPowerMgmtPDUTableEntry 19 }
|
|
|
|
acsPowerMgmtPDUTableTemperature2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 20 }
|
|
|
|
acsPowerMgmtPDUTableTemperature3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Temperature of this PM unit in Celsius degrees.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius)."
|
|
::= { acsPowerMgmtPDUTableEntry 21 }
|
|
|
|
acsPowerMgmtPDUTableTemperature3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum temperature detected in this PM unit in Celsius degrees.
|
|
The value will be Zero when the PDU does not have support for maximum value.
|
|
The value of this object is the actual temperature in
|
|
degrees C * 10. You need to translate the readed value
|
|
(Ex. : value is 240, the temperature is 24 Celsius.)
|
|
If the temperature measurement is not installed this
|
|
value will be 0.
|
|
Valid values are 5 to 999 ( 0.5 to 99.9 Celsius).
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 22 }
|
|
|
|
acsPowerMgmtPDUTableHumidityNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of humidity sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 23 }
|
|
|
|
acsPowerMgmtPDUTableHumidity1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { acsPowerMgmtPDUTableEntry 24 }
|
|
|
|
acsPowerMgmtPDUTableHumidity1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 25 }
|
|
|
|
acsPowerMgmtPDUTableHumidity2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { acsPowerMgmtPDUTableEntry 26 }
|
|
|
|
acsPowerMgmtPDUTableHumidity2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 27 }
|
|
|
|
acsPowerMgmtPDUTableHumidity3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Humidity of this PM unit .
|
|
If the humidity measurement is not installed this
|
|
value will be 0."
|
|
::= { acsPowerMgmtPDUTableEntry 28 }
|
|
|
|
acsPowerMgmtPDUTableHumidity3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum humidity detected in this PM unit.
|
|
If the humidity measurement is not installed or the PDU does not have support for maximum value this
|
|
value will be 0.
|
|
Set with Zero value to clear the max. temperature."
|
|
::= { acsPowerMgmtPDUTableEntry 29 }
|
|
|
|
acsPowerMgmtPDUTableVoltageNOS OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Number of voltage sensors in the PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 30 }
|
|
|
|
acsPowerMgmtPDUTableVoltage1Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 31 }
|
|
|
|
acsPowerMgmtPDUTableVoltage1Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 32 }
|
|
|
|
acsPowerMgmtPDUTableVoltage2Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 33 }
|
|
|
|
acsPowerMgmtPDUTableVoltage2Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 34 }
|
|
|
|
acsPowerMgmtPDUTableVoltage3Value OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Voltage of this sensor in this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 35 }
|
|
|
|
acsPowerMgmtPDUTableVoltage3Max OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-write
|
|
STATUS obsolete
|
|
DESCRIPTION
|
|
"Maximum voltage of this sensor in this PDU unit.
|
|
Set with Zero value to clear the maximum voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 36 }
|
|
|
|
acsPowerMgmtPDUTableNumberOfPhases OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
single-phase (0),
|
|
three-phase (3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of phases of this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 37 }
|
|
|
|
acsPowerMgmtPDUTableNumberOfBanks OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Number of banks of this PDU unit."
|
|
::= { acsPowerMgmtPDUTableEntry 38 }
|
|
|
|
acsPowerMgmtPDUTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 39 }
|
|
|
|
acsPowerMgmtPDUTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 40 }
|
|
|
|
acsPowerMgmtPDUTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 41 }
|
|
|
|
acsPowerMgmtPDUTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for current sensor in this PDU.( A x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 42 }
|
|
|
|
acsPowerMgmtPDUTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of current."
|
|
::= { acsPowerMgmtPDUTableEntry 43 }
|
|
|
|
acsPowerMgmtPDUTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values."
|
|
::= { acsPowerMgmtPDUTableEntry 44 }
|
|
|
|
acsPowerMgmtPDUTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 45 }
|
|
|
|
acsPowerMgmtPDUTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 46 }
|
|
|
|
acsPowerMgmtPDUTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 47 }
|
|
|
|
acsPowerMgmtPDUTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for voltage sensor in this PDU unit.( V )"
|
|
::= { acsPowerMgmtPDUTableEntry 48 }
|
|
|
|
acsPowerMgmtPDUTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of voltage."
|
|
::= { acsPowerMgmtPDUTableEntry 49 }
|
|
|
|
acsPowerMgmtPDUTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power consumption values.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 50 }
|
|
|
|
acsPowerMgmtPDUTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 51 }
|
|
|
|
acsPowerMgmtPDUTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 52 }
|
|
|
|
acsPowerMgmtPDUTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 53 }
|
|
|
|
acsPowerMgmtPDUTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power consumption in this PDU unit.( W x 10 )"
|
|
::= { acsPowerMgmtPDUTableEntry 54 }
|
|
|
|
acsPowerMgmtPDUTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power consumption."
|
|
::= { acsPowerMgmtPDUTableEntry 55 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values."
|
|
::= { acsPowerMgmtPDUTableEntry 56 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 57 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 58 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 59 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power factor in this PDU unit.( PF x 100 )"
|
|
::= { acsPowerMgmtPDUTableEntry 60 }
|
|
|
|
acsPowerMgmtPDUTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power factor."
|
|
::= { acsPowerMgmtPDUTableEntry 61 }
|
|
|
|
acsPowerMgmtPDUTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the PDU alarm status."
|
|
::= { acsPowerMgmtPDUTableEntry 62 }
|
|
|
|
acsPowerMgmtPDUTableEnvSensors OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of environmental sensor in this PDU."
|
|
::= { acsPowerMgmtPDUTableEntry 63 }
|
|
|
|
|
|
acsPowerMgmtTotalNumberOfOutlets OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of outlets managed by the appliance."
|
|
::= { acsPowerMgmt 4 }
|
|
|
|
acsPowerMgmtOutletsTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtOutletsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about outlets."
|
|
::= { acsPowerMgmt 5 }
|
|
|
|
acsPowerMgmtOutletsTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtOutletsTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the outlet."
|
|
INDEX { acsPowerMgmtOutletsTablePortNumber,
|
|
acsPowerMgmtOutletsTablePduNumber,
|
|
acsPowerMgmtOutletsTableNumber }
|
|
::= { acsPowerMgmtOutletsTable 1 }
|
|
|
|
AcsPowerMgmtOutletsTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtOutletsTablePortNumber InterfaceIndex, -- serial port #
|
|
acsPowerMgmtOutletsTablePduNumber InterfaceIndex,
|
|
acsPowerMgmtOutletsTableNumber InterfaceIndex, -- outlet number in PDU
|
|
acsPowerMgmtOutletsTableName DisplayString, -- outlet name
|
|
acsPowerMgmtOutletsTableStatus INTEGER, -- outlet status
|
|
acsPowerMgmtOutletsTablePowerControl INTEGER, -- manage the outlet
|
|
acsPowerMgmtOutletsTablePortName DisplayString, -- serial port name
|
|
acsPowerMgmtOutletsTablePduId DisplayString -- PDU ID
|
|
}
|
|
|
|
acsPowerMgmtOutletsTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { acsPowerMgmtOutletsTableEntry 1 }
|
|
|
|
acsPowerMgmtOutletsTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { acsPowerMgmtOutletsTableEntry 2 }
|
|
|
|
acsPowerMgmtOutletsTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the outlet in the PDU."
|
|
::= { acsPowerMgmtOutletsTableEntry 3 }
|
|
|
|
acsPowerMgmtOutletsTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the outlet."
|
|
::= { acsPowerMgmtOutletsTableEntry 4 }
|
|
|
|
acsPowerMgmtOutletsTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the outlet."
|
|
::= { acsPowerMgmtOutletsTableEntry 5 }
|
|
|
|
acsPowerMgmtOutletsTablePowerControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
powerOn(2),
|
|
powerOff(3),
|
|
powerCycle(4),
|
|
powerLock(5),
|
|
powerUnlock(6)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2-6) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
powerOn(2) = when SET the power On command is sent to PDU.
|
|
powerOff(3) = when SET the power Off command is sent to PDU.
|
|
powerCycle(4)=when SET the power cycle command is sent to PDU.
|
|
powerLock(5)= when SET the power lock command is sent to PDU.
|
|
powerUnlock(6)=when SET the power unlock command is sent to PDU.
|
|
The powerLock and powerUnlock are valid only for Cyclades-PM PDUs"
|
|
::= { acsPowerMgmtOutletsTableEntry 6 }
|
|
|
|
acsPowerMgmtOutletsTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port Name where the PDU is connected."
|
|
::= { acsPowerMgmtOutletsTableEntry 7 }
|
|
|
|
acsPowerMgmtOutletsTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtOutletsTableEntry 8 }
|
|
|
|
acsPowerMgmtNumberOfOutletGroup OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of configured group of outlets."
|
|
::= { acsPowerMgmt 6 }
|
|
|
|
acsPowerMgmtGroupTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtGroupTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about group of outlets."
|
|
::= { acsPowerMgmt 7 }
|
|
|
|
acsPowerMgmtGroupTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtGroupTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about group of outlets."
|
|
INDEX { acsPowerMgmtGroupTableIndex }
|
|
::= { acsPowerMgmtGroupTable 1 }
|
|
|
|
AcsPowerMgmtGroupTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtGroupTableIndex InterfaceIndexOrZero,
|
|
acsPowerMgmtGroupTableName DisplayString, -- group name
|
|
acsPowerMgmtGroupTableStatus INTEGER, -- group status
|
|
acsPowerMgmtGroupTablePowerControl INTEGER -- manage the group
|
|
}
|
|
|
|
acsPowerMgmtGroupTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index of the group."
|
|
::= { acsPowerMgmtGroupTableEntry 1 }
|
|
|
|
acsPowerMgmtGroupTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of the group of outlets."
|
|
::= { acsPowerMgmtGroupTableEntry 2 }
|
|
|
|
acsPowerMgmtGroupTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
off(1),
|
|
on(2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Status of the group of outlet."
|
|
::= { acsPowerMgmtGroupTableEntry 3 }
|
|
|
|
acsPowerMgmtGroupTablePowerControl OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
powerOn(2),
|
|
powerOff(3),
|
|
powerCycle(4)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A set value of power*(2-6) will send command to PDU.
|
|
noAction(1) = always returned in a GET. Does nothing if SET.
|
|
powerOn(2) = when SET the power On command is sent to PDU.
|
|
powerOff(3) = when SET the power Off command is sent to PDU.
|
|
powerCycle(4)=when SET the power cycle command is sent to PDU."
|
|
::= { acsPowerMgmtGroupTableEntry 4 }
|
|
|
|
acsPowerMgmtPhasesTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtPhasesTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains data monitoring of each detected phase."
|
|
::= { acsPowerMgmt 8 }
|
|
|
|
acsPowerMgmtPhasesTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtPhasesTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the data monitoring about phases."
|
|
INDEX { acsPowerMgmtPhasesTablePortNumber, acsPowerMgmtPhasesTablePduIndex, acsPowerMgmtPhasesTablePhaseIndex }
|
|
::= { acsPowerMgmtPhasesTable 1 }
|
|
|
|
AcsPowerMgmtPhasesTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtPhasesTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtPhasesTablePduIndex InterfaceIndexOrZero, -- number of PDU
|
|
acsPowerMgmtPhasesTablePhaseIndex InterfaceIndexOrZero, -- phase index
|
|
acsPowerMgmtPhasesTablePhaseName DisplayString, -- Phase Name
|
|
acsPowerMgmtPhasesTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtPhasesTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtPhasesTableCurrentValue Integer32, -- actual value of Phase current sensor
|
|
acsPowerMgmtPhasesTableCurrentMax Integer32, -- max detected value of current sensor
|
|
acsPowerMgmtPhasesTableCurrentMin Integer32, -- min detected value of current sensor
|
|
acsPowerMgmtPhasesTableCurrentAvg Integer32, -- average value for current sensor
|
|
acsPowerMgmtPhasesTableCurrentReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTableVoltageType INTEGER, -- type of phase voltage
|
|
acsPowerMgmtPhasesTableVoltageValue Integer32, -- actual value of phase voltage
|
|
acsPowerMgmtPhasesTableVoltageMax Integer32, -- max value of voltage sensor
|
|
acsPowerMgmtPhasesTableVoltageMin Integer32, -- min value of voltage sensor
|
|
acsPowerMgmtPhasesTableVoltageAvg Integer32, -- avg value of voltage sensor
|
|
acsPowerMgmtPhasesTableVoltageReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTablePowerType INTEGER, -- type of phase power consumption
|
|
acsPowerMgmtPhasesTablePowerValue Integer32, -- actual value of phase power consumption
|
|
acsPowerMgmtPhasesTablePowerMax Integer32, -- max value
|
|
acsPowerMgmtPhasesTablePowerMin Integer32, -- min value
|
|
acsPowerMgmtPhasesTablePowerAvg Integer32, -- average value
|
|
acsPowerMgmtPhasesTablePowerReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTablePowerFactorType INTEGER, -- type of phase power factor
|
|
acsPowerMgmtPhasesTablePowerFactorValue Integer32, -- actual value of phase power factor
|
|
acsPowerMgmtPhasesTablePowerFactorMax Integer32, -- max value for power factor
|
|
acsPowerMgmtPhasesTablePowerFactorMin Integer32, -- min value for power factor
|
|
acsPowerMgmtPhasesTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtPhasesTablePowerFactorReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtPhasesTableAlarm INTEGER -- phase alarm status
|
|
}
|
|
|
|
acsPowerMgmtPhasesTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPhasesTableEntry 1 }
|
|
|
|
acsPowerMgmtPhasesTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtPhasesTableEntry 2 }
|
|
|
|
acsPowerMgmtPhasesTablePhaseIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase index in the PDU."
|
|
::= { acsPowerMgmtPhasesTableEntry 3 }
|
|
|
|
acsPowerMgmtPhasesTablePhaseName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"phase name in the PDU."
|
|
::= { acsPowerMgmtPhasesTableEntry 4 }
|
|
|
|
acsPowerMgmtPhasesTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtPhasesTableEntry 5 }
|
|
|
|
acsPowerMgmtPhasesTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtPhasesTableEntry 6 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 7 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 8 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 9 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for current sensor in this phase.( A x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 10 }
|
|
|
|
acsPowerMgmtPhasesTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of current."
|
|
::= { acsPowerMgmtPhasesTableEntry 11 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values."
|
|
::= { acsPowerMgmtPhasesTableEntry 12 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 13 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 14 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 15 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for voltage sensor in this phase.( V )"
|
|
::= { acsPowerMgmtPhasesTableEntry 16 }
|
|
|
|
acsPowerMgmtPhasesTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of voltage."
|
|
::= { acsPowerMgmtPhasesTableEntry 17 }
|
|
|
|
acsPowerMgmtPhasesTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power consumption values."
|
|
::= { acsPowerMgmtPhasesTableEntry 18 }
|
|
|
|
acsPowerMgmtPhasesTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 19 }
|
|
|
|
acsPowerMgmtPhasesTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 20 }
|
|
|
|
acsPowerMgmtPhasesTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 21 }
|
|
|
|
acsPowerMgmtPhasesTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power consumption in this phase.( W x 10 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 22 }
|
|
|
|
acsPowerMgmtPhasesTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power consumption."
|
|
::= { acsPowerMgmtPhasesTableEntry 23 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values."
|
|
::= { acsPowerMgmtPhasesTableEntry 24 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 25 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 26 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 27 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power factor in this phase.( PF x 100 )"
|
|
::= { acsPowerMgmtPhasesTableEntry 28 }
|
|
|
|
acsPowerMgmtPhasesTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power factor."
|
|
::= { acsPowerMgmtPhasesTableEntry 29 }
|
|
|
|
acsPowerMgmtPhasesTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the phase alarm status."
|
|
::= { acsPowerMgmtPhasesTableEntry 30 }
|
|
|
|
acsPowerMgmtBanksTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtBanksTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains data monitoring of each detected bank."
|
|
::= { acsPowerMgmt 9 }
|
|
|
|
acsPowerMgmtBanksTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtBanksTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the data monitoring about bank."
|
|
INDEX { acsPowerMgmtBanksTablePortNumber, acsPowerMgmtBanksTablePduIndex, acsPowerMgmtBanksTableBankIndex }
|
|
::= { acsPowerMgmtBanksTable 1 }
|
|
|
|
AcsPowerMgmtBanksTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtBanksTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtBanksTablePduIndex InterfaceIndexOrZero, -- number of PDU
|
|
acsPowerMgmtBanksTableBankIndex InterfaceIndexOrZero, -- bank index
|
|
acsPowerMgmtBanksTableBankName DisplayString, -- Bank Name
|
|
acsPowerMgmtBanksTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtBanksTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtBanksTableCurrentValue Integer32, -- actual value of bank current sensor
|
|
acsPowerMgmtBanksTableCurrentMax Integer32, -- max detected value of current sensor
|
|
acsPowerMgmtBanksTableCurrentMin Integer32, -- min detected value of current sensor
|
|
acsPowerMgmtBanksTableCurrentAvg Integer32, -- average value for current sensor
|
|
acsPowerMgmtBanksTableCurrentReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTableVoltageType INTEGER, -- type of bank voltage
|
|
acsPowerMgmtBanksTableVoltageValue Integer32, -- actual value of bank voltage
|
|
acsPowerMgmtBanksTableVoltageMax Integer32, -- max value of voltage sensor
|
|
acsPowerMgmtBanksTableVoltageMin Integer32, -- min value of voltage sensor
|
|
acsPowerMgmtBanksTableVoltageAvg Integer32, -- avg value of voltage sensor
|
|
acsPowerMgmtBanksTableVoltageReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTablePowerType INTEGER, -- type of bank power consumption
|
|
acsPowerMgmtBanksTablePowerValue Integer32, -- actual value of bank power consumption
|
|
acsPowerMgmtBanksTablePowerMax Integer32, -- max value
|
|
acsPowerMgmtBanksTablePowerMin Integer32, -- min value
|
|
acsPowerMgmtBanksTablePowerAvg Integer32, -- average value
|
|
acsPowerMgmtBanksTablePowerReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTablePowerFactorType INTEGER, -- type of bank power factor
|
|
acsPowerMgmtBanksTablePowerFactorValue Integer32, -- actual value of bank power factor
|
|
acsPowerMgmtBanksTablePowerFactorMax Integer32, -- max value for power factor
|
|
acsPowerMgmtBanksTablePowerFactorMin Integer32, -- min value for power factor
|
|
acsPowerMgmtBanksTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtBanksTablePowerFactorReset INTEGER, -- reset max, min and avg values
|
|
acsPowerMgmtBanksTableAlarm INTEGER -- status of bank alarm
|
|
}
|
|
|
|
acsPowerMgmtBanksTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtBanksTableEntry 1 }
|
|
|
|
acsPowerMgmtBanksTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtBanksTableEntry 2 }
|
|
|
|
acsPowerMgmtBanksTableBankIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank index in the PDU."
|
|
::= { acsPowerMgmtBanksTableEntry 3 }
|
|
|
|
acsPowerMgmtBanksTableBankName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Bank name in the PDU."
|
|
::= { acsPowerMgmtBanksTableEntry 4 }
|
|
|
|
acsPowerMgmtBanksTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtBanksTableEntry 5 }
|
|
|
|
acsPowerMgmtBanksTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtBanksTableEntry 6 }
|
|
|
|
acsPowerMgmtBanksTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 7 }
|
|
|
|
acsPowerMgmtBanksTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 8 }
|
|
|
|
acsPowerMgmtBanksTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 9 }
|
|
|
|
acsPowerMgmtBanksTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for current sensor in this bank.( A x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 10 }
|
|
|
|
acsPowerMgmtBanksTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of current."
|
|
::= { acsPowerMgmtBanksTableEntry 11 }
|
|
|
|
acsPowerMgmtBanksTableVoltageType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of voltage values."
|
|
::= { acsPowerMgmtBanksTableEntry 12 }
|
|
|
|
acsPowerMgmtBanksTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 13 }
|
|
|
|
acsPowerMgmtBanksTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 14 }
|
|
|
|
acsPowerMgmtBanksTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 15 }
|
|
|
|
acsPowerMgmtBanksTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for voltage sensor in this bank.( V )"
|
|
::= { acsPowerMgmtBanksTableEntry 16 }
|
|
|
|
acsPowerMgmtBanksTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of voltage."
|
|
::= { acsPowerMgmtBanksTableEntry 17 }
|
|
|
|
acsPowerMgmtBanksTablePowerType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power consumption values."
|
|
::= { acsPowerMgmtBanksTableEntry 18 }
|
|
|
|
acsPowerMgmtBanksTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 19 }
|
|
|
|
acsPowerMgmtBanksTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 20 }
|
|
|
|
acsPowerMgmtBanksTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 21 }
|
|
|
|
acsPowerMgmtBanksTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power consumption in this bank.( W x 10 )"
|
|
::= { acsPowerMgmtBanksTableEntry 22 }
|
|
|
|
acsPowerMgmtBanksTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power consumption."
|
|
::= { acsPowerMgmtBanksTableEntry 23 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
none-sensor (0),
|
|
estimated (1),
|
|
read (2)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Type of power factor values."
|
|
::= { acsPowerMgmtBanksTableEntry 24 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 25 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 26 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 27 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for power factor in this bank.( PF x 100 )"
|
|
::= { acsPowerMgmtBanksTableEntry 28 }
|
|
|
|
acsPowerMgmtBanksTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
no-action (1),
|
|
reset (2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION "Reset max, min and avg values of power factor."
|
|
::= { acsPowerMgmtBanksTableEntry 29 }
|
|
|
|
acsPowerMgmtBanksTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the bank alarm status."
|
|
::= { acsPowerMgmtBanksTableEntry 30 }
|
|
|
|
acsPowerMgmtEnvMonTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtEnvMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains data monitoring of each detected environmental sensor."
|
|
::= { acsPowerMgmt 10 }
|
|
|
|
acsPowerMgmtEnvMonTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtEnvMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the data monitoring about environmental sensors."
|
|
INDEX { acsPowerMgmtEnvMonTablePortNumber, acsPowerMgmtEnvMonTablePduIndex, acsPowerMgmtEnvMonTableIndex }
|
|
::= { acsPowerMgmtEnvMonTable 1 }
|
|
|
|
AcsPowerMgmtEnvMonTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtEnvMonTablePortNumber InterfaceIndex, -- number of serial port
|
|
acsPowerMgmtEnvMonTablePduIndex InterfaceIndexOrZero, -- number of PDU
|
|
acsPowerMgmtEnvMonTableIndex InterfaceIndexOrZero, -- index
|
|
acsPowerMgmtEnvMonTableName DisplayString, -- sensor name
|
|
acsPowerMgmtEnvMonTablePduId DisplayString, -- PDU identification
|
|
acsPowerMgmtEnvMonTablePortName DisplayString, -- Serial Port Name
|
|
acsPowerMgmtEnvMonTableType INTEGER, -- environmental sensor type
|
|
acsPowerMgmtEnvMonTableStatus INTEGER, -- state of digital sensor
|
|
acsPowerMgmtEnvMonTableValue Integer32, -- value
|
|
acsPowerMgmtEnvMonTableMaxValue Integer32 -- max value
|
|
}
|
|
|
|
acsPowerMgmtEnvMonTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtEnvMonTableEntry 1 }
|
|
|
|
acsPowerMgmtEnvMonTablePduIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"A PDU position in the chain."
|
|
::= { acsPowerMgmtEnvMonTableEntry 2 }
|
|
|
|
acsPowerMgmtEnvMonTableIndex OBJECT-TYPE
|
|
SYNTAX InterfaceIndexOrZero
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"envmon sensor index."
|
|
::= { acsPowerMgmtEnvMonTableEntry 3 }
|
|
|
|
acsPowerMgmtEnvMonTableName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"envmon sensor name."
|
|
::= { acsPowerMgmtEnvMonTableEntry 4 }
|
|
|
|
acsPowerMgmtEnvMonTablePduId OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"PDU identification."
|
|
::= { acsPowerMgmtEnvMonTableEntry 5 }
|
|
|
|
acsPowerMgmtEnvMonTablePortName OBJECT-TYPE
|
|
SYNTAX DisplayString
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Name of serial port when the PDU is connected."
|
|
::= { acsPowerMgmtEnvMonTableEntry 6 }
|
|
|
|
acsPowerMgmtEnvMonTableType OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
temp-internal (1),
|
|
temperature (2),
|
|
humidity (3),
|
|
air-flow (4),
|
|
smoke (5),
|
|
dry-concact (6),
|
|
water-level (7),
|
|
motion (8),
|
|
unplugged (9),
|
|
unknown (10)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "The type of environmental monitor."
|
|
::= { acsPowerMgmtEnvMonTableEntry 7 }
|
|
|
|
acsPowerMgmtEnvMonTableStatus OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal(1),
|
|
triggered(2),
|
|
not-applicable(3)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Status of digital sensors:
|
|
Dry-Contact, Water level, Smoke sensor, Motion sensor."
|
|
::= { acsPowerMgmtEnvMonTableEntry 8 }
|
|
|
|
acsPowerMgmtEnvMonTableValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
|
|
::= { acsPowerMgmtEnvMonTableEntry 9 }
|
|
|
|
acsPowerMgmtEnvMonTableMaxValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value for envmon sensors. Temperature: C x 10. Humidity: %. Air flow: afu."
|
|
::= { acsPowerMgmtEnvMonTableEntry 10 }
|
|
|
|
acsPowerMgmtOutElecMonTable OBJECT-TYPE
|
|
SYNTAX SEQUENCE OF AcsPowerMgmtOutElecMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"This table contains the information about data monitoring of outlets."
|
|
::= { acsPowerMgmt 11 }
|
|
|
|
acsPowerMgmtOutElecMonTableEntry OBJECT-TYPE
|
|
SYNTAX AcsPowerMgmtOutElecMonTableEntry
|
|
MAX-ACCESS not-accessible
|
|
STATUS current
|
|
DESCRIPTION
|
|
"each entry has the information about the outlet."
|
|
INDEX { acsPowerMgmtOutElecMonTablePortNumber,
|
|
acsPowerMgmtOutElecMonTablePduNumber,
|
|
acsPowerMgmtOutElecMonTableNumber }
|
|
::= { acsPowerMgmtOutElecMonTable 1 }
|
|
|
|
AcsPowerMgmtOutElecMonTableEntry ::= SEQUENCE {
|
|
acsPowerMgmtOutElecMonTablePortNumber InterfaceIndex, -- serial port #
|
|
acsPowerMgmtOutElecMonTablePduNumber InterfaceIndex,
|
|
acsPowerMgmtOutElecMonTableNumber InterfaceIndex, -- outlet number in PDU
|
|
acsPowerMgmtOutElecMonTableCurrentValue Integer32, -- actual value for current
|
|
acsPowerMgmtOutElecMonTableCurrentMax Integer32, -- max detected value for current
|
|
acsPowerMgmtOutElecMonTableCurrentMin Integer32, -- min detected value for current
|
|
acsPowerMgmtOutElecMonTableCurrentAvg Integer32, -- average value for current
|
|
acsPowerMgmtOutElecMonTableCurrentReset INTEGER, -- reset max, min and avg values of current
|
|
acsPowerMgmtOutElecMonTablePowerValue Integer32, -- actual value for power
|
|
acsPowerMgmtOutElecMonTablePowerMax Integer32, -- max detected value for power
|
|
acsPowerMgmtOutElecMonTablePowerMin Integer32, -- min detected value for power
|
|
acsPowerMgmtOutElecMonTablePowerAvg Integer32, -- average value for power
|
|
acsPowerMgmtOutElecMonTablePowerReset INTEGER, -- reset max, min and avg values of power
|
|
acsPowerMgmtOutElecMonTableVoltageValue Integer32, -- actual value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageMax Integer32, -- max detected value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageMin Integer32, -- min detected value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageAvg Integer32, -- average value for voltage
|
|
acsPowerMgmtOutElecMonTableVoltageReset INTEGER, -- reset max, min and avg values of voltage
|
|
acsPowerMgmtOutElecMonTablePowerFactorValue Integer32, -- actual value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorMax Integer32, -- max detected value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorMin Integer32, -- min detected value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorAvg Integer32, -- avg value for power factor
|
|
acsPowerMgmtOutElecMonTablePowerFactorReset INTEGER, -- reset max, min and avg values of power factor
|
|
acsPowerMgmtOutElecMonTableAlarm INTEGER -- outlet alarm status
|
|
}
|
|
|
|
acsPowerMgmtOutElecMonTablePortNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Serial Port number."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 1 }
|
|
|
|
acsPowerMgmtOutElecMonTablePduNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Index."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 2 }
|
|
|
|
acsPowerMgmtOutElecMonTableNumber OBJECT-TYPE
|
|
SYNTAX InterfaceIndex
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Number of the outlet in the PDU."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 3 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 4 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 5 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 6 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet current sensor.( A x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 7 }
|
|
|
|
acsPowerMgmtOutElecMonTableCurrentReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet current."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 8 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 9 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 10 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 11 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet power comsumption sensor.( W x 10 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 12 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet power comsumption."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 13 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 14 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 15 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 16 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet voltage sensor.( V )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 17 }
|
|
|
|
acsPowerMgmtOutElecMonTableVoltageReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet voltage."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 18 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorValue OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Actual value of outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 19 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorMax OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Max detected value of outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 20 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorMin OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Min detected value of outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 21 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorAvg OBJECT-TYPE
|
|
SYNTAX Integer32
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Average value for outlet power-factor sensor.( PF x 100 )"
|
|
::= { acsPowerMgmtOutElecMonTableEntry 22 }
|
|
|
|
acsPowerMgmtOutElecMonTablePowerFactorReset OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
noAction(1),
|
|
reset(2)
|
|
}
|
|
MAX-ACCESS read-write
|
|
STATUS current
|
|
DESCRIPTION
|
|
"Reset max, min and avertage values of outlet power-factor."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 23 }
|
|
|
|
acsPowerMgmtOutElecMonTableAlarm OBJECT-TYPE
|
|
SYNTAX INTEGER {
|
|
normal (1),
|
|
blow-fuse (2),
|
|
hw-ocp (3),
|
|
high-critical (4),
|
|
high-warning (5),
|
|
low-warning (6),
|
|
low-critical (7)
|
|
}
|
|
MAX-ACCESS read-only
|
|
STATUS current
|
|
DESCRIPTION "Show the outlet alarm status."
|
|
::= { acsPowerMgmtOutElecMonTableEntry 24 }
|
|
|
|